SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
3/64
2
1
3
4
SION Vacuum
Circuit-Breakers
Medium-Voltage EquipmentCatalog HG 11.02 2006
Contents Page
DescriptionGeneral
Construction and mode of operation, standards
Ambient conditions,
current carrying capacity and dielectric strength
Product range overview and basic equipment
56
7
10
11
Equipment SelectionOrdering data and configuration example
Selection of basic types, standard circuit-breakers
Secondary equipment for standard circuit-breakers
Selection of basic types, slide-in modules
Secondary equipment for slide-in modules
Accessories and spare parts
1314
15
23
28
32
37
Technical DataElectrical data, dimensions and weights:
Voltage levels 7.2 kV, 12 kV, 17.5 kV
Voltage level 24 kV
Operating times, short-circuit protection
of motors, consumption data of releases
Circuit diagrams
41
42
56
59
60
AnnexInquiry form
6162
SION Vacuum Circuit-Breakers Contents
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
4/64
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
5/64
1
DescriptionContents
Industrial application: Refinery
Contents Page
Description
General
Construction and mode of operation:
Switching medium
Pole assemblies
Operating mechanism
Trip-free mechanism
Releases
Closing / Circuit-breaker tripping signal
Interlocking
Low-voltage interface
Slide-in module
Standards
Ambient conditionsCurrent carrying capacity
Dielectric strength
Product range overview and basic equipment
5
6
7
7
7
7
8
8
8
8
9
9
1010
10
11
R-H
G11-
174.t
if
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
6/64
1
SION vacuum circuit-breaker from 7.2 to 24 kV The Innovative
Our comprehensive range of standard circuit-breakers offers
a wide selection for pole-center distances and widths across
The slide-in module contains all components required for
the circuit-breaker compartment of a panel It consists of the
SION vacuum circuit-breakers control all switching
duties in medium-voltage distribution systems and are
suitable for installation in all customary air-insulated
medium-voltage switchgear types. They are applicable
for operation of e.g. overhead lines, cables, transformers,
capacitors, generators, filter circuits, motors and
reactors. The comprehensive installation accessories
enable easy integration in the panel and form
maximally equipped as a slide-in module almost the
complete circuit-breaker compartment.
SION standard circuit-breaker the variable
R-H
G11-
167.e
p
s
SION slide-in module the complete
R-H
G11-
168.e
p
s
DescriptionGeneral
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
7/64
1
Switching medium
The vacuum switching technology of the vacuum interrup-
ters, which has been proven for 30 years, serves as arc-
quenching principle.
Pole assemblies
The pole assemblies consist of the vacuum interrupters and
the pole shells. The vacuum interrupters are air-insulated
and freely accessible. The pole assemblies are fixed on the
mounting plate of the operating mechanism and supported
by means of the pole shell. The vacuum interrupter (3) is
mounted rigidly to the upper interrupter support. The lower
part of the interrupter is guided in the lower interrupter
support, allowing axial movement. The pole shell (4) absorbs
the external forces resulting from switching operations andthe contact pressure.
Operating mechanism
The whole operating mechanism is mounted on its mount-
ing plate, including the motor, releases, indicators and
actuating devices.
Stored-energy operating mechanism
The operating mechanism is a stored-energy spring mechan-ism. The force is transmitted from the operating mechan-
ism to the pole assemblies via operating levers. The closing
spring can be charged either electrically or manually and
latches automatically in when charging is complete. The
closing spring acts as the stored-energy mechanism.
To close the breaker, the closing spring can be unlatched
either mechanically by means of the local ON pushbutton
or electrically by remote control. The closing spring chargesthe contact-pressure / opening springs as the breaker closes.
The now discharged closing spring will be charged again
automatically by the mechanism motor.
The breaker is now capable of performing the OPEN CLOSE
OPEN operating sequence that is required for an unsuc-
cessful auto-reclosing operation All stored-energy mecha-
1 Separating shellto the operatingmechanism
2 Upper connection
3 Interrupter
4 Pole shell
5 Lower connection6 Bell-type insulator
Vacuum circuit-breaker3AE1217.5kV/ 25 kA /1250A
Pole structure
1 Coverof low-voltageinterface
2 Central control board
R-
HG11-1
70.e
ps
DescriptionConstruction and mode of operation
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
8/64
1
Releases
A release is a device which transfers commands from an
external source, such as a control room, to the latching
mechanism of the circuit-breaker so that it can be opened or
closed. The releases are designed for short-time duty up to
1 minute and are reset internally. The various types of
releases available are described in detail below:
The closing solenoid unlatches the charged closing spring
of the vacuum circuit-breaker, closing it by electrical means.
Shunt releases are used for automatic tripping of vacuum
circuit-breakers by suitable protection relays and for delib-
erate tripping by electrical means. They are intended for
connection to an external power supply (DC or AC voltage)
but, in special cases, may also be connected to a voltage
transformer for manual operation. Current-transformer operated releases comprise a
stored-energy mechanism, an unlatching mechanism, and
an electromagnetic system. They are used when there is no
external source of auxiliary power (e.g. a battery). Tripping
is effected by means of a protection relay (e.g. overcurrent-
time protection) acting on the current-transformer operated
release.
Undervoltage releases comprise a stored-energy mecha-nism, an unlatching mechanism and an electromagnetic
system which is permanently connected to the secondary or
auxiliary voltage while the vacuum circuit-breaker is closed.
If the voltage falls below a predetermined value, unlatching
of the release is enabled and the circuit-breaker is opened
via the stored-energy mechanism.
The maximum equipment are 2 freely selected releases. For
release combinations, refer to page 23 or page 32. For con-
sumption data, refer to page 59.
Closing / Circuit-breaker tripping signal
In the standard version, the vacuum circuit-breakers can be
remote-closed electrically. In addition, they can be mechani-
cally closed locally by direct unlatching of the closing spring
The NO contact S6 makes brief contact while the circuit-
breaker is opening, and this is often used to operate a
hazard-warning system which, however, is only allowed to
respond to automatic tripping of the circuit-breaker. There-
fore, the signal from the NO contact must be interrupted
when the circuit-breaker is being opened intentionally. This
is accomplished under local control with the cut-out switchS7 that is connected in series with the NO contact.
For the corresponding circuit diagrams, refer to page 60.
Interlocking
Mechanical interlocking
At the interface of the mechanical interlocking of the
vacuum circuit-breaker, sensors on the switchgear side can
check the switch position and prevent the associated dis-connector from being closed while the vacuum circuit-
breaker is closed. The system also prevents the vacuum
circuit-breaker from being closed while the associated
disconnector is in a faulty position.
Vacuum circuit-breakers mounted on drawout elements are
mechanically interlocked, with the result that the handle for
racking the drawout element can only be inserted in the
OPEN position. The lock of the drawout element can onlybe released in the disconnected position by operating the
pushing handles.
If the vacuum circuit-breaker on the drawout element is in
an intermediate position (neither in the service nor in the
disconnected position), operation is not possible due to the
mechanical interlocking.
Electrical interlocking
The auxiliary and signaling contacts which show the switchposition of the vacuum circuit-breaker or the position of the
drawout element can be integrated in the switchgear inter-
locking concept in order to exclude impermissible switching
sequences.
l i f
DescriptionConstruction and mode of operation
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
9/64
1
Slide-in module
Besides the circuit-breaker installation equipment available for
standard circuit-breakers by means of the packages for the
drawout element, contact arms, fixed contacts and bushings,
it is also possible to supply a complete slide-in module.
The slide-in module contains all necessary components for
the circuit-breaker compartment of a panel. It consists of the
circuit-breaker on a drawout element with contact arms,
mounted in a cartridge with side and rear walls, equipped
with bushings, fixed contacts, shutters and shutter mecha-
nism. The surfaces of the side and rear walls form the tested
connection compartment.
The vacuum circuit-breaker on the drawout element is
racked into the cartridge with the associated handle by the
rotary movement of the spindle. The shutter mechanismis controlled by lateral gates, and the shutters are opened
for contacting. Signals for the service and disconnected
positions are transmitted to the module connector at the
low-voltage interface of the vacuum circuit-breaker via the
position switches of the drawout element.
Slide-in module
1 Contactsystem
2 Fixed contact
3 Shutter
4 Bushing
5 Cartridge
R-H
G11-
171.e
ps
6 Contact arm
7 Low-voltage interface
8 Vacuum circuit-breaker
9 Drawoutelement
DescriptionConstruction and mode of operation
Standards
The vacuum circuit-breakers conform to the followingstandards:
IEC 60 694
IEC 62 271-100
All SION vacuum circuit-breakers fulfil the endurance
classes E2, M2 and C2 according to IEC 62 271-100.
The slide-in modules have been tested according to
IEC 62 271-200 regarding
Dielectric strength
Temperature rise
Switching capacity.
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
10/64
1
Ambient conditions
Condensation can occasionally occur under the ambient
conditions shown opposite.
SION vacuum circuit-breakers are suitable for use in the
following climatic classes according to IEC 60 721, Part 3-3:
Climatic ambient conditions: Class 3K41)
Biological ambient conditions: Class 3B1
Mechanical ambient conditions: Class 3M2
Chemically-active substances: Class 3C22)
Mechanically-active substances: Class 3C23)
1) Low temperature limit: - 5 C
2) Without icingand wind-driven precipitation
3) Restriction: Clean insulationparts
Current carrying capacity
The rated normal currents specified in the diagram have
been defined according to IEC 62 271-100 for an ambient
temperature of + 40 C and apply to open switchgear.
For enclosed switchgear the data of the switchgear
manufacturer applies.
