E400 UPS Datasheet

download E400 UPS Datasheet

of 1

Transcript of E400 UPS Datasheet

  • 7/29/2019 E400 UPS Datasheet

    1/1

    Dale Power Solutions plc reserves the right to make changes in specification without notice or liability. All information is subject to Dale Power Solutions plc own data & is considered accurate at time of publishing.

    Dale Power Solutions plcSalter Road, Eastfield Industrial Estate, Scarborough, North Yorkshire, YO11 3DU, UK

    Telephone: +44 (0) 1723 583511Email: [email protected]

    Website: www.dalepowersolutions.com S5264EU06rev1

    Features

    High frequency & double conversion on-line technology Fully digitized microprocessor control Double conversion or ECO mode of operation Wide input voltage range LCD display Cold start Parallel capacity (maximum of 4 units) Advanced battery management Automatic battery charge in UPS off mode Lightning & surge protection Short circuit and overload protection Fan speed auto control when loads varies EMI/RFI noise filter Smart RS232 communication with monitoring software External battery Optional battery temperature compensation. Optional SNMP Card slot

    Common Specifications

    Voltage Range 184V AC to 276V AC Line-Neutral

    Phase 3 Phase 4 Wire & Earth

    Frequency 45Hz to 65HzInputPower factor > 0.99

    Voltage 220/230/240V AC Line-Neutral (user adjustable)Phase 3 Phase 4 Wire & earth

    Frequency 50/60Hz (user adjustable)

    THD (linear load) < 1%THD (non-linear mode) < 5%

    Wave form Sine waveOverload Capacity 110%: 60 mins, 125%: 10 mins, 150%: 1 min

    Crest factor 3:1 (max)Power Factor 0.8

    Short circuit protection Yes

    Output

    Transfer time 0 ms

    Battery External Configurable 32/34/36/38/40 X 12V monoblocks (192V/204V/216V/228V/240V nominal)

    Operating altitude 1000m at rated power An (-1% for each 100m over 1000m) max 4000mOperate Temperature 0C to 40C

    Storage Temperature -25C to +55C

    Environment

    Relative humidity 95%

    Communication Standard: RS232, Optional: SNMP

    LCD Screen Display Measurements: Input & output voltage/frequency, battery voltage, load power & kVA, UPS temperatureOperation mode: i.e. Online, On Battery, Bypass

    Operation mode Double conversion or ECO mode operation (user selectable)

    LED Indication Mimic of UPS operation

    Noise Level