ISOMETER® iso685-D-P iso685W-D-P iso685-S-P ... - Bender
Transcript of ISOMETER® iso685-D-P iso685W-D-P iso685-S-P ... - Bender
EN Manual
iso685-D-P_D00170_03_M_XXEN/07.2017
ISOMETER® iso685-D-Piso685W-D-Piso685-S-Piso685W-S-P
Insulation Monitoring Device with integrated locating current injectorfor IT AC systemswith galvanically connected rectifiers and invertersand for IT DC systems
Bender GmbH & Co. KGPostfach 1161 • 35301 Gruenberg • GermanyLondorfer Straße 65 • 35305 Gruenberg • Germany
Tel.: +49 6401 807-0Fax: +49 6401 807-259
E-Mail: [email protected]: www.bender.de
© Bender GmbH & Co. KGAll rights reserved.
Reproduction only with permissionof the publisher.
Subject to change.
Customer serviceService-Hotline: 0700-BenderHelp (Telephone and Fax)Carl-Benz-Straße 8 • 35305 Gruenberg • Germany
Tel.:+49 6401 807-760Fax:+49 6401 807-629
E-Mail:[email protected]
PLEASE READ THIS MANUAL AND ANY ACCOMPANYING DOCUMENTS CAREFULLYAND KEEP THEM IN A SECURE PLACE FOR FUTURE REFERENCE.
T
3 iso685-D-P_D00170_03_M_XXEN/07.2017
1
2
3
...........................................................................16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
d panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
s and device buttons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
...........................................................................20
ions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
...........................................................................21
irements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3(N)AC system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
n AC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
DC system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
e X1 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
e supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
e Ethernet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
e relay 1 interface (11 12 14) . . . . . . . . . . . . . . . . . . . . . .26
e relay 2 interface (21 22 24) . . . . . . . . . . . . . . . . . . . . . .26
the BB bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
EDS to the ISOMETER® . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
example ISOMETER® to EDS . . . . . . . . . . . . . . . . . . . . . . .28
to a 3(N)AC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
to an AC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
to a DC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
cture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
...........................................................................33
mmissioning process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
able of contents
. Important information .................................................................... 8
1.1 How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 Technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2.1 First level support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2.2 Repair service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2.3 Field service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3 Training courses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Delivery conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Inspection, transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.6 Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. Safety instructions .......................................................................... 10
2.1 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2 Work activities on electrical installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3 Device-specific safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
. Function ........................................................................................... 12
3.1 Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1.1 Features ISOMETER® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1.2 Features EDS44… . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.1 General product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.2 Special characteristics of ISOMETER® iso685-S-P with front panel 12
3.3 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.4 Insulation fault location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.5 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.6 Self test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.7 Compatibility with EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4. Device overview ..
4.1 Dimensions. . . .
4.2 Device variants
4.3 Connections an
4.4 Display element
5. Mounting ...............
5.1 General instruct
5.2 Screw mounting
5.3 DIN rail mountin
6. Connection ............
6.1 Connection requ
6.2 Connection to a
6.3 Connection to a
6.4 Connection to a
6.5 Connection to th
6.6 Connection to th
6.7 Connection to th
6.8 Connection to th
6.9 Connection to th
6.10 Connection to
6.11 Connecting the
6.11.1 Connection
6.11.2 Connection
6.11.3 Connection
6.11.4 Connection
6.11.5 System stru
7. Commissioning ....
7.1 General initial co
T
iso685-D-P_D00170_03_M_XXEN/07.20174
8
9
1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Insulation alarm 46
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm 1 46
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm 2 46
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault memory 46alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
larm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46(DC-E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47em type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
net. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47SOnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47umber of devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
ice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47art) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47pling monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47ts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48igital 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48) t(on) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48) t(off) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49igital 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49igital 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49tputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Relay 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49.1) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49.2) Relay operating mode . . . . . . . . . . . . . . . . . . . . . . . . . 49.3) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49.4) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50.5) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
10.1 (1.10.2) Relay 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Digital 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50.1) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.2) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.3) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.4) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.5) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Digital 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.1) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.1 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9.2 Operating and navigating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9.2.1 Easy operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9.2.2 Multiple selection in the device menu . . . . . . . . . . . . . . . . . . . . . . . . . . 45
0. Settings .......................................................................................... 46
10.1 Settings in the device menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
10.1 (1.0) Alarm settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
10.1 (1.10.3) 10.1 (1.10.310.1 (1.10.310.1 (1.10.310.1 (1.10.310.1 (1.10.3
10.1 (1.10.4) 10.1 (1.10.5)
10.1 (1.10.5
Table of contentsable of contents
7.2 Initial commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2.1 Set language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2.2 Set time and date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2.3 Setting system type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2.4 Set profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2.5 Setting EDS mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2.6 Setting EDS current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.2.7 Set response value Ran1 for alarm 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.2.8 Set response value Ran2 for alarm 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.3 Recommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.4 Commissioning EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
. Display .............................................................................................. 37
8.1 Standard display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.2 Fault display (active) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.3 Fault display (inactive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8.4 Acknowledging a fault message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.5 Data - isoGraph. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.6 History memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8.7 Initial measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8.8 ISOnet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.9 Insulation fault location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
. Menu ................................................................................................. 43
10.1 (1.1) . . . 10.1 (1.1.1) 10.1 (1.1.2) 10.1 (1.1.3)
10.1 (1.2) DC 10.1 (1.2.1) A10.1 (1.2.2) U
10.1 (1.3) Pro10.1 (1.4) Syst10.1 (1.5) ISO
10.1 (1.5.1) I10.1 (1.5.2) N
10.1 (1.6) Dev10.1 (1.7) T(St10.1 (1.8) Cou10.1 (1.9) Inpu
10.1 (1.9.1) D10.1 (1.9.1.110.1 (1.9.1.210.1 (1.9.1.310.1 (1.9.1.4
10.1 (1.9.2) D10.1 (1.9.3) D
10.1 (1.10) Ou10.1 (1.10.1)
10.1 (1.10.110.1 (1.10.110.1 (1.10.110.1 (1.10.110.1 (1.10.1
T
iso685-D-P_D00170_03_M_XXEN/07.20175
10.1 (2.4.3.2) t(on) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
urrent transformer monitoring. . . . . . . . . . . . . . . . . . . . 60esponse value I∆L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60esponse value I∆n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
puts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60elays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Operating mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60uzzer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60igital output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60ts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60ode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
(on) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60(off) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60unction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60ice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61rigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61ault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61ice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6110.1 (4.0) Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
ry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61e settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
guage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61k . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62ime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62ormat (time). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62ummer time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62ate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62ormat (date). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
10.1 (2.4.3.3) t(off) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5810.1 (2.4.3.4) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
10.1 (2.4.4) Device settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5810.1 (2.4.4.1) System type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5910.1 (2.4.4.2) Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5910.1 (2.4.4.3) Trigger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5910.1 (2.4.4.4) Fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
10.1 (2.5) Channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5910.1 (2.5.1) Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
10.1 (5.0) Histo10.1 (6.0) Devic
10.1 (6.1) Lan10.1 (6.2) Cloc
10.1 (6.2.1) T10.1 (6.2.2) F10.1 (6.2.3) S10.1 (6.2.4) D10.1 (6.2.5) F
Table of contentsable of contents
10.1 (1.10.5.2) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5110.1 (1.10.5.3) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5110.1 (1.10.5.4) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
10.1 (1.10.6) Analogue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5210.1 (1.10.6.1) Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5210.1 (1.10.6.2) Midscale. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5210.1 (1.10.6.3) TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5310.1 (1.10.6.4) Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
10.1 (2.0) EDS (insulation fault location) . . . . . . . . . . . . . . . . . . . . . . . . . . 5310.1 (2.1) General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
10.1 (2.1.1) Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5310.1 (2.1.2) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5410.1 (2.1.3) Using a portable EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
10.1 (2.2) Scanning channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5410.1 (2.3) Activating channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5510.1 (2.4) Group settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
10.1 (2.4.1) Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5510.1 (2.4.1.1) Current transformer (CT) . . . . . . . . . . . . . . . . . . . . . . . 5510.1 (2.4.1.2) CT monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5510.1 (2.4.1.3) I∆L Response value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5610.1 (2.4.1.4) I∆n Response value . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
10.1 (2.4.2) Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5610.1 (2.4.2.1) Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5610.1 (2.4.2.2) Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5710.1 (2.4.2.3) Digital output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5710.1 (2.4.2.4) Function 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5810.1 (2.4.2.5) Function 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5810.1 (2.4.2.6) Function 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
10.1 (2.4.3) Dig. input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5810.1 (2.4.3.1) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
10.1 (2.5.2) C10.1 (2.5.3) R10.1 (2.5.4) R
10.1 (2.6) Out10.1 (2.6.1) R
10.1 (2.6.1.110.1 (2.6.1.210.1 (2.6.1.310.1 (2.6.1.410.1 (2.6.1.5
10.1 (2.6.2) B10.1 (2.6.2.110.1 (2.6.2.210.1 (2.6.2.310.1 (2.6.2.4
10.1 (2.6.3) D10.1 (2.6.3.110.1 (2.6.3.210.1 (2.6.3.310.1 (2.6.3.4
10.1 (2.7) Inpu10.1 (2.7.1) M10.1 (2.7.2) t10.1 (2.7.3) t10.1 (2.7.4) F
10.1 (2.8) Dev10.1 (2.8.1) T10.1 (2.8.2) F
10.1 (2.9) Serv10.1 (3.0) Data
T
iso685-D-P_D00170_03_M_XXEN/07.20176
10.1 (7.0) Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
1
cation ..............................................................70
tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
gs for insulation fault location. . . . . . . . . . . . . . . . . . . . . .70
e display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
opping the insulation fault location . . . . . . . . . . . . . . . . .70
for coupled IT systems .................................71
hen monitoring coupled IT systems. . . . . . . . . . . . . . . .71
n via digital input with two coupled systems. . . . . . . .71
n via ISOnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
...........................................................................74
...........................................................................75
profile power circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
profile control circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
profile generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
profile high capacitance . . . . . . . . . . . . . . . . . . . . . . . . . . .76
profile inverter > 10 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
profile inverter < 10 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
DC alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
ainty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
...........................................................................79
16.1 Alarm messages of the ISOMETER® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
s of the EDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
...........................................................................82
...........................................................................83
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
1. Device communication ............................................................... 65
11.1 Ethernet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11.2 BCOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11.3 Modbus TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11.4 Web server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