At ambient temperatures below + 40 C, higher normalcurrents can be carried (see diagram):
Characteristics curve1 = Rated normal current 800 ACharacteristics curve2 = Rated normal current 1250 ACharacteristics curve3 = Rated normal current 2000 ACharacteristics curve4 = Rated normal current 2500 ACharacteristics curve5 = Rated normal current 3150 A
Dielectric strengthThe dielectric strength of air insulation decreases with
increasing altitude due to low air density. According to
IEC 60 694, the rated lightning impulse withstand voltage
values specified in the chapter Technical Data apply to a
site altitude of 1000 m above sea level. For an altitude
above 1000 m the insulation level must be corrected
DescriptionAmbient conditions, current carrying capacity and dielectric strength
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
11/64
1
Product range overview
Pole centerdistance(in mm)
150 160 210 275
Width acrossflats(in mm)
Type kV kA A 205 275 310 205 275 310 205 275 310 310
3AE10 7.2 16 800/1250
20 800/1250
25 800/1250
25 2000
31.5 800/1250
31.5 2000/2500
40 1250/2000
40 2500/3150
3AE11 12 16 800/1250
20 800/1250 25 800/1250
25 2000/2500
31.5 800/1250
31.5 2000/2500
40 1250/2000
40 2500/3150
3AE12 17.5 12.5 800/1250
16 800/1250
25 800/1250
25 2000/2500 31.5 800/1250
31.5 2000/2500
40 1250/2000
40 2500/3150
3AE13 24 12.5 800/1250
16 800/1250/2000
20 800/1250
20 2000/2500
25 800/1250
25 2000/2500
Standardcircuit-breaker (fixed-mounted/drawout version with installationaccessories) Slide-in module
DescriptionProduct range overview and basic equipment
Rated
voltage
Ratedshort-
circuitbreaking
current
Rated
normalcurrent
Features Standard Alternative Remarks
O i h i El i l i h i Al f l i
Basic equipment
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
12/64
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
13/64
2
Standard circuit-breaker
Contents Page
Equipment Selection
Ordering data and configuration example
Selection of basic types, standard circuit-breakers:
Voltage level 7.2 kV
Voltage level 12 kV
Voltage level 17.5 kV
Voltage level 24 kV
Secondary equipment for standardcircuit-breakersAdditional equipment for standard circuit-breakers
Selection of basic types, slide-in modules:
Voltage level 7.2 kV
Voltage level 12 kV
Voltage level 17.5 kV
Voltage level 24 kV
Secondary equipment for slide-in modules
Additional equipment for slide-in modules
Accessories and spare parts
13
14
15
17
20
22
2327
28
29
30
31
32
36
37
Equipment SelectionContents
R-
HG11-1
76.e
ps
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
14/64
2
Order number structure
The vacuum circuit-breakers consist of a primary and a
secondary part. The relevant data make up the 16-digit
order number. The primary part covers the main electrical
data of the circuit-breaker poles. The secondary part covers
the auxiliary devices which are necessary for operating and
controlling the vacuum circuit-breaker.Order codes
Individual equipment versions, identified with 9orZin the
9th or 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.
Special versions (
)
In case of special versions, -Z is added to the order num-
ber and a descriptive order code follows. If several special
versions are required, the suffix -Z is listed only once.
If a requested special version is not in the catalog and can
therefore not be ordered via order code, it has to be identi-
fied withY 9 9after consultation. The agreement heretois made between your responsible sales partner and the
order processing department (PTD M C S) in our Switchgear
Factory in Berlin.
a: alphabetical n: numerical
Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
OrderNo.: 3 A E n n n n n a a n n n a a n
Primary part
1st position Superior groupSwitching devices
2nd position Main groupCircuit-breaker
3rd position SubgroupCircuit-breaker type series
4th to 8th position BasicequipmentDesign and ratingsprimary part
Secondary part
9th to16th position SecondaryequipmentOperating mechanism, releases, operatingvoltages and further auxiliary equipment
Ordercodes
Group of3 afterthe Order No.Format: a n a
Special versions ( )
Initiated with -ZGroup of3 afterthe Order No.Format: a n n
Equipment SelectionOrdering data and configuration example
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
15/64
2
7.2 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 1
310 1250 3 A E 1 0 8 2 2
275 800 3 A E 1 0 7 2 1
275 1250 3 A E 1 0 7 2 2
205 800 3 A E 1 0 6 2 1205 1250 3 A E 1 0 6 2 2
160 310 800 3 A E 1 0 5 2 1
310 1250 3 A E 1 0 5 2 2
275 800 3 A E 1 0 4 2 1
275 1250 3 A E 1 0 4 2 2
205 800 3 A E 1 0 3 2 1
205 1250 3 A E 1 0 3 2 2
150 310 800 3 A E 1 0 2 2 1
310 1250 3 A E 1 0 2 2 2
275 800 3 A E 1 0 1 2 1
275 1250 3 A E 1 0 1 2 2
205 800 3 A E 1 0 0 2 1
205 1250 3 A E 1 0 0 2 2
7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 1
310 1250 3 A E 1 0 8 3 2
275 800 3 A E 1 0 7 3 1
275 1250 3 A E 1 0 7 3 2
205 800 3 A E 1 0 6 3 1
205 1250 3 A E 1 0 6 3 2
160 310 800 3 A E 1 0 5 3 1
310 1250 3 A E 1 0 5 3 2275 800 3 A E 1 0 4 3 1
275 1250 3 A E 1 0 4 3 2
205 800 3 A E 1 0 3 3 1
205 1250 3 A E 1 0 3 3 2
150 310 800 3 A E 1 0 2 3 1
310 1250 3 A E 1 0 2 3 2
275 800 3 A E 1 0 1 3 1
Seepag
e23
Seepag
e23
Seepag
e24
Seepag
e24
Seepag
e25
Seepag
e25
Seepag
e26
Seepag
e26
Seepag
e27
Rated
voltage
Ratedlightningimpulse
withstandvoltage
Ratedsh
ort-duration
power-f
requency
withstandvoltage
Ratedsh
ort-circuit
breakingcurrent
at36%
ACcomponent
Ratedsh
ort-circuit
making
current
(at50/6
0Hz)
Pole-cen
terdistance
Widthacrossflats
Ratednormal
current
Equipment SelectionSelection of basic types, standard circuit-breakers
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
16/64
2
7.2 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
7.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 1
310 1250 3 A E 1 0 8 4 2
310 2000 3 A E 1 0 8 4 4
275 800 3 A E 1 0 7 4 1
275 1250 3 A E 1 0 7 4 2205 800 3 A E 1 0 6 4 1
205 1250 3 A E 1 0 6 4 2
160 310 800 3 A E 1 0 5 4 1
310 1250 3 A E 1 0 5 4 2
275 800 3 A E 1 0 4 4 1
275 1250 3 A E 1 0 4 4 2
205 800 3 A E 1 0 3 4 1
205 1250 3 A E 1 0 3 4 2
150 310 800 3 A E 1 0 2 4 1
310 1250 3 A E 1 0 2 4 2
275 800 3 A E 1 0 1 4 1
275 1250 3 A E 1 0 1 4 2
205 800 3 A E 1 0 0 4 1
205 1250 3 A E 1 0 0 4 2
7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 1
310 1250 3 A E 1 0 8 5 2
310 2000 3 A E 1 0 8 5 4
310 2500 3 A E 1 0 8 5 6
275 800 3 A E 1 0 7 5 1
275 1250 3 A E 1 0 7 5 2
205 800 3 A E 1 0 6 5 1205 1250 3 A E 1 0 6 5 2
160 310 800 3 A E 1 0 5 5 1
310 1250 3 A E 1 0 5 5 2
275 800 3 A E 1 0 4 5 1
275 1250 3 A E 1 0 4 5 2
205 800 3 A E 1 0 3 5 1
205 1250 3 A E 1 0 3 5 2
Equipment SelectionSelection of basic types, standard circuit-breakers
Seepag
e23
Seepag
e23
Seepag
e24
Seepag
e24
Seepag
e25
Seepag
e25
Seepag
e26
Seepag
e26
Seepag
e27
SION Vacuum Circuit-Breakers
Rated
voltage
Ratedlightningimpulse
withstandvoltage
Ratedshort-duration
power-frequency
withstandvoltage
Ratedshort-circuit
breakingcurrent
at36%
ACcomponent
Ratedshort-circuit
making
current
(at50/6
0Hz)
Pole-centerdistance
Widtha
crossflats
Ratednormal
current
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
17/64
2
12 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
12 75 28 16 40/42 210 310 800 3 A E 1 1 8 2 1
310 1250 3 A E 1 1 8 2 2
275 800 3 A E 1 1 7 2 1
275 1250 3 A E 1 1 7 2 2
205 800 3 A E 1 1 6 2 1205 1250 3 A E 1 1 6 2 2
160 310 800 3 A E 1 1 5 2 1
310 1250 3 A E 1 1 5 2 2
275 800 3 A E 1 1 4 2 1
275 1250 3 A E 1 1 4 2 2
205 800 3 A E 1 1 3 2 1
205 1250 3 A E 1 1 3 2 2
150 310 800 3 A E 1 1 2 2 1
310 1250 3 A E 1 1 2 2 2
275 800 3 A E 1 1 1 2 1
275 1250 3 A E 1 1 1 2 2
205 800 3 A E 1 1 0 2 1
205 1250 3 A E 1 1 0 2 2
12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 1
310 1250 3 A E 1 1 8 3 2
275 800 3 A E 1 1 7 3 1
275 1250 3 A E 1 1 7 3 2
205 800 3 A E 1 1 6 3 1
205 1250 3 A E 1 1 6 3 2
160 310 800 3 A E 1 1 5 3 1
310 1250 3 A E 1 1 5 3 2275 800 3 A E 1 1 4 3 1
275 1250 3 A E 1 1 4 3 2
205 800 3 A E 1 1 3 3 1
205 1250 3 A E 1 1 3 3 2
150 310 800 3 A E 1 1 2 3 1
310 1250 3 A E 1 1 2 3 2
275 800 3 A E 1 1 1 3 1
Equipment SelectionSelection of basic types, standard circuit-breakers
Seepag
e23
Seepag
e23
Seepag
e24
Seepag
e24
Seepag
e25
Seepag
e25
Seepag
e26
Seepag
e26
Seepag
e27
SION Vacuum Circuit-Breakers
Rated
voltage
Ratedlightningimpulse
withstandvoltage
Ratedshort-duration
power-frequency
withstandvoltage
Ratedshort-circuit
breakingcurrent
at36%
ACcomponent
Ratedshort-circuit
making
current
(at50/6
0Hz)
Pole-centerdistance
Widtha
crossflats
Ratedn
ormal
current
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
18/64
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
19/64
2
12 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
12 75 28 40 100/104 210 310 1250 3 A E 1 1 8 6 2
310 2000 3 A E 1 1 8 6 4
310 2500 3 A E 1 1 8 6 6
310 3150 3 A E 1 1 8 6 7
