    Edition: 01.11.2005 EMH-COMBI-MASTER 2000-PHB-E-4.00

    Operation ManualEMH-COMBI-MASTER 2000Communication- and configuration program

  • 8/10/2019 Man Combimaster En

    2/137

    2

    All of the contents published in this operation manual are copyright.Translations, reprints, duplication and also saving of this manual in dataprocessors requires the exclusive permission from EMH.

    All of the trademarks named in this manual are the property of EMH or therespective title holder.

    EMH is certified accord. to DIN ISO 9001:2000 and continually endeavours toimprove the products.

    The contents of this operation manual and the technical specifications can beextended, altered or deleted without prior notice.

    The description of the product specifications in this manual do not representpart of a contract.

    2005 EMH Elektrizittszhler GmbH & Co KG. All Rights reserved.

    If you have any questions or inspirations you can contact us at:

    EMH ElektrizittszhlerGmbH & Co KG

    Sdring 5D - 19243 Wittenburg

    Tel.: +49(0)3 88 52 645-0Fax.: +49(0)3 88 52 645-29

    Email: [email protected]: www.emh-meter.de

  • 8/10/2019 Man Combimaster En

    3/137

    Table of contents 3

    Table of Contents

    Chapter 1: Prologue...........................................................7

    Overview of the program modules ..........................................................8Explanation how to use the manual.........................................................9

    Chapter 2: Installation and release .................................10

    Hardware requirements .......................................................................10Program installation.............................................................................10Release ..............................................................................................15

    Request key code ..........................................................................16Receiving the key code ..................................................................19

    Communication requirements ...............................................................20Installation and settings of the optical communication adapter (OKK).20Setting up the local modem............................................................20

    Chapter 3: Basic program EMH-COM ...............................21

    Menu- and symbol bar .........................................................................21Program description.............................................................................22

    Menu File......................................................................................22Menu option Transfer................................................................22Menu option Exit ......................................................................22

    Menu Direct .................................................................................. 23Menu option Set clock...............................................................23Menu option Cumulate..............................................................23

    Menu option Identity numbers...................................................24Menu option Baud rate..............................................................24Menu option RCR Relay cumulation position................................25Menu option LZQJ - settings (LZQJ 2.1)......................................25Menu option Test mode... .........................................................26Menu option Manipulation... DMZ reset / ITZ reset V2.00/V3.00 /ITZ reset V9.00 ........................................................................26Menu option Single commands... Read command / Writecommand ................................................................................ 26

    Menu Readout...............................................................................27Menu option Table 1 / Table 2 / Table 3 / Service table ...............27

    Menu option P.01 Standard LP...................................................28Menu option P.02 User LP... ......................................................29Menu option P.98 Log book... .................................................... 30Menu option P.99 Certification relevant log book ......................... 31Menu option P.200 User log book...............................................31Menu option Installation check .................................................. 31Menu option eHZ automatic readout...........................................32Menu option Comment..............................................................32Menu option Convert ................................................................33Menu option Graphic display......................................................34

    Menu option Open... .................................................................37Menu option Save.....................................................................37Menu option Print... ..................................................................37

  • 8/10/2019 Man Combimaster En

    4/137

    4 Table of contents

    Menu option Control centre ....................................................... 37Menu Setting.................................................................................38

    Menu option Program settings... ................................................ 38RegisterGeneral..................................................................38RegisterModem ..................................................................40

    RegisterExternal .................................................................42RegisterRepresentation ....................................................... 42

    Field Installation Check ..................................................................43RegisterExport format.........................................................44RegisterMail .......................................................................45

    Menu Modem ................................................................................ 45Menu Configuration .......................................................................45

    Menu option Tariff setting ITZ... ................................................46Menu option Tariff setting ITZ V4.00... .......................................46Menu option Tariff setting DMZ V2.00/3.00.................................46Menu option Tariff setting DMZ V4.00... .....................................46

    Menu option Tariff setting DHZ... ...............................................46Menu option Transformer setting DHZ........................................46Menu option COMBI-TOOL ........................................................ 47

    Menu Info.....................................................................................48Menu option Program info ......................................................... 48Menu option Enter new product key... ........................................49Menu option Release product key...............................................49

    Optional program modules ...................................................................50Program module Installation display................................................50

    Menu option Installation check .................................................. 50

    Menu bar of the installation check...................................................51Explanation of further functions ...................................................... 52Program module P.02 User LP ........................................................ 53

    Menu option P.02 User LP ......................................................... 53Program module: Network quality ................................................... 55Program module Read out harmonics..............................................56Program module Control centre ...................................................... 58

    Menu option Control centre ....................................................... 58RegisterCustomer ...............................................................61RegisterMeter modem.........................................................62RegisterConnection.............................................................62

    RegisterTasks.....................................................................64RegisterAdditional information P.01...................................... 64RegisterAdditional information P.02...................................... 65RegisterMSCONS ................................................................66RegisterMSCONS manual.....................................................67

    Program module Modem ................................................................69Menu Modem ................................................................................ 69Program module Tariff setting ITZ .................................................. 70

    Menu option Tariff setting ITZ... ................................................70RegisterTimes ....................................................................71RegisterCEST / holidays ......................................................71RegisterTariff display ..........................................................72

  • 8/10/2019 Man Combimaster En

    5/137

    Table of contents 5

    Program module Tariff setting ITZ with software version 4.00 ...........73Menu option Tariff setting ITZ V4.00... .......................................73

    Program module Creating tariff files for DMZ with software versions2.xx/3.xx ...................................................................................... 74

    Menu option Creating tariff files DMZ V2.00/3.00........................74

    Creation of tariff files for meters from the series DMZ with the softwareversions 2xx and 3.xx ....................................................................74

    RegisterTimes ....................................................................75RegisterPublic holidays........................................................76RegisterSeason...................................................................76RegisterTariff display ..........................................................78

    Program module Creating tariff files for DMZ since software version4.00 .............................................................................................78

    Menu option Creating tariff files DMZ V4.00... ............................ 78Creation of tariff files for meters from the series DMZ since softwareversion 4.00..................................................................................78

    Program module Tariff setting DHZ ................................................. 79Menu option Tariff setting DHZ... ...............................................79

    RegisterTimes ....................................................................80RegisterMESZ/holidays........................................................81RegisterTariff display ..........................................................82

    Program module Transformer setting DHZ.......................................82Menu option Transformer setting DHZ........................................82

    Questions and answers ........................................................................83Load profile data ................................................................................. 84Load profile import in Excel ..................................................................86

    Chapter 4: COMBI-TOOL..................................................90

    Set-up of the program surface..............................................................91Menu- and symbol bar .........................................................................91Program description.............................................................................92

    Menu File......................................................................................92Menu option New .....................................................................92Menu option Open... .................................................................92Menu option Save.....................................................................92Menu option Save as.................................................................93Menu option Print... ..................................................................93Menu option Print Preview.........................................................93Menu option Printer set-up... ..................................................... 93Menu option Last opened files.................................................93Menu option Exit ......................................................................93

    Menu Meter .................................................................................. 94Menu option Read parameters or start readout ........................... 94Menu option Send parameters or execute an action.....................94Menu option Read complete parameters.....................................94Menu option Write all................................................................94Menu option Stop .....................................................................94

    Menu Options................................................................................95Menu option Settings... .............................................................95

  • 8/10/2019 Man Combimaster En

    6/137

    6 Table of contents

    Menu View....................................................................................96Menu option Navigation ............................................................96Menu option Communication ..................................................... 97Menu option Plausibility Check...................................................97Menu option Standard toolbar....................................................97

    Menu option Full screen toolbar ................................................. 98Menu option Meter toolbar ........................................................98Menu option Status bar.............................................................98Menu option Next .....................................................................98Menu option Back.....................................................................99

    Menu ? .........................................................................................99Menu option Info......................................................................99

    Functional blocks......................................................................... 100Functional block Meter ............................................................ 101

    Register Meter identification ............................................... 101Register Interfaces ............................................................ 102

    Register Reset parameter...................................................105Register Reset inhibition.....................................................106Register Real Time Clock....................................................107Register Tariff control source..............................................109

    Functional block Tariff configuration......................................... 110Register Public holidays......................................................110Register Seasons............................................................... 111Register Energy tariffs........................................................113Register Maximum Demand tariffs....................................... 114

    Function block RCR Parameter (Ripple Control Receiver)............115

    Register RCR Parameter.....................................................116Register Telegram definitions ............................................. 119Functional block Lists..............................................................121Functional block Lists > Display lists......................................... 122

    Register Options................................................................122Register Scrolling list..........................................................123

    Functional block Lists > Readout lists....................................... 125Register Options................................................................125

    Functional block Log books......................................................126Register User log book.......................................................126

    Functional block Parameterization ............................................ 127

    Functional block Configuration list............................................135

    Index .............................................................................136

  • 8/10/2019 Man Combimaster En

    7/137

    Prologue 7

    Chapter 1: Prologue

    The EMH-COMBI-MASTER 2000 software is a modular software with thefollowing communication- and configuration possibilities:

    LZ.. PZ../PE.. DMTZ ITZ DMZ DHZ eHZ

    Communication

    Complete-configuration

    Tariff configuration

    When only the basic program is installed, the program is then called EMH-COM.In the following, all available program modules are described. It is possible thatyour program version does not have some of the described program modules

    which are included here.