11.5 BS bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
16.2 Alarm message
17. Factory settings ..
18. Technical data ....
18.1 Tabular data . .
18.2 Option W . . . . .
18.3 Standards and
Table of contentsable of contents
10.1 (6.2.6) NTP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6210.1 (6.2.7) NTP server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6210.1 (6.2.8) UTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
10.1 (6.3) Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6210.1 (6.3.1) Write access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.2) Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
10.1 (6.3.2.1) DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.2.2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IP 6310.1 (6.3.2.3) SN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.2.4) Std. GW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.2.5) DNS server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.2.6) Domain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
10.1 (6.3.3) BCOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.3.1) System name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.3.2) Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.3.3) Device address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.3.4) Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.3.5) TTL for subscription . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
10.1 (6.3.4) Modbus TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6310.1 (6.3.4.1) Port 502 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.1 (6.3.5) BS bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6410.1 (6.3.5.1) Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.1 (6.4) Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6410.1 (6.4.1) Brightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.1 (6.5) Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6410.1 (6.5.1) Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6410.1 (6.5.2) Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.1 (6.6) Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6410.1 (6.7) Data backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6410.1 (6.8) Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
12. Insulation fault lo
12.1 General descrip
12.2 Required settin
12.3 Indication on th
12.4 Starting and st
13. Special functions
13.1 Particularities w
13.2 System isolatio
13.3 System isolatio
14. Device profiles ....
15. Diagrams .............
15.1 Response time
15.2 Response time
15.3 Response time
15.4 Response time
15.5 Response time
15.6 Response time
15.7 Response time
15.8 Relative uncert
16. Alarm messages .
T
iso685-D-P_D00170_03_M_XXEN/07.20177
1
In
Table of contentsable of contents
18.4 Ordering details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9. Glossary .......................................................................................... 88
dex 89
iso685-D-P_D00170_03_M_XXEN/07.2017
1
1
AThth
rtbleshooting Bender offers you:
rt or e-mail for all Bender products
pecific customer applications
01 807-760*01 807-259
enderHelp (Tel. and Fax)[email protected]
nd replacement service for Bender products
esting and analysing Bender products
update for Bender devices
t devices in the event of faulty or incorrectly delivered
Bender devices, which includes an in-house repair service or no extra cost
01 807-780** (technical issues)01 807-784**, -785** (sales)01 807-789
@bender-service.de
epair to the following address:
r GmbH, Repair-Service,rfer Strasse 65, Grünberg
8
This symbol denotes information intended to assist the user in makingoptimum use of the product.
Please send the devices for r
BendeLondo35305
Important information. Important information
.1 How to use this manual
lways keep this manual within easy reach for future reference.o make it easier for you to understand and revisit certain sections in this manual, we ave used symbols to identify important instructions and information. The meaning of ese symbols is explained below:
This manual is intended for qualified personnel working in electrical en-gineering and electronics!
This signal word indicates that there is a high risk of danger that will re-sult in electrocution or serious injury if not avoided.
This signal word indicates a medium risk of danger that can lead todeath or serious injury if not avoided.
This signal word indicates a low level risk that can result in minor ormoderate injury or damage to property if not avoided.
DANGER
WARNING
CAUTION
1.2 Technical suppoFor commissioning and trou
1.2.1 First level suppoTechnical support by phone
• Questions concerning s
• Commissioning
• Troubleshooting
Telephone: +49 64Fax: +49 64In Germany only: 0700BE-mail: suppo
1.2.2 Repair serviceRepair, calibration, update a
• Repairing, calibrating, t
• Hardware and software
• Delivery of replacemenBender devices
• Extended guarantee forreplacement devices at
Telephone: +49 64+49 64
Fax: +49 64E-mail: repair
Im
iso685-D-P_D00170_03_M_XXEN/07.20179
1O
T
FEIn
*A**
1BTw
1BFTEced(Zentralverband Elektrotechnik- und Elektronikindustrie e. V.) (German Electrical and ES
1 Tspre
ations and laws governing the disposal of this device. Ask sure how to dispose of the old equipment. trical and electronic equipment (WEEE directive) and the di-certain hazardous substances in electrical and electronic apply in the European Community. In Germany, these poli-gh the "Electrical and Electronic Equipment Act" (ElektroG). ing applies:
equipment are not part of household waste.
tors are not part of household waste and must be disposed e regulations.
onic equipment from users other than private households o the market after 13 August 2005 must be taken back by the sed of properly.
e disposal of Bender devices, refer to our homepage at vice & support.
lectronic Manufacturer's Association) also applies.ale and delivery conditions can be obtained from Bender in printed or electronic format.
.5 Inspection, transport and storagehe devices must only be stored in areas where they are protected from dust, damp, and ray and dripping water, and in which the specified storage temperatures can be ensu-d.
Important informationportant information
.2.3 Field servicen-site service for all Bender products
• Commissioning, parameter setting, maintenance, troubleshooting for Bender products
• Analysis of the electrical installation in the building (power quality test, EMC test, thermography)
• Training courses for customers
elephone: +49 6401 807-752**, -762 **(technical issues)+49 6401 807-753** (sales)
ax: +49 6401 807-759-mail: [email protected]: www.bender-de.com
vailable from 7.00 a.m. to 8.00 p.m. 365 days a year (CET/UTC+1)Mo-Thu 7.00 a.m. - 8.00 p.m., Fr 7.00 a.m. - 13.00 p.m.
.3 Training coursesender is happy to provide training regarding the use of test equipment. he dates of training courses and workshops can be found on the Internet at ww.bender-de.com -> Know-how -> Seminars.
.4 Delivery conditionsender sale and delivery conditions apply. or software products the "Softwareklausel zur Überlassung von Standard-Software als eil von Lieferungen, Ergänzung und Änderung der Allgemeinen Lieferbedingungen für rzeugnisse und Leistungen der Elektroindustrie" (software clause in respect of the li-
nsing of standard software as part of deliveries, modifications and changes to general elivery conditions for products and services in the electrical industry) set out by the ZVEI
1.6 DisposalAbide by the national regulyour supplier if you are not The directive on waste elecrective on the restriction of equipment (RoHS directive)cies are implemented throuAccording to this, the follow
• Electrical and electronic
• Batteries and accumulaof in accordance with th
• Old electrical and electrwhich was introduced tmanufacturer and dispo
For more information on thwww.bender-de.com -> Ser
iso685-D-P_D00170_03_M_XXEN/07.2017
2
2Pst
2
Ifau
safety information
that the basic settings meet the requirements of the IT system.nd unauthorised persons must not have access to or contactOMETER®.
that the operating voltage is correct!ulation and voltage tests, the ISOMETER® must be disconnected system for the duration of the test. In order to check the correct of the device, a functional test has to be carried out before start-em.
t of an alarm message of the ISOMETER®, the insulation faultliminated as quickly as possible.
ETER® is installed inside a control cabinet, the insulation faultust be audible and/or visible to attract attention.
g ISOMETER®s in IT systems, make sure that only one active is connected in each interconnected system. If IT systems arected via coupling switches, make sure that ISOMETER®s notsed are disconnected from the IT system and deactivated. IT
systems coupled via diodes or capacitances may also influence the insu-itoring process so that a central control of the different
s is required.
10
lation monISOMETER®
Safety instructions. Safety instructions
.1 General safety instructionsart of the device documentation in addition to this manual is the enclosed "Safety in-ructions for Bender products".
.2 Work activities on electrical installations.
the device is used outside the Federal Republic of Germany, the applicable local stand-rds and regulations must be complied with. The European standard EN 50110 can be sed as a guide.
Only qualified personnel are permitted to carry out the work necessaryto install, commission and run a device or system.
Risk of electrocution due to electric shock!Touching live parts of the system carries the risk of: • An electric shock • Damage to the electrical installation • Destruction of the deviceBefore installing and connecting the device, make sure that the in-stallation has been de-energised. Observe the rules for working on elec-trical installations.
DANGER
2.3 Device-specific
Make sureChildren awith the IS
Make surePrior to insfrom the ITconnectioning the syst
In the evenshould be e
If the ISOMmessage m
When usinISOMETER®interconnecurrently u
WARNING
CAUTION
S
iso685-D-P_D00170_03_M_XXEN/07.20171
e insulation resistance of unearthed AC/DC main circuits (IT s of AC 0…690 V or DC 0…1000 V.
C/DC systems do not influence the operating characteristics. llows de-energised systems to be monitored too. The maxi-akage capacitance is 0…1000 µF, depending on the profile.
lation fault locator (EDS), the ISOMETER® can be used for in-eans of measuring current transformers, the EDS detects the erated by the ISOMETER® in unearthed DC, AC and three-stems) and evaluates them.
formation in the operating manual
tervals
ments of applicable standards, customised parameter set-equipment in order to adapt it to local equipment and oper-d the limits of the area of application indicated in the
Any other use than that described in this manual is regarded as improper.
fied personnel are permitted to carry out the work necessaryommission and run a device or system.
1
Safety instructionsafety instructions
Prevent measurement errors!When a monitored IT system contains galvanically coupled DC circuits, aninsulation fault can only be detected correctly if the rectifier valves (e.g.rectifier diode, thyristors, IGBTs, frequency inverters, …) carry a minimumcurrent of > 10 mA.
Unspecified frequency rangeWhen connecting to an IT system with frequency components below thespecified frequency range, the response times and response values maydiffer from the indicated technical data. However, depending on the ap-plication and the selected measurement method, continuous insulationmonitoring is also possible in this frequency range.There is no influence on the insulation monitoring for IT systems with fre-quency components above the specified frequency range, e.g. within therange of typical switching frequencies of frequency inverters (2…20 kHz).
2.4 Intended use
The ISOMETER® monitors thsystems) with mains voltage
DC components existing in AA separate supply voltage amum permissible system le
In combination with an insusulation fault location. By mlocating current pulses genphase power supplies (IT sy
Intended use also implies:
• The observation of all in
• Compliance with test in
In order to meet the requiretings must be made on the ating conditions. Please heetechnical specifications.
