L1 BC26x_f2

download L1 BC26x_f2

of 2

Transcript of L1 BC26x_f2

  • 8/12/2019 L1 BC26x_f2

    1/2

  • 8/12/2019 L1 BC26x_f2

    2/2

    2002ALSTOM

    Ourpolicyisoneofcontinuousdeve

    lopmentandtherightisreservedtosupplyequipmentwhichmayvaryfrom

    thatdescribed.

    Printedin-house

    Publication:C264/END

    S/Aa

    T&D Energy Automation & Information, Le Sextant, 3, avenue Andr Malraux, 92300 Levallois-Perret. France. www.tde.alstom.com

    Tel: +33 (0) 141 49 20 00 - FAX: +33 (0) 141 49 24 85 - Contact Centre on l ine 24 hours a day : +44 (0) 1785 25 00 70

    Technical data

    Hardware

    Case

    MiCOM C264C

    WxHxD 40T(206 mm) x

    4U(177 mm) x 168 mm

    Slots 4 or 5 free assignment

    MiCOM C264

    WxHxD 80T(405 mm) x

    4U(177 mm) x 168 mm

    Slots 14 or 15 free

    assignment

    Control panel

    Large graphical LCD (optional)

    Display 72 x 72 mm (optional)

    LEDs 17, 12 free configurable

    Buttons 12 : 7 for operations

    5 for control (optional)

    Power supply board

    UN 24, 48/60, 110/125,

    220/250 VDC

    100 - 250 VAC50/60 Hz

    2 Relays Alarm, Watchdog

    Processor board

    32-bit Power PC-based processor

    Internal Watchdog

    Clock 80 Mhz

    RAM 16 Mbytes

    Flash 2 Mbytes

    SRAM 256 Kbytes

    Ethernet-Based 10/100Base-FX

    or 10/100Base-TX

    2 insulated serial interfaces

    RS232/422/485 or 4 insulated

    serial interfaces RS232/422/485

    (optional)

    IRIG-B interface

    Digital Input Board (16 DI)

    16 optically insulated inputs with

    one common for 2 DI.

    UN 24, 48/60, 110/125,

    220/250 VDC

    Digital Output Board (10 DO)

    8 outputs NO + 2 outputs NO/NC

    UN 250 VDC/ 230 VAC

    Making 70 VA / W

    Breaking 30 VA / W

    Communications

    LAN

    UCA2, IEC 61850 LAN node as

    Ethernet-Based 10/100Base-FX

    or 10/100Base-TX

    Standard SCADA protocols

    IEC 60870-5-101, DNP3,

    MODBUS

    Interfaces

    Optical / RS232 / RS422 / RS485

    Standard IEDs protocols

    IEC 60870-5-103, DNP3.0,

    MODBUS, IEC 60870-5-101

    Synchronisation

    External synchronisation using

    IRIG-B

    PLC functions

    Built in applications

    Circuit Breaker monitoring

    Interlocking

    Transformer monitoring

    Voltage regulation

    Auto-recloser

    Synchrocheck (with coupling)

    User applications

    ISaGRAF PLC software tool

    compliant IEC 61131-3:

    Sequential function chart (SFC)

    Function Block Diagram (FBD)

    Ladder Diagram (LD)

    Structured Text (ST)

    Instruction List (IL)

    Available for

    Load shedding application

    Busbar transfer

    Etc.

    Standard compliance

    Superior construction and

    isolations in accordance with IEC

    Mixed board (8 DI / 4DO)

    8 optically insulated inputs with

    one common for 2 DI.

    UN 24, 48/60, 110/125,

    and 220/250 VDC

    4 power outputs relay (2 NO

    contacts)

    UN 250 VDC/ 230 VACSwitching 1000VA/W

    Breaking 5A at 230 VAC

    cos=0.4

    0.5 A at 220 VDCand

    L/R=40 ms

    Continu. 5 A

    Analogue Input Board

    4 isolated analogue inputs for

    measuring transducer connection.

    Range:

    Current: 1 / 2 / 5 / 10 / 20 mAVoltage: 1 / 2.5 / 5 / 10 V

    Transducerless AI Board

    TMS320C6713, DSP integrated

    32/64-Bit data word

    150 MHz clock rate

    6.7 ns Instruction cycle time

    1200 MIPS / 900 MFLOPS

    Current transfo rmers (4CT)

    Features: 1A or 5A (IN)

    0.1 VA at 1 A ,