  • 8/10/2019 Man Combimaster En

    8/137

    8 Prologue

    Overview of the program modules

    Basic program EMH-COM(page 21 onwards)

    Modem (page 45 onwards)

    Write commands (page 23 onwards)- cumulate- transfer files- set baud rate- set identity number- delete manipulation

    Single commands (page 26)- write command- read command

    Set clock (page 23)

    Table 3 read (page 27)

    LP/Graphic (page 28 onwards)- read load profile/log book- graphic LP-display

    Installation check (page 31)

    Tariff ITZ (page 46 onwards)Tariff DHZ (page 46 onwards)Tariff DMZ (page 46 onwards)Transformer settings DHZ (page 46)

    Communication all typesCommunication VDEW 2.1Communication VDEW 2.0

    Communication DHZCommunication DMZCommunication ITZ

    Control centre (page 37 onwards)MSCONS and mail for control centreUser log book (page 31)eHZ automatic readoutBluetooth-OKKNetwork quality (page 55)Read out harmonics U / I (page 56)

    COMBI-TOOL(page 90 onwards)

    EMH-CO

    M/COMBI-MAST

    ER

    2000

    90 day-test version

  • 8/10/2019 Man Combimaster En

    9/137

    Prologue 9

    Explanation how to use the manual

    The simple structure enables you to quickly become familiar with the manual.The manual is basically set up as follows:

    Complete path information

    Explanation of a menu, e.g. File

    File

    M Menu File

    Short description Transfers files and ends the program

    Explanation of a menu option, e.g. of the menu option Transfer...

    File > Transfer...

    MO Menu option Transfer

    Short description Transfers saved set-, parameter-, tariff- and ripple control files

    Explanation of one of the registers e.g. register General

    Setting >Program settings.. > General

    R Register General

    Short description Setting of the COM-interface, passwords and meter address

  • 8/10/2019 Man Combimaster En

    10/137

    10 Installation and release

    Chapter 2: Installation and release

    Hardware requirements

    The PC should fulfil at least the following requirements:

    Processor: Intel Pentium, 100 MHz or higherRAM: at least 32 MB RAMAvailable hard disc memory: at least 50 MBOperating system Microsoft Windows 98/ME/2000/NT4.0 or XP

    Accessories: Optical Communication Adapter OKK (withcommunication via the D0-interface),Local modem for remote configuration with themeter

    Program installation

    Procedure:

    Start the file setup_emhcommas2000kyXXX.exe.The following window appears:

    Here select the language version of the basic program and also the languagewith which the program module COMBI-TOOL should be started.

    Attention:After installation, the language of the basic program cannot bechanged. With the program module COMBI-TOOL this is however possible at alltimes.

    Once the language has been set, click on OKto continue.The following window appears:

    Click on Next >.

  • 8/10/2019 Man Combimaster En

    11/137

    Installation and release 11

    The following window appears:

    We recommend that you accept the proposed program folder. You mayhowever also select a different path.To continue with the installation click on Next >.

    If the selected program folder does not yet exist, e.g. with a new installation,then you will be asked if this folder should be created. To continue click onYes,in order to go back to the previous window and to set a new path or programfolder click on No.

  • 8/10/2019 Man Combimaster En

    12/137

    12 Installation and release

    In the following window the program description is set which is used in thestart menu (Start > Programs...). You can set a new program description oraccept the proposal.

    In order to continue with the installation click on Next >.

    Note :If the program shall not creates a folder in the Windows start menuthen activate the checkbox Dont create a Start Menu folder!Please consider, that with a deactivation the program can only start via theDesktop Icon (if present) or directly from the index.

  • 8/10/2019 Man Combimaster En

    13/137

    Installation and release 13

    In the following window you have the possibility to set if an icon should beinserted on the desktop. With the help of the icon you can start the programdirectly without having to go via the start menu or the index.

    In order to insert an icon, activate the checkbox. Click on Next >to proceed withthe installation.

    The Setup now shows you once again all settings which you have madeconcerning the installation. If you would like to make more changes then youcan go back to the previous installation steps by clicking on < Back.

    Now click on Install.

  • 8/10/2019 Man Combimaster En

    14/137

    14 Installation and release

    At the end of the installation the following window appears:

    Click on Finishto end the installation.

    Note:If, after the installation, you want to start the program activate thecheckbox Start EMHProgram.Otherwise the window is closed and the installation is ended.

  • 8/10/2019 Man Combimaster En

    15/137

    Installation and release 15

    Release

    Before the program can be executed or used it must be released by means of aproduct key and a key code.The following describes how to release a program.

    Start EMH-COMBI-MASTER 2000.The following window appears:

    Please enter the product key which you received with the CD and then click onOK.Entry of the correct product key is confirmed with the following announcement.

    Click on OK. The following announcement then appears.

    Please read the note and confirm with OK.The entry of the product key is now complete. In order to request the key codefor releasing the program a renewed start of the program is necessary.

  • 8/10/2019 Man Combimaster En

    16/137

    16 Installation and release

    Start EMH-COMBI-MASTER 2000.The following window appears:

    The program offers you 2 possibilities to request the key code. You can select ifyou want to receive the key code by Email or Fax. The option Request key code per

    Mail

    is a more simple and quicker method to receive the key code. The optionRequest key code per FAX

    is usually selected when your computer does not have aninternet connection.

    Request key code

    1. Possibility: Request key code per E-mail

    Note: For this option, internet connection is necessary.

    Select the option Request key code per Mail.

    Now click on Request key code.

  • 8/10/2019 Man Combimaster En

    17/137

    Installation and release 17

    The following window appears:

    Please read the announcement and click on OK.

    A new window from your Standard-Email-Program opens automatically.

    The window already contains all information which is necessary forprocessing the key code requirements. You only need to send the Email.Shortly after this you will receive the key code to release the program.

    2. Possibility: Request key code per Fax

    Select the option Request key code per FAX.

    Then click on Request key code.

  • 8/10/2019 Man Combimaster En

    18/137

    18 Installation and release

    The printer menu from your standard printer then opens, e.g.:

    You can now print out the key code request form on your printer.The fax pre-printed form is as follows:

    Please enter in the form the fax number where the key code should befaxed to. You also have the possibility to receive the key code per Email. Forthis, on the form enter the Email address to where the key code should besent. Then send the fax to:

    EMH Elektrizittszhler GmbH & Co KGFax-Number: +49-(0)3 88 52-645-29

    You will receive the key code shortly.

  • 8/10/2019 Man Combimaster En

    19/137

    Installation and release 19

    Receiving the key code

    Once you have received the key code from EMH you can release the program.For this, start the program either via the program icon on the desktop or via thestart menu. The window opens which you already know from the key coderequest.

    If you received the key code by Email then you can copy the key code from theE-mail and insert it into the field. To do this, copy the key code into theclipboard and then place the mouse cursor in the first empty box and use thekey combination Ctrl + V to insert the key code.

    When you have entered the key code (as above) click on OK.If the key code is correct the following announcement appears:

    If the key is incorrect the following announcement appears:

    Enter the correct key code once again.

    The release is now complete. You can start the program via the desktop icon (ifpresent) or via the start menu.

  • 8/10/2019 Man Combimaster En

    20/137

    20 Installation and release

    Communication requirements

    There are several possibilities to communicate with the meter. In the following,communication via both the optical communication adapter OKK and theelectrical interface with a modem is described.

    Installation and settings of the optical communication adapter (OKK)

    The optical communication adapter OKK enables communication between a PCand a meter. At the meter, communication to the optical data interface D0takes place. Connection to the PC takes place, depending on the version anddesign, via a COM-Port or a USB interface.