Only qualito install, c
iso685-D-P_D00170_03_M_XXEN/07.2017
3
3
3
in AC, 3AC and DC IT systems 500 V)
rent transformers of the W…, WR…, WS… measuring cur-can be connected
ulation fault location:
idual current measurement:
components via BS bus (RS-485) or BB bus
tion
descriptionion monitoring device in accordance with IEC 61557-8 and t is universally applicable in AC, 3(N)AC, AC/DC and DC sys-de extensive DC-supplied loads (such as rectifiers, inverters,
ristics of ISOMETER® iso685-S-P with front paneland iso685W-D-P are devices of the iso685 device family with
ual applies in full to these ISOMETER®s. nd iso685W-S-P are sensor variants of the iso685 device fam- difference between these variants and the ISOMETER®s P is that they do not feature a display. The ISOMETER®s must be used in combination with a front panel because the
devices are operated via the front panel. The operation of the front panel is equal to the s with integrated display, which is described in this manual.
nsor variant (ISOMETER® iso685-S-P or iso685W-S-P) can beto the front panel. Connection to the display variant
® iso685-D-P or iso685W-D-P) is not possible.
12
(e.g. if several IT systems are interconnected)
• BCOM, Modbus TCP and web server
• Locating current injection for selective insulation fault location
• Indication of the insulation faults selectively located by the EDS system
• Parameter setting of EDS systems
• Customer-specific texts for each measuring channel
operation of the ISOMETER®
Only the seconnected (ISOMETER
Function. Function
.1 Features
.1.1 Features ISOMETER® • ISOMETER® for IT AC systems with galvanically connected rectifiers or inverters and
for IT DC systems (IT = unearthed systems)
• Automatic adaptation to the existing system leakage capacitance
• Combination of and other profile-specific measurement methods
• Two separately adjustable response value ranges of 1 kΩ…10 MΩ for alarm 1 and alarm 2
• High-resolution graphic LC display for excellent readability and recording of the device status
• Connection monitoring (monitoring of the measuring lines)
• Automatic device self test
• Graphical representation of the insulation resistance over time (isoGraph)
• History memory with real-time clock (buffer for three days) for storing 1023 alarm messages with date and time
• Current or voltage output 0(4)…20 mA, 0…400 µA, 0…10 V, 2…10 V (galvanically separated), which is analogous to the measured insulation value of the system
• Freely programmable digital inputs and outputs
• Remote setting of certain parameters via the Internet (Option; COMTRAXX® gateway)
• Worldwide remote diagnosis via the Internet (made available by Bender Service only)
• RS-485/BS (Bender sensor bus) for communication with other Bender devices
• ISOnet: Internal separation of the ISOMETER® from the IT system to be monitored
*
3.1.2 Features EDS44… • Insulation fault location
(AC 24…690 V, DC 24…
• Up to 12 measuring current transformer series
• Response sensitivity insEDS440 2…10 mAEDS441 0.2…1 mA
• Response sensitivity resEDS440 100 mA…10 AEDS441 100 mA…1 A
• Communication of the
3.2 Product descrip
3.2.1 General productThe ISOMETER® is an insulatIEC 61557-9 for IT systems. Items. AC systems may incluvariable-speed drives).
3.2.2 Special characteThe ISOMETER® iso685-D-P integrated display. This manThe ISOMETER® iso685-S-P aily without display. The onlyiso685-D-P and iso685W-D-iso685-S-P and iso685W-S-P
F
iso685-D-P_D00170_03_M_XXEN/07.20171
Hilv
3Tosethcuemp
TdTcavap3co
easure the insulation resistance reliably and precisely in all hed systems). Due to various applications, system types, op-ion of variable-speed drives, high system leakage capacitanc-chnique must be able to meet varying requirements in order onse time and an optimised relative uncertainty. Different
h can be selected from a setup menu allow optimum adapta-chnique to the specific application.
falls below the value of alarm 1 and/or alarm 2, the associated s ALARM 1 or ALARM 2 light and the measured value is shown insulation faults in DC systems, a trend graph for the faulty ). If the fault memory is activated, the fault message will be utton resets the insulation fault message, provided that the st 25 % above the preset response value. As additional Infor-easuring signal and the time required to update the meas- display. A poor signal quality (1-2 bars) may be an indication
nt profile has been selected.
nal system isolating switch, which makes it possible to oper-oupled IT systems. For this purpose, the ISOMETER®s are con- The integrated ISOnet function ensures that only one uring at a time, while the other devices are completely isolat-iting in standby mode for measuring permission.
3
Functionunction
ereafter, the ISOMETER®s with integrated display are described. This description is sim-ar to the combination of ISOMETER® sensor variants and the front panel FP200. The de-ices to which this manual applies will be referred to as ISOMETER®s hereafter.
.3 Functional descriptionhe insulation monitoring device continuously monitors the entire insulation resistance f an IT system during operation and triggers an alarm when the value falls below a pre-t response value. To obtain a measurement, the device has to be connected between e IT system (unearthed system) and the protective earth conductor (PE). A measuring rrent in the µA range is superimposed onto the system which is recorded and evaluat-
d by a microcontrolled measuring circuit. The measuring time depends on the selected easurement profiles, the system leakage capacitance, the insulation resistance and
ossible system-related disturbances.
he response values and other parameters are set using a commissioning wizard or via ifferent setup menus using the device buttons and a high-resolution graphic LC display. he selected settings are stored in a permanent fail-safe memory. Different languages
n be selected for the setup menus and the messages indicated on the display. The de-ice utilises a clock for storing fault messages and events in a history memory with time nd date stamp. The settings can be protected against unauthorised modifications by a assword. To ensure proper functioning of the connection monitoring, the system type AC, AC or DC must be set and the appropriate terminals L1/+, L2, L3/- must be
nnected.
The ISOMETER® is able to mcommon IT systems (unearterating conditions, applicates etc., the measurement teto ensure an optimised respmeasurement profiles whiction of the measurement te
If the preset response value alarm relays switch, the LEDon the LC display (in case ofconductor L+/L- is displayedstored. Pressing the RESET binsulation resistance is at leamation, the quality of the mured value are shown on thethat the wrong measureme
The ISOMETER® has an interate several ISOMETER®s in cnected via an Ethernet bus.ISOMETER® is actively meased from the system and wa
F
iso685-D-P_D00170_03_M_XXEN/07.20171
3AsutesyinvseethsudbFdloIS
3
ly voltage, the ISOMETER® automatically and continuously g functions, the components of the process control such as mory, as well as the connections to the IT system and earth. connected to the ISOMETER® are tested.
ated manually by means of the test button to check the func-g on the configuration) or it can be selected via the "Control"
self test is shown on the LC display by a bar graph. Depending ystem being monitored, the self test is completed after then returns to the standard mode (measurement mode) lue will be displayed after the measuring time has expired. age Initial measurement until the first valid value is meas-rement” on page 40).
the self test, the respective LEDs of the device light (refer to 79). In addition, the respective message will be indicated on programmed output will provide the respective signal.
The test has been run and the result was positive.
s been run and the result was negative.
ot available and is not carried out specific device settings).
unning.
asurement
upling
rth connection
tputs
33 %
4
• BS bus for communication of Bender devices (RS-485)
• BB bus for communication of Bender devices (Bender-internal device bus)
• Integrated web server for reading out measured values and for parameter settingThe test ha
The test is n(e.g. due to
The test is r
√
Functionunction
.4 Insulation fault locationn additional function of the ISOMETER® in combination with the EDS is the selective in-lation fault location. Therefore, the ISOMETER® generates a periodic locating current af-r the values has fallen below the set response value Ran2 (LED ALARM 2). Thereby, the stem conductors are alternately connected to earth via a defined resistance. The result-g locating current depends on the size of the existing insulation fault and the system
oltage. It is limited by the ISOMETER® depending on the settings. The insulation fault is lectively located by means of the EDS and the measuring current transformer connect-
d to it. The locating current flows from the locating current injector via the live lines to e insulation fault position taking the shortest way. From there, it flows through the in-lation fault and the conductor PE back to the ISOMETER®. This locating current pulse is
etected by the measuring current transformer on the insulation fault path and signalled y the connected EDS.or the duration of the insulation fault location, the function of the insulation monitoring evice is deactivated. If during the insulation fault location the locating current falls be-w the value measurable by the EDS, the insulation fault location is ended by the OMETER®.
.5 Interfaces • Communication protocol Modbus TCP
• BCOM for Bender device communication via Ethernet
Risk of malfunctions due to excessive locating current on sensitivesystem parts!The locating current flowing between the IT system and earth can causecontroller faults in sensitive parts of the system, such as the PLC or relay.Ensure that the level of the locating current is compatible with the systemto be monitored.
CAUTION
3.6 Self testAfter switching on the suppchecks all internal measurinthe data and parameter meAdditionally, all EDS devices
The self test can also be activtions of the relays (dependinmenu (refer to page 61).
The progress of the manual on the conditions in the IT s15…20 seconds. The deviceand the actual measured vaThe display shows the messured (refer to “Initial measu
If a fault is detected during “Alarm messages” on pagethe display and a previously
TEST
√ Me
Co
Ea
Ou
F
iso685-D-P_D00170_03_M_XXEN/07.20171
3
F
F
F
5
ull compatibility, no communication with ISOMETER®
Device Notes
EDS195P EDS195P B91082040
Functionunction
.7 Compatibility with EDS
ull compatibility, communication with ISOMETER® via BS bus
ull compatibility, communication with ISOMETER® via BB bus
Device Notes
EDS440-L EDS440-LEDS440W-L
B91080202B91080202W
EDS441-L EDS441-LEDS441W-L
B91080205B91080205W
EDS441-LAB EDS441-LABEDS441W-LAB
B91080207B91080207W
EDS460/490L Not recommended for new systems
EDS460/490D Not recommended for new systems
EDS461/491L Not recommended for new systems
EDS461/491D Not recommended for new systems
Device Notes
EDS440-S EDS440-SEDS440W-S
B91080201B91080201W
EDS441-S EDS441-SEDS441W-S
B91080204B91080204W
iso685-D-P_D00170_03_M_XXEN/07.2017
mm 39
16
4. Device overview
4.1 Dimensions
108 mm110 mm
D
iso685-D-P_D00170_03_M_XXEN/07.20171
4
ect operation of the device functions.
cal conditions
200 via an RJ45 cable
evice overview
7
.2 Device variants
iso685-D-P: The device variant ISOMETER® iso685-D-P features a high-resolution graphic LC display and operating controls for dirIt cannot be combined with an FP200.
iso685-S-P: The device variant ISOMETER® iso685-S-P features neither a display nor operating controls. It can only be used in combination with the FP200 and it is operated via this front panel.
