  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    1

    Page

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    1

    1. BC8001 Series Fire Alarm Control Unit.....................................2

    BC8001 Compact Control Unit with 1 line (127 Dev) ..................................2

    BC8001P Compact Control Unit with 1 line, printer ..........................2

    BC8001E Compact Control Unit with 2 line (254 Dev).......................3

    BC8001PE Compact Control Unit with 2 line, printer.........................3

    2. BDS Series Field Device.............................................................4

    BDS051 Optical Smoke Detector.......................................................4

    BDS031 Heat Detector (Rate of Rise and Fixed)...............................4

    BDS000 Addressable Detector Base.........................................................4

    OP520 Collective Optical Smoke Detector.........................................5

    HI520 Collective Heat Detector (Rate of Rise and Fixed)..................5

    SO520 Collective Detector Base........................................................5

    BDS121 Manual Call Point.................................................................6

    BDS132 Input Module........................................................................6

    BDS221 Output Module......................................................................7

    BDS331 Fire Alarm Display Panel......................................................7

    BDS161 Collective Input Module........................................................8

    BDS152 Isolation Module...................................................................9

    3. BC80 Panels and Function Cards.............................................10

    BC8013H Wall Mounted Extinguishing Panel...................................10

    BCE8001 Extension Card.................................................................11

    BC8001 Compact CPU Board...........................................................11

    BC8001 Compact Main Board..........................................................11

    TP8000 Printer................................................................................12

    Table of ContentsPage

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    2

    BC8001 is a control unit very suitable for small size projects

    and constructions. It has the following features:

    BC8001 Series Fire Alarm Control Unit

    BC8001 Compact Control Unit with 1 line(127 Dev) A6C50000016

    Number of Detector Lines 1

    Number of Field Devices 127

    System Network -

    Built-in Printer -

    LCD Display 240 x 128, Backlit

    Auto Mapping Yes

    Event History 1000

    Digital I/O's

    - Nr. Of Dry contacts(24V/3A) 1

    - Nr. Of OC outputs 1

    - Nr. Of Monitored inputs 2

    Operating Voltage 100 ~ 240VAC,

    50 ~ 60Hz

    Battery-Backup 24V, 6.5Ah

    Download/Upload USB

    Dimension 370 x 265 x 120mm

    Weight(Without Batteries) 3.0kg

    One printer (TP8000 thermal sensitive printer) is built in with the

    features above.

    BC8001P/e BC8001P Compact Control Unit with 1 line, printer A6C50000018

    BDS series field devices compatible.

    2 Wires and polarity free F-BUS, transmission distance is

    up to 1000m.

    Specialized BDS algorithm enhance immunity to

    environment disturbances.

    Menu driven person-machine interface, very easy to operate.

    With optional extension card can be networked up to 31

    other BC80 control units(BC8001/BC8002/BC8004).

    With optional extension card, possible to connect up to 3

    B-Bus equipment like interlocking and extinguishing panels.

    Optional printer can be mounted in to the control unit.

    System can be easily configured on the panel or via PC.

    Configuration data can be uploaded to PC at any time.

    BC8001/e

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    3

    Same as BC8001, printer and extension card are built in

    additionally.

    BC8001PE/e

    An extension card is built-in additionally in the BC8001 which

    can

    Interconnect via A-Bus up to 31 controllers

    (BC8001/BC8002/BC8004 Control Unit).

    Interconnect up to 3 B-BUS equipments(BT8011/12

    interlocking panel, BC8013 extinguishing panel).

    BC8001E/e A6C50000017

    A6C50000019

    BC8001E Compact Control Unit with 2 line (254 Dev)

    BC8001PE Compact Control Unit with 2 line, printer

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    4

    The BDS051 is smoke detector which can be connected via

    F-Bus to BC80 series control unit.

    Patented labyrinth optical structure.

    New built-in ASIC ensures the high reliability of data

    processing.

    Homogeneous response to different smoke.

    High stability against dust, electromagnetic interference,

    temperature fluctuation, humidity and corrosion.

    Produced with SMT advanced technology.

    BDS Series Field Devices

    BDS051 A6C50000002

    Operating Voltage 16 ~ 32V DC

    Operating Temperature -10 ~ +50 Storage Temperature -25 ~ +75 Relative Humidity 95%(40 2) Quiescent Current 1.0mA Alarm Current 3.0mA EMC 10V/m

    Newly developed circuit and sensor ensure high perfor-

    mance of fixed and rate-of-rise temperature detection.

    High stability against dust, electromagnetic interference,

    temperature fluctuation, humidity and corrosion.

    Produced with SMT advanced technology.

