LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA •...

22
INSTRUCTION MANUAL L E V E L C O N T R O L S W I T C H E S LINC 282 & 282SC SERIES

Transcript of LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA •...

Page 1: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

LINC 282 & 282SC SERIES

Page 2: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 1

To Order, Call 800.455.LINCOr FAX your order anytime to 215.293.0498

For the Nearest AuthorizedRepresentative:By Telephone: 800.455.LINC forthe US & Canada, 215.293.0465or 215.441.0800 for InternationalcustomersBy Fax: 215.293.0498E-mail:[email protected]

Technical SupportBy Telephone: 800.455.LINC or215.293.0498

By e-mail:[email protected]

Convenient HoursOur phone lines are openMonday–Friday 8:00 AM–4:45PM (EST)

LINC WarrantyThree year limited warranty onall our products against defectsin materials.

LINC Technical SupportTechnical service and supportbegins with an easy toll-freecall. Many times, our experi-enced customer service repscan isolate and resolve prob-lems over the phone or providea referral to our authorized rep-resentatives nationwide.We also offer factory repair services with facilities in Ivyland,PA. if a warranty issue that can-not be resolved locally.

Purchase Orders

All mail-in purchase orders mustbe signed by an authorized per-son. When ordering please list:

•Quantity•Description of Items•Shipping Address•Billing Address•Purchase Order Number

Request for Quotation –RFQ’sPlease send RFQ’s to:By Mail:

Linc Milton RoyAttn: Customer Service201 Ivyland RoadIvyland, PA 18974 USA

By Fax:1.215.293.0498

By E-mail:[email protected]

Freight ChargesAll shipments are F.O.B.,Ivyland, PA, USA. Shipping andhandling are included on theinvoice, prepay and add.

TermsWith credit approval, net 30days.

Page 3: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LT A B L E O F C O N T E N T S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 2

Contents – 282 & 282SC Series Pneumatic Level Controls . . . . . . . . . . . . . . . . . . . . . . . . . . .PageGeneral Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3Ordering Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3Scope Of This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Float and Float Arm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Pneumatic Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Assembly Drawings & Parts ListsFigure 1, 282-11 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6282-11 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Figure 2, 282-12 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7282-11 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Figure 3, 282-13 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8282-13 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8Figure 4, 282-33 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9282-33 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9Figure 5, 282-39 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10282-39 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10Figure 6, 282-73 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11282-73 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Figure 7, 282-79 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12282-79 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Figure 8, 282-SC-01 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13282-SC-01 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Figure 9, 282-SC-02 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14282-SC-02 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Figure 10, 282SC-03 Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15282-SC-03 Level Switch Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Figure 11, 282-2 Manual Override & 282-6, 8 Extended Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .16282-2 Manual Override & 282-6, 8 Extended Body Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Standard Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Optional Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

Page 4: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 3

General Specifications: LINC 282 & 282 SC Series Pneumatic Level ControlsOutput:Pressure:

Temperature:Specific Gravity:Materials:Flow Rate:Connections:

Non-bleed, snap-acting

Working: 1,500 psi std., available to 5,000 psi, (1,500 psi maximum with the Manual Override option)

Supply: 30, 60, 100 psi std.

Output: 0-30, 0-60, 0-100 psi

-40 oF to +450 oF

0.5 minimum standard , interface 0.1 differential minimum

316 stainless steel standard, other austenitic metals and plastics available

40 SCFH at 30 psi, with 30 psi cartridge

Process: 2” NPT standard, available 1 1/2” NPT, 3” flanged or larger, and externally caged

Supply: 1/4” NPT

Output: 1/4” NPT

Series:282 - Pneumatic level control282SC - Externally caged pneumatic level control, ring bolted

(available on body style “0” only)Body Style:

0 - Ringer bolted, 1,500 psi WP standard, 3,000 psi WP available only in the 282SC Model

1 - Standard, 2” NPT2 - Standard, 2” NPT with manual override3 - Extended 1, 2” NPT, vertical displacer6 - Extended 1, 2” NPT, vertical displacer, manual override7 - Extended 1, 2” NPT, horizontal displacer8 - Extended 1, 2” NPT, horizontal displacer, manual override

Type:1 - Standard2 - High pressure, 5,000 psi polypropylene displacer, temperature +

180 o max, specific gravity 0.6 min.3 - Interface, 5,000 psi polypropylene displacer, temperature +

180 o max, upper fluid less than : .870 specific gravity: lowerfluid more than .970 specific gravity.