Option "W": The ISOMETER®s with and without integrated display are available with option "W" for extreme climatic and mechani(ISOMETER® iso685W-D-P and iso685W-S-P).
ISOMETER® iso685(W)-D-P
ISOMETER® iso685(W)-S-P connected to front panel FP
D
iso685-D-P_D00170_03_M_XXEN/07.20171
4tage Usonitoredonitoredonitored
T
ONDisplay
RESET
DATA
LEDs: PGH ON, SERVICE, ALARM 1, ALARM 2
MENUESC
TEST
INFOOK
X3
EDS
er devices (e. g. BB bus)FP200
BackF
page 24)
ermination
B
evice overview
8
.3 Connections and panelA1/+, A2/- Connection to the power supply volL1/+ Connector for the IT system to be mL2 Connector for the IT system to be mL3/- Connector for the IT system to be mKE, E Connection to PE
op
PGH ON
iso685-D-P
PGH ON
REMOTE
X4
X3 Optional expansion module for BendX4 REMOTE interface to connect to the
iso685-S-P
ront
ETH X1 Multifunctional I/O interface (refer toETH Ethernet interfaceR Switchable terminating resistor for t
of the RS-485 interface11 12 14 Connector for alarm relay 121 22 24 Connector for alarm relay 2
ottom
D
iso685-D-P_D00170_03_M_XXEN/07.20171
4
D
5 ALARM 1The LED "ALARM 1" lights when the insulation resistance of the IT system
ettings in the respective menu using the menu buttons. try, one of the options displayed below is assigned to the
device menu.
current process or ne step back in the device menu.
tarts the insulation fault location, which runs continuously. nsulation fault location immediately when it is pressed again.
p in a list or increases a value.
evice self test.
orwards (e.g. to the next setting step) or rameter.
ms.
ackwards (e.g. to the previous setting step) or rameter.
rmation.
n action or a selection.
ata and values.
own in a list or reduces a value.
9
falls below the set response value Ran1.
6 ALARM 2The LED "ALARM 2" lights when the insulation resistance of the IT system falls below the set response value Ran2.
Device overviewevice overview
.4 Display elements and device buttons
isplay elements
1 ONThe LED "ON" lights when the device is turned on.The LED "ON" flashes during ISOnet operation if the device is active in the ISOnet interconnection.
2The device display shows information regarding the device and the meas-urements. Other information is available in the chapter “Display” from page 37.
3 PGH ONThe LED "PGH ON" flashes during insulation fault location. It indicates that the locating current for the insulation fault location is generated.
4 SERVICE The LED "SERVICE" lights when there is either a device fault or a connection fault, or when the device is in maintenance mode.
PGH ON
1
7
8
9
10
11
12
2
3
4
5
6
Device buttonsYou can adjust the device sDepending on the menu enbuttons.
7
MENU Opens the
ESC Cancels thenavigates o
8EDS
Manually sStops the i
Navigates u
9
TEST Starts the d
Navigates fselects a pa
10
RESET Resets alar
Navigates bselects a pa
11Info Shows info
OK Confirms a
12DATA Indicates d
Navigates d
iso685-D-P_D00170_03_M_XXEN/07.2017
5
5 g clips delivered with the device (two of them packed separa-a tool, as illustrated below.
s for the M4 thread according to the dimensioned drilling
g three M4 screws.
72 mm108 mm
107,
3 m
m
20
54 mm
Mounting. Mounting
.1 General instructions
Only qualified personnel are permitted to carry out the work necessaryto install, commission and run a device or system.
Risk of electrocution due to electric shock!Touching live parts of the system carries the risk of: • An electric shock • Damage to the electrical installation • Destruction of the deviceBefore installing and connecting the device, make sure that the in-stallation has been de-energised. Observe the rules for working on elec-trical installations.
DANGER
5.2 Screw mountin1. Fix the three mounting
tely) manually or using
2. Drill the mounting holetemplate.
3. Fix the ISOMETER® usin
100
mm
iso685-D-P_D00170_03_M_XXEN/07.20172
uirementsnce to adjacent devices: ttom 20 mm.
ied personnel are permitted to carry out the work necessarymmission and run a device or system.
ctrocution due to electric shock!ve parts of the system carries the risk of:tric shocke to the electrical installation
ction of the devicetalling and connecting the device, make sure that the in-has been de-energised. Observe the rules for working on elec-lations.
ctric shock!ltages up to 1000 V may be present on the terminals L1/+ to
can be lethal. Make sure the terminal covers are properlynd clicked in before putting the device into operation.
ctric shock!e is applied at the terminals, which in case of direct contacthreatening. If the terminals L1/+, L2, L3/- of the device are con-
nected to a live IT system, the terminals E and KE must not be disconnectedrotective conductor (PE).
f insulation monitoring devices that do not work correctly!e terminals KE and E individually to the protective earth con-
DANGER
1
from the p
Warning oConnect thductor PE.WARNING
Connection
5.3 DIN rail mounting1. Fix the three mounting clips delivered with the device (two of them packed sepa-
rately) manually or using a tool, as illustrated below.
2. Snap the ISOMETER® securely onto the DIN rail.
6. Connection
6.1 Connection reqConsider the minimum distalateral 0 mm, top 20 mm, bo
Only qualifto install, co
Risk of eleTouching li • An elec • Damag • DestruBefore insstallation trical instal
Risk of eleNominal voL3/- whichmounted a
Risk of eleHigh voltagcan be life-t
DANGER
DANGER
C
iso685-D-P_D00170_03_M_XXEN/07.20172
carried out as spur lines. Inadmissible load current can result in damage
easurement errors!C system being monitored contains galvanically coupled DC
ke into consideration that: an insulation fault can only be de-rectly when the rectifier valves carry a minimum current of
lications:°C copper lines only! CSA applications, the supply voltage must be protected via 5 A
2
to property and personal injury. Do not apply any load current to the ter-minals.
Check proper connection!Prior to commissioning of the installation, check that the device has beenproperly connected and check the device functions. Perform a functionaltest using an earth fault via a suitable resistance.
CAUTION
Connectiononnection
Provide line protection!According to DIN VDE 0100-430, a line protection shall be provided for thesupply voltage.
Risk of injury from sharp-edged terminals!Risk of lacerations.Touch the enclosure and the terminals with due care.
Ensure disconnection from the IT system!When insulation or voltage tests are to be carried out, the device must beisolated from the system for the test period. Otherwise the device may bedamaged.
Risk of property damage due to unprofessional installation! If more than one insulation monitoring device is connected to a conduc-tively connected system, the system can be damaged. If several devicesare connected, the device does not function and does not signal insula-tion faults. Make sure that only one insulation monitoring device is con-nected in each conductively connected system. The ISOMETER® is suited for use in coupled systems. For the required pa-rameter setting, refer to “Special functions for coupled IT systems” frompage 71.
Risk of property damage due to unprofessional installation! The connecting lines L1/+, L2, L3/- to the system to be monitored must be
CAUTION
CAUTION
CAUTION
CAUTION
Prevent mWhen an Acircuits, tatected cor>10 mA.
For UL appUse 60/70 For UL andfuses.
C
iso685-D-P_D00170_03_M_XXEN/07.20172
6 n AC system
al cover and click it into place
ury, fire and damage to property due to a short circuit! to DIN VDE 0100-430, devices used to protect against a shortn terminals L1/+, L2 und L3/- are coupled to the IT system to be can be omitted if the wiring is carried out in such a manner asthe risk of a short circuit to a minimum. Ensure short-circuit-earth-fault-proof wiring.
L1
L2
PE
3
Connectiononnection
.2 Connection to a 3(N)AC system
Position the terminal cover and click it into place
Risk of injury, fire and damage to property due to a short circuit! According to DIN VDE 0100-430, devices used to protect against a shortcircuit when terminals L1/+, L2 und L3/- are coupled to the IT system to bemonitored can be omitted if the wiring is carried out in such a manner asto reduce the risk of a short circuit to a minimum. Ensure short-circuit-proof and earth-fault-proof wiring.
WARNING
L1
L2
L3
N
PE
US
Un
6.3 Connection to a
Position the termin
Risk of injAccording circuit whemonitoredto reduce proof and
WARNING
Un
US
C
iso685-D-P_D00170_03_M_XXEN/07.20172
6 he X1 interface
cover and click it into place
I1I2I3AB
M+Q2Q1+
Electrical overload protection. Auto shut-off in the event of a short circuit and transients (resettable)
Input 1Input 2Input 3RS-485 ARS-485 B
GroundAnalogue outputOutput 2Output 1+24 V
4
For systems > 690 V and with overvoltage category III a fuse for the connection to the system to be monitored must be provided. Recommendation: 2 A fuses.
Position the terminal
Connectiononnection
.4 Connection to a DC system
Position the terminal cover and click it into place
Risk of injury, fire and damage to property due to a short circuit! According to DIN VDE 0100-430, devices used to protect against a shortcircuit when terminals L1/+, L2 und L3/- are coupled to the IT system to bemonitored can be omitted if the wiring is carried out in such a manner asto reduce the risk of a short circuit to a minimum. Ensure short-circuit-proof and earth-fault-proof wiring.
WARNING
L+
L-
PE
US
Un
6.5 Connection to t
C
iso685-D-P_D00170_03_M_XXEN/07.20172
6 he Ethernet interface
erminal cover and click it into place
5
Connectiononnection
.6 Connection to the supply voltage
External Power supply for powering the ISOMETER® via terminal X1 mustfulfil immunity and emission standards of the required application. Forwiring longer than 1 m the use of a shielded cable is prescribed.
Danger of damage to property due to faulty connections! The device can be damaged if the unit is simultaneously connected to thesupply voltage via the X1 interface, and A1/+ and A2/- terminals. Do notconnect the device simultaneously via X1, and A1/+ and A2/- to differentsupply voltages.
