Susol TS 1600 ÀF Reaflet 1010 LS

6
1600AF MCCB For power distribution - The highest breaking capacity - Optimum coordination technique (Cascading & discrimination) - Powerful engineering tools For protection of motor & its control device - Optimal overload protection For controlling and disconnecting circuits For extensive applications - Wide range of optimized auxiliaries and accessories Introduction of New Product 1600AF, 3&4pole Icu: 50/70/150kA Ics: 100(75)%Icu Icw: 25kA/1s Ui: 1000V Uimp: 8kV Cat. A, B N, A, P, S type L / S / I / G Thermal, Ammeter, Power, Harmonic Outer: 16 type Inner: 5 type Easy connection MCCB OCR Accessory

Transcript of Susol TS 1600 ÀF Reaflet 1010 LS

Page 1: Susol TS 1600 ÀF Reaflet 1010 LS

1600AF MCCB

●●For power distribution- The highest breaking capacity- Optimum coordination technique (Cascading & discrimination)- Powerful engineering tools

●●For protection of motor & its control device- Optimal overload protection

●●For controlling and disconnecting circuits

●●For extensive applications- Wide range of optimized auxiliaries and accessories

Introduction of New Product

●1600AF, 3&4pole

● Icu: 50/70/150kA

● Ics: 100(75)%Icu

● Icw: 25kA/1s

●Ui: 1000V

●Uimp: 8kV

● Cat. A, B

●N, A, P, S type

●L / S / I / G

●Thermal, Ammeter,

Power, Harmonic

●Outer: 16 type

● Inner: 5 type

●Easy connection

MCCB OCR Accessory

Page 2: Susol TS 1600 ÀF Reaflet 1010 LS

TS1600 Rating

Ordering

Ampere frame

1000

TS 1250

1600

Type

N Normal

H High

L Current Limiting

NASwitch-disconnector

Rated current

800A

1000A

1250A

1600A

Poles

3P 3Pole

4P 4Pole

Connection type

- Standard

REAR RearConnection

Trip relay

N Normal

A Ammeter

P Power meter

S Supreme meter

■■MCCB

N phase way (4Pole)

L N-R-S-T

R R-ST-N

TS1600 1600AN A 3P - -

Type TS1000 TS1250 TS1600

Ampere frame 1000 1250 1600

Pole 3, 4 3, 4 3, 4

Rated current,(A) In -5~40°C 800, 1000 1250 1600

50°C 800, 1000 1250 1560

65°C 800, 1000 1240 1420

Rated insulation voltage, (V) Ui 1000 1000 1000

Rated impulse withstand voltage, (kV) Uimp 8 8 8

Rated operational Ue AC50/60Hz 690 690 690

voltage, (V) DC - - -

Rated short-circuit breaking capacity N H L N H N H

IEC60947-2 Rated ultimate short-circuit AC50/60Hz 220/240V 55 75 200 55 75 55 75

(sym) breaking capacity, (kA) (Icu) 380/415V 50 70 150 50 70 50 70

440V/460V 50 65 130 50 65 50 65

480/500V 40 50 100 40 50 40 50

660/690V 35 45 50 35 45 35 45

DC 250V 2P - - - - - - -

500V 2P - - - - - - -

750V 3P - - - - - - -

Rated service breaking capacity, %Icu100% 75% 100% 100% 75% 100% 75%

(Ics)

Rated short-circuit making capacity, AC50/60Hz 1s 25 25 12 25 25 25 25

(kA) (Icw) 3s - - - - - -

Overriding instantaneous protection kA peak 50 50 - 50 50 50 50

Isolation ○ ○ ○

Category B B A B B B B

Mechanical life (operations) 10000 10000 10000

(Life cycle) Electrical life (operations) 440V In/2 6000 6000 4000 5000 5000 5000 5000

