Spark Sensor FM 1-8_eng
Transcript of Spark Sensor FM 1-8_eng
-
8/10/2019 Spark Sensor FM 1-8_eng
1/86
Spark sensor FM 1/8
Instruction manual
Spark detection and extinguisment system
-
8/10/2019 Spark Sensor FM 1-8_eng
2/86
Imprint
GreConTechnical Documentation
All rights reserved
Edition: 03.2008
Subjected to technicalmodifications.
-
8/10/2019 Spark Sensor FM 1-8_eng
3/86
-
8/10/2019 Spark Sensor FM 1-8_eng
4/86
Table of contents
4 600648 02 0
Mounting 39
Information on positioning ................................................................................................... 40General instructions ............................................................................................................ 42
Mounting a FM 1/8 ......................................................................................................... 42Mouting an FM 1/8 Ex II 1/2D ......................................................................................... 42
Mounting tools .................................................................................................................... 43Mounting the screwed-in mounting FM 1/8 and FM 1/8 Ex .................................................. 44Mounting the weld-on mounting FM 1/8 and FM 1/8 Ex ....................................................... 46Mounting the air purge adapter SPA FM 1/8 ....................................................................... 47
Mounting weld-on mounting SPA .................................................................................... 47Mounting the screwed-in mouting SPA and SPA EX ....................................................... 48Mounting the support SPA .............................................................................................. 49Mounting the support SPA Ex ......................................................................................... 49
Mounting the flange ........................................................................................................ 49Setting the throttle check valve ....................................................................................... 50Installation of the terminal boxes on the mounting plate ....................................................... 51
Fastening to mounting plate ........................................................................................... 51Pipe mouting of the assembled mouting plate ................................................................ 52Wall mouting of the assembled mouting plate ................................................................ 52
Wall mounting of the terminal box KELEX II 2/(1) D or KELEX II 3/(1) D .............................. 53 Mounting FM 1/8 without sensor mounting bracket .............................................................. 54
Welded-on mouting ........................................................................................................ 54Screwed-in mounting ..................................................................................................... 55Mouting plate for welded-on mouting .............................................................................. 56Mounting plate for screwed-in mounting .......................................................................... 57
Mounting FM 1/8 with sensor mounting bracket ................................................................. 58Locking plate for welded-on mounting ........................................................................... 58Locking plate for screwed-in mounting .......................................................................... 60Mouting plate for welded-on mounting ............................................................................ 62Mounting plate for screwed-in mounting .......................................................................... 64Mounting bracket SPA ................................................................................................... 66
Electrical installation 69
Mounting instructions for the electrical installation ............................................................... 70Electrical installation FM 1/8 ............................................................................................... 71
Connection to the control console of the type CC 700 - 724 ............................................ 71Connection to the control console of the type CC 7XXX ................................................. 72
Electrical connection FM 1/8 Ex II 1/2D ............................................................................... 74Connection to the control console of the type CC 700 - 724 ............................................ 74Connection to the control console of the type CC 7XXX ................................................. 76
-
8/10/2019 Spark Sensor FM 1-8_eng
5/86
Table of contents
600648 02 0 5
Maintenance 79
General maintenance instructions ....................................................................................... 80Carrying out maintenance work and function tests ............................................................... 81
Safety 83
Safety instructions .............................................................................................................. 84Basic rules for a safety-conscious operation .................................................................. 84Safety of the system ....................................................................................................... 85
Explosion protection .................................................................................................. 85
-
8/10/2019 Spark Sensor FM 1-8_eng
6/86
Table of contents
6 600648 02 0
-
8/10/2019 Spark Sensor FM 1-8_eng
7/86
-
8/10/2019 Spark Sensor FM 1-8_eng
8/86
Conventions
8 600648 02 0
Maintenance contract
According to German insurance regulations (Verband der Schadenversicherer (VdS)), Spark
Extinguishment Systems must be serviced regularly by a VdS-approved company. GreCon is aVdS-approved manufacturer and installation-company of spark extinguishment systems. Wetherefore recommend that you sign a GreCon service contract. This will guarantee reliableservicing and maintenance at regular intervals. This will ensure reliability and a long life of yourinstallation.
For further information, please contact our Service Department.
Technical questions and ordering of spare parts
Our Service Department is ready to deal with any technical questions and takes orders for spareparts on the following phone numbers:
Heinz Eberlie +49 51 81 / 79 - 327Hans Staudach +49 51 81 / 79 - 305
Hotline:On weekdays: 4pm-10pm +49 171 / 306 98 25Daily: 12am - 12am Only for those customers who have signed a
GreCon support contract*
* In order to conclude a GreCon support contract, please contact our Service Department.
Leakage insurance
Even Spark Extinguishment Systems may produce uncontrolled water outlet when subjected toexternal mechanical influences or unusual electrical disturbances (e. g. lightning strikes).
In general, insurance companies will add to the existing policies, at no additional cost, cover againstdamage caused by leakage from a spark extinguishment system.
We suggest you contact your responsible insurance company immediately to arrange suitablecover.
-
8/10/2019 Spark Sensor FM 1-8_eng
9/86
Conventions
600648 02 0 9
CE Conformity
GreCon products are labelled with the CE mark and meet the requirementsof the following CE standards:
CE-standard 89/336/EWG Electromagnetic Compatibilityamended by CE mark standard (93/68/EWG)
CE-standard 73/23/EWG Low-Voltageamended by CE mark standard (93/68/EWG))
CE-standard 94/9/EG Ex-Protectionamended by CE mark standard (93/465/EWG)
The harmonized standards are listed in the Declaration of Conformity.
About this instruction manual
Scope and target group
This instruction manual applies to the spark sensor FM 1/8 and all variants.