CAUTION
US
6.7 Connection to t
Position the t
C
iso685-D-P_D00170_03_M_XXEN/07.20172
6 he relay 2 interface (21 22 24)
l cover and click it into place
212224
Relay 2
Common contact Normally closed (n.c)
Normally open (n.o)
6
Connectiononnection
.8 Connection to the relay 1 interface (11 12 14)
Position the terminal cover and click it into place
111214
Relay 1
Common contact
Normally open (n.o)Normally closed (n.c)
6.9 Connection to t
Position the termina
C
iso685-D-P_D00170_03_M_XXEN/07.20172
6TTthmst
EDS to the ISOMETER®
e maximum output current! connected to the BB-Bus: The maximum output current is re-rding to the formula for the calculation of ILmaxX1. Refer to the the Technical Data under “Digital Outputs (Q1, Q2)” on
lfunctions due to excessive locating current on sensitiverts!g current flowing between the IT system and earth can causeaults in sensitive parts of the system, such as the PLC or relay.t the level of the locating current is compatible with the systemtored.
orrect measuremented locating current may influence other connected insulationion systems. If they measure the injected locating current, theent might be incorrect.
monitoring is deactivated sulation fault location is active.
…-S must be connected to the ISOMETER® via the BB bus.…-L must be connected to the ISOMETER® via the BS bus.
7
A maximum of two EDS44…-S can be connected to an ISOMETER®.
When the BB bus is installed, the EDS44… must always be mounted on theright side of the ISOMETER®. In addition, for protection against short cir-cuits, a BB bus end bracket must be mounted to each first and last deviceon the DIN rail featuring a BB bus.
The EDS44
Connectiononnection
.10 Connection to the BB bushe BB bus is an interface that enables Bender devices to communicate with each other. he BB bus can be used with an ISOMETER® and one or more EDS44…-S. For this purpose, e BB bus is installed at the rear side of both devices and afterwards, both devices are ounted next to each other on the DIN rail. For further information, refer to the quick-art guide enclosed to the BB bus PCBs.
If the ISOMETER® is combined with an EDS44…-S the BB bus 6TE connec-tor listed in “Accessories” on page 87" must be ordered additionally. It is re-quired to connect the ISOMETER® with the EDS44…-S.
Sensor variant devices that are additionally connected to the ISOMETER®do not require additional supply voltage when the devices are connectedto the BB bus via X3.
6.11 Connecting the
Observe thFor devicesduced accoformula inpage 84.
Risk of masystem paThe locatincontroller fEnsure thato be moni
Risk of incThe supplifault locatmeasurem
Insulation while the in
The EDS44
CAUTION
CAUTION
C
iso685-D-P_D00170_03_M_XXEN/07.20172
6
EDS44…-L
ISOSCAN®EDS440 I L
76 5
3
0
4
2
01
6
5
34 2
01
9
8
EDS440ISOSCAN®
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
1 7
l l
A1/+ A2/-
I L I n
I∆L
I∆n
X1
to the loads to the loads
L1
L2
L3
N
PE
onnection
8
.11.1 Connection example ISOMETER® to EDS
PGH ON
IT-System
O K
23 s
R(an) 40kΩ/10kΩ
O K>20 MΩ>20 MΩ
ISOSCAN®EDS440 I L I n
ON
ON
to the loads to the loads
BS-Bus
BB-B
us
iso685-D-P EDS44…-S
L1/+ L3/-L2 KE E
X1
A1/+ A2/-
US
Un
C
iso685-D-P_D00170_03_M_XXEN/07.20172
6
L1
L2
L3
N
PE
to the loads
I L
32
01
6
5
34 2
01
9
8
TEST
MUTE
RESET
SS
121110
4 5 6
7
I L I n
5 6 7 8 9 10 11 12
13 14 23 24
onnection
9
.11.2 Connection to a 3(N)AC system
BS-Bus
PGH ON
IT-System
O K
R(an) 40kΩ/10kΩ
O K>20 MΩ>20 MΩ
US
Un
to the loads
A1/+ A2/- L1/+ L3/-L2 KE E
X1
ISOSCAN®EDS440
76 5
8
4
EDS440ISOSCAN®
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRE
987
1 2 3
1
I∆L
I∆n
A1/+ A2/- lk
1 2 3 4
X1
US
A1 A2
l l
X1
C
iso685-D-P_D00170_03_M_XXEN/07.20173
6
L1
L2
PE
to the loads
I L
34 2
01
TEST
MUTE
RESET1211
5 6
I L I n
13 14 23 24
7 8 9 10 11 12
onnection
0
.11.3 Connection to an AC system
BS-Bus
IT-System
O K
R(an) 40kΩ/10kΩ
O K>20 MΩ>20 MΩ
US
Un
to the loads
PGH ON
A1/+ A2/- L1/+ L3/-L2 KE E
X1
ISOSCAN®EDS440
76 5
3
8
4
2
01
6
5
9
8
EDS440ISOSCAN®
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
10987
1 2 3 4
1 7
I∆L
I∆n
l l
X1
X1
A1/+ A2/- lk
1 2 3 4 5 6
US
A1 A2
C
iso685-D-P_D00170_03_M_XXEN/07.20173
6
Fo vided. Re
L+
L-
PE
to the loads
I L
34 2
01
TEST
MUTE
RESET121
5 6
I L I n
7 8 9 10 11 12
3 14 23 24
onnection
1
.11.4 Connection to a DC system
r systems > 690 V and with overvoltage category III a fuse for the connection to the system to be monitored must be procommendation: 2A screw fuses.
BS-Bus
IT-System
O K
R(an) 40kΩ/10kΩ
O K>20 MΩ>20 MΩ
US
Un
to the loads
A1/+ A2/- L1/+ L3/-L2 KE E
X1
ISOSCAN®EDS440
76 5
3
8
4
2
01
6
5
9
8
EDS440ISOSCAN®
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
110987
1 2 3 4
1 7
I∆L
I∆n
l l
X1
A1/+ A2/- lk
1 2 3 4 5 6
1X1
US
A1 A2
PGH ON
C
iso685-D-P_D00170_03_M_XXEN/07.20173
6Th -S.
Input Output VFD
M
onnection
2
.11.5 System structuree application example below shows the monitoring of a control system with the ISOMETER® iso685-D-P and the EDS441
PGH ON
IT-System
O K
R(an) 40kΩ/10kΩ
O K>20 MΩ>20 MΩ
A1/+ A2/- L1/+ L3/-L2 KE E
X1
ISOSCAN®EDS440EDS441
ISOSCAN®I L I n
ON
PLC
AC 24 V DC 110 V
L1
L2
PE
US
Un
iso685-D-P_D00170_03_M_XXEN/07.2017
7
71
2
3
Afite
Control and/or connect the EDS to the ISOMETER®:
* EDS44…-L: use BS bus* EDS44…-S: use BB-Bus
Make any other necessary settings for the EDS44… in the
ISOMETER®menu: EDS
Set the maximum locating current in the ISOMETER® menu:
EDS General Current * EDS440…: 10…50 mA
* EDS441…: 1…5 mA
Commissioning the EDS44…
Function test with a suitable resistance between system and earth. Resistance value: 50% of
the response value Alarm 2
Remove the resistance
The ISOMETER® and EDS44... combination is properly connected
and functions reliably
System commissioning ofISOMETER® with EDS44…
Install the device according to the wiring diagram and documentation
Connect the supply voltage
Delete the alarm messages as described in the device
documentation
The EDS44… is properly connected and ready for operation
Disconnect supply voltage of all devices
Connect the supply voltage to all devices
Search for adjustable measuring channels in the ISOMETER®
menu: EDS Scan for channels
Activate measuring channels in ISOMETER® menu:
EDS Enable channel
The ON LED flashes until the device is ready for use
Set EDS mode in the ISOMETER® menu: EDS General
Mode
EDS44…-L:Set the BS adress using
the rotary switches on the EDS
rding de-r “Settings”
33
For further information regavice settings, refer to chaptefrom page 46.
Commissioning. Commissioning
.1 General initial commissioning process. Check that the ISOMETER® is properly connected to the system to be monitored.
. Connect the supply voltage to the ISOMETER®. Adjust the device using the commis-sioning wizard. Afterwards, the ISOMETER® performs a self test in four steps. The alarm relays are not checked during this test. After completion of the test, the meas-ured insulation resistance is shown on the display. If the value exceeds the response values indicated in the lowest line of the display, the message "OK" will additionally be displayed.
. Check the ISOMETER® in the system being monitored, e.g. using a suitable resistance to earth.
fter setting the response value Ran2 for alarm 2, the device starts a self test, makes the rst measurement and outputs the measured insulation resistance values of the IT sys-m being monitored, then commissioning is completed.
For customer-specific configured devices, the commissioning wizardmight be deactivated and cannot be run. In this case, the device is preset.However, the commissioning wizard can be started as described at“Recommissioning” on page 35.
Observe device status!The device is in an alarm state until initial commissioning has beencompleted.
Commissioning flow chart
Commissioning the ISOMETER®
Adjust basic settings if necessary
Install the device according to the wiring diagram
and documentation
Connect the supply voltage
Connect the system voltage
The ISOMETER® performs a self test
Function test with a suitable resistance between system and earth. Resistance value: 50% of
the response value Alarm 2
Remove the resistance
The ISOMETER® is properly connected and
functions reliably
Set BS address = 1 (Master)
Run the commissioning wizard
C
iso685-D-P_D00170_03_M_XXEN/07.20173
7
F
7T
7Ao
min. 1l
ypehe insulation monitoring device can be optimally adapted to . The system type is essential information for the insulation to determine the insulation resistance correctly.
the insulation monitoring device to the system to be moni-hat suits your system. For an overview of the profiles refer to . The profile "Power circuits" is suitable for most IT systems.
eion fault location to manual, automatic or 1 cycle. r to “Mode” on page 54.
6.6.6
• DCo ACo 3AC
System type
6.6.7Profile
• Power circuitso Control circuitso Generatoro High capacitanceo Inverter>10 Hzo Inverter<10 Hz
Mode
• manualo autoo 1 cycle
6.6.8
4
31max. 31 2/9 lle Please select the EDS mode.
7/11
Commissioningommissioning
.2 Initial commissioning
ollow the instructions of the commissioning wizard on the display.
.2.1 Set languagehe language selected here will be used in the menu and for device messages.