Special version (available for all 12 kV standard circuit-breakers)Ud = 42 kV Z E 1 3
Circuit-breaker for installation in NXAIR
12 75 28 31.5 80/82 210 275 1250 3 A E 1 5 7 5 2
275 2500 3 A E 1 5 7 5 6
160 275 1250 3 A E 1 5 4 5 2
12 75 28 40 100/104 210 275 1250 3 A E 1 5 7 6 2
275 2000 3 A E 1 5 7 6 4
275 2500 3 A E 1 5 7 6 6275 3150 3 A E 1 5 7 6 7
Special version (available for all 12 kV standard circuit-breakers)
Ud = 42 kV Z E 1 3
Equipment SelectionSelection of basic types, standard circuit-breakers
Seepag
e23
Seepag
e23
Seepag
e24
Seepag
e24
Seepag
e25
Seepag
e25
Seepag
e26
Seepag
e26
Seepag
e27
SION Vacuum Circuit-Breakers
Rated
voltage
Ratedlightningimpulse
withsta
ndvoltage
Ratedshort-duration
power-frequency
withsta
ndvoltage
Ratedshort-circuit
breakin
gcurrent
at36%
ACcomponent
Ratedshort-circuit
making
current
(at50/6
0Hz)
Pole-centerdistance
Widtha
crossflats
Ratedn
ormal
current
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
20/64
2
17.5 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 1
310 1250 3 A E 1 2 8 1 2
275 800 3 A E 1 2 7 1 1
275 1250 3 A E 1 2 7 1 2
205 800 3 A E 1 2 6 1 1205 1250 3 A E 1 2 6 1 2
160 310 800 3 A E 1 2 5 1 1
310 1250 3 A E 1 2 5 1 2
275 800 3 A E 1 2 4 1 1
275 1250 3 A E 1 2 4 1 2
205 800 3 A E 1 2 3 1 1
205 1250 3 A E 1 2 3 1 2
150 310 800 3 A E 1 2 2 1 1
310 1250 3 A E 1 2 2 1 2
275 800 3 A E 1 2 1 1 1
275 1250 3 A E 1 2 1 1 2205 800 3 A E 1 2 0 1 1
205 1250 3 A E 1 2 0 1 2
17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 1
310 1250 3 A E 1 2 8 2 2
275 800 3 A E 1 2 7 2 1
275 1250 3 A E 1 2 7 2 2
205 800 3 A E 1 2 6 2 1
205 1250 3 A E 1 2 6 2 2
160 310 800 3 A E 1 2 5 2 1
310 1250 3 A E 1 2 5 2 2
275 800 3 A E 1 2 4 2 1
275 1250 3 A E 1 2 4 2 2
205 800 3 A E 1 2 3 2 1
205 1250 3 A E 1 2 3 2 2
150 310 800 3 A E 1 2 2 2 1
310 1250 3 A E 1 2 2 2 2
275 800 3 A E 1 2 1 2 1
Equipment SelectionSelection of basic types, standard circuit-breakers
Seepag
e23
Seepag
e23
Seepag
e24
Seepag
e24
Seepag
e25
Seepag
e25
Seepag
e26
Seepag
e26
Seepag
e27
SION Vacuum Circuit-Breakers
Rated
voltage
Ratedlightningimpulse
withsta
ndvoltage
Ratedshort-duration
power-frequency
withsta
ndvoltage
Ratedshort-circuit
breakin
gcurrent
at36%
ACcomponent
Ratedshort-circuit
making
current
(at50/6
0Hz)
Pole-centerdistance
Widtha
crossflats
Ratedn
ormal
current
i l iSION V Ci i B k
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
21/64
2
17.5 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
17.5 95 38 25 63/65 210 275 800 3 A E 1 2 7 4 1
275 1250 3 A E 1 2 7 4 2
205 800 3 A E 1 2 6 4 1
205 1250 3 A E 1 2 6 4 2
160 310 800 3 A E 1 2 5 4 1310 1250 3 A E 1 2 5 4 2
275 800 3 A E 1 2 4 4 1
275 1250 3 A E 1 2 4 4 2
205 800 3 A E 1 2 3 4 1
205 1250 3 A E 1 2 3 4 2
150 310 800 3 A E 1 2 2 4 1
310 1250 3 A E 1 2 2 4 2
275 800 3 A E 1 2 1 4 1
275 1250 3 A E 1 2 1 4 2
205 800 3 A E 1 2 0 4 1
205 1250 3 A E 1 2 0 4 217.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 1
310 1250 3 A E 1 2 8 5 2
310 2000 3 A E 1 2 8 5 4
310 2500 3 A E 1 2 8 5 6
275 800 3 A E 1 2 7 5 1
275 1250 3 A E 1 2 7 5 2
205 800 3 A E 1 2 6 5 1
205 1250 3 A E 1 2 6 5 2
160 310 800 3 A E 1 2 5 5 1
310 1250 3 A E 1 2 5 5 2
275 800 3 A E 1 2 4 5 1
275 1250 3 A E 1 2 4 5 2
205 800 3 A E 1 2 3 5 1
205 1250 3 A E 1 2 3 5 2
150 310 800 3 A E 1 2 2 5 1
310 1250 3 A E 1 2 2 5 2
275 800 3 A E 1 2 1 5 1
Equipment SelectionSelection of basic types, standard circuit-breakers
Seepage23
Seepage23
Seepage24
Seepage24
Seepage25
Seepage25
Seepage26
Seepage26
Seepage27
SION Vacuum Circuit-Breakers
Rated
voltage
Ratedlightningimpulse
withsta
ndvoltage
Ratedshort-duration
power-frequency
withsta
ndvoltage
Ratedshort-circuit
breakin
gcurrent
at36%
ACcomponent
Ratedshort-circuit
making
current
(at50/6
0Hz)
Pole-centerdistance
Widtha
crossflats
Ratedn
ormal
current
E i t S l ti SION V c Ci c it B k s
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
22/64
2
24 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
24 125 50 12.5 31/33 210 310 800 3 A E 1 3 2 1 1
310 1250 3 A E 1 3 2 1 2
24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 1
310 1250 3 A E 1 3 2 2 2
310 2000 3 A E 1 3 2 2 4
275 310 800 3 A E 1 3 5 2 1
310 1250 3 A E 1 3 5 2 2
310 2000 3 A E 1 3 5 2 4
24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 1
310 1250 3 A E 1 3 2 3 2
310 2000 3 A E 1 3 2 3 4
310 2500 3 A E 1 3 2 3 6
275 310 800 3 A E 1 3 5 3 1
310 1250 3 A E 1 3 5 3 2
310 2000 3 A E 1 3 5 3 4
310 2500 3 A E 1 3 5 3 624 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 1
310 1250 3 A E 1 3 2 4 2
310 2000 3 A E 1 3 2 4 4
310 2500 3 A E 1 3 2 4 6
275 310 800 3 A E 1 3 5 4 1
310 1250 3 A E 1 3 5 4 2
310 2000 3 A E 1 3 5 4 4
310 2500 3 A E 1 3 5 4 6
Special version (available for all 24 kV standard circuit-breakers)
Ud
= 55 kV Z E 5 5
Circuit-breaker for installation in NXAIR
24 125 50 25 63/65 210 320 1250 3 A E 1 7 2 4 2
275 320 2500 3 A E 1 7 5 4 6
Special version (available for all 24 kV standard circuit-breakers)
Equipment SelectionSelection of basic types, standard circuit-breakers
Seepage23
Seepage23
Seepage24
Seepage24
Seepage25
Seepage25
Seepage26
Seepage26
Seepage27
SION Vacuum Circuit-Breakers
Rated
voltage
Ratedlightningimpulse
withsta
ndvoltage
Rateds
hort-duration
power-
frequency
withsta
ndvoltage
Rateds
hort-circuit
breakin
gcurrent
at36%
ACcomponent
Rateds
hort-circuit
making
current
(at50/6
0Hz)
Pole-ce
nterdistance
Widtha
crossflats
Ratedn
ormal
current
SION Vacuum Circuit Breakers Equipment Selection
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
23/64
2
9th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Release combination Order No.: 3 A E 1
A
B
C
G
H
F
E
N P
Q
J
L
M
10th position
Operating voltage of the closing solenoid
24VDC B
48VDC C
60VDC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz1)
J230 V AC 50/60 Hz 1) K
30VDC M
32VDC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
1stshun
trelease
2ndshuntrelease
Undervoltage
release
C.t.-ope
rated
release
0.5
A
C.t.-ope
rated
release
1.0
A
C.t.-ope
ratedrelease
withtrippingpulse
W
0.1
W
s(20O)
Standard voltages Specialvoltages
SION Vacuum Circuit-Breakers Equipment SelectionSecondary equipment for standard circuit-breakers
Seepage24
Seepage24
Seepage25
Seepage25
Seepage26
Seepage26
Seepage27
Equipment Selection SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
24/64
2
Equipment SelectionSecondary equipment for standard circuit-breakers
11th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Operating voltage of the1st release Order No.: 3 A E 1
C.t.-operated release 0
24VDC 1
48VDC 2
60VDC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 VDC 9 With order code L 1 A
32 VDC 9 With order code L 1 B
120 V DC 9 With order code L 1 C125 V DC 9 With order code L 1 D
127 V DC 9 With order code L 1 E
240 V DC 9 With order code L 1 F
120 V AC 50/60 Hz 1) 9 With order code L 1 K
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M
12th position
Operating voltage of the2nd release
Without, or c.t.-operated release 0
24VDC 1
48VDC 2
60VDC 3
110 V DC 4
220 V DC 5
100 V A C 50/60 Hz 1) 6
110 V A C 50/60 Hz 1) 7
230 V A C 50/60 Hz 1) 8
30 VDC 9 With order code M 1 A
32 VDC 9 With order code M 1 B
120 V DC 9 With order code M 1 C
125 V DC 9 With order code M 1 D
Standard voltages Specialvoltages
Standard voltages Specialvoltages
Seepage25
Seepage25
Seepage26
Seepage26
Seepage27
SION Vacuum Circuit Breakers
Equipment SelectionSION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
25/64
2
13th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Circuit-breaker installationaccessories Order No.: 3 A E 1
Options
Without circuit-breaker installation accessories,fixed-mountedcircuit-breaker 0
Withdrawout element 1
With drawout element, contact arms andcontact system 2
With drawout element, contact arms andcontact system,fixedcontacts and bushings 3
14thposition
Operating voltage of the motor operating mechanism
24VDC B
48VDC C
60VDC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30VDC M32VDC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W
1) The ACfrequency 50or 60Hz isselected at the 16th position of theordernumber together with the language (see page 26)
Standard voltages Specialvoltages
Equipment SelectionSecondary equipment for standard circuit-breakers
Seepage26
Seepage26
Seepage27
SION Vacuum Circuit Breakers
Equipment Selection SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
26/64
2
15th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Interlocking, auxiliary switch, circuit-breaker Order No.: 3 A E 1
trippingsignal and control cable connection
B
D
F
H
K
M
R
Q
A
C
E
G
J
L
N
P
Special versions
Auxiliary switch contacts 12 NO + 12 NC and pinsof the 64-pole plug connector gold-plated Z A 2 1
Key-interlocking (RONIS-lock at the vacuum circuit-breaker)Only for circuit-breakers without mechanical interlocking Z J 6 0
16th position
AC frequency of operating voltages