    Procedure:Connect the optical communication adapter OKK to a free COM-Portor a free USB interface on your PC (depending on the design of the OKK). Ifyou have an OKK with USB connection then a special USB driver must be

    installed. The driver can be found on the CD-ROM which is contained in thedelivery with the OKK. Tips for the installation of the driver can also be foundon the CD-ROM.

    Note :Before communication can take place with the meter the interface mustbe configured under Setting > Program settings ...>RegisterGeneral(see page 38).

    Setting up the local modem

    In order to communicate with the meter via the modem function someparameters need to be defined for the local modem and the meter modem inadvance. For more information about this see page 40.

    Note:For remote meter readout a standard commercial PC modem is used. Onthe basis of our many years of experience we recommend an external modemwhich is addressed with the Standard-Hayes-operations set. The advantage ofthis modem is its audible loud speaker function and the LED status display.With the set up of a communication line you can observe the connectionestablishment (visually by means of the LED and acoustically by means of theloud speaker).

    A modern analog modem is able to call both analog meter modems and GSM

    meter modems and is also able to read out the meter.On the basis of our long term experience we would like to inform you of thefollowing:Internal modem cards are technically equivalent however, if there areproblems, the error search is more difficult. Admittedly ISDN-cards offer thepossibility of an analog modem emulation via the so-called virtual COM-Portshowever, in practice, they often cause many problems. Therefore it is notrecommended to use an ISDN-card.

  • 8/10/2019 Man Combimaster En

    21/137

    Basic program 21

    Chapter 3: Basic program EMH-COM

    Menu- and symbol bar

    Note:The program consists of individual program modules (see page 8). If inthe following, menu options and functions are described which are not includedin your program then these program modules have not been released and aretherefore not available.If you are interested in further modules please contact us.

    In the upper area of the program window the menu bar can be found. Thesymbol bar is found below te menu bar. Via the symbols on the symbol bar youcan access the frequently used functions.When you go over a symbol with the mouse a function description appears.

    Set clock

    Read out table 1

    Read out table 2

    Read out table 3

    Read out service table

    eHZ automatic readout

    Read out standard load profile

    Read out user load profile

    Read out log book

    Comment readout

    Load profile-conversion

    Load profile graphic display

    Read out network quality

    Installation check

    Save protocol

    Print protocol

    Create modem connection

    Cancel modem connection

    Cancel communication

    Start COMBI-TOOL

  • 8/10/2019 Man Combimaster En

    22/137

    22 Basic program

    Program description

    File

    M Menu File

    Transfers files and ends the program

    File > Transfer ...

    MO Menu option Transfer...

    Transfers saved set-, parameter-, tariff- and ripple control files

    Procedure:Click on Transfer...Select the file which is to be transferred and clickon Open. The file is now transferred to the meter.In order to close the window click on Cancel.

    Note:Please make sure that in the selection field Files of typethe file type isselected which you want to transfer. Otherwise the file to be transferred will notbe shown in the window.

    File > Exit

    MO Menu option Exit

    Ends the program

  • 8/10/2019 Man Combimaster En

    23/137

  • 8/10/2019 Man Combimaster En

    24/137

    24 Basic program

    Direct > Identity numbers...

    MO Menu option Identity numbers...

    Sets and sends identity numbers to the meter

    Here you can read out the identity numbers from the meter or send the identitynumbers to the meter. To do this click either on Read orWrite. Select theappropriate meter type via the option buttons.

    Note:Please note that identity numbers with more than 8 digits cannot berepresented in the display.

    Direct > Baud rate...

    MO Menu option Baud rate...

    Sets and sends the start- and data baud rate for the external interfaces

    Here you can read out the start- and data baud rates of the meter or sendthem to the meter. Please make sure that you have selected the appropriatemeter in advance via the option buttons.

  • 8/10/2019 Man Combimaster En

    25/137

    Basic program 25

    Direct > RCR cumulation position...

    MO Menu option RCR Relay cumulation position...

    Reads out and sets the relay cumulation position of the ripple control receiver

    After activation of the menu option the following window opens:

    Here you have the possibility to read out the relay cumulation of the ripplecontrol receiver. For this click on Read. After the readout, the relevant relay

    cumulation is marked with an X.With a double click in the appropriate field the relay cumulation can bechanged. In order to send the changed settings to the meter click on Write.

    Direct > LZQJ - settings (VDEW 2.1)...

    MO Menu option LZQJ - settings (LZQJ 2.1)...

    Setting possibilities for impulse constants, overload threshold and tan phi

    Here it is possible to read out the impulse constants for in- and outputs, changethem and then write them back to the meter. The same applies for the overload

    threshold and for the copper and iron losses.

  • 8/10/2019 Man Combimaster En

    26/137

    26 Basic program

    Direct > Test mode...

    MO Menu option Test mode...

    Conversion of the impulse-LED

    Here you can convert the function of the LED pulses and if it is supported bythe meter activate a certain tariff.

    Note:The function test mode is not supported by all meters.

    Direct > Manipulation...

    MO Menu option Manipulation... DMZ reset / ITZ reset V2.00/V3.00 / ITZ reset V9.00

    Resets the manipulation register of the DMZ or ITZ meter

    Note:After activation of one of these menu options the relevant command issent to the meter immediately.

    Direct > Single commands...

    MO Menu option Single commands... Read command / Write commandSends read- or write commands to the meter

    1. Example:Read out time from the meter

    2. Note:Send identity number to the meter(see also Menu option Identity numbers...on page 24)

  • 8/10/2019 Man Combimaster En

    27/137

    Basic program 27

    Readout

    M Menu Readout

    The menu Readoutcontains menu options for reading out the meter and also forprocessing the data readouts.

    Readout > Table 1 etc.

    MO Menu option Table 1 / Table 2 / Table 3 / Service table

    Read out of the data lists from the meter

    Table 1: Billing dataTable 2: Load profile with pre-adjustment of the load x days (standard: last 40

    days)Table 3: EMH-internal dataService table: Service data (momentary values)

    Note:At the end of every meter read out, a BCC-Check takes place (withspecial applications CRC). By means of a checksum sent by the meter a check iscarried out to see if the meter readout was totally correct (information: BCC =xx OK).

    With a faulty data read out, at the end of the read out the announcementappears that the sent BCC is not the same as the calculated BCC. The totalreadout is represented in red. If, in spite of many attempts, it is still notpossible to read out the meter correctly then refer to chapter Questions andanswers page 83 onwards to find out possible causes.To save the readout tables click on Readout > Save...Now select the index whereyou want to save the file. In the field File nameenter the name of the file andselect the desired file in the field Files of type > Readout files (*.tab). Then click onSave.

  • 8/10/2019 Man Combimaster En

    28/137

    28 Basic program

    Readout > Standard LP...

    MO Menu option P.01 Standard LP...

    Read out of the load profile data from the meter

    Start date Setting the start date of the load profile to beread out, start time is 24:00 oclock

    End date Setting the end date of the load profile to beread out, end time is 24:00 oclock

    Read out compressed Read out of the compressed load profile

    Note:This function can only be used if themeter supports the reading out of compressed

    load profiles.

    Read out complete Read out the complete load profile

    Note: With the activation of the checkbox Readout complete, the readout of the load profilescan take a long time depending on the sizeand number of channels.

    Read out identity number additionally In addition to the load profile entries, theselected meter address or identity number

    from the selection list is read out in order tobe able to allocate the load profile to themeter at a later date.

    Read out R6 block by block Activate this option to read out the loadprofile block by block. In the corresponding,dropdown box you can enter the number ofrows which should be read out within areadout cycle. A block by block readout makessense when you read out the load profile via

    the telephone- or GSM network.

  • 8/10/2019 Man Combimaster En

    29/137

    Basic program 29

    By means of this, destroying of the loadprofiles due to interference in the networkshould be avoided.

    Button Read out of single load profile channels,

    selection leads to extension of the window.

    First of all read out all available channels via the button read out available channels.Then you can select the load profile channels to be read out by clicking on thecheckbox. To read out the marked load profile channels click on OK.

    Readout > User LP...

    MO Menu option P.02 User LP...

    Optional program module. Description see page 53.

  • 8/10/2019 Man Combimaster En

    30/137

    30 Basic program

    Readout > P 98 Log book...

    MO Menu option P.98 Log book...