4 - Other gravities for interface , specify gravities of fluids (upper & lower)9 - Displacer, 5,000 psi polypropylene displacer, temperature + 180 o max,

specific gravity 0.5 min.Supply Pressure:

1 - Maximum, 30 psi, flow rate at 30 psi, 40 scfh2 - Maximum, 60 psi, flow rate at 30 psi, 25 scfh3 - Maximum, 100 psi, flow rate at 30 psi, 15 scfh

Other 2:0 - None2 - Annulus plug5 - This number means special: specify your requirements. i.e.3”

- flanged 150# RFOrder Number:

( ) - Factory will assign an option number based on specified requirements

1 Body styles 3, 6, 7, 8 available only on Type 9.2 If no further requirements are desired , omit “Other” option codes from the part number.Example: 282-11-10

Ordering Chart:

LINC-_______-_________-_______( )Example: LINC-282-11-15 pneumatic level control

Page 5: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 4

Scope Of This Manual:This manual describes and

provides instructions andparts list for the LINC 282and LINC 282SC SeriesPneumatic Level Control.

Installation:Before installing the level

control, inspect the unit forany damage. Also check theclearance in the piping foroperation. The float on thestandard unit (282-11) musthave 2 3/4" minimum clear-ance for the level control tofunction properly. Checkdrawing on the followingpages to determine the prop-er clearance required onother units. The float armmust swing freely withoutbinding. Use an acceptablethread compound dope wheninstalling the unit to the ves-sel to avoid thread galling.

For direct acting, (increasedoutput on the level increase)connect the supply gas toport "A", port "B" is exhaust.Supply gas must be filteredand not exceed specified limitof cartridge. Air is the recom-mended supply; however, anydry filtered gas may be used.Connect the out port,stamped "C", to the unit to becontrolled.

For indirect acting,(decreased output on level

increase) connect supply gasto the port "B". Port "A" isexhaust.

If a larger volumetric outputor faster speed of response isrequired, a pilot or boosterrelay should be installed inthe output line. The exhaustmay be piped away if desired.The manual override featureallows the unit to be testedwhile installed in a vessel. Tooperate the manual override,push down on the knob. Theoutput pressure should go tothe full supply pressure or to0 depending on whether thecontrol is connected in thedirect acting or indirect actingmode. The knob is springloaded and will return to thenormal position whenreleased.

Note: See pages at theback of this manual foroptional installation configura-tions.

Product Description:Used as a level control or ahigh or low level alarm. Thepneumatic output can beused to operate valves,sound alarms or perform anyother desired pneumatic func-tion. Any liquid or liquid or liq-uid interface can be moni-tored.

Operation:As the float is moved by vary-ing liquid height, a magnet inthe float arm is moved. Themagnet operates the 282'sthree-way two-position switchcartridge thru a magneticlinkage only. The output issnap-acting from 0 psi to fullsupply pressure or converselyon float movement.The arm containing the mag-net also acts as a counter-weight for the float.As a result, the float is smalland can operate in liquidswith specific gravity of 0.5 orhigher. This small float per-mits economical installationwhere other types of controlswould be cost prohibitive.Direct acting (increase in liq-uid level increases output) orindirect acting (increase inliquid level decreases output)is selected simply by chang-ing the supply pressure andexhaust connections.The SC Series is designedto eliminate the threadedcontrol connection in mount-ing with the use of a boltedring per API recommendedpractice RP14E. The externalcage allows for the installa-tion of the control at any ele-vation.