Please pay also attention to product documentations describing other systems installed in yourinstallation.
This manual is to be used by those persons who operate the system and carry out maintenanceand repairs on it.
Operators have to be trained by GreCon employees.
-
8/10/2019 Spark Sensor FM 1-8_eng
10/86
Conventions
10 600648 02 0
Symbols used in this manual
This symbol indicates useful tips or special information.This symbol indicates all important information on how to protect the product fromdamage.
This symbol indicates safety instructions for protection of persons against injury.
This symbol indicates safety instructions for protection against electric voltage.
-
8/10/2019 Spark Sensor FM 1-8_eng
11/86
600648 02 0 11
Description
-
8/10/2019 Spark Sensor FM 1-8_eng
12/86
Description
12 600648 02 0
Functional description
Spark sensors detect sparks in the infrared range. Spark sensors are sensitive to daylight.
Via a terminal box, a prefabricated three conductor cable serves to connect the spark sensors tothe control console. This console checks whether there is a broken wire or a short- circuit. Further-more, it automatically verifies whether the sensors function correctly (automatic sensor test).
Variants
In order to be able to use the spark sensor at many different plates, it is available in differentvariants. In the following, the different variants of the spark sensor FM 1/8 with their specificproperties and components are represented.
FM 1/8
Use in dust explosive atmosphere: impossible
Required components: spark sensor FM 1/8,terminal box KELEX Ex II 3/(1)D
Optional components: -
Usable fastening materials: screwed-in mounting FM 1/8Welded-on mounting FM 1/8Purge air adapter SPA FM 1/8Mounting plate for screwed-in mountingMounting plate for welded-on mountingMounting plate SPALocking plate for screwed-in mountingLocking plate for welded-on mountingLocking bracket for screwed-in and welded-onmounting
-
8/10/2019 Spark Sensor FM 1-8_eng
13/86
Description
600648 02 0 13
FM 1/8 Ex II 1/2D
Use in dust-explosive atmosphere: Material flow: Zone 20 / 21 / 22 Ambience: Zone 21 / 22
Required components: spark sensor FM 1/8 Ex II 1/2D,Terminal box KELEX Ex II 3/(1)D,Sensor mounting bracket shortConnector protection cap
Optional components: terminal box KELEX Ex II 2/(1) D
Usable fastening materials: welded-on mounting ExScrewed-in mounting Ex II 1/2DPurge air adapter SPA FM 1/8 ExMounting plate for screwed-in mounting
Mounting plate for welded-on mountingMounting plate SPALocking plate for screwed-in mountingLocking plate for welded-on mountingLocking bracket for screwed-in and welded-onmounting
-
8/10/2019 Spark Sensor FM 1-8_eng
14/86
Description
14 600648 02 0
Proper usage
The systems described in this manual can only be used together with GreCon spark
extinguishment systems.Do not make any unauthorised modifications at the system on your own. The manufactureraccepts no liability for any damage or impaired function of the system, resulting fromthis.
The manufacturer accepts no liability for any damage caued by impropre usage.
Proper usage includes observance of the instruction manual as well.
-
8/10/2019 Spark Sensor FM 1-8_eng
15/86
Description
600648 02 0 15
Technical data
Spark sensor FM 1/8 and FM 1/8 Ex II 1/2 D
Fig. 1: spark sensor FM 1/8
Supply voltage: ................................................. + 20 V 2%
Current consumption: ...................................... 10 mA 2%
Spectral response: ........................................... 780 - 1100 nm
Ambient temperature: ....................................... - 20C to + 70C
Protection class: .............................................. IP 65
Viewing angle: .................................................. 100
Material: ............................................................ aluminium die cast
Labelling: .......................................................... Ex free: none
Ex II 1/2D: GreCon Alfeld (Leine) Funkenlschanlage Typ: BS7CE 0044 II 1/2 D T80C TV 03 ATEX 2267X
IP 65/65 ID-Nr.: 58154015EX SN:.................... /.....
GreCon Alfeld (Leine) Funkenlschanlage Typ: BS7
CE 0044 II 1/2 D T80C TV 03 ATEX 2267X
IP 65/65 ID-Nr.: 58154015EX SN:.................... /.....
Labelling place: ................................................. rating plate glued on housing
-
8/10/2019 Spark Sensor FM 1-8_eng
16/86
Description
16 600648 02 0
Terminal box KELEX Ex II 3/(1) D
1
3
2
1 0 8
6 14,5 50,5
A
B
C
Fig.2: KELEX w ith hole size
1 Connection sensor 1
2 Connection console
3 Connection sensor 2
Dimensions (L x W x D): .................................. 80 mm x 120 mm x 57 mm
Protection class: .............................................. IP 65
Ambient temperature: ....................................... - 20C to + 60C
Material: ............................................................ Makrolon
Labelling: .............................................. ............
GreCon Alfeld (Leine) Funkenlschanlage BS7Typ:
CE 0044 II 3/(1) D T74C TV 02 ATEX 1838X
IP 65 ID-Nr.: 5815885EX SN:............................
GreCon Alfeld (Leine) Funkenlschanlage BS7Typ:
CE 0044 II 3/(1) D T74C TV 02 ATEX 1838X
IP 65 ID-Nr.: 5815885EX SN:............................
Labelling place: ................................................. e.g. labelling of circuit board and additional ratingplate on the housing.(Fig.4 Pos. A/B/C: rating plate / information sign)
-
8/10/2019 Spark Sensor FM 1-8_eng
17/86
Description
600648 02 0 17
Terminal box KELEX Ex II 2/(1) D
1
3
2
1 1 3
5 , 7
5
14,5 52
A
B
C C
Fig.3: KELEX w ith hole size
1 Connection sensor 12 Connection console
3 Connection sensor 2
Dimensions (L x W x D): .................................. 80 mm x 125 mm x 57 mm
Protection class: .............................................. IP 65
Ambient temperature: ....................................... - 20C to + 50C
Material: ............................................................ Aluminium
Labelling: ................................................ ..........