.2.2 Set time and datelarm messages in the history memory and the insulation resistance value over time can nly be assigned correctly to the isoGraph when the date and time are set correctly.
Check network function!When the device has been integrated into a network, the influence on thenetwork has to be checked with the device switched on and off.
Language 6.6.2
• Deutscho Englisho ...
6.6.4
14.01.2014
Datele Commissioning 6.6
Please set the
current date and time.
7.2.3 Setting system tBy setting the system type tthe system to be monitoredmonitoring device in order
7.2.4 Set profileIn order to optimally adapt tored, select a profile here t“Device profiles” on page 74
7.2.5 Setting EDS modSet the mode for the insulatFor further information, refe
lle 6.6
5/11
Commissioning
Please choose the type of system that best suits your installation.
lle 6.6
6/11
Commissioning
Please select a profile that suits your application.
Commissioning 6.6
C
iso685-D-P_D00170_03_M_XXEN/07.20173
7SEEF
7YA
7YA
ll
Alarm 2 5.6.9lCommissioning 5.6
ngen put into operation once, the self test will be carried out supply voltage. The commissioning wizard will not restart. sioning wizard using the following menu path:
missioning
odify settings made previously.
evice status!l commissioning has been completed and the initial measure-een taken, the device changes from the alarm state to normalhering to the set response values.
5
10 kΩ
Min.Max.
1 kΩ10MΩ
le Please set a response value for R(an2) for
Alarm 2.
8/9
Commissioningommissioning
.2.6 Setting EDS currentet the maximum locating current. DS441: 1-5 mADS440: 10-50 mA or further information, refer to “Current” on page 53.
.2.7 Set response value Ran1 for alarm 1ou can set the prewarning response value here. value of 100 Ω/V is recommended for prewarning.
.2.8 Set response value Ran2 for alarm 2ou can set the response value for the main alarm here. value of 50 Ω/V is recommended for the main alarm.
Current 6.6.9
o 1mA
o 1.8mA
o 2.5mA
o 5mA
• 10mA
le Commissioning 6.6
Please selectthe locatingcurrent
8/11
Alarm 1 5.6.8
40 kΩ
Min. 1 kΩMax. 10MΩ
le Commissioning 5.6
Please set a response value for R(an1) for
Alarm 1.
7/9
7.3 RecommissioniIf the device has already beshortly after connecting theYou can restart the commis
Menu/Device settings/Com
This menu can be used to m
Observe dOnce initiament has bstate by ad
C
iso685-D-P_D00170_03_M_XXEN/07.20173
7P
1
2
3
Inis
lll
6
addition to this chapter, commissioning of the ISOMETER® in combination with an EDS described in the “Commissioning flow chart” on page 33.
le o 1.8mA
o 2.5mA
o 5mA
• 10mA
Commissioningommissioning
.4 Commissioning EDSroceed as follows to put into operation an EDS after commissioning the ISOMETER®:
. First, search for all available measuring channels.Menu path: Menu/EDS/Scan channels.
. Activate all or only selected measuring channels. Additionally, select the required menu item, confirm your selection with "OK" and start activation with Menu path: Menu/EDS/Activate channel.
. Test if the maximum locating current to the EDS is correct and adjust if necessary (refer to 7.2.6 “Setting EDS current” on page 35).Menu path: Menu/EDS/General/Current
Channel
√ BB-Bus
BS-Bus
33 %
le Scanning channels 2.2
Search for EDS channels?
Cancel Start
Channel
√ BB-Bus
BS-Bus
33 %
le Activating channels 2.3
Select allNo selectionInvert selection
Channel 1 Channel 2
Current 6.6.9
o 1mA
iso685-D-P_D00170_03_M_XXEN/07.2017
8
8Dre
Inp
ctive)y . The upper part of the display will become orange and
ault, the LEDs ALARM 1, ALARM 2 or SERVICE are activated.
sulation resistance is still 7 kΩ. Since the values Ran1=40 kΩ low the set response value, ALARM 1 and ALARM 2 have been
ve appeared, you can navigate through the faults using the
n a DC system or a DC offset is detected in an AC system, ad- regarding the DC offset will be displayed as illustrated
7 kΩ
ulation fault
7 kΩ
1/4
37
If the value falls below Ran1 iditional detailed informationabove.
Display. Display
.1 Standard displayuring normal operation, the ISOMETER® displays the message OK and below, the cur-ntly measured insulation resistance.
the bottom line of the display, the set limit values for R(an) are indicated. In the exam-le below, Ran1=40 kΩ and Ran2=10 kΩ.
The signal quality of the measurement suits the selected profile.The better the signal quality, the faster and more exact the device can measure.
The signal quality of the measurement does not suit the selected pro-file. Select a different measurement profile.
Update period between the test pulses
IT System
OK 230 kΩ
R(an) 40kΩ/10kΩ
OK 230 kΩ
PGH ON
8.2 Fault display (aAn active fault is displayed bdisplays the fault message.
Depending on the type of f
In the example below, the inand Ran2=10 kΩ are both betriggered.
If several fault messages haand button.
Ins
PGH ON
D
iso685-D-P_D00170_03_M_XXEN/07.20173
8Aw
Tb
ve appeared, you can navigate through the faults using the n to the type of fault and the associated alarm value, you can rred and for how long it has been active.
7 kΩ
Insulation fault
28.03.14 17:02 28.03.14 17:18
2/4
7 kΩ
8
Displayisplay
.3 Fault display (inactive)n inactive fault is displayed by . If several faults have occurred, the number of faults ill also be indicated.
he message shown on the display below means that there has been a fault in the past ut the device is no longer in fault condition.
230 kΩ
IT System
3x
1/4
230 kΩPGH ON
If several fault messages haand buttons. In additio
see when the fault has occu
PGH ON
D
iso685-D-P_D00170_03_M_XXEN/07.20173
8Inp
Te
Ptu
chronological sequence of the insulation resistance over ntation can be displayed over the following time periods: year. ividual representations are stored in a separate memory. Up
available to represent each graph. and the resolution of each se values.
16:52
Graph 2
1/4
Change parameter value
Leave view
Modify scale
Modify scale
Change parameter value
Current time scale
9
Displayisplay
.4 Acknowledging a fault message order to acknowledge the fault message and return to the ISOMETER®'s standard dis-
lay, all faults must be acknowledged by means of the reset button.
his means that fault messages can only be reset when the cause of the fault has been liminated.
ress the reset button, then and OK to clear the fault memory. The ISOMETER® then re-rns to the standard display.
RESET 3.2
Reset currentmessages? All messages are saved in the history memory.
Cancel RESET
PGH ON
8.5 Data - isoGraphThe isoGraph represents thetime. This graphical represehour, day, week, month andThe measured values for indto 100 measured values are graph is determined by the
1,0,100,010,001 MΩHour 16:26
Data-iso
PGH ON
D
iso685-D-P_D00170_03_M_XXEN/07.20174
8UaR
entent, the device records all measured values.y have been recorded before will be discarded if a new initial
IT System
Initial measurementInitial
measurement
R(an) 40kΩ/10kΩ
0
Displayisplay
.6 History memoryp to 1023 alarm messages and device errors are stored in the history memory with date nd time stamp. When the history memory is deleted, the minimum insulation resistance min will also be reset at Menu/Data Measured values - Data insulation.
History 4.1
Insulation fault11kΩ 28.03.14 17:02 28.03.14 17:18
8/8
PGH ON
Next message
Leave view
Fault description Alarm value
Feault occuredFault disappearedPrevious message
Number of selected errors/Total number of error messages
8.7 Initial measuremDuring the initial measuremAll measured values that mameasurement is started.
PGH ON
D
iso685-D-P_D00170_03_M_XXEN/07.20174
8TISth
bar indicating the progress of measurement is pulsing, actively in the ISOnet mode.
automatic test. During this test, the ISOMETER® checks the and earth. Afterwards, the ISOMETER® performs an initial
ll measured values (see page 40).
easures for one measuring cycle and then forwards the au-easurement to the ISOMETER® with the next higher address.
IT system
Automatic testAutomatic test
R(an) 40kΩ/10kΩ
1
Displayisplay
.8 ISOnet modehe ISOMETER® displays the message „ISOnet active“, if the ISOMETER® works in the Onet mode but does not measure at the moment. The "ON" LED lights continuously and e bar indicating the progress of measurement is not pulsing.
PGH ON
IT system
ISOnet activeISOnet active
R(an) 40kΩ/10kΩ
230 kΩ230 kΩ
The LED „ON“ blinks and theif the ISOMETER® measures
The ISOMETER® performs anconnections to the IT systemmeasurement and records a
Hereafter, the ISOMETER® mthorisation for insulation m
PGH ON
D
iso685-D-P_D00170_03_M_XXEN/07.20174
8Wloth
Adp
auto mode and 1 cycle.
s been started manually.
IT-System
1x
1/2
1x
ult locationult location
s
IT-System
1x
1/2
1x
ult locationult location
s
2
FaFaPGH ON
Displayisplay
.9 Insulation fault locationhen EDS mode is activated, the ISOMETER® indicates the message "Ins. fault locat.". Be-w, on the left side it indicates which EDS mode is activated. On the right side it indicates e polarity change of the measuring pulses including the pause in between .
n active fault is displayed by . The upper part of the display will become orange and isplays the fault message. The alarm LEDs are lit. If several fault messages have ap-eared, you can navigate through the faults using the and buttons.
Positive measuring pulse
Pause
Negative measuring pulse
The insulation fault location has been started manually and runs contin-uously.No insulation measurement takes place.
43 s Insulation fault location in auto mode and 1 cycle. Time countdown of a measurement cycle.