In 5000 5000 3000 4000 4000 2000 2000

690V In/2 4000 4000 3000 3000 3000 2000 2000

In 2000 2000 2000 2000 2000 1000 1000

Pollution degree 3 3 3

Dimension (mm) a (3p/4p) 210/280

b 327

c1 155.5

c2 162.7

d 185.3

Weight (kg) 3P 13

4P 16.8

a

b

dc2c1

Page 3: Susol TS 1600 ÀF Reaflet 1010 LS

Trip relay types

Classification N type A type P type S type

Externals

Current �L / S / I / G / Thermal �L / S / I / G / Thermal �L / S / I / G / Thermal(Continuous) �P type

protection �ZSI(Protective coordination) �ZSI(Protective coordination)

� Earth leakage (Option) �Earth leakage(Option) �P type

Other�Over/Under current

protection�Over/Under frequency

�Unbalance(Voltage/Current)

�Reverse power

�Current (R / S / T / N) �3 Phase Voltage/Current �3 Phase Voltage/Current

RMS/Vector RMS/Vector

�Power(P, Q, S), PF(3-Phase) �Power(P, Q, S), PF(3-Phase)

�Energy(Positive/Negative) �Energy(Positive/Negative)

Measurement �Frequency, Demand �Frequency, Demand

function �Voltage/Current harmonics

(1st~63th)

�3 Phase Waveforms

�THD, TDD, K-Factor

Fine adjustment�Fine adjustment for long/short �P type

time delay/instantaneous/ ground

�Overload protection relays �P type

Pre Trip Alarm: DO (Alarm)

(Ground fault is not available

when using Pre trip alarm)

Digital Output�3DO (Fixed) �3DO (Programmable) �P type

�L, S/I, G Alarm �Trip, Alarm, General

IDMTL setting�Compliance with IEC60255-3 �P type

SIT, VIT, EIT, DT

Communication�Modbus/RS-485 �Modbus / RS-485 �Modbus / RS-485

�Profibus-DP �Profibus-DP �Profibus-DP

�Self Power �Self Power �AC/DC 100~250V �AC/DC 100~250V

- Power source works over 30% - Power source works over 30% �DC 24~60V �DC 24~60V

current of In (one pole) current of In (one pole)

Power supply - External power source are

required for comm.

�AC/DC 100~250V

�DC 24~60V

RTC timer �Available �Available �Available �Available

LED for�Long time delay �N type �N type �N type

trip info.�Short time delay/

Instantaneous

�Ground fault

�10 records �256 records �256 records

Fault recording (Fault/Current/Date and Time) (Fault/Current/Date and Time) �Last fault wave

recording (3 Phase)

Event recording �256 records(Content, Status, Date) �P type

Operating �Reset button �Reset, Menu �A type �A type

button Up/Down, Left/Right, Enter

Basic protection function(L / S / I / G)is still under normal operation

without control power.

-

-

-

-

-

-

-

-

-

-

-

-

Page 4: Susol TS 1600 ÀF Reaflet 1010 LS

Trip relay

000 Without trip relay

N

Trip relay type

G 0

N

N Normal

A Ammeter

A

G Ground fault

Z Without comm. + Earth leakage (<30A)

E Without comm. + Earth leakage (>30A)

C Comm.

K Comm. + Earth leakage (<30A)

X Comm. + Earth leakage (>30A)

G

0 Self-Power, 60Hz

1 AC/DC 100V~250V, 60Hz

2 DC 24V~60V, 60Hz

5 Self-Power, 50Hz

6 AC/DC 100V~250V, 50Hz

7 DC 24V~60V, 50Hz

0

P Power meter

P

C Ground fault + Com

K Comm. + Earth leakage (<30A)

X Comm. + Earth leakage (>30A)

A Comm. + Pre-trip alarm

C

1 AC/DC 100V~250V, 60Hz

2 DC 24V~60V, 60Hz

6 AC/DC 100V~250V, 50Hz

7 DC 24V~60V, 50Hz

1

S Supreme meter

S

C Ground fault + Com

K Comm. + Earth leakage (<30A)

X Comm. + Earth leakage (>30A)

A Comm. + Pre-trip alarm

C

1 AC/DC 100V~250V, 60Hz

2 DC 24V~60V, 60Hz

6 AC/DC 100V~250V, 50Hz

7 DC 24V~60V, 50Hz

1

* L/S/I/G configuration as standard-with LED indicators-without output contacts

* Ground fault system by vector sum

* L/S/I/G configuration as standard* Ground fault system by vector sum* Earth leakage system

