EPS2 Short Sem Report

download EPS2 Short Sem Report

of 22

Transcript of EPS2 Short Sem Report

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    1/22

    EEPB383 ELECTRICAL POWER SYSTEM II

    SEMESTER 3 2015/2016

    GROUP PROJECT

    EVALUATION OF

    UNBALANCED FAULT IN 11KV NETWORK

    LECTURERS NAME:ASSOC. PROF. DR. JAGADEESH PASUPULETISECTION:01

    GROUP MEMBERS:

    1

    KHAIRUL ANWAR SYAHMI BIN CHE ISMAIL EE090586

    2 MUHAMMAD NAQIUDDIN BIN MOHD NORDIN EP092689

    3 HANIF BIN ABDUL AZIZ EP093691

    DATE OF SUBMISSION:3rd MAY 2016

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    2/22

    2

    TABLE OF CONTENTS

    1. PART A .................................................................................................................................3

    1.1 Positive Sequence ............................................................................................................. 3

    1.2 Negative Sequence ............................................................................................................ 6

    1.3 Zero Sequence .................................................................................................................. 6

    1.4 Symmetrical Components of Bus Voltages During Fault ................................................ 9

    1.5 Bus Voltages during Fault ................................................................................................ 9

    1.6 Symmetrical Components of Fault Currents In Lines for Phase A ................................ 10

    2. PART B .............................................................................................................................. 11

    2.1 Positive Sequence ........................................................................................................... 11

    2.2 Negative Sequence .......................................................................................................... 15

    2.3 Zero Sequence ................................................................................................................ 15

    2.4 Symmetrical Components of Bus Voltages During Fault .............................................. 18

    2.5 Bus Voltages during Fault .............................................................................................. 18

    2.6 Symmetrical Components of Fault Currents In Lines for Phase A ................................. 19

    3. PART C .............................................................................................................................. 21

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    3/22

    3

    X1

    XA1

    = XA2

    = j1.3716

    X1

    XA2= 9km x 0.1524 /km

    =j1.3716

    X YB1

    = 3km x 0.0949/km

    = j0.2847

    X1

    YB1

    = X1YB1

    = j0.2847

    Fault Level (MVA) = Fault Level (p.u.) * Sbase

    2500 = F.L.G1 x 100FLG1= 25 p.u.

    XG1 = 1 / 25 = j0.04 p.u.

    2000 = F.L.G2 x 100

    FLG2= 20 p.u.

    XG2 = 1 / 20 = j0.05 p.u.

    BOLTED

    FAULT1 2

    5

    43

    6

    1. PART A

    1.1 Positive Sequence Network

    X1

    T1= j0.08

    X1

    T2=j0.08

    X T3

    = j0.10

    X1T4

    = j0.10

    X G1

    = j0.04

    X G2

    = j0.05

    X1AB4

    = 6km x 0.0949/km

    = j0.5694

    Though the operating conditions at the time

    of fault are important, the loadscan usually

    be neglected during short circuits, asvoltages dip very low so that currents drawn

    by loads can be neglected in comparison

    with short circuit currents. Thus, the 4MVA

    and 7MVAloads are ignored in determining

    the equivalent Thevenin network impedance

    as seen from the faulted bus/point..

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    4/22

    4

    X

    1

    XA12= (j1.3716) (j1.3716)(j1.3716 +j1.3716)

    = j0.0686

    X1T34

    = (j0.1) (j0.1)

    (j0.1 +j0.1)

    = j0.05

    XYB

    12

    = (j0.2847) (j0.2847)(j0.2847 +j0.2847)

    = j0.14235

    X1T12

    =(j0.08) (j0.08)

    (j0.08 +j0.08)