Page 6: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 5

Float and Float Arm:The float arm must swing freely.Solvent cleaning of the float armchamber may be required incontrol is used in viscous ordirty liquids. If the float is col-lapsed or perforated, unscrewthe float from the float arm andreplace with a new float. Use ananaerobic adhesive to securethe float to the float arm. Toremove the float arm assemblydrive out the pivot pin using a1/8" punch. Be careful not tolose the float arm spacers andbe sure they are in place whenreinstalling the arm.

Pneumatic Switch Cartridge:To service the switch cartridge,disconnect the supply and ventpiping from control Loosen andremove both port adapters.Remove the switch cartridgefrom the body. Do not attempt todisassemble switch cartridge.The switch cartridge may besolvent cleaned only. Reinstallthe switch cartridge using newo-rings. Reinstall both portadapters. Tighten securely.Reinstall the piping. If the switchcartridge does not functionproperly after cleaning, replacethe switch cartridge.

Features:

Easy to Repair•Repair on-site in 20 minuteswith the Quick-change pneumatic cartridge

Easy to Field Test•The manual override option enables mechanical andpneumatic function testingwhile installed.

No Leaks•Environmentally isolated designkeeps operational fluid awayfrom supply gas.

Lower Operating Cost•Quick-change replacementparts.

•Non-bleed output saves gas.Lower Inventory•Direct or indirect acting bychanging the supply andexhaust ports.

•Use one 282 on either high orlow level activation

Safe•Pneumatically activation in anenvironmentally-isolated design

Corrosion Resistant•Standard 316 Stainless Steelwetted parts for corrosionresistance.

Optional Corrosion ResistantMaterials•Monel, Kynar, Teflon, TeflonCoated, Hastelloy C, PVC,Polypropylene, and Alloy 20optional Corrosion ResistantMaterials available.

Hi & Low PressureApplications•Available with Stainless Steeland Polypropylene displaceroptions for various pressures.

Page 7: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 6

3 11/16"

2 11/16"

7 5/16"

Figure 1, LINC 282-11 Level Switch

Item Part # Description Material Qty1 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .12 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .13 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .24 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .36 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .37 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .28 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .29 . . . . . . . . .22068 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .110 . . . . . . . . .30816 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .20334 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .112 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .213 . . . . . . . . .13217 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .1

The LINC 282-11 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Page 8: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 7

Figure 2, LINC 282-12 Level Switch

Item Part # Description Material Qty1 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .12 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .13 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .24 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .36 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .37 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .28 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .29 . . . . . . . . .22068 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .110 . . . . . . . . .30816 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .20334 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .112 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .213 . . . . . . . . .20892 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .1

The LINC 282-12 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Page 9: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 8

Item Part # Description Material Qty1 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .12 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .13 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .24 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .36 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .37 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .28 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .29 . . . . . . . . .22166 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .110 . . . . . . . . .30816 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .20334 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .112 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .213 . . . . . . . . .20898 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .1

The LINC 282-13 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 3, LINC 282-13 Level Switch

Page 10: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 9

Item Part # Description Material Qty1 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .12 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .13 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .24 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .36 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .37 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .28 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .29 . . . . . . . . .31074 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .110 . . . . . . . . .31072 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .23537 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .112 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .213 . . . . . . . . .24182 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .114 . . . . . . . . .11571 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-7 PH ss . . . . . . . .115 . . . . . . . . .11566 . . . . . . . . . . . .Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . .24”16 . . . . . . . . .23500 . . . . . . . . . . . .Stop Ring . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .217 . . . . . . . . .11565 . . . . . . . . . . . .Crimp . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .318 . . . . . . . . .24181 . . . . . . . . . . . .Weight . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .1

The LINC 282-33 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 4, LINC 282-33 Level Switch

Page 11: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 10

Item Part # Description Material Qty1 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .12 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .13 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .24 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .36 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .37 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .28 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .29 . . . . . . . . .31074 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .110 . . . . . . . . .31072 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .23537 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .112 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .213 . . . . . . . . .23503 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .114 . . . . . . . . .11571 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-7 PH ss . . . . . . . .115 . . . . . . . . .11566 . . . . . . . . . . . .Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . .24”16 . . . . . . . . .23500 . . . . . . . . . . . .Stop Ring . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .217 . . . . . . . . .11565 . . . . . . . . . . . .Crimp . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .3