    Read out of the operation log book from the meter

    Start date Setting the start date of the log book which isto be read out, start time is 24:00 oclock

    End date Setting the end date of the log book which isto be read out, end time is 24:00 oclock

    Read out complete Read out the complete log book

    Read out identity number in additionally In addition to the log book entries, theselected meter address or identity number inthe selection list is read out in order to beable to allocate the log book entries to themeter at a later date.

    Read out R6 block by block Activate this option to read out the loadprofile block by block. In the corresponding,dropdown box you can enter the number ofrows which should be read out within areadout cycle. A block by block readout makessense when you read out the load profile viathe telephone- or GSM network. By means ofthis, destroying of the load profiles due tointerference in the network should beavoided.

  • 8/10/2019 Man Combimaster En

    31/137

    Basic program 31

    Readout > P.99 Certification relevant log book

    MO Menu option P.99 Certification relevant log book

    Read out of the certification relevant log book P.99 (if configured )

    In the verification relevant log book changes of the LED-pulse constants andalso of the pulse values from the P-and Q-output are saved. Altogether amaximum of 46 entries are contained in the certification relevant log book.

    Readout > P.200 User log book

    MO Menu option P.200 User log book

    Read out of the user log book P.200 (if configured)

    The user log book can be configured customer specific. As a rule the log bookcontains events such as voltage failures and manipulation attempts with a timestamp. Up to 204 events can be saved.

    Readout > Installation check

    MO Menu option Installation check

    Optional program module. Description see page 50.

  • 8/10/2019 Man Combimaster En

    32/137

    32 Basic program

    Readout > eHZ automatic readout

    MO Menu option eHZ automatic readout

    Readout from electronic meters eHZ

    Procedure:Click on Readout > eHZ automatic readout. The EMH-COMBI-MASTER2000 now automatically receives a data telegram sent from a eHZ approx.every 2 secs(according to eHZ-specifications Elektronische Haushaltszhler

    Version 1.01). If no data telegram is received for a period of 14 seconds thenthe readout is interrupted (Timeout).

    Readout > Comment

    MO Menu option Comment

    Comments line by line the read out tables, load profiles and log books.

    Example:Table 1

    without comments: with comments:

    Note:The tables, load profiles and log books are always read out withoutcomments. A comment is also only possible after the readout.

  • 8/10/2019 Man Combimaster En

    33/137

    Basic program 33

    Readout > Convert

    MO Menu option Convert

    Conversion of load profile data as preparation for data export

    Example: Load profile data after conversionNote:An explanation of the load profile conversion can be found in the chapterLoad profile data, page 84.

    Attention:After a conversion for a data export, a graphic load profile display isno longer possible!

    Export of the load profile data

    To export the load profile click on Readout > Save ...Select the path where the file should be saved and enter the name of the file inthe field File name. As the file type select load profile export (*.txt) and click onSave.

    Afterwards you can import the file in a table calculation programe.g. MS Excel, (for more information see page 86 onwards).

  • 8/10/2019 Man Combimaster En

    34/137

    34 Basic program

    Readout > Graphic display

    MO Menu option Graphic display

    Graphic display of load profile data

    Note:The x-axis describes the time, the y-axis the performance. For everychannel a separate scaling of the y-axis can be represented. This must be pre-defined Readout > Graphic display > Channel > Selection.With the horizontal scrolling beam you can move the time axis.With the sliding controller Zoomwhich can be found in the lower area of the

    window it is possible to make the view field of the load profile curve larger orsmaller.If several days are shown in the graphic then you can change over to a dailydisplay via a double click on one of the shown dates.The cursor always marks a measuring period duration and the measuring periodduration can be moved with the cursor buttonsand also Pic , Pic, Pos 1 and End.When you move the cursor in the main area of the window then, in the fieldbelow this, the relevant load profile values appear with information about thetime stamp and the status entries.

  • 8/10/2019 Man Combimaster En

    35/137

    Basic program 35

    Menu bar of the graphic display

    Graphic > Print... Prints the content of the window

    Graphic > Exit Closes the graphic display, return to the main window

    Channel After activation of the menu option channelthe following

    window appears.

    Via the buttons you can activate all channelsor deactivate allchannels.Via the checkboxes you can however also activate ordeactivate individual channels.

    In the load profile graphic individual calculations of each channel

    In the graphic load profile display the scaling of the y-axis isseparately shown for every channel.

    Set zero point of the Y-axis automatically

    In the graphical load profile display the bottom limit of the y-axis is modified to reach a higher resolution.

    Scaling only in the visible area

    Representation of the load profile is scaled to the window sizedepending on the zoom setting.

    CE(S)T display / evaluation

    Here you can set if the graphic should always be displayed inMEZ (each day has 96 periods) or in ME(S)Z (spring switching92 periods, autumn switching 100 periods) independent ofhow the load profile is filed in the meter.

    Transformer factor Multiplication of the load profile data with a transformerfactor.

  • 8/10/2019 Man Combimaster En

    36/137

  • 8/10/2019 Man Combimaster En

    37/137

    Basic program 37

    Readout > Open...

    MO Menu option Open...

    Opens files e.g. read out tables, load profiles (also converted), protocol filesetc.

    Readout > Save...

    MO Menu option Save...

    Saves files e.g. read out tables, load profiles (also converted), protocol files

    Readout > Print...

    MO Menu option Print...

    Prints the content of the window (data readout)

    Readout > Control centre

    MO Menu option Control centre

    Optional program module. Description see page 53.

  • 8/10/2019 Man Combimaster En

    38/137

    38 Basic program

    Setting

    M Menu Setting

    Setting possibilities for interfaces, modems, passwords, program representationetc.

    Setting > Program settings...

    MO Menu option Program settings...

    Setting possibilities for interfaces, modems, passwords, program representationetc.

    Setting > Program settings... > General

    R RegisterGeneral

    Setting of the COM-interface, passwords and meter address

    Port Setting of the COM-Port when using an optical communicationadapter OKK

    Note:In order to determine the COM-Port when using an OKKwith USB connection look under Start > Settings > System control >System-[Hardware]-device manager. Further information about thiscan be found on the CD-ROM which is included in delivery withthe OKK.

    Baud rate Setting of the interface speed

    Note:When using an OKK you should always use Mode C.

  • 8/10/2019 Man Combimaster En

    39/137

    Basic program 39

    Bluetooth OKK Activate this checkbox when a Bluetooth-OKK is used.

    Login-password Input of the login-password

    With activation of this menu option, when logging in, apassword is sent to the meter. The password is saved in codewith the program settings.

    W5-password Input of the W5-password

    Certain set commands (e.g. setting of the clock time, writing ofthe identity number) are only sent to the meter withinformation about the W5-password. The pre-setting 00000000must only be changed if a different password was agreed on.

    Meter-address Input of the meter-address

    Note:This information is only important if the meter has a

    meter-address. The meter-address only applies to the meterselectrical interface and therefore only comes into question witha remote readout or a special solution. The meter-address canbe discovered by reading out the service table.The OBIS-codefor the meter-address is 0.0.0.

    Send break before every communication (VDEW2.0/2.1)

    With activation, a running data transmission on the usedinterface is interrupted. Otherwise communication at this timeis impossible.

    Note:If you have any problems with connection please read the chapterQuestions and answers page 83 onwards.

  • 8/10/2019 Man Combimaster En

    40/137

    40 Basic program

    Setting > Program settings... > Modem

    R RegisterModem

    Setting the local modem and the meter modem.

    Telephone number Entry of the telephone number of the meter modemto be called

    Note:If dialling a number for an outside line isnecessary then (often with telephone sets), thisnumber must be at the front of the telephone

    number. Then enter a w. The w causes a shortdialling break after reaching the network beforedialling further. If the w does not operate properlythen please contact the telephone administrator andask for the interval signal.

    Local modem initialization Selecting the local modem to be used

    Note:The modems which are most frequently usedare listed. If your modem is not included in the listthen select the setting allg. Hayes-Modem;AT&FE0X3. This

    setting functions with most types of modems.

  • 8/10/2019 Man Combimaster En

    41/137

    Basic program 41

    FieldMeter modem selection Selection of the meter modem to be dialled.

    EMH-COMBI-MASTER 2000 supports metermodems from the manufacturer Dr. Neuhaus(ZDUE), Grlitz (ENC 280), Elster (DM 100) andSparkline Modem.

    Note:As a rule, for simple transparent modems itis sufficient if you activate Auto-Transparent modem. Inthe field Modem-Timeout as a standard 90 s areentered. This information causes the program tobe automatically interrupted if there is a faultyconnection. It is not recommended to select asmaller value.