    = j0.04

    X1G1

    = j0.04

    X G2

    = j0.05

    X AB4

    = 6km x 0.0949/km

    = j0.5694

    1

    3

    5

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    5/22

    5

    1 2

    1

    j0.81175

    j0.1486

    X G1 + X T12 +XXA12

    = j0.04+ j0.04+ j0.0686

    = 0.1486

    X1G2 + X

    1T34 + X

    1YB12

    = j0.05+ j0.05 +j0.14235

    = 0.24235

    X1AB4

    = j0.5694

    X1(G2 + T34 + YB12+ AB4) =j(0.24235 + 0.5694)

    =j0.81175

    Paralleling the two equivalent impedances at the Faulted Bus No. 5:-

    Z1 =(j0.1486) (j0.81175)

    (j0.1486+j0.81175)

    =j0.1256

    In the next part, the impedances to the point of fault for both the

    negative-sequence and zero-sequence (Z2and Z

    0) are to be determined

    before fault current in this unbalanced network can be found.

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    6/22

    6

    X0

    XA1

    = X0XA2

    = j0.2808

    XXA2

    = 9km x 0.0312 /km

    =j0.2808

    X0YB1

    = 3km x 0.0303/km

    = j0.0909

    XYB1

    = X0YB1

    = j0.0909

    BOLTED

    FAULT1 2

    6

    21

    5

    1.2Negative Sequence Network for Part A

    Since negative-sequence reactances are the same as positive-sequence reactances,

    Z2= Z

    1 =j0.1256

    1.3 Zero Sequence Network for Part A

    X T1

    = j0.08

    X T2

    =j0.08

    X T3

    = j0.10

    X0T4

    = j0.10

    G1 G2

    X AB4

    = 6km x 0.0303/km

    = j1.818

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    7/22

    7

    X

    0

    XA12= (j0.2808) (j0.2808)(j0.2808+ j0.2808)

    = j0.01404

    X0T34

    = (j0.1) (j0.1)

    (j0.1 +j0.1)

    = j0.0500

    XYB

    12

    = (j0.0909) (j0.0909)(j0.0909 +j0.0909)

    = j0.04545

    3

    1

    4

    6

    2

    5

    1

    X0T12

    = (j0.08) (j0.08)

    (j0.08 +j0.08)

    = j0.04000

    G1 G2

    X AB4

    = j1.818

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    8/22

    8

    X T34 + X

    YB12= j0.05 +j0.04545

    = j0.09545

    X AB4

    = j1.818

    1 2

    X0AB4

    = j0.0907

    COPYRIGHT -JOHN-HANIF-SYAHMI-NAQIUBOGARD

    Z1bus=

    0474.00021.00374.00077.0

    0021.00383.00121.00338.0

    0374.0010.01812.00375.0

    0077.00338.00375.01256.0

    jjj

    jjjj

    jjjj

    jjjj

    Z0bus=

    25.0000

    020.000

    000907.00026.0

    000026.00525.0

    j

    j

    jj

    jj

    X T12 +X XA12

    = j0.04+ j0.01404

    = j0.05404

    X AB4 = (j0.09545 *j1.818) =j0.0907

    (j0.09545 +j1.818)

    X

    0

    = Z

    0

    = (j0.05404) (j1.91345)(j0.05404+j1.91345)

    = j0.0525

    I10(F) = I1

    1(F) = I1

    2(F )= 1.0

    (X0+ X1+ X2)

    = (1.0 p.u.) = 3.29-90 puj(0.1256 + 0.1256 + 0.0525)

    = -j3.29 pu

    I3abc(F )= 3I1

    0= 3(V5(F))

    (X0+ X1+ X2)

    = 3(1.0 p.u.) = 9.87-90 puj(0.1256 + 0.13256 + 0.0525)

    = -j9.87pu

    j0.05404

    The bus impedance matrices

    (Zero Sequence reactance for generator assumed to be half of the

    Positive Sequences reactance)

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    9/22

    9

    The symmetrical components of bus voltages during fault:

    =

    3.29)(-1256.00

    3.29)j0.1256(-1

    3.29)(-0526.00

    jj

    j

    jj

    =

    4132.0

    587.0

    173.0

    =

    3.29)j0.0375(--0

    3.29)(-0375.01

    3.29)j0.0026(-0

    j

    jj

    j

    =

    1234.0

    88.0

    1055.8 3

    x

    =

    3.29)j0.0338(--0

    3.29)(-0338.01

    3.29)j0(--0

    j

    jj

    j

    =

    111.0

    89.0

    0

    =

    3.29)j0.0077(--0

    3.29)j0.0077(--1

    3.29)j0(--0

    j

    j

    j

    =

    0253.0

    974.0

    0

    Bus voltages during fault:

    435.0

    564.0

    173.0

    =

    10694.0

    10694.0

    0

    1210.0

    88.0

    1055.8 3x

    =

    11495.0

    11495.0

    748.0

    111.0

    89.0

    0

    =

    11394.0

    11394.0

    779.0

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    10/22

    10

    0253.0

    974.0

    0

    =

    11999.0

    11999.0

    9497.0

    Symmetrical components of fault currents in lines for phase a:

    =

    5694.0

    )41727.0(1234.0

    5694.0

    587.088.0

    818.1

    )16578.0(55.8

    j

    j

    j

    m

    =

    9051.0

    9051.0

    900867.0

    =

    1086.0

    )4132.0(1314.01086.0

    58273.089.0

    )16578.0(0

    j

    j=

    9078.2

    9078.2

    0

    =

    19325.0

    )1234.0(0253.0

    19235.0

    879.0974.0

    )55.8(0

    j

    j

    m

    =

    905.0

    905.0

    0

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    11/22

    11

    9051.0

    9051.0

    900867.0

    =

    90433.0

    90433.0

    901.1

    9078.2

    9078.2

    0

    =

    9078.2

    9078.2

    56.5

    2

    2

    42

    1

    1

    111

    aa

    aa(F)Iabc

    905.0

    905.0

    0

    =

    9042.0

    9042.0

    9001.1

    Finally; questions asked for fault currents flowing in the 11 kV underground cables.

    For XA1 and XA2, they are between the designated Bus 1 and Bus 3. So we divide

    the fault current by half:

    2

    121 (F)I

    abc

    XAXA

    9078.2

    9078.2

    56.5

    =

    9039.1

    9039.1

    78.2

    pu

    For YB1 and YB2, they are located between bus 2 and bus 4. Again, divided by half:

    5.021 (F)Iabc

    XBXB

    9051.0

    9051.0

    9001.1

    =

    90255.0

    90255.0

    9051.0

    pu

    As for XAB4, its the current which flows between bus 1 and 2, which is:

    =

    9042.0

    9042.0

    9011.1

    pu.

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    12/22

    12

    X1

    XA1

    = X1 XA2

    = j1.3716

    X1

    XA2= 9km x 0.1524 /km

    =j1.3716

    X1YB1

    = 3km x 0.0949/km

    = j0.2847

    X1

    YB2

    = X1YB1

    = j0.2847

    Fault Level (MVA) = Fault Level (p.u.) * Sbase

    2500 = F.L.G1 x 100

    FLG1= 25 p.u.

    XG1 = 1 / 20 = j0.04 p.u.

    2000 = F.L.G2 x 100

    FLG2= 20 p.u.

    XG2 = 1 / 20 = 0.05 .u.

    BOLTED

    FAULT

    1

    2. PART B

    2.1 Positive Sequence Network

    X1

    T1= j0.08

    X1

    T2=j0.08

    X1T3= j0.10

    X1T4

    = j0.10

    X G1

    = j0.04

    X G2

    = j0.05

    X1AB4

    = 6km x 0.0949/km

    = j0.5694

    Though the operating conditions at the time

    of fault are important, the loadscan usually

    be neglected during short circuits, as

    voltages dip very low so that currents drawn

    by loads can be neglected in comparison

    with short circuit currents. Thus, the 4MVA

    and 7MVAloads are ignored in determining

    the equivalent Thevenin network impedance

    as seen from the faulted bus/ oint..