GreCon Alfeld (Leine) Funkenlschanlage BS7Typ:
CE 0044 II 2/(1) D T70C TV 04 ATEX 2678X
IP 65 ID-Nr.: 5815886EX SN:............................
GreCon Alfeld (Leine) Funkenlschanlage BS7Typ:
CE 0044 II 2/(1) D T70C TV 04 ATEX 2678X
IP 65 ID-Nr.: 5815886EX SN:............................
Labelling place: ................................................. e.g. labelling of circuit board and additional ratingplate on the housing.(Fig. 5 Pos. A/B/C: rating plate / information sign)
-
8/10/2019 Spark Sensor FM 1-8_eng
18/86
Description
18 600648 02 0
Mouting plate screwed-in mounting FM 1/8 and FM 1/8 Ex II 1/2 D
1
2 1
2
Fig. 4: Mounting plate, screwed-in mounting
1 Diagonal screwed-in position for KELEX II 3/(1)D
2 Diagonal screwed-in position for KELEX II 2/(1) D
Material (material number): .............................. 1.4305
Labelling: .......................................................... mounting plate Ex: 581564EX.01
Labelling place: ................................................. marked on component with a laser
-
8/10/2019 Spark Sensor FM 1-8_eng
19/86
Description
600648 02 0 19
Locking plate screwed-in mounting FM 1/8 and FM 1/8 Ex II 1/2 D
Fig. 5: Locking plate, screwed-in mounting
Material (material number): .............................. 1.4305
Labelling: .......................................................... locking plate Ex: 581564EX.02
Labelling place: ................................................. marked on component with a laser
-
8/10/2019 Spark Sensor FM 1-8_eng
20/86
Description
20 600648 02 0
Mouting plate welded-on mounting FM 1/8 and FM 1/8 Ex II 1/2 D
1
2 1
2
Fig. 6: Mounting plate, welded-on mounting
1 Diagonal screwed-in position for KELEX II 3/(1)D
2 Diagonal screwed-in position for KELEX II 2/(1) D
Material (material number): .............................. 1.4305
Labelling: .......................................................... mounting plate Ex: 58156615EX.06
Labelling place: ................................................. marked on component with a laser
-
8/10/2019 Spark Sensor FM 1-8_eng
21/86
Description
600648 02 0 21
Locking plate welded-on mounting FM 1/8 and FM 1/8 Ex II 1/2 D
Fig. 7: Locking plate, welded-on mounting
Material (material number): .............................. 1.4305
Labelling: .......................................................... locking plate Ex: 58156615EX.05
Labelling place: ................................................. marked on component with a laser
-
8/10/2019 Spark Sensor FM 1-8_eng
22/86
Description
22 600648 02 0
Securing bracket for screwed-in and welded-on mounting FM 1/8 and FM 1/8 Ex II 1/2 D
Fig. 8: Securing bracket for screwed-in and welded-on mounting
Material (material number): .............................. 1.4305
Labelling: .......................................................... 581564EX.04
Labelling place: ................................................. marked on component with a laser
-
8/10/2019 Spark Sensor FM 1-8_eng
23/86
Description
600648 02 0 23
Mounting plate for purge air adapter SPA
Fig. 9: Mounting plate for SPA
Material (material number): .............................. 1.4305
Labelling: .......................................................... mounting plate Ex: 5814948EX.1
Labelling place: ................................................. marked on component with a laser
-
8/10/2019 Spark Sensor FM 1-8_eng
24/86
Description
24 600648 02 0
Screwed-in mounting FM 1/8
Fig. 10: E xample of screwed-in mounting
1 = support 3b = Washer Ex
2 = Washer, slotted 4 = nut
3a = Washer without slot 5 = O-ring
Screwed-in mounting FM 1/8
Hole diameter for mounting: ............................. 32 mm
Material (material number): .............................. 1.4305
Labelling: .......................................................... none
-
8/10/2019 Spark Sensor FM 1-8_eng
25/86
Description
600648 02 0 25
Installation dimensions
120
3 0
5 4
84
1 1 5
5 0
90
135
4 0
23
Fig. 11: Installation dimensions if screwed-in sensor mounting FM 1/8 is used
-
8/10/2019 Spark Sensor FM 1-8_eng
26/86
Description
26 600648 02 0
2:1
KELEX II 3 (1)D 120x80x57
108
13
KELEX II 2 (1)D 152x80x57
130
8 0
5 2
5 0
, 5
2 0 0
2 5 0
6 9
57
8 0
75
7 , 5
2 9
, 5
4 2
5 0
4 2
135
4 0
2323
Fig. 12: Installation dimensions if screwed-in sensor mounting and a mounting plate is used
-
8/10/2019 Spark Sensor FM 1-8_eng
27/86
Description
600648 02 0 27
Screwed-in mounting FM 1/8 Ex II 1/2D
A B C
D E F G
Fig. 13: E xample of screwed-in mounting
A = washer with slot E = support
B = Silicone sealing F = grooves for O-rings
C = Locking plate G = Locking groove
D = Nut
Screwed-in mounting FM 1/8 Ex II 1/2D
Hole diameter for mounting: ............................. 32 mm
Material (material number): .............................. 1.4305
Labelling: .......................................................... 581564EX
Labelling place: ................................................. marked on component (C) with a laser
Screwed-in sensor mounting EX must not be mounted on bend places(e.g.pipes).
