_B16-B24_ Instructie Manual Cassette inverter 2012 (4,03 MB)
PV Inverter Seminar
Transcript of PV Inverter Seminar
-
7/28/2019 PV Inverter Seminar
1/23
Testing grid-connected PV-inverters
for compliance in different countries
By Grady YeIntertek Testing Services Guangzhou
2011-05
-
7/28/2019 PV Inverter Seminar
2/23
Country Safety Grid-tied
USA UL 1741 IEEE 1547
Canada CSA C22.2 No. 107.1 CSA C22.2 No. 107.1
Germany EN 62109-1, EN 62109-2 VDE 0126-1-1
Spain EN 62109-1, EN 62109-2 RD 1663
UK EN 62109-1, EN 62109-2 ER G83/1 (16A)
ER G59/1 (16A)
EU EN 62109-1, EN 62109-2 EN 50438
Australia AS/NZS 3100 AS 4777.2, AS 4777.3
PV-inverter Regulation/Standard List
-
7/28/2019 PV Inverter Seminar
3/23
Typical Testing for PV Inverter
-
7/28/2019 PV Inverter Seminar
4/23
PVI Enclosure Design (1/2)
Outdoor use: Water, Dust, Temperature, UV, Corrosion
:
US requirement: NEMA xx, tested to UL 50E
: NEMA xx,UL50E
PV-inverter commonly rated NEMA 3R
3R
NEMA 3R: Rain test
-
7/28/2019 PV Inverter Seminar
5/23
PVI Enclosure Design (2/2)
Gasket may be required and tested
European market: Follow the IPxx IPxx
IEC/EN 60529 to be followed IEC/EN 60529
PV inverter is commonly rated IP65 or IP54 IP65 or IP54
-
7/28/2019 PV Inverter Seminar
6/23
Spacings/Clearances/Creepages
UL 1741: Basic requirement 12.7 mm (between live partsand enclosure)
UL 174112.7 mm ()
Decided by working voltage & mains voltage which isinfluenced by DC input voltage and inverter topology.
AC &DC
-
7/28/2019 PV Inverter Seminar
7/23
GFDI (Ground Fault Detection/Interruption)
UL 1741 requires a GFDI for PV-inverter to protect againstfire hazard
UL 1741GFDI
Four functions of GFDI GFDI detecting a ground fault,
providing an indication of the fault,
interrupting the flow of fault current, and
either isolating the faulted array section or disabling the inverter to cease
the export of power.
-
7/28/2019 PV Inverter Seminar
8/23
Output overload test
UL 1741 requires the output of the inverter be protectedagainst overload.
UL1741
If protection is achieved by a software, firmware & DSPThe software shall be evaluated to UL1998 (additional cost
and additional testing time), and sensing circuit shall be
special evaluated.
,
UL1998
-
7/28/2019 PV Inverter Seminar
9/23
Surge Test
UL 1741 requires GFDI subjected to surge testing
UL 1741GFDI
Ring wave surge: 0.5 s (10-90%), oscillatory wave 10 s,3 kV / 6 kV
After surge Calibration test to GFDI
GFDI
-
7/28/2019 PV Inverter Seminar
10/23
IEC 62109 Special Requirement
A new standard which harmonizes American standardsUL1741 & IEEE 1547, IEC standards IEC 60950 & IEC
62103, and German standard VDE 0126-1-1
Concept from UL 1741: Input and output powercharacteristic, Abnormal tests, Markings
UL1741
-
7/28/2019 PV Inverter Seminar
11/23
IEEE 1547 Voltage trip
Overvoltage: 110% - 120% UN < 1.00 s
120% UN < 0.16 s
Undervoltage: 50% - 88% UN < 2.00 s
< 50% UN < 0.16 s
-
7/28/2019 PV Inverter Seminar
12/23
IEEE 1547 Frequency trip
Overfrequency: > 60.5 Hz < 0.16 s
Underfrequency: < 59.3 Hz < 0.16 s
-
7/28/2019 PV Inverter Seminar
13/23
IEEE 1547 Power Quality
DC injection Test Shall not inject 0.5% of DC current of the full rated
output current to the AC mainsDCAC0.5%
Harmonics Test
-
7/28/2019 PV Inverter Seminar
14/23
IEEE 1547 Anti-islanding
Using an R-L-C oscillation circuit RLC
Q = 1.0 (Quality factor) 1.0
It shall detect & trip < 2.0 s &2.0
Test shall be conducted in 100%, 66%, 33% output power
-
7/28/2019 PV Inverter Seminar
15/23
VDE 0126-1-1
Applicable to the Germanmarket
Applicable for the grid-interaction protocol
Other EU countries havesimilar requirements to
VDE 0126-1-1
-
7/28/2019 PV Inverter Seminar
16/23
VDE 0126-1-1 - Output Switch
Single-fault free for the trip relay
Voltage, Frequency and Current sensing shall besingle-fault free, &
Provide two separate relays (double poles)
Dual CPU CPU
-
7/28/2019 PV Inverter Seminar
17/23
VDE 0126-1-1 - Voltage Tripping
Overvoltage, 1.15 Un, < 0.2 s
Undervoltage, 0.8 Un, < 0.2 s
Overvoltage monitoring, 1.1 Un, 10 min
-
7/28/2019 PV Inverter Seminar
18/23
VDE 0126-1-1 - Frequency Tripping
Overfrequency: 50.2 Hz, < 0.2 s
Underfrequency: 47.5 Hz, < 0.2 s
-
7/28/2019 PV Inverter Seminar
19/23
VDE 0126-1-1 - DC current monitoring
DC 1 A
< 0.2 s
-
7/28/2019 PV Inverter Seminar
20/23
VDE 0126-1-1 - Anti-islanding
Method 2: By resonant circuit
RLC parallel resonant circuit RLC
100%, 50%, 25% load tested
Q 2 Tripping time: < 5 s
-
7/28/2019 PV Inverter Seminar
21/23
VDE 0126-1-1 - RCMU (Leakage Current)
In the VDE standard, this is forelectric shock protection & firehazard ---
300 mA is continuous current for firehazard300 mA
30/60/150 mA is for sudden changecurrent for electric shock protection
30/60/150 mA 30 mA, < 0.3 s
60 mA, < 0.15 s 150 mA, < 0.04 s > 300 mA, < 0.3 s
-
7/28/2019 PV Inverter Seminar
22/23
AS 4777.3
AS 4777.3 Grid connection of energy systems via
Inverters --- Part 3 Grid protection requirements
Passive anti-islanding --- Voltage & Frequency limit (< 2s)200V270V,45Hz55Hz
Active Anti-islanding (< 2s) light electronic load;
load match; and 100% (RLC)
load match plus 10%. 110% (RLC)
-
7/28/2019 PV Inverter Seminar
23/23