    With meter modems which have a passwordprotection in the field Modem password the passwordcan be entered. If there is no password activatedin the meter modem then the field stays empty.

    Path to the INI-files In the path C:\Dokument and settings\All Users\ApplicationData\EMHas a standard the files modem.iniandtelefon.iniare found.The file modem.inicontains the modem types whichare listed in the selection field local modeminitialization. In the file modem.inifurther modemtypes can be extended. This should however onlybe performed by experienced users.

    The file telefon.inicontains telephone numberswhich are listed in the selection field. In the filetelefon.ininew telephone numbers can be enteredwhich are then available with every start of theprogram in the selection box Telephone number.

  • 8/10/2019 Man Combimaster En

    42/137

    42 Basic program

    Settings > Program settings... > External

    R RegisterExternal

    Selection of the start files for opening the program module COMBI-TOOL

    Procedure: In order to define the path and the start fileclick on thebutton . Once you have confirmed the setting with OKyou can start theCOMBI-TOOL via the menu- or symbol bar.

    R RegisterRepresentation

    Sets the software surface

  • 8/10/2019 Man Combimaster En

    43/137

    Basic program 43

    Large tool buttons The buttons in the toolbar are shown enlarged.

    Flat tool buttons The buttons in the toolbar are no longer shown as arelief structure.

    Enlarge font for protocol The font of the data read out is larger.

    Note:This function is especially helpful with monitorswith a very high resolution.

    Field Installation Check

    Display clockwise The voltages are displayed clockwise:U1=0, U2=240, U3=120

    Display anticlockwise The voltages are displayed anticlockwise:U1=0, U2=120, U3=240 (EMH-Standard)

  • 8/10/2019 Man Combimaster En

    44/137

    44 Basic program

    Setting > Program settings... > Export format

    R RegisterExport format

    Setting the export formats for the export of load profiles.

    Here you can define the layout of the text rows for the export of load profiles.

    The row is composed from the field Data compositionin the above shownsequence.With a double click, individual fields are inserted into or removed from the datacomposition.

    Example:01.01.2005 TAB 09:15 TAB Value Channel 1 TAB Value Channel 2 TAB Status

    Separator is always a TAB-character.

  • 8/10/2019 Man Combimaster En

    45/137

    Basic program 45

    Setting > Program settings... > Mail

    R RegisterMail

    Setting the mode for sending Emails

    Here it is possible to determine how the data from the control centre should besent per Email. There are two possibilities:

    Mail sending by standard mail program (e.g. Outlook)

    The Emails are sent with your computers standardEmail program.

    If automatic sending with Outlook does not work due to a service pack (sinceyou have to confirm a request with every Email) try the following setting:

    Mail sending by SMTP The Emails are sent via your networks SMTP-Server.

    Modem

    M Menu Modem

    Optional program module. Description see page 69.

    Configuration

    M Menu Configuration

    Tariff settings for ITZ, DMZ, DHZ and also transformer settings for the DHZ

  • 8/10/2019 Man Combimaster En

    46/137

    46 Basic program

    Configuration > Tariff setting ITZ...

    MO Menu option Tariff setting ITZ...

    Optional program module. Description see page 70.

    Configuration > Tariff setting ITZ V.400...

    MO Menu option Tariff setting ITZ V4.00...

    Optional program module. Description see page 73.

    Configuration > Tariff setting DMZ V2.00/3.00...

    MO Menu option Tariff setting DMZ V2.00/3.00...

    Optional program module. Description see page 74.

    Configuration > Tariff setting DMZ V4.00...

    MO Menu option Tariff setting DMZ V4.00...

    Optional program module. Description see page 78.

    Configuration > Tariff setting DHZ...

    MO Menu option Tariff setting DHZ...

    Optional program module. Description see page 79.

    Configuration > Transformer setting DHZ...

    MO Menu option Transformer setting DHZ...

    Optional program module. Description see page 82.

  • 8/10/2019 Man Combimaster En

    47/137

    Basic program 47

    Configuration > COMBI-TOOL

    MO Menu option COMBI-TOOL

    Start of the program module COMBI-TOOL

    The detailed description of the COMBI-TOOL can be found in chapter Chapter4: COMBI-TOOL on page 90 onwards.

    Note:In order for the COMBI-TOOL to be started via the menu option, the path

    information must be entered correctly under Setting > Program settings... > External(see for this the paragraph RegisterExternalon page 42).When the program module is opened the EMH-COMBI-MASTER 2000 continuesto run in the background. It can however not be used since the COM-interfacecan only be used by one program. If the COMBI-TOOL is closed again the basicprogram then becomes active again.

  • 8/10/2019 Man Combimaster En

    48/137

    48 Basic program

    Info

    M Menu Info

    Program information and release options

    Info > Program info

    MO Menu option Program info

    Program information

    The menu option Program infocontains information about the program and alsothe areas of application.Here you also receive the path information for the INI- and control centre filesand also the save files. The meter types which the program can communicatewith are also listed here.If the installed program is a 90 day test version then it is shown here howmany days the program will still run for.

  • 8/10/2019 Man Combimaster En

    49/137

    Basic program 49

    Info > Enter new product key...

    MO Menu option Enter new product key...

    Entering a new product key for releasing further program modules

    Procedure:The release of new program modules takes place as described inchapter Release, page 15.

    Info > Release product key...

    MO Menu option Release product key...

    Requesting a new key code and releasing further program modules

    Procedure:The release of new program modules takes place as described inchapter Release, page 15.

  • 8/10/2019 Man Combimaster En

    50/137

    50 Basic program

    Optional program modules

    Program module Installation display

    Readout > Installation check

    MO Menu option Installation check

    Graphic display of the current network behaviour for the installation check

    After activation of the menu option the above displayed windows opens.

    When all required data has been read out the data is immediately graphicallydisplayed, otherwise click on Readout meter. After the readout , the window is asfollows:

    In the table, the current network behaviour of phases L1, L2, L3 and also thesum of all phases are shown.

  • 8/10/2019 Man Combimaster En

    51/137

    Basic program 51

    If the meter was not installed correctly then this can be read in the graphicinstallation display. In the table, the affected values are marked in red.

    Installation errors could be incorrectly connected current- or voltage connectorsor interchanged transformer connectors.

    Menu bar of the installation check

    File > Open... Opening a saved text file

    File > Save as... Saving the current values as a text file (*.txt)

    Note:The text file can be opened later with every text

    editor or with MS-Excel.

  • 8/10/2019 Man Combimaster En

    52/137

    52 Basic program

    File > Exit Closes the installation display.

    Print Printing the current window of the installation check

    Explanation of further functions

    Meter identity number Display of the meter-identity number 0.0.0

    update values cyclically With activation of this button, 2 seconds after the lastreadout a renewed readout takes place and the valuesare updated.

    Note:With activation, the buttons Saveand Print arenot available.

    Name of fitter Here the name of the fitter can be entered who

    carried out the installation check.Note:Before you save the values from the text filethis field must be filled in.

    Customer Here the customers name can be entered where theinstallation check was carried out.

    Comment Field for the entry of additional comments

  • 8/10/2019 Man Combimaster En

    53/137

    Basic program 53

    Program module P.02 User LP

    Readout > P.02 User LP

    MO Menu option P.02 User LP

    Read out user load profile data from the meter

    Start date Setting the start date of the load profile to beread out, start time is 24:00 oclock

    End date Setting the end date of the load profile to beread out, end time is 24:00 oclock

    Read out compressed Read out of the compressed load profile

    Note:This function can only be used if themeter supports the reading out of compressedload profiles.

    Read out complete Read out the complete load profile

    Note: With the activation of the checkbox Readout complete, the readout of the load profilescan take a long time depending on the sizeand number of channels.

    Read out identity number additionally In addition to the load profile entries, the

    selected meter address or identity numberfrom the selection list is read out in order tobe able to allocate the load profile to themeter at a later date.

    Read out R6 block by block Activate this option to read out the loadprofile block by block. In the corresponding,dropdown box you can enter the number ofrows which should be read out within areadout cycle. A block by block readout makes

    sense when you read out the load profile viathe telephone- or GSM network.

  • 8/10/2019 Man Combimaster En

    54/137

    54 Basic program

    By means of this, destroying of the loadprofiles due to interference in the networkshould be avoided.

