CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
Directions for use
61221
CPS/XPS - Condensor / Dry cooler
2
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
3
CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
Declaration by the Manufacturer, Annex II B
As defined by the EC Machinery Directive (MD) 98/37/EC, the Low Voltage Directive (LVD)2006/95/EC and the EMC Directive 2004/108/EC.
Type of machinery Heat Exchangers supplied with direct cranking fans
Productdescription Unit Coolers Antarctic, EVFI, EVDL, DDXAir cooled Condensers CPS, CPM, DCPAir Coolers Antarctic, CBFI, CBDL, DDBDry Coolers XPS, XPM, XP, DXP
developed and designed in accordance with the MD 98/37/EC, LVD 2006/95/EC andEMC Directive 2004/108/EC on the own responsibility of:
Company Asarums Industri ABS. Industrivägen 2-4SE 374 50 ASARUMSweden
Harmonized Standards:
EN ISO 12100-1:2003 EN 61000-6-1EN ISO 12100-2:2003 EN 61000-6-2EN ISO 13857:2008 EN 61000-6-3EN 60204-1:2006 EN 61000-6-4EN ISO 4871
The product is not allowed to put in operation until the machine or system, which it is to beincorporated or which it is to be a part of, is in accordance with the Machinery Directive 98/37/EC.The compliance with EMC Directive 2004/95/EC is valid if the product is connected directly tothe main supply. If the product is integrated in a system or combined with other products (e.g. othercontrollers) the system manufacturer is responsible for compliance with EMC Directive 2004/95/ECfor the complete system.
Date : 2008-12-04
Signed by : Tord Engberg
Title: R&D Manager
CPS/XPS - Condensor / Dry cooler
4
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
INDEX Page
General description 5System of designations 6Receiving and fitting 7Installation 8-11Motor winding diagram 12Preventive maintenance 13-14
5
CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
General description
GeneralThis product is designed for outdoor location and is intended for refrigerants that arenot aggressive in contact with copper. The product is provided with axial fans and thecasing is made of aluminium sheeting as standard.
ImportantDo not allow the product to be covered by foreign objects when in operation.Unobstructed circulation of air is necessary to achieve the highest cooling efficiency.The laminar surfaces of the coil must be free of deposits.
1
3
4
5
2
6 7 8
9
Item Designation Item Designation Item Designation1 Cooling coil 4 Connecting pipe 7 Junction box2 Leg 5 * Air vent. 8 Fan guard grill3 * Drain 6 Axial fan 9 Safety switch*= Applies to Dry Cooler
CPS/XPS - Condensor / Dry cooler
6
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
C E 45 – 1 1 3 C – C F – 4 D 3 400 50 – 2 – X
SerieTube size code
Fan size in cm
Lines of fans
Fans per line
Coil rows deep
Fin pitch code
Product applicationC = CondensorD = Dry cooler
Product orientationF = Flat modelU = Upright model
(poles) Motor speed4 = 1400 rpm6 = 900 rpm
Motor winding connectionD = deltaY = StarYD = 2 speedS = Singel phase
Number of phases
Voltage400 = 400 V230 = 230 V
Frequency50 = 50 Hz
Number of circuits
Option above standard
System of designations
7
CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
Receiving and fittingThe product is subjected to thorough inspection of quality and function before leavingthe factory. If faults or damage due to transportation are detected on the product, thetransporter and point of sale is to be contacted without delay.
Assembly1. Move the product to the place ofinstallation before removing the packing.The cooler is provided with eyebolts (A)and shall only be lifted using theseaccording to instructions on the coolerand the directions for use.
2. The legs on are mounted in the trans-port mode during transportation. Theseare to be fitted for installation in the twoupper pairs of holes on the outermostpart.
3. Bolt the product through the pre-drilledmounting holes to a firm base.
A
CPS/XPS - Condensor / Dry cooler
8
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
Y Y
>2xY
>2xY
Y
>Y
>Y
InstallationThe following instructions should be read together with the technical leaflet.