Languages of operating instructions and rating plate
German 50 Hz or DC 0
60Hz 1
English 50 Hz or DC 2
Mechanica
l
interlocking
6NO+6N
C
12NO+12
NC
Circuit-breaker
trippingsig
nal
27-pole
terminalstrip
24-poleplu
g
64-poleplu
g
Auxiliaryswitch Controlcableconnection
Language Frequency
Equipment SelectionSecondary equipment for standard circuit-breakers
Seepa
ge27
Equipment SelectionSION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
27/64
2
Additional equipment Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Order No.: 3 A E 1
Options
Wiring cables, halogen-free and flame-retardant Z A 1 0
Condensation protection,heating for230 V AC,50 W Z A 3 0
Silicone-free design Z A 3 1
Forcircuit-breaker operationat ambient airtemperatures down to -25 C Z A 4 0
Electricalclosing lock-out Z A 4 7
Additional ratingplate, loosedelivery Z B 0 0
Separatingshell towards contact arm side(standard version) Z D 9 0
Separatingshell towards contact arm side (short version) Z D 9 1
Routine testcertificate(enclosed with delivery) Z F 2 0
Routine testcertificate(withstampand signature) Z F 2 1
Routine testcertificate (to orderer) Z F 2 3
Hand crank (for manualcharging of theclosing spring) Z F 3 0Handle fordrawoutelement(forrackingthecircuit-breaker on thedrawoutelement)
Z F 3 2
Indication of disconnected position of the circuit-breaker(circuit-breaker with drawout element)
Z J 6 1
q pAdditional equipment for standard circuit-breakers
Equipment Selection SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
28/64
2
7.2 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 1
310 1250 3 A E 1 0 8 2 2
275 800 3 A E 1 0 7 2 1
275 1250 3 A E 1 0 7 2 2
150 310 800 3 A E 1 0 2 2 1
310 1250 3 A E 1 0 2 2 2
275 800 3 A E 1 0 1 2 1
275 1250 3 A E 1 0 1 2 2
7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 1
310 1250 3 A E 1 0 8 3 2
275 800 3 A E 1 0 7 3 1
275 1250 3 A E 1 0 7 3 2
150 310 800 3 A E 1 0 2 3 1
310 1250 3 A E 1 0 2 3 2
275 800 3 A E 1 0 1 3 1
275 1250 3 A E 1 0 1 3 27.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 1
310 1250 3 A E 1 0 8 4 2
310 2000 3 A E 1 0 8 4 4
275 800 3 A E 1 0 7 4 1
275 1250 3 A E 1 0 7 4 2
150 310 800 3 A E 1 0 2 4 1
310 1250 3 A E 1 0 2 4 2
275 800 3 A E 1 0 1 4 1
275 1250 3 A E 1 0 1 4 2
7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 1
310 1250 3 A E 1 0 8 5 2
310 2000 3 A E 1 0 8 5 4
310 2500 3 A E 1 0 8 5 6
275 800 3 A E 1 0 7 5 1
275 1250 3 A E 1 0 7 5 2
150 310 800 3 A E 1 0 2 5 1
310 1250 3 A E 1 0 2 5 2
Selection of basic types, slide-in modules
Seepa
ge32
Seepa
ge32
Seepa
ge33
Seepa
ge33
Seepa
ge34
Seepa
ge34
Seepa
ge35
Seepa
ge35
Seepa
ge36
Rated
voltage
Ratedlightningimpulse
withstandvoltage
Ratedshort-duration
power-frequency
withstandvoltage
Ratedshort-circuit
breakingcurrent
at36%
ACcomponent
Ratedshort-circuit
makingcurrent
(at50/60Hz)
Pole-ce
nterdistance
Widthacrossflats
Ratednormal
current
Equipment SelectionSION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
29/64
2
12 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
12 75 28 16 40/42 210 310 800 3 A E 1 1 8 2 1
310 1250 3 A E 1 1 8 2 2
275 800 3 A E 1 1 7 2 1
275 1250 3 A E 1 1 7 2 2
150 310 800 3 A E 1 1 2 2 1
310 1250 3 A E 1 1 2 2 2
275 800 3 A E 1 1 1 2 1
275 1250 3 A E 1 1 1 2 2
12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 1
310 1250 3 A E 1 1 8 3 2
275 800 3 A E 1 1 7 3 1
275 1250 3 A E 1 1 7 3 2
150 310 800 3 A E 1 1 2 3 1
310 1250 3 A E 1 1 2 3 2
275 800 3 A E 1 1 1 3 1
275 1250 3 A E 1 1 1 3 212 75 28 25 63/65 210 310 800 3 A E 1 1 8 4 1
310 1250 3 A E 1 1 8 4 2
310 2000 3 A E 1 1 8 4 4
310 2500 3 A E 1 1 8 4 6
275 800 3 A E 1 1 7 4 1
275 1250 3 A E 1 1 7 4 2
150 310 800 3 A E 1 1 2 4 1
310 1250 3 A E 1 1 2 4 2
275 800 3 A E 1 1 1 4 1
275 1250 3 A E 1 1 1 4 2
12 75 28 31.5 80/82 210 310 800 3 A E 1 1 8 5 1
310 1250 3 A E 1 1 8 5 2
310 2000 3 A E 1 1 8 5 4
310 2500 3 A E 1 1 8 5 6
275 800 3 A E 1 1 7 5 1
275 1250 3 A E 1 1 7 5 2
150 310 800 3 A E 1 1 2 5 1
Selection of basic types, slide-inmodules
Seepa
ge32
Seepa
ge32
Seepa
ge33
Seepa
ge33
Seepa
ge34
Seepa
ge34
Seepa
ge35
Seepa
ge35
Seepa
ge36
Rated
voltage
Ratedlightningimpulse
withstandvoltage
Ratedshort-duration
power-frequency
withstandvoltage
Ratedshort-circuit
breakingcurrent
at36%
ACcomponent
Ratedshort-circuit
makingcurrent
(at50/
60Hz)
Pole-centerdistance
Width
acrossflats
Ratednormal
curren
t
Equipment SelectionS l ti f b i t lid i d l
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
30/64
2
17.5 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 1
310 1250 3 A E 1 2 8 1 2
275 800 3 A E 1 2 7 1 1
275 1250 3 A E 1 2 7 1 2
150 310 800 3 A E 1 2 2 1 1
310 1250 3 A E 1 2 2 1 2
275 800 3 A E 1 2 1 1 1
275 1250 3 A E 1 2 1 1 2
17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 1
310 1250 3 A E 1 2 8 2 2
275 800 3 A E 1 2 7 2 1
275 1250 3 A E 1 2 7 2 2
150 310 800 3 A E 1 2 2 2 1
310 1250 3 A E 1 2 2 2 2
275 800 3 A E 1 2 1 2 1
275 1250 3 A E 1 2 1 2 217.5 95 38 25 63/65 210 310 800 3 A E 1 2 8 4 1
310 1250 3 A E 1 2 8 4 2
310 2000 3 A E 1 2 8 4 4
310 2500 3 A E 1 2 8 4 6
275 800 3 A E 1 2 7 4 1
275 1250 3 A E 1 2 7 4 2
150 310 800 3 A E 1 2 2 4 1
310 1250 3 A E 1 2 2 4 2
275 800 3 A E 1 2 1 4 1
275 1250 3 A E 1 2 1 4 2
17.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 1
310 1250 3 A E 1 2 8 5 2
310 2000 3 A E 1 2 8 5 4
310 2500 3 A E 1 2 8 5 6
275 800 3 A E 1 2 7 5 1
275 1250 3 A E 1 2 7 5 2
150 310 800 3 A E 1 2 2 5 1
Selection of basic types, slide-in modules
Seepa
ge32
Seepa
ge32
Seepa
ge33
Seepa
ge33
Seepa
ge34
Seepa
ge34
Seepa
ge35
Seepa
ge35
Seepa
ge36
Rated
voltage
Ratedlightningimpulse
withstandvoltage
Ratedshort-duration
power
-frequency
withstandvoltage
Ratedshort-circuit
breakingcurrent
at36%
ACcomponent
Ratedshort-circuit
makingcurrent
(at50/60Hz)
Pole-centerdistance
Width
acrossflats
Ratednormal
curren
t
Equipment SelectionS l i f b i lid i d l
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
31/64
2
24 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A E 1
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm mm A
24 125 50 12.5 31/33 210 310 800 3 A E 1 3 2 1 1
310 1250 3 A E 1 3 2 1 2
24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 1
310 1250 3 A E 1 3 2 2 2
310 2000 3 A E 1 3 2 2 4
275 310 800 3 A E 1 3 5 2 1
310 1250 3 A E 1 3 5 2 2
310 2000 3 A E 1 3 5 2 4
24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 1
310 1250 3 A E 1 3 2 3 2
310 2000 3 A E 1 3 2 3 4
310 2500 3 A E 1 3 2 3 6
275 310 800 3 A E 1 3 5 3 1
310 1250 3 A E 1 3 5 3 2
310 2000 3 A E 1 3 5 3 4
310 2500 3 A E 1 3 5 3 624 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 1
310 1250 3 A E 1 3 2 4 2
310 2000 3 A E 1 3 2 4 4
310 2500 3 A E 1 3 2 4 6
275 310 800 3 A E 1 3 5 4 1
310 1250 3 A E 1 3 5 4 2
310 2000 3 A E 1 3 5 4 4
310 2500 3 A E 1 3 5 4 6
Selection of basic types, slide-inmodules
Seepa
ge32
Seepa
ge32
Seepa
ge33
Seepa
ge33
Seepa
ge34
Seepa
ge34
Seepa
ge35
Seepa
ge35
Seepa
ge36
Rated
voltage
Ratedlightningimpulse
withstandvoltage
Ratedshort-duration
power
-frequency
withstandvoltage
Ratedshort-circuit
breakingcurrent
at36%
ACcomponent
Ratedshort-circuit
makingcurrent
(at50/60Hz)
Pole-centerdistance
Width
acrossflats
Ratednormal
curren
t
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
32/64
SION Vacuum Circuit-Breakers Equipment SelectionSecondary equipment for slide-inmodules
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
33/64
2
11th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Operating voltage of the1st release Order No.: 3 A E 1
C.t.-operated release 0
24VDC 1
48VDC 2
60VDC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 VDC 9 With order code L 1 A
32 VDC 9 With order code L 1 B
120 V DC 9 With order code L 1 C125 V DC 9 With order code L 1 D
127 V DC 9 With order code L 1 E
240 V DC 9 With order code L 1 F
120 V AC 50/60 Hz 1) 9 With order code L 1 K
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M
12th position
Operating voltage of the2nd release
Without, or c.t.-operated release 0
24VDC 1
48VDC 2
60VDC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 VDC 9 With order code M 1 A
32 VDC 9 With order code M 1 B
120 V DC 9 With order code M 1 C
125 V DC 9 With order code M 1 D
Standard voltages Specialvoltages
Standard voltages Specialvoltages
Seepage34
Seepage34
Seepage35
Seepage35
Seepage36
Secondary equipment for slide-inmodules
Equipment SelectionSecondary equipment for slide-in modules
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
34/64
2
13th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Circuit-breaker installationaccessories Order No.: 3 A E 1
On cartridge,with drawout element, contact arms, contact system,
fixedcontacts,bushingsand shutters 5
On cartridge,with drawout element, contact arms, contact system,
fixedcontacts,bushings,shuttersand earthing switch
with short-circuit making capacity 6
Drawings of the fullyequipped slide-in-module.