Insulation fault location in
Insulation fault location ha
FaFa
43
PGH ON
iso685-D-P_D00170_03_M_XXEN/07.2017
9
9
5. Function 3
eneral 1. Current2. Mode3. Use portable EDS
can for Channelsnable Channelroup settings 1. Channel 1. CT
2. CT Monitor3. I∆L Response value4. I∆L Response value
2. Outputs 1. Relay 1. TEST2. Relay mode3. Function 14. Function 25. Function 3
2. Buzzer 1. TEST2. Function 13. Function 24. Function 3
3. Digital Output 1. TEST2. Function 13. Function 24. Function 3
3. Digital Input 1. Mode2. t(on)3. t(off)4. Function
4. Device settings 1. System type2. Frequency3. Trigger4. Fault memory
hannel 1. Name2. CT monitor3. I∆L Response value4. I∆n Response value
utputs 1. Relay 1. TEST2. Relay mode3. Function 14. Function 25. Function 3
2. Summer 1. TEST2. Function 13. Function 24. Function 3
3. Digital Output 1. TEST2. Function 13. Function 24. Function 3
puts 1. Mode2. t(on)3. t(off)4. Function
vice 1. Name2. Trigger3. Fehlerspeicher
rvice
43
4. Digital 2 1. Test2. Relay mode3. Function 14. Function 25. Function 3
5. Summer 1. Test2. Function 13. Function 24. Function 3
6. Analogue 1. Mode2. Midscale3. TEST4. Function
7. In
8. De
9. Se
Menu. Menu
.1 Menu structure1. Alarm settings 1. Insulation alarm 1. Alarm 1
2. Alarm 23. Memory
2. DC Alarm 1. Alarm2. U(DC-E)
3. Profile4. System type5. ISOnet 1. ISOnet
2. Number of devices
6. Device7. t(start)8. Coupling monitoring9. Inputs 1. Digital 1 1. Mode
2. t(on)3. t(off)4. Function
2. Digital 2 1. Mode2. t(on)3. t(off)4. Function
3. Digital 3 1. Mode2. t(on)3. t(off)4. Function
10 Outputs 1. Relay 1 1. Test2. Relay mode3. Function 14. Function 25. Function 3
2. Relay 2 1. Test2. Relay mode3. Function 14. Function 25. Function 3
3. Digital 1 1. Test2. Relay mode3. Function 14. Function 2
2. EDS 1. G
2. S3. E4. G
5. C
6. O
M
iso685-D-P_D00170_03_M_XXEN/07.20174
T
navigatinge menu using the device buttons. The functions of the device chapter “Display elements and device buttons” on page 19.
avigate using required
e a value using an move to
fferent values . The value po-bols is the val-
numbers and lay by using the button
e right using ext character. as been en-tons to navi-deleted and
and buttons. th "OK".
lle Current 6.6.9
o 1mA
o 1.8mA
o 2.5mA
o 5mA
• 10mA
lle 6.6.4
14.01.2014
31
Date
min. 1max. 31
lle Ethernet 6.3.2
-.0123456789abcdefghijklmnopqrstuvwxyz del
4
he menu structure may vary when different EDS types are connected.
gate to the character to be then select "del" using the Confirm the entered text wi
Menuenu
3. Data meas. values
4. Control
5. History
6. Device settings 1. Language2. Clock 1. Time
2. Format3. Summer time4. Date5. Format6. NTP7. NTP Server8. UTC
3. Interface 1. Write access2. Ethernet 1. DHCP
2. IP3. SN4. Std. GW5. DNS Server6. Domäne
3. BCOM 1. System name2. Subsystem3. Device address4. Timeout5. TTL
4. Modbus TCP 1. Port 502
5. BS-Bus 1. Address
4. Display 1. Brightness
5. Passwort 1. Passwort2. Status
6. Commissioning7. Data protection8. Service
7. Info
9.2 Operating and Navigate through the devicbuttons are described in the
9.2.1 Easy operation
Navigation in listsTo make a selection in a list, nthe and buttons to themenu item. Then click "OK".
Navigation with arrowsYou can increase or decreasthe and buttons. You cthe left or the right to set diusing the and buttonssitioned between the symue that is set.
Text inputGo step by step through theletters indicated on the dispthe button (forwards) and(backwards). Navigate to ththe button to enter the nTo delete a character that htered, use the and but
M
iso685-D-P_D00170_03_M_XXEN/07.20174
9
Ab
SbIf
5
Menuenu
.2.2 Multiple selection in the device menu
t some points in the menu, you can select several channels, relays, etc. at a time. There-y, you can make settings for several selection points simultaneously.
elect 1…n selection points using the and buttons. Each selection in the list must e confirmed with "OK". you have made your selection, there are two options depending on the menu item:
• Navigating to the settings for the previous selection using .
• Initiating the respective action (e.g. activate selected channels) using .
Activating channels 2.3
Select allNo selectionInvert selection
Channel 1 Channel 2
iso685-D-P_D00170_03_M_XXEN/07.2017
1
1T
1Tthvti
1InseAluAce
1F
1F
oryfaults at the outputs relay 1, relay 2, digital output 1, digital
the event of a DC offset voltage (UDC-E) in the system.
between 20 V and 1 kV.
a fault becomes inactive, the programmed outputs remain fault condition until they are reset manually.
a fault becomes inactive, the programmed outputs auto-atically change the state.
e DC alarm is triggered in the event of a DC offset voltage.
e DC alarm is NOT triggered in the event of a DC offset ltage.
t
DC+
DC-
200 V
RfU1
U1
U2
U2
UDC-E=(U1+U2)/2=(120 V-80 V)/2=20 V
UDC-E
46
-80 V
-100 V
Settings0. Settings
0.1 Settings in the device menuhe settings of the ISOMETER® are explained in the order of the device menu.
0.1 1.0 Alarm settingshe limit values for the insulation resistances of alarm 1 and alarm 2 can be specified in e alarm settings menu and can be adapted to the user profile of the ISOMETER®. A de-
ice password is required for entering the settings. You can adjust the following func-ons:
0.1 (1.1) Insulation alarm the Insulation alarm menu, the ISOMETER® limit values for alarm 1 and alarm 2 can be t.
ctivation or deactivation of the two alarm levels Ran1 (alarm 1) and Ran2 (alarm 2) are il-strated in the following graphic:n alarm will become inactive as soon as the hysteresis of the set operating value is ex-eded.
0.1 (1.1.1) Alarm 1or alarm 1 an insulation resistance of 1 kΩ…10 MΩ can be set irrespective of alarm 2.
0.1 (1.1.2) Alarm 2or alarm 2 an insulation resistance of 1 kΩ…10 MΩ can be set irrespective of alarm 1.
t
R
Ran1
Ran2
Alarm 1 active
Alarm 2 active
Alarm 2 inactive
Alarm 1 inactive
hysteresis
hysteresis
10.1 (1.1.3) Fault memAutomatic reset of inactive output 2:
10.1 (1.2) DC alarmThe DC alarm is triggered in
10.1 (1.2.1) Alarm
10.1 (1.2.2) U(DC-E)Set the DC alarm to a value
•on If in
•off If m
•on Th
•off Thvo
120 V
V
100 V
0 VRf
S
iso685-D-P_D00170_03_M_XXEN/07.20174
1AoT
1A
10.1 (1.5) ISOnetMTinFe
Onet function
devicesvices (2…20) in a subsystem.
n resistance measurement function to active or inactive:
ated with a start-up delay of 0…120 seconds. The start-up is surement takes place.
nitoringly monitors the coupling of energised systems. The coupling onitored at 8-hour intervals. This monitoring function can be
e ISOnet is deactivated
e ISOnet function is activated via BCOM
e device is active.
e device DOES NOT measure the insulation resistance, the essage Device inactive appears on the display. The system is NOT being monitored!
upling monitoring is activated.
upling monitoring is deactivated.
7
ake the settings to use the ISONet function.he ISOnet function ensures via the Ethernet connection that only one ISOMETER® of the terconnection is active when several ISOMETER®s are connected to an IT system.
or further information regarding the ISOnet function, refer to “System isolation via ISOn-t” from page 72.
•off Co
Settingsettings
0.1 (1.3) Profiledapt the area of application of the ISOMETER® to your system profile. For a description f the profiles, refer to “Device profiles” on page 74. he following can be selected:
0.1 (1.4) System typedapt the ISOMETER® to the IT system to be monitored. The following can be selected:
•Power circuits Suitable for most IT systems.
•Control circuits Not recommended for voltages > 230 V.
•Generator Fast measuring times, fast fault location possible.
•High capacitance Suitable for system with high leakage capacitances.
•Inverter > 10 Hz Suitable for systems with dynamic frequency control by inverters in the range 10…460 Hz.
•Inverter < 10 Hz Suitable for systems with extremely low frequency control in the range 1…460 Hz.
•DC DC system (refer to “Connection to a DC system” on page 31)
•AC Single-phase AC system(refer to “Connection to an AC system” on page 30)
•3AC 3AC system(refer to “Connection to a 3(N)AC system” on page 29)
10.1 (1.5.1) ISOnetActivate or deactivate the IS
10.1 (1.5.2) Number ofConfigure the number of de
10.1 (1.6) DeviceSet the ISOMETER® insulatio
10.1 (1.7) T(Start)The ISOMETER® can be operdelayed until the initial mea
10.1 (1.8) Coupling moThe ISOMETER® continuousof de-energised systems is mactivated or deactivated.
•off Th
•BCOM Th
•Active Th
•Inactive ThmIT
•on Co
S
iso685-D-P_D00170_03_M_XXEN/07.20174
1TT
1T
1T
r a switch-on signal can be set between 100 milliseconds and 1.9.1.1) Mode”).
r a switch-off signal can be set between 100 milliseconds and 1.9.1.1) Mode”).
An event is carried out on the falling edge of the digital input (high to low).Response time t(on)/t(off ) after a switch-off sig-nal.
+ Ix
X1 X1
tt(on)
Reaction ReactionImpulse onImpulse off
8
t0
1
t(on)
ReactionImpulse on
Reaction
< t(on)
Impulse off
Settingsettings
0.1 (1.9) Inputshe ISOMETER® provides a total of three digital inputs.he exemplary wiring diagram shows how the digital inputs can be wired:
0.1 (1.9.1) Digital 1he following parameters can be set for the digital input:
0.1 (1.9.1.1) Modehe operating mode for the digital input can be set to the following values:
•Active high An event is carried out on the rising edge of the digital input (low to high).Response time t(on)/t(off ) after a switch-on sig-nal.
