CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN 23 & 24 AUGUSTUS 2016 – Patrick Hagen

ECOLOGIE ECONOMIE HVAC-SECTOR

BUSINESS AS USUAL

Eu-richtlijnen, Ecodesign, EPB àverplichtingen, andere aanpak, nieuwe systemen

CONSUMENT

COMFORT OP DE EERSTE PLAATS

Duurzaamheid & ecologie = filosofie. Doet enkel verplichte investering.

GEBREK AAN OVERHEIDSINITIATIEVEN KORTE TERMIJN-DENKEN VERKEERDE PERCEPTIE

Comfort

Budget

Duurzaamheid

DUURZAAMHEID EFFICIENTIE COMFORT

HYDRAULISCH CONCEPT COMPONENTSELECTIE INREGELING HAALBARE BUDGETTEN

SYSTEEMOPTIMALISATIE

DUURZAAM INGEREGELDE INSTALLATIES

HOOGST MOGELIJK COMFORT

LAAGST MOGELIJK VERBRUIK

HOOGST MOGELIJK RENDEMENT

WAAROM INREGELEN?

INSTALLATIE IN ONBALANS •  HOOG ENERGIEVERBRUIK •  MOGELIJK KOUDE RUIMTES •  SLECHT COMFORT

•  LAAG ENERGIEVERBRUIK •  HOOG COMFORT

NIET INGEREGELD

INGEREGELD

SYSTEEMOPTIMALISATIE WHAT’S IN IT FOR YOU?

EINDGEBRUIKER

•  COMFORT •  DUURZAME EN EFFICIËNTE

INSTALLATIE •  ZEER KORTE TERUGVERDIENTIJD •  KLEINE INVESTERING

INSTALLATEUR

•  SOLIDE BASIS VAN CONCEPT •  COMPONENTSELECTIE IN DETAIL •  MINIMALE FOUTMARGE •  OPSPOORBARE STORINGEN

Systeemoptimalistie is beste oplossing naargelang de wens van de klant, volgens budget, waarbij foutenmarges in de uitvoering ervan geminimaliseerd worden.

BASISTHEORIE INREGELEN

KV-WAARDE ▪  Geleidingsvermogen klep Kv-waarde ▪  Tegenovergestelde van weerstand

▪  Geeft het debiet aan waarbij een drukverschil van 100 kPa (1 bar) ontstaat

▪  Uitgedrukt in m3/h

▪  Temperatuur water: tussen 5°C en 40°C (gewoonlijk 15-16°C)

▪  Speciaal geval van Kv-waarde ▪  Geeft het debiet aan bij de volledig geopende klep

waarbij een drukverschil van 100 kPa (1 bar) ontstaat ▪  Uitgedrukt in m3/h

▪  Temperatuur water: tussen 5°C en 40°C (gewoonlijk 15-16°C)

KVS-WAARDE

G = [m3/h] Debiet Δp =[bar] Drukverschil Kvs = [m3/h] Hydraulische kenmerken van het ventiel

BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KV-WAARDE

BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // CIRCUIT CURVE

BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KLEPKARAKTERISTIEK

Lineair gedrag indien Δpklep = constant

BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KLEPKARAKTERISTIEK

Lineair gedrag indien Δppomp = constant en ∆pklep ≠ constant klepautoriteit β (reactie debiet op gedrag van klep)

Stel: Klep sluit, debiet verkleint

∆Ppomp = ∆Prest + ∆P klep

cte ↘ ↗

BASISTHEORIE POMPGEGEVENS // VERSCHUIVING WERKINGSPUNT

BASISTHEORIE POMPGEGEVENS // VERSCHUIVING WERKINGSPUNT

van A naar C

Sluiten van de klep (Kv1 < Kv)

Klep

sluit

van A naar B

Openen van de klep (Kv2 > Kv )

Klep

opent

BASISTHEORIE POMPGEGEVENS // TOERENTALGEREGELDE POMP

BASISTHEORIE POMPGEGEVENS // TOERENTALGEREGELDE POMP KENMERKEN

Automatische drukverschilregeling op Δp-c (drukconstant modus)

Opvoe

rhoo

gteH[m

]

VolumestroomV[m³/h]

nmax

1

2

nregel

3

1. Toerengeregelde pomp ingesteld op setpunt opvoerhoogte (punt 1).

2. De elektronica meet het verschil tussen het setpunt (punt 1) en actuele meetwaarde (punt 2).

3. De regelaar reduceert het toerental en brengt de opvoerhoogte weer op setpuntwaarde (punt 3).

H2

V2

nregel

nregel

nregel

nregel

V1

H1

NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES

(Ventilator)convector nominaal debiet G 330 l/h

Drukverlies veroorzaakt bij nominaal debiet ΔP 1500 Pa

Lengte van de stijgleidingen – aansluitingen (ventilator)convectoren l 4 m

Bochten tussen stijgleidingen en (ventilator)convectoren nr. 2 (90°)

8 SECUNDAIRE CIRCUITS

8 SECUNDAIRE CIRCUITS

Leidingen h8 790 Pa

Hulpstukken z8 960 Pa

Afgifte k8 1500 Pa

TOTAAL h8 3250 Pa = 3,25 kPa

NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES

SECTIE VAN STIJGLEIDING 8 - 7

SECUNDAIR CIRCUIT 7

Leidingen h8-7 287 Pa

Hulpstukken z8-7 57 Pa

TOTAAL ∆P8-7 344 Pa

H8 3250 Pa

∆P8-7 344 Pa

DRUKVERLIES H7 3594 Pa = 3,59 kPa

NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES

G7 = gebalanceerd debiet H7 = nieuw drukverlies van het circuit G8 = te balanceren debiet H8 = drukverlies van het te balanceren circuit