-
8/10/2019 Spark Sensor FM 1-8_eng
28/86
Description
28 600648 02 0
Welded-on mounting FM 1/8 and FM 1/8 Ex
Fig. 14: W eld-on sensor mounting
1 = O-ring 2 = slot for washer
Weld-on sensor mounting FM 1/8
Diameter of required hole: ................................ 40 mm
Material (material number): .............................. 1.4305
Labelling: .......................................................... none
Weld-on sensor mounting FM 1/8 Ex
Diameter of required hole: ................................ 40 mm
Material (material number): .............................. 1.4305
Labelling: .......................................................... 581568EX
Labelling place: ................................................. marked on component with a laser
-
8/10/2019 Spark Sensor FM 1-8_eng
29/86
Description
600648 02 0 29
Installation dimensions
120
3 0
5 4
84
90
5 0
1 1 5
135
4 0
23
Fig. 15: Installation dimensions if weld-on sensor mounting FM 1/8 is used
-
8/10/2019 Spark Sensor FM 1-8_eng
30/86
Description
30 600648 02 0
KELEX II 3 (1)D 120x80x57
108
13
KELEX II 2 (1)D 152x80x57
130
8 0
5 2
5 0
, 5
2 0 0
2 5 0
6 9
2 9
. 5
4 2
7 . 5
4 2
5 0
8 0
57
75
X (2:1)
X
135
4 0
23
Fig. 16: Installation dimensions if weld-on sensor mounting and a mounting plate is used
-
8/10/2019 Spark Sensor FM 1-8_eng
31/86
Description
600648 02 0 31
Air purge adapter SPA FM 1/8
Fig. 18: SPA FM 1/8 incl. screwed-in sensor mounting SPA,
Legend
1 = flange for FM 1/8
2 = Support, not Ex with throttle valve
3 = Weld-on sensor mounting SPA
4 = Screw-in sensor mounting SPA
4a = Compression seal
SPA FM 1/8 incl. weld-on sensor mounting SPA
Mouting place: .................................................. inside: ex free zoneoutside: ex free zone
SPA FM 1/8 incl. screwed-in sensor mounting SPA
Mouting place: .................................................. inside: ex free zoneoutside: ex free zone
-
8/10/2019 Spark Sensor FM 1-8_eng
32/86
Description
32 600648 02 0
Air purge adapter SPA FM 1/8 ex
Fig. 19: SPA FM 1/8 Ex incl. weld-on sensor mounting -SPA
1a 2 4
b a
Fig. 20: SPA FM 1/8 Ex with screwed-in sensor mounting-SPA
Legend
1a = flange for FM 1/8
1b = Flange ex for FM 1/8 with connection for locking plate
2 = Support Ex with cutting ring screwing
3 = Weld-on sensor mounting SPA
4 = Screw-in sensor mounting SPA
4a = Silicone sealing
4b = Metal plate
SPA FM 1/8 Ex incl. weld-on sensor mounting SPA
Mounting place: ................................................ inside: zone 20 / 21outside: zone 21 / 22 / Ex free zone
SPA FM 1/8 Ex incl. screwed-in-mounting SPA
Mounting place: ................................................ inside: zone 20/21outside: zone 21/22 / Ex free zone
-
8/10/2019 Spark Sensor FM 1-8_eng
33/86
Description
600648 02 0 33
Air purge adapter SPA FM 1/8
Compressed air consumption: ......................... 0-35 l/min at 1.5 bar (reference value)
Minimum operating pressure: ........................... 1,5 bar referred to the compressed air connection
of the air purge adapterConnection pipe: .............................................. compressed air hose 8 mm
Material (material number): .............................. 1.4305
Labelling: .......................................................... none
Air purge adapter SPA FM 1/8 Ex
Compressed air consumption: ......................... 0-35 l/min at 1.5 bar (reference value)
Minimum operating pressure: ........................... 1,5 bar referred to the compressed air connectionof the air purge adapter
Connection pipe: .............................................. Copper pipe 8 mm
Material (material number): .............................. 1.4305
Labelling: ................................................ .......... weldable 1/2D 581499.001Exscrewable 3/3D 581499.40EXscrewable 1/2D 581564EX
Labelling place: ................................................. e.g. identification number glued on support
-
8/10/2019 Spark Sensor FM 1-8_eng
34/86
Description
34 600648 02 0
If the spark sensor FM 1/8 with the SPA FM 1/8 is used, the used mountingdepends on the properties of the installation site.The mounting bracket to be used depends on the ambient temperatureand the wall thickness of the transport pipe. For wall thicknesses smallerthan or equal to 3mm ,a screwed-in mounting should be used. If the wallthickness of the transport pipe is larger than 3mm, a weld-on mounting hasto be used.
At the installation site, the welded-on mounting SPA can be used in non-explosive environments and at ambient temperatures below 70C as gluedmountings also. Here, it must be rememberd that the glueing may only bedone with a special glueing and sealing putty(Loctite 5221).
Screwed-in mounting SPA FM 1/8 Ex may only be used from a pipe-width of400 mm onwards, since otherwise, there is a fear of zone dragging.