LocationPlace the product so that air can pass freely over the entire coil surface and if possibleso that the wind direction does not affect the evacuation air because re-circulationcould otherwise occur. This applies particularly to modelsthat have low revs.The product is to be mounted on a firm base and secured with foundation bolts.The frame of the product is provided with pre-drilled holes.
9
CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
0,7 x B
0,6 x Y
A
X
Y
B
B
A
0,8 x B
0,8 x B
0,7 x Y
0,7 x Y
0,8 x B
0,8 x B
>A / 4>B / 2
0,7 x Y
>x / 4>Y / 2
>x / 4>Y / 2
0,7 x Y
>x / 4>Y / 2
>x / 4>Y / 2
0,7 x B
0,6 x Y
>A / 4>B / 2
>A / 4>B / 2
>A / 4>B / 2
X
Y
Installation
CPS/XPS - Condensor / Dry cooler
10
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
2
1
Tube installation for Condensor
The product is to be filled with the amountand type of refrigerant stated by the installa-tion engineer. The connecting tubes arelocated on one end of the unit.
The hot-gas inlet is connected to tube (1).The liquid outlet is connected to tube (2).
Tube installation for Dry Cooler
The product is to be filled with the amountand type of heat transfer medium stated bythe installation engineer. The connectingtubes are located on one end of the unit.
The air vent is at the highest point of themanifold tube (1).The incoming lead is connected to tube (2).The return lead is connected to tube (3).The drain (4) is located at the bottom of themanifold tube.
1
2
43
Installation
11
CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
InstallationInstallations may only be made byauthorised persons and in accordancewith national standards.The cooler may not be connected toother voltage or frequency than itsrated data.
Connecting the fan
To be connected to the safety switch asfollows:Loosen the screws (1) with a screwdriverand remove the cover (2). Connect thecable through the screw fitting (3) on theside of the cover.
N.B. Ensure that the fan rotates in thedirection indicated by the arrow.
Setting the motor protectorThe maximum current valu e at -30ºCis indicated on the rating plate. Referto the diagram for dimensioning ofover-current protection at otherambient temperature. The over-current protection should have anadjustment range of +/- 20%.
I
1.0
0.9
°C+10–10–300.8
–20 0
2
1
3
CPS/XPS - Condensor / Dry cooler
12
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
Motor winding diagram
3/400V 4 POLES
3/400V 6 POLES3/400V 4 POLES
3/400V 6 POLES
L1 L2 L3 PE L1 L2 L3 PE
TK TK W2 U1 U2 V1 V2 W1 TK TK W2 U1 U2 V1 V2 W1
1/230V 4 POLES
1/230V 6 POLES
TK TKU1U2
L1
Z2 Z1
3/230V 4 POLES
L1 L2 L3 PE
TK TK W2 U1 U2 V1 V2 W1
N PE
13
CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
Preventive maintenanceWarning. Make certain that the powersupply is disconnected.
StandstillDuring long periods when the unit is notin operation the fans should be run at leasttwice a month. They are to be run untilthe motor reaches normal workingtemperature, ie, about 15 minutes.
Changing the fanDisconnect the electric terminals in thejunction box for the fan (1).Remove the bolts (2) (4 off) and washersand take off the fan (3).
Mounting the fanFit the bolts (2) and washers in the fourholes.Observe that there is a tagged washerbetween the casing and the fan grille.Upright modelFit the bolts (2) and washers loosely inthe two upper holes. Then fit the lowerbolts and tighten them.
3
12
CPS/XPS - Condensor / Dry cooler
14
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
Preventive maintenance Warning. Make certain that the power supply is disconnected.
Cleaning the cooling battery
1. Cooling batteries that are lightly soiledcan be cleaned by brushing and blowingwith compressed air.
2. Then wash the battery with water andenvironment-friendly detergent that doesnot corrode aluminium or copper.Ammoniac may not be used.
3. Rinse and allow to dry.
Caution
Always wear protective gloves whencleaning or when in contact with thebatteries.
15
CPS/XPS - Condensor / Dry cooler
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
CPS/XPS - Condensor / Dry cooler
16
Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden
2009-02-10