    BDS031 A6C50000001

    Operating Voltage 16 ~ 32V DC

    Operating Temperature -10 ~ +50Storage Temperature -25 ~ +75Relative Humidity 95%(40 2)Quiescent Current 1.0mAAlarm Current 3.0mAEMC 10V/m

    The detector base is for mounting the field devices BDS051

    and BDS031.

    The detector covers the whole base, the wiring capacity is 1.0

    to 1.5 mm2 .

    BDS000 A6C50000000

    BDS051 Optical Smoke Detector

    BDS031 Heat Detector (Rate of Rise and Fixed)

    BDS000 Detector Base

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    The OP520 is an colletive detector can be connected in to S11

    system and BC80 system via corresponding collective input

    modules.

    Patented optical structure and labyrinth.

    Homogeneous sensitivity to different smokes.

    High stability against dust, electromagnetic interference,

    temperature fluctuation, humidity and corrosion.

    Manufactured by advanced SMT technology.

    Polarity detection and wrong connection fault-free.

    5

    OP520

    BDS Series Field Devices

    A6C50000010

    Operating Voltage 21~ 29V DC

    Output Voltage 5 ~ 13V

    Quiescent Current 100 uAOperating Temperature -10 ~ +50Storage Temperature -30 ~ +75Working Humidity 95%(40 2)EMC 10V/m

    Alarm Indicator Current 1.5mA

    Newly developed circuit and sensor ensure high perfor-

    mance of fixed and rate of rise temperature detection.

    High stability against dust, electromagnetic interference,

    temperature fluctuation, humidity and corrosion.

    Produced with SMT advanced technology.

    Operating Voltage 21 ~ 29V DC

    Output Voltage 5 ~ 13V

    Operating Temperature -10 ~ +50Storage Temperature -30 ~ +75Relative Humidity 95%(40 2)Quiescent Current 100 uAAlarm Current 1.5 mAEMC 10V/m

    HI520 Collective Heat Detector (Rate- of- Rise and Fixed) A6C50000009

    The detector base is for mounting the field devices HI520 and

    OP520.

    SO520 Collective Detector Base A6C50000011

    OP520 Collective Optical Smoke Detector

    HI520

    SO520

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    6

    Manual call point can immediate trigger a fire alarm by

    breaking the glass.

    Direct connected on the BDS F-Bus, P,S polarity free.

    Installed in the public area such as staircase, elevator

    lobby.

    Address can be set via Dip-switch.

    A built-in dry contact can be used for activating other

    equipment.

    Mounted on the wall 1.5 meters above the ground.

    Delivered electronic part and housing separately.

    BDS Series Field Devices

    BDS121 Manual Call Point A6C50000003

    Operating Voltage 24VDC

    Quiescent Current 1mAAlarm Current 3mAWorking Temperature -20 ~ +55Working Humidity 95%(40 2)Capacity of the dry contact 24VDC/ 0.1A

    EMC 10V/m

    The input module can be a interface to transmit the alarm or

    technical signal from other equipment to Fire Alarm Control Unit.

    BDS132 Input Module A6C50000004

    Operating Voltage 24VDC

    Quiescent Current 1mAActivation Current 3mAWorking Temperature -10 ~ +50Relative Humidity 95% (40 2)Wiring Capacity 1.0 ~ 1.5mm2

    Connect on the BDS F-Bus directly, address can be set

    by a built-in Dip-switch.

    Be used for interfacing the signals from flow switch,

    pressure switch, etc and other parties to the fire alarm

    system.

    Input signal has to be a potential free digital signal. The

    signal will be transmitted to controller and trigger

    corresponding activations by preset logic expressions.

    Fault will be automatic detected and displayed on the

    controller.

    BDS121/e

    BDS132/e

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    The output module is to activate external equipments according

    to the preset logic expressions and also expecting to receive a

    confirmation of activation.

    Connect on the F-Bus directly, address set via Dip-switch.

    Can activate external devices by preset logic, the output

    can be a pulse or steady signal according to Dip-switch

    set up.

    On the BDS detection line P , S can be connected with

    polarity free.

    The input signal is a potential free contact.

    Can be used for activating high voltage devices via

    connecting ZA2225 and ZA2226 in between.

    It is not recommended to use this module for extinguishing

    control directly.

    Fault will be automatic detected and displayed on the

    controller.

    Operating Voltage 24VDC

    Quiescent Current 1mAActivation Current 3mAWorking Temperature -10 ~ +50Relative Humidity 95% (40 2)Capacity of the output relay AC125V/0.6A, DC24V/2A

    Confirmation LED Steady outputSteady ON

    Pulse Output Flashing

    7

    BDS Series Field Devices

    BDS221 Output Module A6C50000007

    The panel is used for display alarm event on the floor.

    1 BDS331 can display information of the devices on the

    same F-BUS. Up to 127 devices can be displayed.

    Can display fire alarm and control information.