-
8/10/2019 Spark Sensor FM 1-8_eng
35/86
Description
600648 02 0 35
Installation dimensions
135
84
5 0
4 0
5 4
150
4 0
23
5 0
5 2
6 7
84
Fig. 21: Installation dimensions when using an SPA in the Ex free zone and in the Ex zone
-
8/10/2019 Spark Sensor FM 1-8_eng
36/86
Description
36 600648 02 0
60
135
4 0
6 7
5 0
84
8 0
64
2 5 0
Fig. 22: Installation dimensions when using an SPA and a terminal box in the Ex free zone
-
8/10/2019 Spark Sensor FM 1-8_eng
37/86
Description
600648 02 0 37
150
4 0
64
2 5 0
5 2
6 7
5 0
84
8 0
23
Fig. 23: Installation dimensions when using an SPA and a terminal box in the Ex zone
-
8/10/2019 Spark Sensor FM 1-8_eng
38/86
Description
38 600648 02 0
-
8/10/2019 Spark Sensor FM 1-8_eng
39/86
600648 02 0 39
Mounting
-
8/10/2019 Spark Sensor FM 1-8_eng
40/86
Mounting
40 600648 02 0
Information on positioning
These instructions only refer to transport pipes. If you wish to use thesensors somewhere else, please contact the GreCon agent responsible foryour company.He/ she will give you information on how to position thesensors correctly.
False alarm produced by light incidence
Incident light, e.g. via defective or open pipes, inspection flaps or windows,can cause false alarms.
Seal the transport pipe against incident light in order to prevent false alarms.
In the case of transport pipe being equipped with flaps for taking samples, disable thecorresponding line while taking samples.
Protecting the sensor optics system against dirt
Do not mount the spark sensor at the bottom of the transport pipe !Material deposits or extinguishing water flowing back contaminate the lower sensor opticssystem.
Installation for a horizontal pipe
Fig. 24: Installation for a horizontal pipe
-
8/10/2019 Spark Sensor FM 1-8_eng
41/86
Mounting
600648 02 0 41
Protecting the sensor optics system against wear
Installation in pipe bends
Fig. 25: Installation in, behind or in front of bends
A Transportation direction
B min.2000mm
Do not mount spark sensors directly in pipe bends!Generally, you have to mount them behind or in front of bends.
Installation behind a fan
Fig. 26: Installation behind a fan
A min. 1500
Do not mount the spark sensors directly in the blow direction of the fan!Sparks produced by the fan can cause spark alarms.
-
8/10/2019 Spark Sensor FM 1-8_eng
42/86
-
8/10/2019 Spark Sensor FM 1-8_eng
43/86
Mounting
600648 02 0 43
Mounting tools
Fig.. 27: M ounting fixture
A Locking for mounting screwed-in mountingB Mounting screwed-in mounting and weld-on mounting
Abb. 28: Mounting device SPA
A WingB Twist gripC Theaded rodD O-ring
-
8/10/2019 Spark Sensor FM 1-8_eng
44/86
Mounting
44 600648 02 0
Mounting the screwed-in mounting FM 1/8 and FM 1/8 Ex
Define where to mount the sensor.
Drill a hole into the pipe: 32 mm.
Remove the circular cutter very carefully sothat the opening material does not fall into thepipe.
Insert the two o-rings into the inner slots (B) ofthe support (A).
Place the individual parts on the mountingdevice.
Please observe the following order:
1 = nut2 = washer, round3 = washer, with slot4 = support
Fig. 29: E xample of screwed in mounting
For mounting the screwed-in mounting EX II 1/2D,2 is replaced by a silicone sealing and sensormounting bracket.
-
8/10/2019 Spark Sensor FM 1-8_eng
45/86
Mounting
600648 02 0 45
Insert the support and the ring (with slot) intothe hole.
Pull the mounting device back until the threadof the support juts out of the hole and the ring(with slots) touches the inner wall.
Push the round washer against the outer wall.
Screw the nut on the support and tighten itusing a wrench.
Pull the mounting tool out of the screwed-inmounting.
Abb. 30: M ounting the screwed in mounting
-
8/10/2019 Spark Sensor FM 1-8_eng
46/86
Mounting
46 600648 02 0
Mounting the weld-on mounting FM 1/8 and FM 1/8 Ex
Before mounting, make sure that the o-rings are not yet situated in the innerslots of the weld-on mounting.
Define the installation site.
Drill a hole into the pipe: 40 mm.
Mark the wall thickness on the weld-onmounting (1). The wall thickness correspondsto the weld depth. Thus, the weld-on mountingis even with the pipe wall.
Place the weld-on mounting on the mountingtool (2).
Secure the weld-on mounting against shiftingon the mounting tool by tightening the wingscrew or socket screw.
Insert the weld-on mounting into the hole sothat its marking is even with the outer side ofthe pipe.
Locate the weld-on mounting by means of twowelding points.
Remove the mouting device (2).
Weld the mounting by creating a circular seamusing the step-back welding process.
Fig. 31: M ounting a weld on mounting
Insert both the two delivered o-rings into theinner slots of the screwed-in mounting.
The weld-on mounting has to be mounted in the pipe such that the guideslot for the washer is directed to the outside.
-
8/10/2019 Spark Sensor FM 1-8_eng
47/86
Mounting
600648 02 0 47
Mounting the air purge adapter SPA FM 1/8
Mounting weld-on mounting SPA
The weld-on mounting is made of high-grade steel 1.4301.Use adeqate electrodes for the welding process.
Define the installation site.
Drill a hole into the pipe: 50 mm.
Remove the circular cutter very carefully sothat the opening material does not fall into thepipe.
Insert the mounting into the hole.
Locate the weld-on mounting by means of twowelding points.
Remove the mouting device (2).
Weld the mounting by creating a circular seamusing the step-back welding process.
Fig. 32: Weld-on mounting SPA
Alternatively, the mounting can be glued at the installation site with Loctite5221. Follow the processing instructions for the glue.
-
8/10/2019 Spark Sensor FM 1-8_eng
48/86
Mounting
48 600648 02 0
Mounting the screwed-in mouting SPA and SPA EX
For mounting the screwed-in-mounting, a wrench (wrench
size 50mm) is necessary.