SECUNDAIR CIRCUIT 7

Debiet G7-8

Debiet 8 G8 330 l/h

Debiet 7 G7 348 l/h

TOTAAL G7-8 678 l/h

NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES

SECTIE VAN STIJGLEIDING 7 - 6

Drukverlies ∆P7-8

Leiding h7-6 1096 Pa

Hulpstukken z7-6 250 Pa

TOTAAL ∆P7-6 1346 Pa = 1,37 kPa

SECUNDAIR CIRCUIT 6

H7 3250 Pa

∆P7-6 1350 Pa

DRUKVERLIES H6 4940 Pa = 4,94 kPa

NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES

INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN

VOLLAST

G8 = 330 l/h Ø8 = ½” V8 = 0,44 m/s G7 = 330 l/h Ø7 = ½” V7 = 0,44 m/s G6 = 330 l/h Ø6 = ½” V6 = 0,44 m/s G5 = 330 l/h Ø5 = ½” V5 = 0,44 m/s G4 = 330 l/h Ø4 = ½” V4 = 0,44 m/s G3 = 330 l/h Ø3 = ½” V3 = 0,44 m/s G2 = 330 l/h Ø2 = ½” V2 = 0,44 m/s G1 = 330 l/h Ø1 = ½” V1 = 0,44 m/s

G8-7 = 330 l/h Ø8-7 = ¾” G7-6 = 660 l/h Ø7-6 = ¾” G6-5 = 990 l/h Ø6-5 = 1” G5-4 = 1320 l/h Ø5-4 = 1 ¼” G4-3 = 1650 l/h Ø4-3 = 1 ¼” G3-2 = 1650 l/h Ø3-2 = 1 ¼” G2-1 = 1980 l/h Ø2-1 = 1 ¼” G1-0 = 2310 l/h Ø1-0 = 1 ½”

VOLLAST

(Ventilator)convector nominaal debiet G 330 l/h Drukverlies veroorzaakt bij nominaal debiet ΔP 1500 Pa Lengte van de stijgleidingen – aansluitingen (ventilator)convectoren l 4 m

Bochten tussen stijgleidingen en (ventilator)convectoren nr. 2 (90°)

INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening

DEBIETBEREKENING

SECUNDAIR CIRCUIT 8

Leidingen h8 790 Pa

Hulpstukken z8 960 Pa

Afgifte k8 1500 Pa

Inregelventiel ∆Pv8 1110 Pa

TOTAAL h8 4360 Pa = 4,36 kPa

INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening

Inregelventiel ingesteld op POSITIE 6

SECUNDAIR CIRCUIT 8

INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening

Sectie van stijgleiding 8 - 7

Debiet G8-7 = G8 = 333 l/h

Leiding h8-7 287 kPa

Hulpstukken z8-7 57 kPa

TOTAAL ∆P8-7 344 kPa

INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening

INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening

3250 Pa SECUNDAIR CIRCUIT 7

Drukverlies

H8 4360 Pa

∆P8-7 344 Pa

H7 EFF 4704 Pa = 4,70 kPa

Inregelstand

H7EFF 4704 Pa

H8 3250 Pa

∆PREG.VENT 1454 Pa = 1,45 kPa

Inregelventiel ingesteld op POSITIE 4.5

SECUNDAIR CIRCUIT 7

INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening

Statisch inregelen

Inregelventiel met debietmeter serie 132

Inregelventiel met venturi serie 130

Inregelventiel met flensaansluiting serie 130

Dynamisch inregelen

Drukonafhankelijk ventiel Flomatic® serie 145

Automatische debietregelaar Autoflow®

serie 121-126 serie 127 serie 120-125 serie 103

∆p regelen

Drukverschilregelaar serie 140

Inregelventiel met voorinstelling serie 142

Drukverschilregelaar serie 519

INREGELEN // toepassingen & componenten

Statisch inregelen Dynamisch inregelen ∆P inregelen

Serie 130 Serie 132

Serie 145 Flomatic®

Serie 120 / 121 /125 / 126 / 107 / 103

Autoflow®

Serie 140 Serie 142 Serie 519

Solar Geothermie Tapwater

Radiatoren Vloerverwarming Satellietunit

Koelplafonds Luchtverhitter Stralingspanelen Convectoren Luchtgroep Cascade

INREGELEN // toepassingen

INREGELEN // toepassingen RADIATOREN

INREGELEN // toepassingen RADIATOREN

INREGELEN // toepassingen VLOERVERWARMING

INREGELEN // toepassingen VLOERVERWARMING

INREGELEN // toepassingen VLOERVERWARMING

INREGELEN // toepassingen DISTRIBUTIE-UNITS

INREGELEN // toepassingen DISTRIBUTIE-UNITS

INREGELEN // toepassingen DISTRIBUTIE-UNITS

INREGELEN // toepassingen DISTRIBUTIE-UNITS

INREGELEN // toepassingen VENTILOCONVECTOREN | KOELBALKEN | LUCHTVERHITTERS | STRALINGSPANELEN

INREGELEN // toepassingen VENTILOCONVECTOREN | KOELBALKEN | LUCHTVERHITTERS | STRALINGSPANELEN

INREGELEN // toepassingen LUCHTGROEPEN

INREGELEN // toepassingen LUCHTGROEPEN

INREGELEN // toepassingen LUCHTGROEPEN

INREGELEN // toepassingen CASCADE

THANK YOU

CARE.CALEFFI.BE