The LINC 282-39 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 5, LINC 282-39 Level Switch

Page 12: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 11

Item Part # Description Material Qty1 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .12 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .13 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .24 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .36 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .37 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .28 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .29 . . . . . . . . .31113 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .110 . . . . . . . . .31072 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .23537 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .112 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .213 . . . . . . . . .23512 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .114 . . . . . . . . .11571 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-7 PH ss . . . . . . . .1

The LINC 282-73 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 6, LINC 282-73 Level Switch

Page 13: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 12

Item Part # Description Material Qty1 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .12 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .13 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .24 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .36 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .37 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .28 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .29 . . . . . . . . .31074 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .110 . . . . . . . . .31072 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .23537 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .112 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .213 . . . . . . . . .23512 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .114 . . . . . . . . .11571 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-7 PH ss . . . . . . . .1

The LINC 282-79 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 7, LINC 282-79 Level Switch

Page 14: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 13

Item Part # Description Material Qty1 . . . . . . . . .40256 . . . . . . . . . . . .Cage . . . . . . . . . . . . . . . . . . . . . . . . . . . .Steel . . . . . . . . . . . .12 . . . . . . . . .11257 . . . . . . . . . . . .Gasket . . . . . . . . . . . . . . . . . . . . . . . . . .PTFE . . . . . . . . . . . .13 . . . . . . . . .30258 . . . . . . . . . . . .Ring Flange . . . . . . . . . . . . . . . . . . . . . .Steel . . . . . . . . . . . .14 . . . . . . . . .11216 . . . . . . . . . . . .Cap Screw . . . . . . . . . . . . . . . . . . . . . . .Plated, B7 . . . . . . . .65 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .16 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .27 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . .Sealed . . . . . . . . . . .18 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .39 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .310 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .212 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .213 . . . . . . . . .30848 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .114 . . . . . . . . .22068 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .115 . . . . . . . . .20334 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .116 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .217 . . . . . . . . .10245 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .2

The LINC 282SC-01 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 8, LINC 282SC-01 Level Switch

Page 15: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 14

Item Part # Description Material Qty1 . . . . . . . . .40256 . . . . . . . . . . . .Cage . . . . . . . . . . . . . . . . . . . . . . . . . . . .Steel . . . . . . . . . . . .12 . . . . . . . . .11257 . . . . . . . . . . . .Gasket . . . . . . . . . . . . . . . . . . . . . . . . . .PTFE . . . . . . . . . . . .13 . . . . . . . . .30258 . . . . . . . . . . . .Ring Flange . . . . . . . . . . . . . . . . . . . . . .Steel . . . . . . . . . . . .14 . . . . . . . . .11216 . . . . . . . . . . . .Cap Screw . . . . . . . . . . . . . . . . . . . . . . .Plated, B7 . . . . . . . .65 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .16 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .27 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . .Sealed . . . . . . . . . . .18 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .39 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .310 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .212 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .213 . . . . . . . . .30848 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .114 . . . . . . . . .22068 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .115 . . . . . . . . .20334 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .116 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .217 . . . . . . . . .20892 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .1

The LINC 282SC-02 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 9, LINC 282SC-02 Level Switch