Define the installation site.
Drill a hole into the pipe: 50 mm.
Remove the circular cutter very carefully sothat the opening material does not fall into thepipe.
Push the individual parts of the screwed-inmounting loosely on the mounting tool in the
following order.1. Ring nut2. Compression sealing (or metal plate andsilicone sealing in the ex-zone)3. Metal ring with slots4. Support (screwed-in mounting)
Locate the support on the wrench!By turning the twist grip in a clockwisedirection, the o-ring is queezed. It expands tothe side and holds the screwed-in mounting.
Insert the screwed-in mounting and the meatalring with slots into the bore hole and pull themounting tool towards yourself when the metalring with slots touches the inner wall of thepipe.
Place the compression sealing ring, or in theEx zone the silicone sealing and then themetal ring on the screwed-in mounting.
Now turn the ring nut on the support and
tighten it by means of the wrench (wrench size50).
Turn the twist grip of the mounting tool back.The o-ring expands and you can take out thewrench.
If the screwed-in mounting is not tightendenough, insert the wing of the mounting toolinto the slots of the mounting and tighten itagain with the wrench.
Fig. 33: M ounting the screwed-in mounting SPA
-
8/10/2019 Spark Sensor FM 1-8_eng
49/86
-
8/10/2019 Spark Sensor FM 1-8_eng
50/86
Mounting
50 600648 02 0
Setting the throttle check valve
First, set the valve in such a manner that as little airas possible flows through it. There should be a slightair flow tangible before the purge air adapter.
Observe the degree of fouling at the sensor visual
Open the valve a little in case of excess fouling,to facilitate a greater air flow.
In this manner, feel your way to the optimumcompressed air consumed for the given conditions.
The objective is to get the optimum relationshipbetween degree of fouling and compressed airconsumption.
Fig. 36: Throttle check valve
-
8/10/2019 Spark Sensor FM 1-8_eng
51/86
Mounting
600648 02 0 51
Installation of the terminal boxes on the mounting plate
Fastening to mounting plate
12
1 2
Fig. 37: Fastening on the mounting plate
1 Diagonal screwed-in position for KELEX II 3/(1)D
2 Diagonal screwed-in position for KELEX II 2/(1) D
-
8/10/2019 Spark Sensor FM 1-8_eng
52/86
Mounting
52 600648 02 0
Pipe mouting of the assembled mouting plate
When using a screwed-in mounting or a purge air adapter, the mounting plate can be mounteddirectly on the pipe. In this case, the mounting plate is placed in front of the washer (without slot) onthe support of the screwed-in mounting or is placed between the support SPA and the mountingSPA.
A
B
A
B
A A
Fig. 38: Mounting for horizontal and vertical pipes
A Sensor
B Terminal box mounted on mounting plate
Wall mouting of the assembled mouting plate
For wall mouting of the mouting plate, please use the two holes ( 5mm) of the mouting plate.Theses holes are used to attach the mounting plate to the wall by means of adequate screws anddowels.
Fig. 39: Mounting for horizontal and vertical pipes
-
8/10/2019 Spark Sensor FM 1-8_eng
53/86
Mounting
600648 02 0 53
Wall mounting of the terminal box KELEX II 2/(1) D or KELEX II 3/(1) D
Fig.. 40: W all mounting
The terminal boxes can be directly mounted to the wall..
Use the housing as a template in order to mark the boreholes.Drill a corresponding number of dowel holes.
Provide each hole with a corresponding dowel.
Fasten the components with the help of screws that are screwed in dowels.
-
8/10/2019 Spark Sensor FM 1-8_eng
54/86
Mounting
54 600648 02 0
Mounting FM 1/8 without sensor mounting bracket
Welded-on mouting
Fig. 41: Mouting of FM 1/8 with welded-on mouting
Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
-
8/10/2019 Spark Sensor FM 1-8_eng
55/86
Mounting
600648 02 0 55
Screwed-in mounting
1
2
Fig. 42: Mouting of FM 1/8 with screwed-in mouting
Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
-
8/10/2019 Spark Sensor FM 1-8_eng
56/86
Mounting
56 600648 02 0
Mouting plate for welded-on mouting
1
2 3
Fig. 43: Installation of FM 1/8 with mounting plate for welded-on holder
Remove the bracket at the top of the mounting plate by bending it back and forth severaltimes.
Push the mounting plate from the side onto the welded-on mounting.
Fix the mounting plate with a welding spot on the welded-on mounting.
Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
-
8/10/2019 Spark Sensor FM 1-8_eng
57/86
Mounting
600648 02 0 57
Mounting plate for screwed-in mounting
2
11
Fig. 44: Installation of FM 1/8 with mounting plate for screwed-on holder
Remove the bracket at the top of the mounting plate by bending it back and forth several
times.Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
-
8/10/2019 Spark Sensor FM 1-8_eng
58/86
Mounting
58 600648 02 0
Mounting FM 1/8 with sensor mounting bracket
Locking plate for welded-on mounting
1
23
4
A
A
Fig. 45: Installation of FM 1/8 Ex with locking plate for welded-on holder
-
8/10/2019 Spark Sensor FM 1-8_eng
59/86
Mounting
600648 02 0 59
Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
Put the connection cable through the screwed cable gland of the connector protection cap.
Attach the connector protection cap with two screws =to the spark sensor (3).
Push the locking plate from the side onto the spark sensor (4).
Fasten the locking bracket with 2 screws and 4 insulating washers on the plug protection cap.
Fasten the locking bracket with a screw to the locking plate. .
The insulating disks seperate the electric potentials from the pipe and thesensor.