Scopeof supply includes fixed-mounted circuit-breaker 8
14th position
Operating voltage of the motor operating mechanism
24VDC B
48VDC C
60VDC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 VDC M
32 VDC N
120 V DC P
125 V DC Q
127 V DC R
240 V DC S
120 V AC 50/60 Hz 1) U
125 V AC 50/60 Hz 1) V
240 V AC 50/60 Hz 1) W
1) The ACfrequency 50or 60Hz isselected at the 16th position of theordernumber together with the language (see page 35)
Standard voltages Specialvoltages
y q p
Seepage35
Seepage35
Seepage36
Options
Equipment SelectionSecondary equipment for slide-inmodules
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
35/64
216th positionAC frequency of operating voltagesLanguages of operating instructionsandrating plate
German 50 Hz or DC 0
60Hz 1
English 50 Hz or DC 2
60Hz 3
French 50 Hz or DC 4
60Hz 5
Spanish 50 Hz or DC 6
60Hz 7Other languages on request
Language Frequency
y q p
15th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Interlocking, auxiliary switch, circuit-breaker Order No.: 3 A E 1
trippingsignal and control cable connection
A
C
J
L
N
P
Special versions
Auxiliary switch contacts 12NO + 12 NCandpins
of the 64-pole plug connectorgold-plated Z A 2 1
Mechanical
interlockin
g
6NO+6N
C
12NO+1
2NC
Circuit-bre
aker
trippingsignal
27-pole
terminalstrip
64-poleplug
Seepage36
Auxiliaryswitch Control cable connection
Equipment SelectionAdditional equipment for slide-in modules
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
36/64
2
Additional equipment Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes
Order No.: 3 A E 1
Options
Wiring cables, halogen-free and flame-retardant Z A 1 0
Condensationprotection, heating for 230 V AC,50 W Z A 3 0
Silicone-free design Z A 3 1
Forcircuit-breaker operation at ambient air temperatures down to -25 C Z A 4 0
Electrical closing lock-out Z A 4 7
Additional ratingplate, loosedelivery Z B 0 0
Routine testcertificate (enclosed withdelivery) Z F 2 0
Routine testcertificate(withstamp and signature) Z F 2 1
Routine testcertificate(to orderer) Z F 2 3
Hand crank (for manualchargingof theclosing spring) Z F 3 0
Handlefor drawout element (for racking thecircuit-breaker on thedrawout element)
Z F 3 2
Handle forearthing switch(for operatingthe switchat themodule) Z F 3 4
Equipment SelectionAccessories and spare parts
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
37/64
2
Designation Remarks Operating voltage Order No.
Handles Hand crankfor circuit-breaker 3AX15 30-2B
Long hand crankfor circuit-breaker 3AX14 30-2B
Handlefor drawout element 3AX14 30-2C
Handle for earthing switch (forslide-in module) 3AX14 30-2D
Lubricant 180g of Klber-Isoflex Topas L32 3AX11 33-3H
1 kg of Klber-Isoflex Topas L32 3AX11 33-3E
1 kg of Molykote grease 3AX11 33-2L
Operatingsolenoid Used as closing solenoid or 24 V DC 3AY15 10-5B
1st shunt release 30/32 V DC 3AY15 10-5M
48VDC 3AY15 10-5C
60VDC 3AY15 10-5D100/124 V DC 3AY15 10-5E
125/144 V DC 3AY15 10-5N
220/250 V DC 3AY15 10-5F
100/125 V AC,50/60Hz 3AY15 10-5E
230/240 V AC,50/60Hz 3AY15 10-5F
2nd shuntrelease 24/32 V DC 3AX11 01-2B
Retrofitting
When releases / solenoids are retrofitted, the order num-
bers of the built-on parts must also be specified. For other
additional equipment, the required mounting parts are
included in the delivery.
Spare partsWhen releases / solenoids are required as spare parts, the
order number and the type of construction of the asso-
ciated standard circuit-breaker must also be specified.
Remark for orders
The order numbers are applicable to standard circuit-
breakers of current manufacture. When mounting parts
or spare parts are being ordered for an existing standardcircuit-breaker, always quote the type designation, serial No.,
design code and the year of manufacture of the circuit-
breaker to be sure to get the correct delivery.
Accessories for the plug connector
Included in the scope of supply of the basic equipment for
standard circuit-breakers:
For 24-pole plug connector
Lower part of plug
Crimp sockets acc. to number of contacts
Upper part of plug with screwed contacts(no crimp sockets required)
For 64-pole plug connector
Lower part of plug
Upper part of plug
Crimp sockets according to number of contacts
Vacuum interrupters and other spare parts must only be
replaced by instructed personnel.
Equipment SelectionAccessories and spare parts
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
38/64
2
Designation Remarks Operating voltage Order No.
Undervoltage release 24VDC 3AX11 03-2B
30/32 V DC 3AX11 03-2L
48VDC 3AX11 03-2C
60VDC 3AX11 03-2D
110 V DC 3AX11 03-2E120/127 V DC 3AX11 03-2N
220 V DC 3AX11 03-2F
240 V DC 3AX11 03-2P
100 V AC, 50Hz 3AX11 03-2G
110/125 V AC, 50Hz 3AX11 03-2H
230 V AC, 50Hz 3AX11 03-2J
240 V AC, 50Hz 3AX11 03-2M
100 V AC, 60Hz 3AX11 03-3G
110/125 V AC, 60Hz 3AX11 03-3H
230 V AC, 60Hz 3AX11 03-3J240 V AC, 60Hz 3AX11 03-3M
Mounting parts For undervoltagerelease 3AX14 11-2A
Drive motor 24/30/32 V DC 3AY17 11-2B
48VDC 3AY17 11-2C
60VDC 3AY17 11-2D
100/110/125 V DC/AC 3AY17 11-2E
220 V DC/230V AC 3AY17 11-2F
Auxiliary contactor 24VDC SWB:55656
type 3RH11 22 for anti-pumping 30/32 V DC SWB:55658
48VDC SWB:55659
60VDC SWB:55660110 V DC SWB:55661
120/127 V DC SWB:55662
220 V DC SWB:55663
240/250 V AC SWB:55665
110 V AC, 50/60 Hz SWB:55666
120 V AC, 50/60 Hz SWB:55667
125 V AC, 50/60 Hz SWB:55668
230 V AC, 50/60 Hz SWB:55669
240 V AC, 50/60 Hz SWB:55670
Position switch Type SE4 without installationaccessories SWB:46677
Used for: Nos.
Electrical anti-pumping (-S3) 1
Electrical interlocking (-S12) 1
Motor control (-S21, -S22) 2
Closing spring charged (-S4) 1
C ircuit-breaker t ripping s ignal ( -S6, - S7) 2
El t i l l i l k t ( S5) 1
Equipment SelectionAccessories and spare parts
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
39/64
2
Designation Remarks Operating voltage Order No.