    3

    56

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    13/22

    13

    X XA1= X

    1XA2

    = j1.3716

    X1T34

    = (j0.1) (j0.1)

    (j0.1 +j0.1)

    = j0.05

    1

    X1T12

    =(j0.08) (j0.08)

    (j0.08 +j0.08)

    = j0.04

    X1G1

    = j0.04

    X G2

    = j0.05

    X AB4

    = 6km x 0.0949/km

    = j0.5694

    X1

    YB2= X

    1YB1

    = j0.2847

    2

    34

    6

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    14/22

    14

    1 2

    1

    j0.9541

    j1.3616

    X G1 + X T12 +XXA2

    = j0.04+ j0.04+ j1.3716

    = 1.3616

    X1G2 + X

    1T34 + X

    1YB1

    = j0.05+ j0.05 +j0.2847

    = 0.3847

    X1AB4

    = j0.5694

    X1(G2 + T34 + YB1+ AB4) =j(0.3847+ 0.5694)

    =j0.9541

    Paralleling the two equivalent impedances at the Faulted Bus No. 5:-

    Z1 =(j1.3616) (j0.9541)

    (j1.3616+j0.9541)

    =j0.56

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    15/22

    15

    X0

    XA1

    = X0XA2

    = j0.2808

    XXA2

    = 9km x 0.0312 /km

    =j0.2808

    X0YB1

    = 3km x 0.0303/km

    = j0.0909

    XYB1

    = X0YB1

    = j0.0909

    BOLTED

    FAULT1 2

    6

    43

    5

    2.2Negative Sequence Network for Part B

    Since negative-sequence reactances are the same as positive-sequence reactances,

    Z2= Z

    1 =j0.56

    2.3 Zero Sequence Network for Part B

    X T1

    = j0.08

    X T2

    =j0.08

    X T3

    = j0.10

    X0T4

    = j0.10

    G1 G2

    X AB4

    = 6km x 0.0303/km

    = j1.818

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    16/22

    16

    X

    0

    XA2= j0.2808

    X0T34

    = (j0.1) (j0.1)

    (j0.1 +j0.1)

    = j0.05

    XYB

    1

    = j0.0909

    3

    1

    4

    6

    2

    5

    1

    X0T12

    = (j0.08) (j0.08)

    (j0.08 +j0.08)

    = j0.04

    G1 G2

    X AB4

    = j1.818

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    17/22

    17

    X0T34 + X

    0YB1

    = j0.05 +j0.0909

    = j0.1409

    X AB4

    = j1.818

    1

    2

    X AB4

    = j1.9589

    1

    Z1bus=

    049.00008.00420.00302.0

    0008.00393.00064.00159.0

    042.00064.03232.02321.0

    0302.00159.02321.05757.0

    jjjj

    jjjj

    jjjj

    jjjj

    Z0bus=

    25.0000

    020.000

    001322.00198.0

    000198.002757.0

    j

    j

    jj

    jj

    X T12 +XXA2

    = j0.04+ j0.2808

    = j0.3208

    X0AB4= (j0.1409 +j1.818) =j1.9589

    X0= Z55

    0= (j0.3208) (j1.9589)

    (j0.3208+j1.9589)

    = j0.2757

    If = 3Ia0= 3(V5(F))

    (X0+ X1+ X2)

    = 3(1.0 p.u.)

    j(0.5736 + 0.5736 + 0.2757)

    = -j2.1084 pu

    I11(F) = -j2.1084/3

    = -j0.703 pu

    Bus impedance matrix for case B

    j0.3208

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    18/22

    18

    Symmetrical components of bus voltages during fault:

    =

    )703.0(-.5757.00

    )703.0j0.5757(-1

    )703.0(-2757.00

    jj

    j

    jj

    =

    405.0

    595.0

    194.0

    =

    )703.0j0.2321(-0

    )703.0(2321.01

    )703.0j0.0198(0

    j

    jj

    j

    =

    .16.0

    837.0

    0139.0

    =

    )703.0j0.0159(-0

    )703.0(0159.01

    )703.0j0(-0

    j

    jj

    j

    =

    011.0

    988.0

    0

    =

    )703.0j0.0302(-0

    )703.0j0.0302(-1

    )703.0j0(-0

    j

    j

    j

    =

    0212.0

    98.0

    0

    Bus voltages during fault:

    405.0

    595.0

    194.0

    =

    10694.0

    10694.0

    0

    .16.0

    837.0

    0139.0

    =

    11494.0

    11494.0

    663.0

    011.0

    988.0

    0

    =

    11399.0

    11399.0

    997.0

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    19/22

    19

    0212.0

    98.0

    0

    =

    11999.0

    11999.0

    96.0

    Symmetrical components of fault currents in lines for phase a:

    =

    5694.0

    )405.0(16.05694.0

    595.0837.0818.1

    )194.0(0139.0

    j

    j

    j

    =

    90425.0

    90425.0

    90099.0

    =

    4116.1

    )405.0(011.04116.1

    595.0988.0

    )194.0(0

    j

    j=

    90278.0

    90278.0

    0

    =

    3347.0

    )16.0(0212.0

    3347.0

    837.098.0

    )0139.0(0

    j

    j=

    90427.0

    90427.0

    0

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    20/22

    20

    90425.0

    90425.0

    90099.0

    =

    90326.0

    90326.0

    9095.0

    90278.0

    90278.0

    0

    =

    90278.0

    90278.0

    556.0

    2

    2

    42

    1

    1

    111

    aa

    aa(F)Iabc

    90427.0

    90427.0

    0

    =

    9042.0

    9042.0

    90854.0

    For XA1, it is between the designated Bus 1 and Bus 3. The current does not flow

    through XA2 because its disconnected by the circuit breaker A0. So the fault current

    flowing through XA1 is equal to (F)IabcXA1

    90326.0

    90326.0

    9095.0

    pu.

    For YB1, no current flow through the cable due to closed circuit breaker B0,

    effectively disconnecting it from the bus network. Whereas the cable YB2 carries

    current equal to the current from cable AB4 which is:

    (F)I(F)I(F)I abcABabc

    YB

    abc

    4242 =

    9042.0

    9042.0

    90854.0

    pu.

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    21/22

    21

    XXA1

    = XA2

    = j1.3716

    XXA2

    = 9km x 0.1524 /km

    =j1.3716

    X1YB1

    = 3km x 0.0949/km

    = j0.2847

    X1

    YB1

    = X1YB1

    = j0.2847

    1 2 (11kV)

    6

    43

    5

    7 (0.4kV)

    3. PART C

    X T1

    = j0.08

    X T2

    =j0.08X

    1T3

    = j0.10

    X T4

    = j0.10

    X1G1

    = j0.04

    X1G2

    = j0.05

    X1AB4

    = 6km x 0.0949/km

    = j0.5694

  • 7/26/2019 [PDF] EPS2 Short Sem Report

    22/22

    22

    1 2

    7 (0.4kV)

    2

    7 (0.4kV)

    X G1 + X T12 +XXA12

    = j0.04+ j0.04+ j0.0686

    = 0.1486

    If= 1.0 / Z

    = 1.0 / j0.33= 3.03 -90 pu

    IB= SB/ VB

    = 100MVA / (3*0.4kV)= 144.34kA

    Iactual= 144.34K * 3.06 = 437.35kA (very high and dangerous)

    Scc= (3)(400)(437.35)/1M= 303MVA

    X1AB4

    = j0.5694

    X1G2 + X

    1T34 + X

    1YB12

    = j0.05+ j0.05 +j0.14235

    = 0.24235

    X T5

    =j0.15

    (X1G1 + X

    1T12 +X

    1XA12) + X

    1AB4

    =j0.1486+j0.5694

    =j0.718

    Zs= (j0.728) (j0.23235) / (j0.728+j0.23235)

    =j0.18

    Z= j0.18+j0.15

    =j0.33

    j0.18

    j0.15