    The numbers of devices can be displayed on the LED

    display.

    Fault will be automatic detected and displayed on the

    controller.

    An relay output is built-in.

    Additional power supply by 24-28VDC, is necessary.

    Operating Voltage 24VDC

    Monitoring Current 6mAAlarm Current 60mAWorking Temperature -10 ~ +50Working Humidity 95% (40 2)Relay Output 125VAC/1A, 24VDC/1.25A

    BDS331/e BDS331 Fire Alarm Display Panel A6C50000008

    BDS221/e

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    8

    BDS Series Field Devices

    This collective input module can connect collective detectors

    to the F-Bus.

    Directly connected on the F-Bus, address can be set by

    Dip-switch, and the other 2 wires connect the collective

    detectors.

    Can be connected only in BC80 system.

    One BDS161 can connect up to 25 collective detectors,

    with the end of line element P6KE18CA.

    Can transmit alarm, fault, normal danger level signal to

    control unit and has also indication on the module.

    On the BDS detection line P, S can be connected with

    polarity free.

    Collective detector's terminal "1,2 and 3,4 "connected to

    BDS161 "D+ and D _ "correspondingly.

    Alarm Indicator AI340 and AI300 can be connected on "L+, L_ ".

    Fault will be automatic detected and displayed on the

    controller.

    Alarm Voltage 3.7V ~ 16.4VDC

    Fault Voltage(Short) 0V ~ 3.7VDC

    Fault Voltage(open) 22.1VDC

    Normal Voltage 16.4V ~ 22.1VDC

    Quiescent Current 4mAAlarm Current 16mAOperating Voltage -10 ~ +50Working Temperature 95% (40 2)Alarm Indicator 1.5mA

    Wiring Capacity 1.0 ~ 1.5mm2

    BDS161 Collective Input Module A6C50000006BDS161/e

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    9

    The isolation module is used for isolating the short point on

    the detection bus so that the devices which are connected to

    the controller before the short point will not be influenced. It

    will automatically recover to its normal status when the fault is

    eliminated.

    In case the short happens on the detection bus, the

    isolation module activates so that the devices before the

    short point can work normally.

    Parallel connection on the first place of each branch or

    stub.

    No need to set address.

    When one loop monitors several floors, on each floor

    one Isolation module shall be installed.

    One isolation module can connect up to 25 field devices.

    P0, S0 on BDS152 connect to control unit P,S terminal

    with polarity sensitive. The P,S terminal on BDS152 can

    connect to the P,S of other field devices with polarity free.

    Fault will be automatic detected and displayed on the

    controller.

    Working Temperature -20 ~ +50 Working Humidity 95% (40 2) Activation Current 0.5mA Pass through Voltage 1V Wiring Capacity 1.0 ~ 1.5mm2

    BDS152/e BDS152 Isolation Module A6C50000005

    BDS Series Field Devices

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    10

    BC80 Panels and Function Cards

    The extinguishing panel is used for controls of extinguishing

    section.

    Operating Voltage DC24V ~ 28V

    Quiescent Current 40.0mA

    Operating Current 200 mA

    Nominal Output Current 80mA

    Maximum Current per output 200mA

    Working Temperature -20 ~ 40

    One panel monitors 2 extinguishing section, for each

    section 3 outputs and 3 confirmation signals for those

    outputs are equipped for activation of extinguishing alert,

    extinguishing section separation, gas release.

    Can be connected via B-Bus, address set by Dip-switch,

    Information of extinguishing section can be displayed on

    the control unit.

    Parameters can be configured on panel and via PC-Tool.

    Can operate the controlled section on site or on the panel.

    External control wires are monitored automatically

    against the short.

    Panel can be set in automatic mode and manual mode.

    Auto mapping is possible.

    Fault is automatically detected and displayed on the

    panel.

    BC8013H Wall Mounted Extinguishing Panel A6C50000022BC8013H/e

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    11

    BCC8010 BC8001 Compact CPU Board

    Function of the CPU board is storing, loading the configuration

    data.

    80040600

    BCC8001 BC8001 Compact Main Board

    Function of the main board is to handle the data and event

    received from field.

    80010100

    BC80 Panels and Function Cards

    A-Bus interface can make the compact controller

    networkable to 31 controllers.

    B-Bus interface can make the controller connect up to 3

    B-Bus equipments.

    F-Bus interface can connect one detection bus

    additionally which can connect up to 127 devices more.

    BCE8001 BCE8001 Extension Card

    It is the extension card for the BC8001 compact controller.

    A6C50000024

  • BC80 Catalogue

    c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

    Type Description/Technical Data Stock Code Picture

    12

    BC80 Panels and Function Cards

    TP8000 TP8000 Printer

    A thermal sensitive printer can print out the event on the

    logger paper when event occurs.