Electricalclosing lock-out 24VDC 3AX14 05-2B
30/32 V DC 3AX14 05-2K
48VDC 3AX14 05-2C
60VDC 3AX14 05-2D
110/127 V DC 3AX14 05-2E220/240 V DC 3AX14 05-2F
100 V AC, 50/60 Hz 3AX14 05-2G
110/125 V AC,50/60Hz 3AX14 05-2H
220/240 V AC,50/60Hz 3AX14 05-2J
Mounting parts For electrical closing lock-out 3AX14 15-2A
Bushing 7.2 to17.5kV to1250A 3AX14 51-2A
7.2 to17.5kV to3150A 3AX14 51-2B
24kVto 2500A 3AX14 51-2B
Separatingshell towards Additional shielding fornarrow mounting conditions
contact arm side, forstandard Standardversion, width acrossflats310mm 7.2to17.5kV 3AX14 38-2A
circuit-breakers only Standardversion, width acrossflats275mm 7.2to17.5kV 3AX14 38-2C
Standardversion, width acrossflats205mm 7.2to17.5kV 3AX14 38-2D
Standardversion,widthacross f lats310mm 24kV 3AX14 38-2B
Short version, width across flats 310 mm 24 kV 3AX14 38-3B
Gatefor cartridge Shortversion 3AX14 52-2B
Contact system 7.2/12/24 kV, 800to 1250 A 3AX14 42-2A
17.5kV,800to 1250A 3AX14 42-2B
7.2/12/24kV, to 3150 A 3AX14 42-2C
17.5kV,to 3150A 3AX14 42-2D
Note:
For any query regarding spare parts,
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
40/64
Technical DataContents
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
41/64
3
SION vacuum circuit-breaker with drawout element,
contact arms and contact system
Contents Page
Technical Data
Electrical data, dimensions and weights:
Voltage level 7.2 kV
Voltage level 12 kV
Voltage level 17.5 kV
Voltage level 24 kV
Dimension drawings:
Voltage levels 7.2 to 17.5 kV
Voltage level 24 kV
Operating times, short-circuit protectionof motors, consumption data of releases
Circuit diagrams
41
42
46
50
56
54
58
59
60
R-H
G11-
178.e
ps
Technical DataElectrical data, dimensions and weights
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
42/64
3
7.2 kV50/60 Hz
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3AE1 002-1 ... 800 205 150
3 16 36 17.9
40/
42 60 20 2.1 129 140 105 75 80/
3M442
02010 001 1 K/
3AE1 002-2 ... 1250 205 150 3 16 36 17.9 40/
42 60 20 2.1 129 140 105 75 80/ 3M442
02010 001 1 K/
3AE1 003-1 ... 800 205 150 3 20 36 22.4 50/52
60 20 2.1 129 140 105 75 80/ 3M44202010 001
2 K/
3AE1 003-2 ... 1250 205 150 3 20 36 22.4 50/52
60 20 2.1 129 140 105 75 80/ 3M44202010 001
2 K/
3AE1 004-1 ... 800 205 150 3 25 36 28 63/
65 60 20 2.1 129 140 105 75 80/ 3M442
02010 001 3 K/
3AE1 004-2 ... 1250 205 150 3 25 36 28 63/
65 60 20 2.1 129 140 105 75 80/ 3M442
02010 001 3 K/
3AE1 005-1 ... 800 205 150 3 31.5 36 35.4 80/
82
60 20 2.1 129 140 105 75 80/ 3M442
02010 001
4 K/
3AE1 005-2 ... 1250 205 150 3 31.5 36 35.4 80/82
60 20 2.1 129 140 105 75 80/ 3M44202010 001
4 K/
3AE1 012-1 ... 800 275 150 3 16 36 17.9 40/42
60 20 2.1 129 140 105 75 80/120
3M 44202011 001
1 I/J
3AE1 012-2 ... 1250 275 150 3 16 36 17.9 40/
42 60 20 2.1 129 140 105 75 80/
1203M 44202011 001
1 I/J
3AE1 013-1 ... 800 275 150 3 20 36 22.4 50/
52 60 20 2.1 129 140 105 75 80/
1203M 44202011 001
2 I/J
3AE1 013-2 ... 1250 275 150 3 20 36 22.4 50/52
60 20 2.1 129 140 105 75 80/120
3M 44202011 001
2 I/J
3AE1 014-1 ... 800 275 150 3 25 36 28 63/65
60 20 2.1 129 140 105 75 80/120
3M 44202011 001
3 I/J
3AE1 014-2 ... 1250 275 150 3 25 36 28 63/
65 60 20 2.1 129 140 105 75 80/
1203M 44202011 001
3 I/J
3AE1 015-1 ... 800 275 150 3 31.5 36 35.4 80/
82 60 20 2.1 129 140 105 75 80/
1203M 44202011 001
4 I/J
3AE1 015-2 ... 1250 275 150 3 31.5 36 35.4 80/82
60 20 2.1 129 140 105 75 80/120
3M 44202011 001
4 I/J
3AE1 022-1 ... 800 310 150 3 16 36 17.9 40/42
60 20 2.1 129 140 100 75 80/120
3M 44202012 001
1 H/J
OrderNo.
Ratednormalcurr
ent
Widthacrossflats
Pole-centerdistan
ce
Ratedoperatingsequence:
O-3min-CO-3m
in-CO
O-0.3s-CO-3min-CO
O-0.3s-CO-15s
-CO
Ratedshort-circuitduration
Ratedshort-circuitbreakingcurrent
DCcomponentin%
ofthe
ratedshort-circuitb
reakingcurrent
Asymmetricalbreakingcurrent
Ratedshort-circuitmakingcurrent
(at50/60Hz)
Ratedlightningimp
ulsewithstandvoltage
Ratedshort-duratio
npower-frequency
withstandvoltage
VoltagedropUbe
tweenconnections
(accordingtoIEC60694atDC100A)
Minimum
creepage
distance,
interrupter
Minimum
creepage
distance,
phase-to-earth
Minimum
clearance,
phase-to-phase
Minimum
clearance,
phase-to-earth
Weight1)
(fixed-mountedcirc
uit-breaker/slide-inmodule)
Detaileddimension
drawing
(hastobeordered)
Operatingcycledia
gram
No.
(seepage45)
Catalogdimensiond
rawings(seepages54/55)
(fixed-mountedcircuit-breaker/slide-inmodule)
Technical DataElectrical data, dimensions and weights
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
43/64
3
7.2 kV50/60 Hz
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3AE1 032-1 ... 800 205 160
3 16 36 17.9
40/
42 60 20 2.1 129 140 115 75 80/
3M442
02016 001 1 G/
3AE1 032-2 ... 1250 205 160 3 16 36 17.9 40/
42 60 20 2.1 129 140 115 75 80/ 3M442
02016 001 1 G/
3AE1 033-1 ... 800 205 160 3 20 36 22.4 50/52
60 20 2.1 129 140 115 75 80/ 3M44202016 001
2 G/
3AE1 033-2 ... 1250 205 160 3 20 36 22.4 50/52
60 20 2.1 129 140 115 75 80/ 3M44202016 001
2 G/
3AE1 034-1 ... 800 205 160 3 25 36 28 63/
65 60 20 2.1 129 140 115 75 80/ 3M442
02016 001 3 G/
3AE1 034-2 ... 1250 205 160 3 25 36 28 63/
65 60 20 2.1 129 140 115 75 80/ 3M442
02016 001 3 G/
3AE1 035-1 ... 800 205 160 3 31.5 36 35.4 80/
82
60 20 2.1 129 140 115 75 80/ 3M442
02016 001
4 G/
3AE1 035-2 ... 1250 205 160 3 31.5 36 35.4 80/82
60 20 2.1 129 140 115 75 80/ 3M44202016 001
4 G/
3AE1 042-1 ... 800 275 160 3 16 36 17.9 40/42
60 20 2.1 129 140 115 75 80/ 3M44202017 001
1 F/
3AE1 042-2 ... 1250 275 160 3 16 36 17.9 40/
42 60 20 2.1 129 140 115 75 80/ 3M442
02017 001 1 F/
3AE1 043-1 ... 800 275 160 3 20 36 22.4 50/
52 60 20 2.1 129 140 115 75 80/ 3M442
02017 001 2 F/
3AE1 043-2 ... 1250 275 160 3 20 36 22.4 50/52
60 20 2.1 129 140 115 75 80/ 3M44202017 001
2 F/
3AE1 044-1 ... 800 275 160 3 25 36 28 63/65
60 20 2.1 129 140 115 75 80/ 3M44202017 001
3 F/
3AE1 044-2 ... 1250 275 160 3 25 36 28 63/
65 60 20 2.1 129 140 115 75 80/ 3M442
02017 001 3 F/
3AE1 045-1 ... 800 275 160 3 31.5 36 35.4 80/
82 60 20 2.1 129 140 115 75 80/ 3M442
02017 001 4 F/
3AE1 045-2 ... 1250 275 160 3 31.5 36 35.4 80/82
60 20 2.1 129 140 115 75 80/ 3M44202017 001
4 F/
3AE1 052-1 ... 800 310 160 3 16 36 17.9 40/42
60 20 2.1 129 140 110 75 80/ 3M44202018 001
1 E/
OrderNo.
Ratednormalcurr
ent
Widthacrossflats
Pole-centerdistan
ce
Ratedoperatingsequence:
O-3min-CO-3m
in-CO
O-0.3s-CO-3min-CO
O-0.3s-CO-15s
-CO
Ratedshort-circuitduration
Ratedshort-circuitbreakingcurrent
DCcomponentin%
ofthe
ratedshort-circuitb
reakingcurrent
Asymmetricalbreakingcurrent
Ratedshort-circuitmakingcurrent
(at50/60Hz)
Ratedlightningimp
ulsewithstandvoltage
Ratedshort-duratio
npower-frequency
withstandvoltage
VoltagedropUbe
tweenconnections
(accordingtoIEC60694atDC100A)
Minimum
creepage
distance,
interrupter
Minimum
creepage
distance,
phase-to-earth
Minimum
clearance,
phase-to-phase
Minimum
clearance,
phase-to-earth
Weight1)
(fixed-mountedcirc
uit-breaker/slide-inmodule)
Detaileddimension
drawing
(hastobeordered)
Operatingcycledia
gram
No.