-
8/10/2019 Spark Sensor FM 1-8_eng
60/86
Mounting
60 600648 02 0
Locking plate for screwed-in mounting
2
3
1
A
A
Fig. 46: Installation of FM 1/8 Ex with locking plate for screwed-in holder
-
8/10/2019 Spark Sensor FM 1-8_eng
61/86
-
8/10/2019 Spark Sensor FM 1-8_eng
62/86
Mounting
62 600648 02 0
Mouting plate for welded-on mounting
1
2
34
A A
Fig. 47: Installation of FM 1/8 Ex with mounting plate for welded-on mounting
-
8/10/2019 Spark Sensor FM 1-8_eng
63/86
Mounting
600648 02 0 63
Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
Put the connection cable through the screwed cable gland of the connector protection cap.
Attach the connector protection cap with two screws =to the spark sensor (3).
Bend the locking bracket on the mounting plate through 90 as can be seen on the drawing.
Push the mounting plate with the terminal box on it from the side onto the spark sensor (4).
Fasten the locking bracket with 2 screws and 4 insulating washers on the plug protection cap.
Fasten the locking bracket with a screw to the mounting plate.
The insulating disks seperate the electric potentials from the pipe and thesensor.
-
8/10/2019 Spark Sensor FM 1-8_eng
64/86
Mounting
64 600648 02 0
Mounting plate for screwed-in mounting
23
1
A A
Fig. 48: Installation of FM 1/8 Ex with mounting plate for screwed-in mounting
-
8/10/2019 Spark Sensor FM 1-8_eng
65/86
Mounting
600648 02 0 65
Bend the locking bracket on the mounting plate through 90 as can be seen on the drawing.
Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
Put the connection cable through the screwed cable gland of the connector protection cap.
Attach the connector protection cap with two screws =to the spark sensor (3).
Fasten the locking bracket with 2 screws and 4 insulating washers on the plug protection cap.
Fasten the locking bracket with a screw to the locking plate.
The insulating disks seperate the electric potentials from the pipe and thesensor.
-
8/10/2019 Spark Sensor FM 1-8_eng
66/86
Mounting
66 600648 02 0
Mounting bracket SPA
Fig. 49: Installation of FM 1/8 Ex with mounting plate SPA
-
8/10/2019 Spark Sensor FM 1-8_eng
67/86
Mounting
600648 02 0 67
Insert sensor optics into the mounting by pushing and simultaneously distorting it (1).
Screw the connector to the connection terminal on the spark sensor (2).
Put the connection cable through the screwed cable gland of the connector protection cap.
Attach the connector protection cap with two screws and four insulating disks to the sparksensor (3).
Place the sensor mounting bracket from above on the spark sensor(4).
Attach the sensor mounting bracket with two screws and two insulating disks to the sparksensor. By means of a third screw attach the sensor mounting bracket to the air purgeadapter.
The insulating disks seperate the electric potentials from the pipe and thesensor. The insulating disks have to be inserted such that the bead fits into
the hole.
-
8/10/2019 Spark Sensor FM 1-8_eng
68/86
Mounting
68 600648 02 0
-
8/10/2019 Spark Sensor FM 1-8_eng
69/86
-
8/10/2019 Spark Sensor FM 1-8_eng
70/86
-
8/10/2019 Spark Sensor FM 1-8_eng
71/86
Electrical connection
600648 02 0 71
Electrical installation FM 1/8
Connection to the control console of the type CC 700 - 724
IO 71
IO 71
MFB
MFB
A
A
B
B
A
A
B
B
C
C
C
C
KELEX 3/(1) D
KELEX 3/(1) D
FM 1/8
FM 1/8 FM 1/8
A
A A
A
A
A
A
A1
A1
B
B B
B
B
B
B
B
B
C
C C
C
C
C
C
C
C
A2
A2
1
1 1
1
1
1
1
1
1
2
2 2
2
2
2
2
2
2
3
3 3
3
3
3
3
3
3
1
1
on S1
on S1
Console
Console
on S1
Console
Console
Fig. 52: Connection of one or two spark sensors FM 1/8
-
8/10/2019 Spark Sensor FM 1-8_eng
72/86
Electrical connection
72 600648 02 0
Connection to the control console of the type CC 7XXX
I01I01T
3I01I01T
4
I02TI02
19
I02TI02
20
KELEX II 3/(1) D
FM 1/8
A
A A A1
B
B B B
C
C C C A2
1
1 1 1
2
2 2 2
3
3 3 3 1
on S1
Line modulepossible connecting terminals
Line modulepossible connecting terminals
Fig. 53: Connection of a spark sensor FM 1/8
-
8/10/2019 Spark Sensor FM 1-8_eng
73/86
-
8/10/2019 Spark Sensor FM 1-8_eng
74/86
Electrical connection
74 600648 02 0
Electrical connection FM 1/8 Ex II 1/2D
Connection to the control console of the type CC 700 - 724
IO 71MFB
A B A B C
C
KELEX II 3/(1)DKELEX II 2/(1)D
FM 1/8
A
A A A1
B
B B B
C
C C C A2
1
1 1 1
2
2 2 2
3
3 3 3 1
on S1
ConsoleConsole
Fig. 55: Connecting an FM 1/8 Ex II 1/2D
-
8/10/2019 Spark Sensor FM 1-8_eng
75/86
Electrical connection
600648 02 0 75
IO 71MFB
A B A B C
C
KELEX II 3/(1)DKELEX II 2/(1)D
FM 1/8
A
A A A1
B
B B B
C
C C C A2
1
1 1 1
2
2 2 2
3
FM 1/8
A B C1 2 3
3 3 3 1
on S1
ConsoleConsole
Fig. 56: Connecting two spark sensors FM 1/8 Ex II 1/2D
-
8/10/2019 Spark Sensor FM 1-8_eng
76/86
Electrical connection
76 600648 02 0
Connection to the control console of the type CC 7XXX
TestGND
3
TestGND
4
TestGND
19
TestGND
20
KELEX II 3/(1)DKELEX II 2/(1)D
FM 1/8
A
A A A1
B
B B B
C
C C C A 2
1
1 1 1
2
2 2 2
3
3 3 3 1
on S1
Line modulepossible connecting terminalsLine modulepossible connecting terminals
Fig. 57: Connection of a spark sensor FM 1/8 Ex II 1/2D and FM 1/8 VEx II 1/2D
-
8/10/2019 Spark Sensor FM 1-8_eng
77/86
Electrical connection
600648 02 0 77
KELEX II 3/(1)DKELEX II 2/(1)D
FM 1/8 FM 1/8
A A
A A A1
B B
B B B
C C
C C C A 2
1 1
1 1 1
2 2
2 2 2
3 3
3 3 3 1