Page 16: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 15

Item Part # Description Material Qty1 . . . . . . . . .43561 . . . . . . . . . . . .Cage . . . . . . . . . . . . . . . . . . . . . . . . . . . .Steel . . . . . . . . . . . .12 . . . . . . . . .11257 . . . . . . . . . . . .Gasket . . . . . . . . . . . . . . . . . . . . . . . . . .PTFE . . . . . . . . . . . .13 . . . . . . . . .30258 . . . . . . . . . . . .Ring Flange . . . . . . . . . . . . . . . . . . . . . .Steel . . . . . . . . . . . .14 . . . . . . . . .11216 . . . . . . . . . . . .Cap Screw . . . . . . . . . . . . . . . . . . . . . . .Plated, B7 . . . . . . . .65 . . . . . . . . .23339 . . . . . . . . . . . .Vent Assembly . . . . . . . . . . . . . . . . . . . .Brass . . . . . . . . . . . .16 . . . . . . . . .22451 . . . . . . . . . . . .Port Adapter . . . . . . . . . . . . . . . . . . . . . .303 ss . . . . . . . . . . .27 . . . . . . . . .See Chart Below . . . .Switch Cartridge . . . . . . . . . . . . . . . . . . .Sealed . . . . . . . . . . .18 . . . . . . . . .10403 . . . . . . . . . . . .Retaining Screen . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .39 . . . . . . . . .11006 . . . . . . . . . . . .Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .310 . . . . . . . . .10998 . . . . . . . . . . . .Nameplate . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .111 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . . . . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .212 . . . . . . . . .10108 . . . . . . . . . . . .O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . .Fluorocarbon . . . . . .213 . . . . . . . . .30848 . . . . . . . . . . . .Body . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .114 . . . . . . . . .22166 . . . . . . . . . . . .Float/Magnet Arm . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .115 . . . . . . . . .20334 . . . . . . . . . . . .Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .116 . . . . . . . . .22066 . . . . . . . . . . . .Spacer . . . . . . . . . . . . . . . . . . . . . . . . . .316 ss . . . . . . . . . . .217 . . . . . . . . .20898 . . . . . . . . . . . .Float/Displacer . . . . . . . . . . . . . . . . . . . .Polypropylene . . . . . .1

The LINC 282SC-03 Pneumatic Series Parts List.

Pneumatic Switch CartridgePart # Model Option Description 22935 . . . . . . . . . . .-1 . . . . . . . . . . .0-30 PSI Switch22936 . . . . . . . . . . .-2 . . . . . . . . . . .0-60 PSI Switch22899 . . . . . . . . . . .-3 . . . . . . . . . . .0-100 PSI Switch

All 282 Ports are 1/4” NPT Female

For Direct Acting Operation:Connect Supply to Port “A”Connect Output to Port “C”Port “B” is Vent

For Indirect Acting Operation:Connect Supply to Port “B”Connect Output to Port “C”Port “A” is Vent

Figure 10, LINC 282SC-03 Level Switch

Page 17: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 16

Figure 11, LINC 282 Pneumatic Series:Manual Override Standard Units & Extended Body,Diagram and Parts List

Model 282-2 282-6, -8Item Part # Part # Description Material Qty

1 . . . . . . . . .10282 . . . . . . . . .10282 . . . . . . . . . . . .O-Ring . . . . . . . . . . . .Fluorocarbon . . . . . .12 . . . . . . . . .11139 . . . . . . . . .11139 . . . . . . . . . . . .O-Ring . . . . . . . . . . . .Fluorocarbon . . . . . .13 . . . . . . . . .24991 . . . . . . . . .24991 . . . . . . . . . . . .Nut, manual overdrive .303 ss . . . . . . . . . . .14 . . . . . . . . .24993 . . . . . . . . .24993 . . . . . . . . . . . .Knob . . . . . . . . . . . . . .303 ss . . . . . . . . . . .15 . . . . . . . . .11186 . . . . . . . . .11186 . . . . . . . . . . . .Nameplate . . . . . . . . .316 ss . . . . . . . . . . .16 . . . . . . . . .10324 . . . . . . . . .10324 . . . . . . . . . . . .Drive Screw . . . . . . . .18-8 ss . . . . . . . . . . .17 . . . . . . . . .11361 . . . . . . . . .11361 . . . . . . . . . . . .Socket Head Screw . .316 ss . . . . . . . . . . .18 . . . . . . . . .24992 . . . . . . . . .24992 . . . . . . . . . . . .Stem . . . . . . . . . . . . . .316 ss . . . . . . . . . . .19 . . . . . . . . .13175 . . . . . . . . .13175 . . . . . . . . . . . .Spring . . . . . . . . . . . . .18-8 ss . . . . . . . . . . .110 . . . . . . . . .30809 . . . . . . . . .31103 . . . . . . . . . . . .Level Control Body . . .316 ss . . . . . . . . . . .1