- K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)- X: External CT - Private ZCT applied(faullt current >30A)

* Applicable to generator protection purpose

* L/S/I/G configuration as standard* Ground fault system by vector sum* Earth leakage system

- K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)- X: External CT - Private ZCT applied(faullt current >30A)

* Applicable to generator protection purpose

Note) 1. L/S/I/G configuration as standard2. Ground fault, earth leakage and pre-trip alarm functions are alternative.3. The functions like Metering, Communication, ZSI, Remote reset and Digital output are NOT available only under Self-power condition.4. Voltage module should be required for P and S types(supplied seperately)

* L/S/I/G configuration as standard* Ground fault system by vector sum(G,C)* Earth leakage system

- Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)- E,X: External CT - Private ZCT applied(faullt current >30A)

* Comm. and output contacts DO NOT work under self-power condition.

G

G Ground fault + L/S/I/G

Communication & protection Control voltage & frequency

0

0 Self-Power, 60Hz

5 Self-Power, 50Hz

Page 5: Susol TS 1600 ÀF Reaflet 1010 LS

Characteristic curves

Long-time delay (L) Short-time delay (S)

Instantaneous (I)Ground fault (G) IDMTL

× Ir

5000

2000

1000

500

200

100

50

3040

20

10

345

2

1

0.40.3

0.2

0.1

0.05

0.02

0.01

2010754321

0.7

0.5

t(s)

tr = 0.5...20s

20

8

4

2

1

0.5

12

Ir = 0.4...1 In

5000

2000

1000

500

200

100

50

30

20

40

10

45

3

2

1

0.40.3

0.2

0.1

0.05

0.02

0.011

0.7

0.5

t(s)

× Ir

201075432

Isd = 1.5...10 Ir

0.4

0.3

0.2

0.1

0.4

0.3

0.2

0.1

0.05

I2t OFF

I2t ON

× In

100

50

40

30

20

10

5

4

3

2

1

0.4

0.3

0.2

0.1

0.05

0.02

0.01

321

0.7

0.5

0.4

0.3

0.2 1075432

0.1

0.07

0.05

t(s)

Ig = 0.2...1 In

Ii = 2...15 In

0.4

0.3

0.2

0.1

0.4

0.3

0.2

0.1

0.05

I2t OFF

I2t ON

× Ir

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.05

2010754321

0.7

0.5

t(s)

EIT

VIT

SIT

DT

Page 6: Susol TS 1600 ÀF Reaflet 1010 LS

Dimensions

■ HEAD OFFICELS Tower, 1026-6 Hokyeh 1dong, Dongan-gu, Anyang, Kyonggi-Do, 431-848, KoreaTel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648

LS constantly endeavor to improve our products so that information in thiscatalog is subject to change without notice.

Susol 1600AF MCCB / October.2010 Printed in korea STAFF

4- 5.5 or M5

3P 4P

199

4- 5.5 or M5

269

CL

CL CL CL

CL CL CL

CLCL

199210

212

258

1443.5

1513

5

269280

212

258

190.6

115.7149.8152.5155.5162.7

114.7 84

372

42

37.2

283.

5

4470 70 70

31

70 7044

25

31

212

212

3P 4P 3P 4P

119

67

15

199

200

95

119

15

67

199

200

951111

212

19970 70

210

327

404

374

5077

252577

267

270

16.515

190.6

115.7149.8152.5

47.5

155.5162.7

212

26970 70

280

327

404

374

252577

362

270

252577

70

18

37.2

25

25115.7

283.

5

307 404

5.55.5

11 11

212

19970 70

210

327

270

190.6

115.7149.8152.5

47.5

155.5162.7

212

26970 70

280

327

270

70

25

115.7

16.5

320250Insulation barrier

Insulation barrier

Plate protection

Plate protection

Insulation barrier

Mounting hole

Mounting hole

Trip button

Trip button

Insulation barrier

Mounting hole

Trip button

25

37.2

283.

5

16.5

5.5 5.5

11

25

■■Front panel cutting

■■Panel drilling■■Rear Type

■■Front Type ■■Front Type Busbar