(seepage45)
Catalogdimensiond
rawings(seepages54/55)
(fixed-mountedcircuit-breaker/slide-inmodule)
Technical DataElectrical data, dimensions and weights
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
44/64
3
7.2 kV50/60 Hz
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3AE1 063-1 ... 800 205 210
3 20 36 22.4 50/
52 60 20 2.1 129 140 165 75 90/ 3M442
02022 001 2 D/
3AE1 063-2 ... 1250 205 210 3 20 36 22.4 50/
52 60 20 2.1 129 140 165 75 90/ 3M442
02022 001 2 D/
3AE1 064-1 ... 800 205 210 3 25 36 28 63/65
60 20 2.1 129 140 165 75 90/ 3M44202022 001
3 D/
3AE1 064-2 ... 1250 205 210 3 25 36 28 63/65
60 20 2.1 129 140 165 75 90/ 3M44202022 001
3 D/
3AE1 065-1 ... 800 205 210 3 31.5 36 35.4 80/
82 60 20 2.1 129 140 165 75 90/ 3M442
02022 001 4 D/
3AE1 065-2 ... 1250 205 210 3 31.5 36 35.4 80/
82 60 20 2.1 129 140 165 75 90/ 3M442
02022 001 4 D/
3AE1 072-1 ... 800 275 210 3 16 36 17.9 40/
42
60 20 2.1 129 140 165 75 90/
130
3M 442
02023 001
1 B/C
3AE1 072-2 ... 1250 275 210 3 16 36 17.9 40/42
60 20 2.1 129 140 165 75 90/130
3M 44202023 001
1 B/C
3AE1 073-1 ... 800 275 210 3 20 36 22.4 50/52
60 20 2.1 129 140 165 75 90/130
3M 44202023 001
2 B/C
3AE1 073-2 ... 1250 275 210 3 20 36 22.4 50/
52 60 20 2.1 129 140 165 75 90/
1303M 44202023 001
2 B/C
3AE1 074-1 ... 800 275 210 3 25 36 28 63/
65 60 20 2.1 129 140 165 75 90/
1303M 44202023 001
3 B/C
3AE1 074-2 ... 1250 275 210 3 25 36 28 63/65
60 20 2.1 129 140 165 75 90/130
3M 44202023 001
3 B/C
3AE1 075-1 ... 800 275 210 3 31.5 36 35.4 80/82
60 20 2.1 129 140 165 75 90/130
3M 44202023 001
4 B/C
3AE1 075-2 ... 1250 275 210 3 31.5 36 35.4 80/
82 60 20 2.1 129 140 165 75 90/
1303M 44202023 001
4 B/C
3AE1 082-1 ... 800 310 210 3 16 36 17.9 40/
42 60 20 2.1 129 140 160 75 90/
1303M 44202024 001
1 A/C
3AE1 082-2 ... 1250 310 210 3 16 36 17.9 40/42
60 20 2.1 129 140 160 75 90/130
3M 44202024 001
1 A/C
3AE1 083-1 ... 800 310 210 3 20 36 22.4 50/52
60 20 2.1 129 140 160 75 90/130
3M 44202024 001
2 A/C
OrderNo.
Ratednormalcurr
ent
Widthacrossflats
Pole-centerdistan
ce
Ratedoperatingsequence:
O-3min-CO-3m
in-CO
O-0.3s-CO-3min-CO
O-0.3s-CO-15s
-CO
Ratedshort-circuitduration
Ratedshort-circuitbreakingcurrent
DCcomponentin%
ofthe
ratedshort-circuitb
reakingcurrent
Asymmetricalbreakingcurrent
Ratedshort-circuitmakingcurrent
(at50/60Hz)
Ratedlightningimpulsewithstandvoltage
Ratedshort-duratio
npower-frequency
withstandvoltage
VoltagedropUbe
tweenconnections
(accordingtoIEC60694atDC100A)
Minimum
creepagedistance,
interrupter
Minimum
creepagedistance,
phase-to-earth
Minimum
clearance,
phase-to-phase
Minimum
clearance,
phase-to-earth
Weight1)
(fixed-mountedcirc
uit-breaker/slide-inmodule)
Detaileddimension
drawing
(hastobeordered)
Operatingcycledia
gram
No.
(seepage45)
Catalogdimensiondrawings(seepages54/55)
(fixed-mountedcircuit-breaker/slide-inmodule)
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
45/64
Technical DataElectrical data, dimensions and weights
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
46/64
3
12 kV50/60 Hz
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3AE1 102-1 ... 800 205 150 3 16 36 17.9 40/
42 75 28 2.1 129 140 105 75 80/ 3M442
02010 001 1 K/
3AE1 102-2 ... 1250 205 150 3 16 36 17.9 40/
42 75 28 2.1 129 140 105 75 80/ 3M442
02010 001 1 K/
3AE1 103-1 ... 800 205 150 3 20 36 22.4 50/52
75 28 2.1 129 140 105 75 80/ 3M44202010 001
2 K/
3AE1 103-2 ... 1250 205 150 3 20 36 22.4 50/52
75 28 2.1 129 140 105 75 80/ 3M44202010 001
2 K/
3AE1 104-1 ... 800 205 150 3 25 36 28 63/
65 75 28 2.1 129 140 105 75 80/ 3M442
02010 001 3 K/
3AE1 104-2 ... 1250 205 150 3 25 36 28 63/
65 75 28 2.1 129 140 105 75 80/ 3M442
02010 001 3 K/
3AE1 105-1 ... 800 205 150 3 31.5 36 35.4 80/
82
75 28 2.1 129 140 105 75 80/ 3M442
02010 001
4 K/
3AE1 105-2 ... 1250 205 150 3 31.5 36 35.4 80/82
75 28 2.1 129 140 105 75 80/ 3M44202010 001
4 K/
3AE1 112-1 ... 800 275 150 3 16 36 17.9 40/42
75 28 2.1 129 140 105 75 80/120
3M 44202011 001
1 I/J
3AE1 112-2 ... 1250 275 150 3 16 36 17.9 40/
42 75 28 2.1 129 140 105 75 80/
1203M 44202011 001
1 I/J
3AE1 113-1 ... 800 275 150 3 20 36 22.4 50/
52 75 28 2.1 129 140 105 75 80/
1203M 44202011 001
2 I/J
3AE1 113-2 ... 1250 275 150 3 20 36 22.4 50/52
75 28 2.1 129 140 105 75 80/120
3M 44202011 001
2 I/J
3AE1 114-1 ... 800 275 150 3 25 36 28 63/65
75 28 2.1 129 140 105 75 80/120
3M 44202011 001
3 I/J
3AE1 114-2 ... 1250 275 150 3 25 36 28 63/
65 75 28 2.1 129 140 105 75 80/
1203M 44202011 001
3 I/J
3AE1 115-1 ... 800 275 150 3 31.5 36 35.4 80/
82 75 28 2.1 129 140 105 75 80/
1203M 44202011 001
4 I/J
3AE1 115-2 ... 1250 275 150 3 31.5 36 35.4 80/82
75 28 2.1 129 140 105 75 80/120
3M 44202011 001
4 I/J
3AE1 122-1 ... 800 310 150 3 16 36 17.9 40/42
75 28 2.1 129 140 100 75 80/120
3M 44202012 001
1 H/J
OrderNo.
Ratednormalcurrent
Widthacrossflats
Pole-centerdistan
ce
Ratedoperatingsequence:
O-3min-CO-3m
in-CO
O-0.3s-CO-3min-CO
O-0.3s-CO-15s
-CO
Ratedshort-circuitduration
Ratedshort-circuitbreakingcurrent
DCcomponentin%
ofthe
ratedshort-circuitbreakingcurrent
Asymmetricalbreakingcurrent
Ratedshort-circuitmakingcurrent
(at50/60Hz)
Ratedlightningimpulsewithstandvoltage
Ratedshort-duratio
npower-frequency
withstandvoltage
VoltagedropUbetweenconnections
(accordingtoIEC6
0694atDC100A)
Minimum
creepagedistance,
interrupter
Minimum
creepagedistance,
phase-to-earth
Minimum
clearance,
phase-to-phase
Minimum
clearance,
phase-to-earth
Weight1)
(fixed-mountedcircuit-breaker/slide-inmodule)
Detaileddimension
drawing
(hastobeordered)
Operatingcycledia
gram
No.
(seepage49)
Catalogdimensiondrawings(seepages54/55)
(fixed-mountedcirc
uit-breaker/slide-inmodule)
Technical DataElectrical data, dimensions and weights
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
47/64
3
12 kV50/60 Hz
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3AE1 133-1 ... 800 205 160 3 20 36 22.4 50/
52 75 28 2.1 129 140 115 75 80/ 3M442
02016 001 2 G/
3AE1 133-2 ... 1250 205 160 3 20 36 22.4 50/
52 75 28 2.1 129 140 115 75 80/ 3M442
02016 001 2 G/
3AE1 134-1 ... 800 205 160 3 25 36 28 63/65
75 28 2.1 129 140 115 75 80/ 3M44202016 001
3 G/
3AE1 134-2 ... 1250 205 160 3 25 36 28 63/65
75 28 2.1 129 140 115 75 80/ 3M44202016 001
3 G/
3AE1 135-1 ... 800 205 160 3 31.5 36 35.4 80/
82 75 28 2.1 129 140 115 75 80/ 3M442
02016 001 4 G/
3AE1 135-2 ... 1250 205 160 3 31.5 36 35.4 80/
82 75 28 2.1 129 140 115 75 80/ 3M442
02016 001 4 G/
3AE1 142-1 ... 800 275 160 3 16 36 17.9 40/
42
75 28 2.1 129 140 115 75 80/ 3M442
02017 001
1 F/
3AE1 142-2 ... 1250 275 160 3 16 36 17.9 40/42
75 28 2.1 129 140 115 75 80/ 3M44202017 001
1 F/
3AE1 143-1 ... 800 275 160 3 20 36 22.4 50/52
75 28 2.1 129 140 115 75 80/ 3M44202017 001
2 F/
3AE1 143-2 ... 1250 275 160 3 20 36 22.4 50/
52 75 28 2.1 129 140 115 75 80/ 3M442
02017 001 2 F/
3AE1 144-1 ... 800 275 160 3 25 36 28 63/
65 75 28 2.1 129 140 115 75 80/ 3M442
02017 001 3 F/
3AE1 144-2 ... 1250 275 160 3 25 36 28 63/65
75 28 2.1 129 140 115 75 80/ 3M44202017 001
3 F/
3AE1 145-1 ... 800 275 160 3 31.5 36 35.4 80/82
75 28 2.1 129 140 115 75 80/ 3M44202017 001
4 F/
3AE1 145-2 ... 1250 275 160 3 31.5 36 35.4 80/
82 75 28 2.1 129 140 115 75 80/ 3M442
02017 001 4 F/
3AE1 152-1 ... 800 310 160 3 16 36 17.9 40/
42 75 28 2.1 129 140 110 75 80/ 3M442
02018 001 1 E/
3AE1 152-2 ... 1250 310 160 3 16 36 17.9 40/42
75 28 2.1 129 140 110 75 80/ 3M44202018 001
1 E/
3AE1 153-1 ... 800 310 160 3 20 36 22.4 50/52
75 28 2.1 129 140 110 75 80/ 3M44202018 001
2 E/
OrderNo.