Manual Override Standard Units & Extended Body Parts List

PARTS FOR 282 CONTROLS WITH MANUAL OVERRIDEOTHER PARTS ARE SAME AS STANDARD UNIT

Page 18: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 17

Standard Unit Options

282 & 700 CageCompact external cage available in steel orstainless steel.

282SCThis rig bolt configuration eliminates the 2”pipe threads on control mount and meets API-RP14E Specifications.

282 FlangedFlanged units are available in 3” and largerand all pressure ratings.

282-13 InterfacedThe interface unit will operate in fluids withspecific gravity differential as low as 0.1.

282 Manual OverridePushing the external causes the float arm tomove, operating the pneumatic cartridge bymanual means.

282 Annulus PlugThe Annulus Plug prevents foreign materialfrom getting into the cavity. Available on allmodels.

Page 19: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LL E V E L C O N T R O L S W I T C H E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 18

Optional Configurations

282-39Allows direct replacement of other manufactur-er level control. Patent # 4,481,389.

Choice of threaded, beveled or flangedconnections.

282-39-05 with Model 233 adapter. Model 221.

CHOICEOF

FLANGE SIZE

MODEL 233

Model 223. Model 233.

Page 20: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LN O T E S

L I N C M I L T O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D P A , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8Page 19

Page 21: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

I N S T R U C T I O N M A N U A LN O T E S

L I N C M I LT O N R O Y • 2 0 1 I V Y L A N D R O A D • I V Y L A N D PA , 1 8 9 7 4 • U S A • T E L . 2 1 5 . 2 9 3 . 0 4 6 5 • F A X 2 1 5 . 2 9 3 . 0 4 9 8 Page 20

Page 22: LINC 282 & 282SC SERIES · LINC MILTON ROY • 201 IVYLAND ROAD • IVYLAND PA, 18974 • USA • TEL. 215.293.0465 • FAX 215.293.0498 Page 4 Scope Of This Manual: This manual describes

LINC Milton Roy. represents and warrants that for a period of 3 years from receipt of the product: (1) the product will be free from defects in materialsand workmanship; and (2) the product will perform substantially in accordance with product manuals, literature, or documentation. Any written or oral informationor advice given by LINC Milton Roy representatives, agents, or employees will in no way increase the scope of this warranty. If the product fails to comply with thewarranty set forth herein, LINC Milton Roy's entire liability and the customer's exclusive remedy will be replacement of the product(s) or, at LINC Milton Roy's option,LINC Milton Roy's reasonable effort to make the product meet the warranty set forth herein. LINC Milton Roy disclaims all other warranties, either expressedor implied, including but not limited to, implied warranties or merchantability and fitness for a particular purpose, with respect to the product. This lim-ited warranty gives you specific legal rights. You may have others, which vary from state to state. These remedies are not available outside of the United Statesand Canada. In no event shall LINC Milton Roy or its suppliers be liable for any damages whatsoever (including, without limitation, damages for loss of profits, busi-ness interruption, loss of information, or other pecuniary loss) arising out of the use of or inability to use the product, even if LINC Milton Roy has been advised ofthe possibility of such damages. Information contained in this document is subject to change without notice and does not represent a commitment on the part ofLINC Milton Roy. All prices quoted are in U.S. dollars, F.O.B. Ivyland, PA. LINC, LINC Chemical Pumps, and LINC Level & Flow Switches are trademarks of LINCMilton Roy. All other product names and/or registered trademarks are the property of their respective holders. LINC Milton Roy support services are subject to LINCMilton Roy's then-current prices, terms, and conditions, which are subject to change without notice. All prices and specifications, if published, are subject to changewithout notice.

© Copyright 2004 Milton Roy USA