PV Inverter Seminar

download PV Inverter Seminar

of 23

Transcript of PV Inverter Seminar

  • 7/28/2019 PV Inverter Seminar

    1/23

    Testing grid-connected PV-inverters

    for compliance in different countries

    By Grady YeIntertek Testing Services Guangzhou

    2011-05

  • 7/28/2019 PV Inverter Seminar

    2/23

    Country Safety Grid-tied

    USA UL 1741 IEEE 1547

    Canada CSA C22.2 No. 107.1 CSA C22.2 No. 107.1

    Germany EN 62109-1, EN 62109-2 VDE 0126-1-1

    Spain EN 62109-1, EN 62109-2 RD 1663

    UK EN 62109-1, EN 62109-2 ER G83/1 (16A)

    ER G59/1 (16A)

    EU EN 62109-1, EN 62109-2 EN 50438

    Australia AS/NZS 3100 AS 4777.2, AS 4777.3

    PV-inverter Regulation/Standard List

  • 7/28/2019 PV Inverter Seminar

    3/23

    Typical Testing for PV Inverter

  • 7/28/2019 PV Inverter Seminar

    4/23

    PVI Enclosure Design (1/2)

    Outdoor use: Water, Dust, Temperature, UV, Corrosion

    :

    US requirement: NEMA xx, tested to UL 50E

    : NEMA xx,UL50E

    PV-inverter commonly rated NEMA 3R

    3R

    NEMA 3R: Rain test

  • 7/28/2019 PV Inverter Seminar

    5/23

    PVI Enclosure Design (2/2)

    Gasket may be required and tested

    European market: Follow the IPxx IPxx

    IEC/EN 60529 to be followed IEC/EN 60529

    PV inverter is commonly rated IP65 or IP54 IP65 or IP54

  • 7/28/2019 PV Inverter Seminar

    6/23

    Spacings/Clearances/Creepages

    UL 1741: Basic requirement 12.7 mm (between live partsand enclosure)

    UL 174112.7 mm ()

    Decided by working voltage & mains voltage which isinfluenced by DC input voltage and inverter topology.

    AC &DC

  • 7/28/2019 PV Inverter Seminar

    7/23

    GFDI (Ground Fault Detection/Interruption)

    UL 1741 requires a GFDI for PV-inverter to protect againstfire hazard

    UL 1741GFDI

    Four functions of GFDI GFDI detecting a ground fault,

    providing an indication of the fault,

    interrupting the flow of fault current, and

    either isolating the faulted array section or disabling the inverter to cease

    the export of power.

  • 7/28/2019 PV Inverter Seminar

    8/23

    Output overload test

    UL 1741 requires the output of the inverter be protectedagainst overload.

    UL1741

    If protection is achieved by a software, firmware & DSPThe software shall be evaluated to UL1998 (additional cost

    and additional testing time), and sensing circuit shall be

    special evaluated.

    ,

    UL1998

  • 7/28/2019 PV Inverter Seminar

    9/23

    Surge Test

    UL 1741 requires GFDI subjected to surge testing

    UL 1741GFDI

    Ring wave surge: 0.5 s (10-90%), oscillatory wave 10 s,3 kV / 6 kV

    After surge Calibration test to GFDI

    GFDI

  • 7/28/2019 PV Inverter Seminar

    10/23

    IEC 62109 Special Requirement

    A new standard which harmonizes American standardsUL1741 & IEEE 1547, IEC standards IEC 60950 & IEC

    62103, and German standard VDE 0126-1-1

    Concept from UL 1741: Input and output powercharacteristic, Abnormal tests, Markings

    UL1741

  • 7/28/2019 PV Inverter Seminar

    11/23

    IEEE 1547 Voltage trip

    Overvoltage: 110% - 120% UN < 1.00 s

    120% UN < 0.16 s

    Undervoltage: 50% - 88% UN < 2.00 s

    < 50% UN < 0.16 s

  • 7/28/2019 PV Inverter Seminar

    12/23

    IEEE 1547 Frequency trip

    Overfrequency: > 60.5 Hz < 0.16 s

    Underfrequency: < 59.3 Hz < 0.16 s

  • 7/28/2019 PV Inverter Seminar

    13/23

    IEEE 1547 Power Quality

    DC injection Test Shall not inject 0.5% of DC current of the full rated

    output current to the AC mainsDCAC0.5%

    Harmonics Test

  • 7/28/2019 PV Inverter Seminar

    14/23

    IEEE 1547 Anti-islanding

    Using an R-L-C oscillation circuit RLC

    Q = 1.0 (Quality factor) 1.0

    It shall detect & trip < 2.0 s &2.0

    Test shall be conducted in 100%, 66%, 33% output power

  • 7/28/2019 PV Inverter Seminar

    15/23

    VDE 0126-1-1

    Applicable to the Germanmarket

    Applicable for the grid-interaction protocol

    Other EU countries havesimilar requirements to

    VDE 0126-1-1

  • 7/28/2019 PV Inverter Seminar

    16/23

    VDE 0126-1-1 - Output Switch

    Single-fault free for the trip relay

    Voltage, Frequency and Current sensing shall besingle-fault free, &

    Provide two separate relays (double poles)

    Dual CPU CPU

  • 7/28/2019 PV Inverter Seminar

    17/23

    VDE 0126-1-1 - Voltage Tripping

    Overvoltage, 1.15 Un, < 0.2 s

    Undervoltage, 0.8 Un, < 0.2 s

    Overvoltage monitoring, 1.1 Un, 10 min

  • 7/28/2019 PV Inverter Seminar

    18/23

    VDE 0126-1-1 - Frequency Tripping

    Overfrequency: 50.2 Hz, < 0.2 s

    Underfrequency: 47.5 Hz, < 0.2 s

  • 7/28/2019 PV Inverter Seminar

    19/23

    VDE 0126-1-1 - DC current monitoring

    DC 1 A

    < 0.2 s

  • 7/28/2019 PV Inverter Seminar

    20/23

    VDE 0126-1-1 - Anti-islanding

    Method 2: By resonant circuit

    RLC parallel resonant circuit RLC

    100%, 50%, 25% load tested

    Q 2 Tripping time: < 5 s

  • 7/28/2019 PV Inverter Seminar

    21/23

    VDE 0126-1-1 - RCMU (Leakage Current)

    In the VDE standard, this is forelectric shock protection & firehazard ---

    300 mA is continuous current for firehazard300 mA

    30/60/150 mA is for sudden changecurrent for electric shock protection

    30/60/150 mA 30 mA, < 0.3 s

    60 mA, < 0.15 s 150 mA, < 0.04 s > 300 mA, < 0.3 s

  • 7/28/2019 PV Inverter Seminar

    22/23

    AS 4777.3

    AS 4777.3 Grid connection of energy systems via

    Inverters --- Part 3 Grid protection requirements

    Passive anti-islanding --- Voltage & Frequency limit (< 2s)200V270V,45Hz55Hz

    Active Anti-islanding (< 2s) light electronic load;

    load match; and 100% (RLC)

    load match plus 10%. 110% (RLC)

  • 7/28/2019 PV Inverter Seminar

    23/23