    Button Read out of single load profile channels,

    selection leads to extension of the window.

    First of all read out all available channels via the button read out available channels.Then you can select the load profile channels to be read out by clicking on thecheckbox. To read out the marked load profile channels click on OK.

  • 8/10/2019 Man Combimaster En

    55/137

    Basic program 55

    Program module: Network quality

    The program module network quality contains the read out of data on thenetwork quality and also the instantaneous harmonic values.To start the program module, click on the button .

    The following selection window opens:

    Click onRead out network quality load profile. The further proceedings are described inchapter Program module P.02 User LP page 53.

    Once all data has been read, the graphic display opens. All evaluations whichare possible for the standard load profile also apply for the load profile with thedata on the network quality (see page 34 onwards).In addition to this, an analysis of the voltage values can be carried out. For this,click on Total evaluation > network quality.The following window opens:

    Under Evaluation criteriayou can find three pre-defined profiles. These profilescontain the pre-defined nominal voltage and the threshold values. You can clickon the selection field and create your own profile (e.g. low voltage 127 V) witha different nominal voltage and different threshold values.

  • 8/10/2019 Man Combimaster En

    56/137

    56 Basic program

    If you activate the check box Mark periods which exceed threshold in the LPall areaswhich exceed the set threshold values are marked in blue in the graphicdisplay.

    Program module Read out harmonics

    For this, click on in the symbol bar and then on Read out harmonics.The following window then opens:

    Click on Readout meterto read out the harmonics one time as instantaneousvalues or on Read out meter and form average valueto read out the harmonicsperiodically over a fixed period with a mean-value generation. Afterwards, thereadout is displayed as a diagram in the window (see page 57). Via Display >Tableyou can change to the tabular representation (see page 57). The limitingvalues for the voltages according to EN 50160 are each shown in grey.

  • 8/10/2019 Man Combimaster En

    57/137

    Basic program 57

    MenuFile

    Open... Open a saved readout (*.txt)

    Save as... Save the current readout as a text file (*.txt)

    Note:The text file can be opened at a later date with every

    text editor or MS-Excel.

    Print... Print the readout (Graphic display and table evaluation)

    Exit Close the window

    MenuDisplay

    Graphic Display of the readout in the form of diagrams

    Table Display of the readout in a tabular form

  • 8/10/2019 Man Combimaster En

    58/137

    58 Basic program

    Program module Control centre

    Readout > Control centre

    MO Menu option Control centre

    Control centre module for the administration of meters

    After selection of the menu option Readout > Control centre you can open anexisting control centre file. If you do not want to open an existing control centrefile simply click on Cancel. An empty control centre file is then opened.

    Empty control centre file:

    Note:To begin with, in the selection field Control centre main directoryyou shoulddefine the path where the read out files of the control centre are / will besaved.

    Menu bar Control centre

    File > New data bank Creation of an empty data bank

    File > Load data bank Loading of a saved data bank

    File > Save data bank Saving a data bank

  • 8/10/2019 Man Combimaster En

    59/137

    Basic program 59

    File > Save data bank as telefon.ini Saving a data bank as a telefon.ini

    Note:When you save the data bank as atelefon.ini all telephone numbers containedin the data bank are saved in the filetelefon.iniin the index C:\Documents and

    Applications\All Users\ Application Data\EMH.

    Attention:The telefon.iniis also used for themodem function of the main programWhen you save the data bank as atelefoni.inithe file is overwritten. All oldentries are overwritten and are thereforealso deleted.

    File > Import ZKP-control centre file Import (loading) of a LS100-control centrefile from the former EMH-Software EMW-ZKP

    File > End control centre End the control centre

    Table > Add empty row(s) Adding an empty row

    Note:The new row is always inserted overthe marked row.

    Table > Delete rows Delete a row in the table

    Table > Cut row(s) Cut out a row, the content of the row iscopied in to the Windows-clipboard

    Table > Copy row(s) Copy the contents of the row in theWindows-clipboard

    Table > Insert row(s) Insert an empty or a previously copied row

    The new row is always inserted over themarked row

    Table > Rows in program setting Take-over of the modem settings of theselected rows in the program settings ofthe basic program (Setting > Program settings... > Modem see page 40)

  • 8/10/2019 Man Combimaster En

    60/137

    60 Basic program

    Readout > Start Open the window for setting the readouttime.

    Start immediately The specified meters in the opened controlcentre file are read out immediately afteractivation of the button Start.

    Start one-time The specified meters in the opened controlcentre file are read out one-time after

    activation of the button Start.

    The data, time and also the number of re-dialings can be set via the dropdown box.

    Start daily The specified meters in the opened controlcentre file are read out daily at a set time.

    The time and also the number of redialingscan be set via the dropdown box. Afterclick on Startto save the settings.

    The following describes how you can define customers/tasks. Every row standsfor a meter/customer. For every further meter define a new row. You canprocess the rows by clicking with the mouse in the row and carry out thedesired settings in the registers.These settings are then automatically taken over in the selected rows.

  • 8/10/2019 Man Combimaster En

    61/137

    Basic program 61

    Readout > Control centre > Customer

    R RegisterCustomer

    General information about the customer and the meter

    Read out these meters If this checkbox is activated then, with an existingtelephone connection, the meter is automatically readout. The fixed tasks are then carried out. Activation ofthis function is shown in the row customer/meter andis symbolized by a cross in the column Selection.

    Name Entry of the customer name

    Address (Place, Street, No.) Entry of the customer address

    Customer number Entry of the customer number

    Meter-Property number Entry of the meter property numberNote:This number can be found on the metersnameplate.

    Additional info Here you have the possibility to enter additionalinformation about the meter/customer

  • 8/10/2019 Man Combimaster En

    62/137

    62 Basic program

    Readout > Control centre > Meter modem

    R RegisterMeter modem

    Selection of the meter modem

    In the selection field select the meter modem.If the modem used by you is not listed here select the setting Auto-Transparent modem.

    Readout > Control centre > Connection

    R RegisterConnection

    Information on the telephone connection

    Telephone number Entry of the telephone number of the meter modem to becalled

    Note:If dialing a number for an outside line is necessary (oftenwith telephone sets) then, this number must be at the front ofthe telephone number. Then enter a w. The w causes ashort dialing break after reaching the network before dialingfurther.

  • 8/10/2019 Man Combimaster En

    63/137

    Basic program 63

    Meter address Input of the meter address

    Note:This information is only important if the meter has ameter address. The meter address only applies to the meterselectrical interface and therefore only comes into question witha remote readout or a special solution. The meter address can

    be discovered by reading out the service table.The OBIS-codefor the meter address is 0.0.0.

    Port Setting of the COM-Port to which the PC-modem is connected

    Baud rate Setting of the interface speed

    Login password Entry of the login password

    With activation, when logging in, a password is sent to the

    meter.W5-password Entry of the W5-password

    The W5-passwordserves to transfer certain set commands (e.g.setting the clock, writing of the identity number) to the meter.The pre-setting 00000000 must only be changed if anotherpassword was agreed.

    Send break before every communication (VDEW2.0/2.1)

    With activation, a running data transmission on the usedinterface is interrupted. Otherwise communication at this time

    is impossible.

  • 8/10/2019 Man Combimaster En

    64/137

    64 Basic program

    Readout > Control Centre > Tasks

    R RegisterTasks

    Defining of tasks

    In this register, the tasks which should be carried out when there is a telephoneconnection are defined. In order to define a task, click with a double click in therelevant field (alternatively you can mark the field and press the space bar). Settasks are symbolized by a cross.

    Readout > Control centre > Additional information P.01

    R RegisterAdditional information P.01

    Setting additional information for the standard load profile P.01

    Read out load profile x days Defining how many days of the load profileshould be read out.

    Identity number for reading the LP Defining if the meter address or an identitynumber should be read out additionally to theload profile.

  • 8/10/2019 Man Combimaster En

    65/137

    Basic program 65

    Read individual LP channels Defining which individual load profiles should beread out. When this files is empty the completeload profile is read out.

    Mail address(es) for sending Entry of E-mail address(es)

    If the readouts should be sent by E-mail thenyou can enter one or more addresses here.Please pay attention that the addresses areseparated by a semicolon.

    Transformer factor Entry of the transformer factor

    Note:With direct connected meters a 1 mustbe entered. With transformer connected metersthe transformer factor must be entered here sothat correct values are given out with the

    readout.

    For subsequent CE(S)T postponement in MSCONS read out a larger field

    When this option is activated the summer timeswitching is taken into consideration (with meterswhich only support a winter load profile).