on S1
3 4 19 20I01I01T
I01I01T I02T
I02I02TI02
Line modulepossible connecting terminals
Line modulepossible connecting terminals
Fig. 58.: Connection of two spark sensors FM 1/8 Ex II 1/2D and FM 1/8 VEx II 1/2D
-
8/10/2019 Spark Sensor FM 1-8_eng
78/86
Electrical connection
78 600648 02 0
-
8/10/2019 Spark Sensor FM 1-8_eng
79/86
600648 02 0 79
Maintenance
-
8/10/2019 Spark Sensor FM 1-8_eng
80/86
Maintenance
80 600648 02 0
General maintenance instructions
This chapter describes maintenance measures and function tests you haveto carry out in the given intervalls.The explained maintenance measures comprise preventive measures aswell as cleaning of the system components. Maintenance measures carriedout regularly make your spark extinguishment system more safe andreliable.
All maintenance measures and function tests are to be carried out byspecially trained personnel only.
You must enter all maintenance measures carried out in the operators logand sign them.
-
8/10/2019 Spark Sensor FM 1-8_eng
81/86
Maintenance
600648 02 0 81
Carrying out maintenance work and function tests
Before carrying out the required maintenance measures, switch off the linesat the control console.
Function tests carried out at the control console:
Every four hours, the control console automatically checks the correctfunctioning of the sensors. The console simulates alarms in the sensorsand then tests their reaction. If the console finds out that the monitoringfunction of a sensor does not work correctly, it will display this error. Thetest serves to determine whether the sensors will function correctly if a real
alarm occurs.The operating menu of the control console serves to manually activate thisfunction test for each monitoring line separately. The manual test and theautomatic test are identical. The result of the manual test appears on thedisplay as well.
Maintenance interval: monthly
Remove the sensor from its mounting.
Check whether the optics system fits tightly and whether it is defective or worn.
Check whether the mounting is defective or worn.Check whether the cable glands are leakproof and whether they function correctly.
-
8/10/2019 Spark Sensor FM 1-8_eng
82/86
Maintenance
82 600648 02 0
-
8/10/2019 Spark Sensor FM 1-8_eng
83/86
-
8/10/2019 Spark Sensor FM 1-8_eng
84/86
Safety
84 600648 02 0
Safety instructions
The reliable GreCon Spark Extinguishment Systems correspond to the latest state of the art, are
manufactured in accordance with the accepted rules of engineering and are safe and reliable. It is,however, required that you observe various safety instructions for all activities which will protect youagainst injury and the system against damage.
Therefore, please read the safety instructions and this manual carefully.
Basic rules for a safety-conscious operation
Documentation
Always keep the documentations at hand.
Operation
Ensure that the Spark Extinguishment System is exclusively operated by personnel who receivedspecific training to do so by GreCon service engineers during commissioning.
Rules
For any activities please observe the rules valid in your location, e.g. rules of the public utilities.
Production stop
Mouting, maintenance and replacement of components may only be done with the production plantshut down.
Work safety
If you have to carry out the required work on ladders or working platforms, please protect yourselffrom falling.
-
8/10/2019 Spark Sensor FM 1-8_eng
85/86
Safety
600648 02 0 85
Safety of the system
Qualified personnel
Installation, maintenance and service work is to be carried out by qualified and trained personnelonly.
Comissioning
Commissioning is to be done bz GreCon sercice engineers only or bz personnel authoriyed bzGreCon to do so.
Maintenance of the system
A GreCon Spark Extinguishment System is part of the system-safety installation. Operate the sparkextinguishing system only in a technically impeccable condition.
According to German insurance regulations (Verband der Schadenversicherer (VdS)), SparkExtinguishment Systems must be serviced at least once a year by a VdS-approved company. If thesystem is extremely dirty or if it is charged up to 100%, you have to service it several times a year.
Eliminate any trouble immediately after its appearance. In case there is a trouble that you cannoteliminate by yourself, please contact either the GreCon Service Department or a GreCon agentnear your site.
Choice of installation site
Considering technical prerequisites, installation sites have to be chosen in a way that the systemcan be reached easily for maintenance work. (see VDS Directive 2106 Edition 5/2003, Paragraphs3.2 and 4.8). Compliance is required with the conditions according to the Technical Data.
Explosion protection
For spark sensors in dust explosive atmosphere the following applies: The housing of the sensor may only be opened in a zero voltage condition.
The connector may be pulled only when the system is switched off for at least 3 seconds.
For terminal boxes in dust explosive atmosphere the following applies:
Only open the housing after the plant has been switched off for at least 3 seconds.
Dust layers larger than 3 mm must be removed. Terminal boxes may only be wiped moistly.
-
8/10/2019 Spark Sensor FM 1-8_eng
86/86