Ratednormalcurrent
Widthacrossflats
Pole-centerdistan
ce
Ratedoperatingse
quence:
O-3min-CO-3m
in-CO
O-0.3s-CO-3m
in-CO
O-0.3s-CO-15s
-CO
Ratedshort-circuit
duration
Ratedshort-circuit
breakingcurrent
DCcomponentin%
ofthe
ratedshort-circuitbreakingcurrent
Asymmetricalbrea
kingcurrent
Ratedshort-circuit
makingcurrent
(at50/60Hz)
Ratedlightningimpulsewithstandvoltage
Ratedshort-duratio
npower-frequency
withstandvoltage
VoltagedropUbetweenconnections
(accordingtoIEC6
0694atDC100A)
Minimum
creepagedistance,
interrupter
Minimum
creepagedistance,
phase-to-earth
Minimum
clearanc
e,
phase-to-phase
Minimum
clearanc
e,
phase-to-earth
Weight1)
(fixed-mountedcircuit-breaker/slide-inmodule)
Detaileddimension
drawing
(hastobeordered)
Operatingcycledia
gram
No.
(seepage49)
Catalogdimensiondrawings(seepages54/55)
(fixed-mountedcirc
uit-breaker/slide-inmodule)
Technical DataElectrical data, dimensions and weights
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
48/64
3
12 kV50/60 Hz
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3AE1 164-1 ... 800 205 210 3 25 36 28 63/
65 75 28 2.1 129 140 165 75 90/ 3M442
02022 001 3 D/
3AE1 164-2 ... 1250 205 210 3 25 36 28 63/
65 75 28 2.1 129 140 165 75 90/ 3M442
02022 001 3 D/
3AE1 165-1 ... 800 205 210 3 31.5 36 35.4 80/82
75 28 2.1 129 140 165 75 90/ 3M44202022 001
4 D/
3AE1 165-2 ... 1250 205 210 3 31.5 36 35.4 80/82
75 28 2.1 129 140 165 75 90/ 3M44202022 001
4 D/
3AE1 172-1 ... 800 275 210 3 16 36 17.9 40/
42 75 28 2.1 129 140 165 75 90/
1303M 44202023 001
1 B/C
3AE1 172-2 ... 1250 275 210 3 16 36 17.9 40/
42 75 28 2.1 129 140 165 75 90/
1303M 44202023 001
1 B/C
3AE1 173-1 ... 800 275 210 3 20 36 22.4 50/52
75 28 2.1 129 140 165 75 90/130
3M 44202023 001
2 B/C
3AE1 173-2 ... 1250 275 210 3 20 36 22.4 50/52
75 28 2.1 129 140 165 75 90/130
3M 44202023 001
2 B/C
3AE1 174-1 ... 800 275 210 3 25 36 28 63/65
75 28 2.1 129 140 165 75 90/130
3M 44202023 001
3 B/C
3AE1 174-2 ... 1250 275 210 3 25 36 28 63/
65 75 28 2.1 129 140 165 75 90/
1303M 44202023 001
3 B/C
3AE1 175-1 ... 800 275 210 3 31.5 36 35.4 80/
82 75 28 2.1 129 140 165 75 90/
1303M 44202023 001
4 B/C
3AE1 175-2 ... 1250 275 210 3 31.5 36 35.4 80/82
75 28 2.1 129 140 165 75 90/130
3M 44202023 001
4 B/C
3AE1 182-1 ... 800 310 210 3 16 36 17.9 40/42
75 28 2.1 129 140 160 75 90/130
3M 44202024 001
1 A/C
3AE1 182-2 ... 1250 310 210 3 16 36 17.9 40/42 75 28 2.1 129 140 160 75 90/
1303M 44202024 001
1 A/C
3AE1 183-1 ... 800 310 210 3 20 36 22.4 50/
52 75 28 2.1 129 140 160 75 90/
1303M 44202024 001
2 A/C
3AE1 183-2 ... 1250 310 210 3 20 36 22.4 50/52
75 28 2.1 129 140 160 75 90/130
3M 44202024 001
2 A/C
3AE1 184-1 ... 800 310 210 3 25 36 28 63/65
75 28 2.1 129 140 160 75 90/130
3M 44202024 001
3 A/C
OrderNo.
Ratednormalcurrent
Widthacrossflats
Pole-centerdistan
ce
Ratedoperatingse
quence:
O-3min-CO-3m
in-CO
O-0.3s-CO-3m
in-CO
O-0.3s-CO-15s
-CO
Ratedshort-circuit
duration
Ratedshort-circuit
breakingcurrent
DCcomponentin%ofthe
ratedshort-circuitbreakingcurrent
Asymmetricalbrea
kingcurrent
Ratedshort-circuit
makingcurrent
(at50/60Hz)
Ratedlightningimpulsewithstandvoltage
Ratedshort-duratio
npower-frequency
withstandvoltage
VoltagedropUbetweenconnections
(accordingtoIEC6
0694atDC100A)
Minimum
creepagedistance,
interrupter
Minimum
creepagedistance,
phase-to-earth
Minimum
clearanc
e,
phase-to-phase
Minimum
clearanc
e,
phase-to-earth
Weight1)
(fixed-mountedcircuit-breaker/slide-inmodule)
Detaileddimensiondrawing
(hastobeordered)
Operatingcyclediagram
No.
(seepage49)
Catalogdimensiondrawings(seepages54/55)
(fixed-mountedcirc
uit-breaker/slide-inmodule)
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
49/64
Technical DataElectrical data, dimensions and weights
SION Vacuum Circuit-Breakers
-
8/13/2019 Sion HG11_02_en_2006-12-21_3AE1
50/64
3
17.5 kV50/60 Hz
Ir tk Isc Ima Up Ud
A mm mm s kA % kA kA kV kV mV mm mm mm mm kg
3AE1 201-1 ... 800 205 150 3 12.5 36 14.9 31/
33 95 38 2.1 129 2 75 2 37 1 50 80/ 3M442
02013 001 1 K/
3AE1 201-2 ... 1250 205 150 3 12.5 36 14.9 31/
33 95 38 2.1 129 2 75 2 37 1 50 80/ 3M442
02013 001 1 K/
3AE1 202-1 ... 800 205 150 3 16 36 17.9 40/42
95 38 2.1 129 2 75 2 37 150 80/ 3M44202013 001
2 K/
3AE1 202-2 ... 1250 205 150 3 16 36 17.9 40/42
95 38 2.1 129 2 75 2 37 1 50 80/ 3M44202013 001
2 K/
3AE1 204-1 ... 800 205 150 3 25 36 28 63/
65 95 38 2.1 129 2 75 2 37 150 80/ 3M442
02013 001 3 K/
3AE1 204-2 ... 1250 205 150 3 25 36 28 63/
65 95 38 2.1 129 2 75 2 37 1 50 80/ 3M442
02013 001 3 K/
3AE1 205-1 ... 800 205 150 3 31.5 36 35.4 80/82
95 38 2.1 129 2 75 2 37 150 80/ 3M44202013 001
4 K/
3AE1 205-2 ... 1250 205 150 3 31.5 36 35.4 80/82
95 38 2.1 129 2 75 2 37 1 50 80/ 3M44202013 001
4 K/
3AE1 211-1 ... 800 275 150 3 12.5 36 14.9 31/33
95 38 2.1 129 2 75 2 14 150 80/120
3M 44202014 001
1 I/J
3AE1 211-2 ... 1250 275 150 3 12.5 36 14.9 31/
33 95 38 2.1 129 2 75 2 14 1 50 80/
1203M 44202014 001
1 I/J
3AE1 212-1 ... 800 275 150 3 16 36 17.9 40/
42 95 38 2.1 129 2 75 2 14 150 80/
1203M 44202014 001
2 I/J
3AE1 212-2 ... 1250 275 150 3 16 36 17.9 40/42
95 38 2.1 129 2 75 2 14 1 50 80/120
3M 44202014 001
2 I/J
3AE1 214-1 ... 800 275 150 3 25 36 28 63/65
95 38 2.1 129 2 75 2 14 150 80/120
3M 44202014 001
3 I/J
3AE1 214-2 ... 1250 275 150 3 25 36 28 63/65 95 38 2.1 129 2 75 2 14 1 50 80/
1203M 44202014 001
3 I/J
3AE1 215-1 ... 800 275 150 3 31.5 36 35.4 80/
82 95 38 2.1 129 2 75 2 14 150 80/
1203M 44202014 001
4 I/J
3AE1 215-2 ... 1250 275 150 3 31.5 36 35.4 80/82
95 38 2.1 129 2 75 2 14 1 50 80/120
3M 44202014 001
4 I/J
3AE1 221-1 ... 800 310 150 3 12.5 36 14.9 31/33
95 38 2.1 129 2 75 1 90 150 80/120
3M 44202015 001
1 H/J
OrderNo.
Ratednormalcurrent
Widthacrossflats
Pole-centerdistan
ce
Ratedoperatingse
quence:
O-3min-CO