    Readout > Control centre > Additional information P.02

    R RegisterAdditional information P.02

    Setting additional information for the user load profile P.02

    Read out load profile x days Defining how many days of the load profileshould be read out.

    Identity number for reading the LP Defining if the meter address or an identitynumber should be read out additionally to theload profile.

    Read individual LP channels Defining which individual load profiles should be

    read out. When this files is empty the completeload profile is read out.

  • 8/10/2019 Man Combimaster En

    66/137

    66 Basic program

    Readout > Control centre > MSCONS

    R RegisterMSCONS

    Defining the MSCONS-information

    MSCONS = Metered Services Consumption Report

    Sender Entry of the sender

    ILN: International Location Number (13 digits)VDEW: Sender-Code accord. to VDEW

    Recipient Entry of the recipient

    ILN: International Location Number (13 digits)VDEW: Sender-Code accord. to VDEW

    Metering-code Entry of the metering-code

    Measuring point number 33 digit measuring point number

    Basic file name of the readout Selection of the saving format of the MSCONS-fileand defining of the file ending (*.edi or *.msc)

    Version Selection of the MSCONS-Version (1.5 or 1.6)

    CEST Data always winter time

    The load profile is read out 1:1

    Data with CE(S)T

    The load profile is read out with summer timeshifting

    Substitute value If data is missing in the load profile e.g. due tonetwork failure then this data is filled in with 0values so that the load profile can be completelygiven out. The added load profile data and periods

  • 8/10/2019 Man Combimaster En

    67/137

    Basic program 67

    with status information are marked in the outputlists. Such periods can be marked either with 99estimated quantityor 262 quantity with reservation.

    Data transfer Export power [kW]

    The read out data is always saved as power values

    in kW in the MSCONS-file and passed on.

    Export to energy feed [kWh]

    The read out data are converted in to energy feedvalues before being saved in the MSCONS-file andtransferred.

    Readout > Control centre > MSCONS manual

    R RegisterMSCONS manual

    Manual MSCONS-converting of a load profile

    In this register you have the possibility to carry out manually a MSCONS-conversion of a load profile.

    Procedure:Click on the button Open load profile file.

    Select a load profile file and click on Open.

  • 8/10/2019 Man Combimaster En

    68/137

    68 Basic program

    In order to now convert the selected load profile to MSCONS click on CreateMSCONS. Then the following window opens:

    In order to be able to read the long character string activate the checkboxDisplay with time feed functions. Line breaks are now automatically created. Thedisplay then changes as follows:

    To close the window click on OK.

    Note:The MSCONS-conversions are automatically saved in the same loadprofile files as the MSCONS-file (*.edi).

    In the register MSCONS manualyou still have the possibility to open an existingMSCONS-file. For this click on the button Display existing MSCONS-file.

  • 8/10/2019 Man Combimaster En

    69/137

    Basic program 69

    Select the file to be displayed and click on Open. The MSCONS-display nowappears.Program module Modem

    Modem

    M Menu Modem

    Connecting and separating a telephone connection to the meter modem

    If the information under Setting > Program settings... > Modemis correct you can setup the telephone connection to the meter by selecting the menu option Connectmodem in the menu Modem. Then, in the main window the announcement Set uptelephone connection...is displayed. After a successful telephone connection the

    announcement Connection ready appears.

    Now you can read out the readout tables, the load profile, the log book or sendcommands ( see menu Menu Directpage 23 onwards) or set files (*.set, *.par,*.trf, *.rse) to the meter.

  • 8/10/2019 Man Combimaster En

    70/137

    70 Basic program

    Program module Tariff setting ITZ

    Configuration > Tariff setting ITZ...

    MO Menu option Tariff setting ITZ...

    Creation of tariff files for meters from the series ITZ with software version 2.0,

    3.0 and 9.0

    Menu bar Creating tariff files for ITZ

    File > New Create an empty tariff file

    File > Open... Load a saved tariff file

    File > Read out Read out tariff file from a meter

    File > Save... Save tariff fileNote:In order to save this tariff information as a tariff file(*.trf) enter in the input field Tariff Number (0.2.2)an 8 digittariff number. Only the characters 0-9, A-F and blank spacesare allowed

    File > Transfer Transfer the opened tariff settings to the meter

    File > Exit... Close program window, return to main window

  • 8/10/2019 Man Combimaster En

    71/137

    Basic program 71

    Configuration > Tariff setting ITZ... > Times

    R RegisterTimes

    Define the switching times for the individual weekdays

    In the following, a tariff file formation for an ITZ with the software version 3.0is explained.

    Define days

    Procedure:Click on a field in the column Switching point x. A pop-up menuappears where you can define the tariff switching times for every weekday. Inorder to write the definition of the tariff switching times in to the table, click on

    Apply.

    Configuration > Tariff setting ITZ... > CEST / holidays

    R RegisterCEST / holidays

    Defining holidays

    Define holidays

  • 8/10/2019 Man Combimaster En

    72/137

    72 Basic program

    Procedure:Via the selection box you can select a country. Afterwards theholidays for the selected country are shown. Click on the check box for the dayswhich should be set as a holiday. The holidays are marked with a tick. Enter theyear from which the public holiday settings should apply into the input field Startyear. You can also define if the summer time switching should be used. To

    activate the summer time switching , click on the check box use summer- / wintertime switching.

    Configuration > Tariff setting ITZ... > Tariff display

    R RegisterTariff display

    Graphic display of the defined tariff switching times

    Display tariff switching times

    In the register Tariff display the defined tariff switching times are graphicallyrepresented so that it is easier for the user to check the plausibility of the tariffswitching times.

  • 8/10/2019 Man Combimaster En

    73/137

    Basic program 73

    Program module Tariff setting ITZ with software version 4.00

    Configuration > Tariff setting ITZ V.400...

    MO Menu option Tariff setting ITZ V4.00...

    Creation of tariff files for meters from the series ITZ with software version 4.00

    The description for the Program module Tariff setting ITZ applies, page 70.

  • 8/10/2019 Man Combimaster En

    74/137

    74 Basic program

    Program module Creating tariff files for DMZ with software versions2.xx/3.xx

    Configuration > Creating tariff files for DMZ V2.00/3.00...

    MO Menu option Creating tariff files DMZ V2.00/3.00...

    Creation of tariff files for meters from the series DMZ with the softwareversions 2xx and 3.xx

    Menu bar Tariff file creation DMZ V2.xx/3.xx

    File > New Creation of an empty tariff file

    File > Open... Load a saved tariff file

    File > Read out Read out tariff file from a meter

    File > Save... Save tariff file

    Note:In order to save this tariff information as a tariff file(*.trf) enter in the input field Tariff Number (0.2.2)an 8 digittariff number. Only the characters 0-9, A-F and blank spacesare allowed

    File > Transfer Transfer the opened tariff settings to the meter

    File > Exit

    Close program window, return to main window

    Note:It is important that you define via the checkbox the software version ofthe meter. The software < 3.xx does not support any season settings.

  • 8/10/2019 Man Combimaster En

    75/137

    Basic program 75

    Configuration > Creating tariff files for DMZ V2.00/3.00... > Times

    R RegisterTimes

    Defining the switching times for the individual profiles

    Define days

    Procedure:Click on a field in the column Days. A selection menu appears whereyou can define the days for the relevant profile. In order to write the definitionsof the weekdays in the table click onApply.

    Define switching times

    Procedure:When you click on one of the fields a selection menu appears inwhich you can define the tariff and switching times. In order to write thedefinitions of the switching times in the table click onApply.

  • 8/10/2019 Man Combimaster En

    76/137

    76 Basic program

    Configuration > Creating tariff files for DMZ V2.00/3.00... > Public holidays

    R RegisterPublic holidays

    Defining the holidays for the individual profiles

    Define holidays

    Procedure:Via the selection box you can select a country. Afterwards theholidays for the selected country are shown. Click on the check box for the dayswhich should be set as a holiday. The holidays are marked with a tick. Enter theyear from which the public holiday settings should apply into the input field Startyear.

    Configuration > Creating tariff files for DMZ V2.00/3.00... > Season

    R RegisterSeason

    Defining of the season switching times (only with the software version >3.xx)

    Define season times

    Note:The register Seasononly appears when you have activated the checkboxSoftware > V3.xx.

  • 8/10/2019 Man Combimaster En

    77/137

    Basic program 77

    Procedure:Click on one of the fields in the row Start or End. A selection menunow appears where you can define the start and end of the season. In order towrite the time period of the season in the table click onApply.

    In order to set the season to be switched click on one of the fields in thecolumn Switch. A selection menu appears again in which you can set the seasonby means of one of the option buttons. By clicking on Applythis season is takenover in table.

  • 8/10/2019 Man Combimaster En

    78/137

    78 Basic program

    Configuration > Creating tariff files for DMZ V2.00/3.00... > Tariff display

    R RegisterTariff display

    Graphic display of the set tariff switching times

    Display tariff switching times

    In the register Tariff displaythe set tariff switching times are graphicallydisplayed. By means of this it is easier for the user to check the plausibility ofthe tariff switching times.

    Program module Creating tariff files for DMZ since software version

    4.00

    Configuration > Creating tariff files for DMZ V4.00...

    MO Menu option Creating tariff files DMZ V4.00...

    Creation of tariff files for meters from the series DMZ since software version4.00

    The description for the Program module Tariff setting ITZ applies, page 70.

  • 8/10/2019 Man Combimaster En

    79/137

    Basic program 79

    Program module Tariff setting DHZ

    Configuration > Tariff setting DHZ...

    MO Menu option Tariff setting DHZ...

    Creation of tariff files for meters from the series DHZ

    Menu bar Tariff file creation DHZ

    File > New Create an empty tariff file

    File > Open... Load a saved tariff file

    File > Read out Read out tariff file from a meter

    File > Save... Save tariff file

    Note:In order to save this tariff information as a tariff file(*.trf) enter in the input field Tariff Number (0.2.2)an 8 digittariff number. Only the characters 0-9, A-F and blank spacesare allowed

    File > Transfer Transfer the opened tariff settings to the meter

    File > Exit... Close program window, return to main window

  • 8/10/2019 Man Combimaster En

    80/137

    80 Basic program

    Configuration > Tariff setting DHZ...> Times

    R RegisterTimes

    Defining the switching times for the individual weekdays

    Define switching times

    Procedure:When you click on one of the fields a selection menu appears inwhich you can define the tariff and switching times. In order to write thedefinitions of the switching times in the table click onApply.

  • 8/10/2019 Man Combimaster En

    81/137

  • 8/10/2019 Man Combimaster En

    82/137

    82 Basic program

    Configuration > Tariff setting DHZ...> Tariff display

    R RegisterTariff display

    Graphical display of the set tariff switching times

    Show tariff switching times

    In the register Tariff displaythe set tariff switching times are graphicallydisplayed. By means of this it is easier for the user to check the plausibility ofthe tariff switching times.

    Program module Transformer setting DHZ

    Configuration > Transformer setting DHZ...

    MO Menu option Transformer setting DHZ...

    Setting of the transformer ratio current for transformer meters from the seriesDHZ

  • 8/10/2019 Man Combimaster En

    83/137

    Basic program 83

    Questions and answers

    1. No communication to the meter takes place. After a few seconds theannouncement Timeout in the communication, Login not possibleappears.

    Possible causes :- The optical communication adapter is not attached properly or not

    connected correctly.

    - The interface is not set correctly. When using an optical communicationadapter OKK please check the information for the COM-Port in the menuSettings. Perhaps you must select another COM-Port.

    - The baud rate is not selected correctly. When using an opticalcommunication adapter OKK select in the menu Settings-Mode C. With thissetting, the PC and the meter set the optimal baud rate themselves.

    2. Communication with the meter takes place however, the read out seems tobe faulty. After ending the communication the error announcement appearsthat the BCC check was incorrect.

    Possible causes :

    - With laptops the energy saving function can be activated which switchesoff the hard disc after a certain period of time. If a hard disc access thentakes place (e.g. for the saving of storage area elsewhere),it is not

    possible to access the hard disc immediately. Delays in the programoperation then occur and this can cause reading errors. In this casedeactivate the energy saving function via Start > Settings > Control Panel >Power Options.

    - Your PC does not have enough RAM (Random Access Memory). If lessthan 32 MB are installed then often the RAM has to be put on to a harddisc. With some computers, due to delays, reading mistakes are caused.

    - The Buffer (FIFO) of the serial interface has not been set correctly. Withtransmission problems try out different settings. Unfortunately a generalsetting tip cannot be given.

    - When using a laptop and a passive optical communication adapter OKKthen, due to a reduced voltage supply, the voltage at the serial interfaceis no longer enough for a faultless data transmission. In this case werecommend using an optical communication adapter OKK with a USBconnection.

  • 8/10/2019 Man Combimaster En

    84/137

    84 Basic program

    Load profile data

    The meter sends for example the following load profile data:

    /EMH4\@01LZQJC0014F_P0_()_`

    P.01(10304280000;10304290000)_P.01(1030428001500)(00000000)(15)(2)(1.5)(kW)(3.5)(kvar)(1.484)(0.600)(1.480)(0.600)...

    This format can be converted by EMH-COMBI-MASTER 2000 so that the datacan be saved as a changed text file and then imported into a table calculatione.g. MS Excel. When table 2 from the meter (pre-configured with load profiles)or the load profile is read out via the menu optionReadout > Load Profile...,themeter sends all measured load profile channels. Depending on the type orconfiguration of the meter the load profile channels can be defined differently.The load profile contains information about which OBIS value (OBIS=Object-Identification-System) stands for the individual channels.

    Explanation of the rows:P.01(1030428001500)(00000000)(15)(2)(1.5)(kW)(3.5)(kvar):

    (1.5) OBIS code of the first channel (P+)(kW) Unit of the first channel(3.5) OBIS code of the second channel (Q+)(kvar) Unit of the second channel

    Explanation of the rows (1.484)(0.600):

    (1.484) 1,484 kW(0.600) 0,600 kvar

    After conversion, the load profile file (without separators) is as follows1:

    Date Start End 1.5kW 3.5kvar Su/Wi Status28.04.04 00:00 00:15 1,484 0,6 S 0000 000028.04.04 00:15 00:30 1,48 0,6 S 0000 0000

    Every row is equal to a measuring period (usually 15 minutes) and containsinformation about the start- and end time. If the meter supports informationabout the season identifier then Sfor summer time or Wfor winter time isentered. The status column contains information about certain events which themeter saves (for the construction see VDEW requirement specifications). Theseevents are mainly voltage failure/return, setting the clock, season change(winter/summer time), cumulation etc. If nothing occurs then 0000 0000 is theoutput.

    1The layout of the text rows can be changed via Setting > Program settings... > Export format.

  • 8/10/2019 Man Combimaster En

    85/137

    Basic program 85

    Events can occur within a measuring period individually or with other eventstogether. The following tables show a few examples:

    One event per measuring period

    Meaning Entry in the load profile

    Measured value interrupted 0000 0004Season change 0000 0008Reset 0000 0010Clock set 0000 0020

    Voltage return 0000 0040Voltage failure 0000 0080

    Two events per measuring period

    Meaning Entry in the load profileClock set + Measured value interrupted 0000 0024Clock set + Season change 0000 0028Clock set + Reset 0000 0030

    Voltage return + Reset 0000 0050Power failure + Voltage return 0000 00C0

    Three events per measuring period

    Meaning Entry in the load profile

    Clock set + Reset + Season change 0000 0038

  • 8/10/2019 Man Combimaster En

    86/137

    86 Basic program

    Load profile import in Excel

    The exported load profile file (here named Musterlastprofil)

    looks as follows whenopened:

    In order to import the file Musterlastprofilin Excel and to represent the load profilegraphically proceed as follows:

    1.

    Open Excel.

    2. Click on Datei > ffnen.

    3. Select the file type Dateityp (*.prn; *.txt; *.csv).The file Musterlastprofilcan now beseen.

    4. Open the file Musterlastprofil.

  • 8/10/2019 Man Combimaster En

    87/137

    Basic program 87

    5. In the following window click on Ende.

    6. Mark the desired display area, e.g. 1 day over the columns A to E.

  • 8/10/2019 Man Combimaster En

    88/137

    88 Basic program

    7. Now call up the Diagram-Assistant and select the Standardtypen Linie.

    8. Click on the button Weiter >until the following window appears

    In the box Diagrammtitelenter for example Load profile,in the boxRubrikenachse (X) enter Timeand in the box Grenachse (Y) enter P+,Q+.

    Then click on the box Weiter >.

  • 8/10/2019 Man Combimaster En

    89/137

    Basic program