I2I3AB
M+Q2Q1+
Deviceinactive
Reset Test
I1
+ Ix
X1 X1
10.1 (1.9.1.2) t(on)The response time t(on) afte300 seconds (refer to “10.1 (
10.1 (1.9.1.3) t(off)The response time t(off) afte300 seconds (refer to “10.1 (
•Active low
0
1
< t(on)
S
iso685-D-P_D00170_03_M_XXEN/07.20174
1Te
1R
1R
otal of six outputs. an be set for the outputs:
an be set for each relay:
lay can be activated or deactivated. This only applies to the cyclic device self test:
rating modeted to the application:
1e assigned to one output. The functions are linked to an OR
e manual test checks the switching function of the relay
e manual test does not check the switching function of the relay
rmally closed- N/C operation contacts11-12-14 / 21-22-24 fault-free condition, the alarm relay is energised).
rmally opened - N/O operation contacts 11-12-14 / 21-22-24 fault-free condition, the alarm relay is de-energised).
≥ 1 ResponseFunction 2
9
Function 3
Settingsettings
0.1 (1.9.1.4) Functionhe parameters for the function of the digital inputs of the ISOMETER® can be set differ-ntly:
0.1 (1.9.2) Digital 2efer to “10.1 (1.9.1) Digital 1”.
0.1 (1.9.3) Digital 3efer to “10.1 (1.9.1) Digital 1”.
•off Digital input without function
•TEST Device self test
•RESET Reset of fault and alarm messages
•Deactivate device
The device DOES NOT measure the insulation resistance, the mes-sage Device inactive appears on the display.The IT system is NOT being monitored!The device uncouples itself from the system to be monitored through an internal system isolating switch.
•Start initialmeasurement
All recorded measurements are discarded and a new measurement is started
•Insulation faultlocation
The insulation fault location is started.
10.1 (1.10) OutputsThe ISOMETER® provides a tThe following parameters c
10.1 (1.10.1) Relay 1The following parameters c
10.1 (1.10.1.1) TESTThe functional test of the remanual test and not to the
10.1 (1.10.1.2) Relay opeThe relay mode can be adap
10.1 (1.10.1.3) Function Up to three functions can boperator:
•on Th
•off Th
•N/C No(in
•N/O No(in
Function 1
S
iso685-D-P_D00170_03_M_XXEN/07.20175
S
alarm between DC+ and DC- of 25 % to 75 %.
0
2ction 1”.
3ction 1”.
1”.
n be set for each of the digital outputs:
e status of the output changes in the event of an internal device lt.
e status of the output changes on the occurrence of any alarm d fault messages s. alarm 1 & 2, DC- / DC+ alarm, symmetrical alarm, connection d device faults).
e status of the output changes at the end of the initial measure-ent.
e status of the output changes when the device has been deacti-ted via a digital input or the control menu.
e status of the output changes on the occurrence of a DC offset ltage in the system.
e status of the output changes on the occurrence of any message ggered by the EDS.
0
DC+ alarm Symmetrical alarm DC- alarm
% 25 % 50 % 75 % 100 %
Settingsettings
elect the appropriate setting for function 1. The following parameters can be set.
•off The function is not used.
•Ins. Alarm 1 The status of the output changes when the value falls below the set response value Ran1.
•Ins. Alarm 2 The status of the output changes when the value falls below the set response value Ran2.
•Connection fault The status of the output changes when one of the following connec-tion fault occurs:• No low-resistance connection between the line conductors.• No low-resistance connection between the terminals E and KE to
earth (PE).• The load connected to the current output is too low• The load connected to the current output is too high.• Load on X1 too high.
•DC alarm The status of the output changes in case of an earth fault in the direction of DC when 75 % of the value are exceeded. This does not concern symmetrical faults. This function will only be carried out when the value falls below the response value Ran1 and when the nominal system voltage is Un ≥ 50 V.
•DC+ alarm The status of the output changes in case of an earth fault in the direction of DC+ when 25 % of the value are exceeded. This does not concern symmetrical faults. This function will only be carried out when the value falls below the response value Ran1 and when the nominal system voltage is Un ≥ 50 V.
•Symmetrical The status of the output changes in the event of a resistance ratio
10.1 (1.10.1.4) Function Refer to “10.1 (1.10.1.3) Fun
10.1 (1.10.1.5) Function Refer to “10.1 (1.10.1.3) Fun
10.1 (1.10.2) Relay 2Refer to “10.1 (1.10.1) Relay
10.1 (1.10.3) Digital 1The following parameters ca
•Device fault Thfau
•Common alarm Than(Inan
•Measurement complete
Thm
•Device inactive Thva
•DC offset alarm Thvo
•Common alarm EDS Thtri
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1Tto
1T
1ction 1”.
2ction 1”.
3ction 1”.
l 1”.
an be set for the buzzer:
zzer can be activated or deactivated. This only applies to the cyclic device self test:
1ction 1”.
2ction 1”.
3ction 1”.
e manual test activates the buzzer sound.
e manual test does not activate the buzzer sound.
1
Observe the maximum output current!Maximum output current in case of internal voltage supplyvia A1/+ and A2/-: 200 mA in total to X1.Also refer to the formula for calculating ILmaxX1 in the Technical Data un-der “Digital Outputs (Q1, Q2)” on page 84.
Settingsettings
0.1 (1.10.3.1) TESThe functional test of the digital output can be activated or deactivated. This only applies the manual test and not to the cyclic device self test:
0.1 (1.10.3.2) Modehe following settings can be used to set the operating mode for the digital output:
•on The manual test changes the status of the digital output.
•off The manual test does not change the status of the digital output.
•Active In the active mode +24 V will be internally applied across the output.
•Passive In the passive mode ≤ 32 V are externally connected (see technical data). The output switches the applied potential to ground.
X1
iso6
85 Qx
+
X1
iso6
85 Qx
+oder
X1
iso6
85
+
Qx
X1
iso6
85
+
Qx
internal external
10.1 (1.10.3.3) Function Refer to “10.1 (1.10.1.3) Fun
10.1 (1.10.3.4) Function Refer to “10.1 (1.10.1.3) Fun
10.1 (1.10.3.5) Function Refer to “10.1 (1.10.1.3) Fun
10.1 (1.10.4) Digital 2Refer to “10.1 (1.10.3) Digita
10.1 (1.10.5) BuzzerThe following parameters c
10.1 (1.10.5.1) TESTThe functional test of the bumanual test and not to the
10.1 (1.10.5.2) Function Refer to “10.1 (1.10.1.3) Fun
10.1 (1.10.5.3) Function Refer to “10.1 (1.10.1.3) Fun
10.1 (1.10.5.4) Function Refer to “10.1 (1.10.1.3) Fun
•on Th
•off Th
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1T
1T
cale. The following parameters can be set:
resistance using the analogue output:
e switching signal is linear to the insulation resistance in the indi-ted measuring range.
e switching signal is analogue to the mid scale of 28 kΩ or 120 kΩ a measuring instrument.
Lower value Analogue output A10 mA4 mA0 µA0 V2 V
Upper valueAnalogue output A220 mA20 mA400 µA10 V10 V
10 kΩ 1 MΩ
I/U20 mA / 400 µA10 V
0 mA / 4 mA0 V / 2 V
1 k
1 M
100
100
k
Ω28 kΩ
120 kΩ
100 Ω 1 MΩ
I/U20 mA / 400 µA10 V
0 mA / 4 mA0 V / 2 V
120 kΩ28 kΩ
M
ale
A3= Measured value analogue output
2
RSKM= 28 kΩ or 120 kΩ/midsc
RF= Insulation fault in kΩ
Settingsettings
0.1 (1.10.6) Analoguehe following parameters can be set for the analogue output:
0.1 (1.10.6.1) Modehe following values can be set for the operating mode of the analogue output
Current output
•0-20 mA Permissible load ≤ 600 Ω
•4-20 mA Permissible load ≤ 600 Ω
•0-400 µA Permissible load ≤ 4 kΩ
Voltage output
•0-10 V Permissible load ≥ 1 kΩ
•2-10 V Permissible load ≥ 1 kΩ
M+
X1 X1A
M+
X1 X1
V
10.1 (1.10.6.2) MidscaleSelect the appropriate mids
Calculation of the insulation
•Linear Thca
•28 kΩ•120 kΩ
Thon
RF = (A2 - A1) * RSKM - RSK A3 - A1
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1Tthte
1Sse
0000
fault location)
urrent in the ISOMETER®. You can find the device-specific in the table below.
lfunctions due to excessive locating current on sensitiverts!g current flowing between the IT system and earth can causeaults in sensitive parts of the system, such as the PLC or relay.t the level of the locating current is compatible with the systemtored.
r EDS441…
r EDS441…
r EDS441…
r EDS441…, EDS440…
r EDS440…
r EDS440…
r EDS440…
3
Settingsettings
0.1 (1.10.6.3) TESThe functional test of the analogue output can be activated or deactivated. In this way, e analogue output is adjusted once for the entire range. This only applies to the manual st and not to the cyclic device self test:
0.1 (1.10.6.4) Functionelect the appropriate setting for the analogue output. The following parameters can be t.
•on The manual test checks the analogue output function.
•off The manual test does not check the analogue output function.
•Insulation value Depending on the measured insulation value, an analogue current or voltage signal is provided at the output.
•DC offset Depending on the measured DC offset, an analogue current or volt-age signal is provided at the output. This setting can only be used when Linear is selected in the menu "Midscale".
DC+ alarm Symmetrical alarm DC- alarm
% 25 % 50 % 75 % 100 % V/2 V mA/4 mA µA
10 V20 mA
400 µA
10.1 (2.0) EDS (insulation
10.1 (2.1) General
10.1 (2.1.1) Current
Set the maximum locating cmaximum locating currents
Risk of masystem paThe locatincontroller fEnsure thato be moni
•1 mA fo
•1.8 mA fo
•2.5 mA fo
•5 mA fo
•10 mA fo
•25 mA fo
•50 mA fo
CAUTION
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1Tlo
Insulation fault location pauses
To
Manual stop.
rtable EDSrtable EDS, activate this function here. After that, the insula-ill be automatically adjusted.
nnelsault location, all active measuring channels must be deter-d like to start the search for EDS measuring channels.
g EDS” on page 36.
ry out a manual test during a manually started insulation faultnce the insulation fault location would be aborted by that.
ulation faults can be located with a portable EDS.
ulation faults cannot be located with a portable EDS
er mode is set to "auto", the use of a portable EDS must be acti-e menu as the measurement method is correspondingly adjust-
enu point (also refer to “10.1 (2.4.4.3) Trigger”).
orts the scan process.
arts the scan process (search) for EDS channels.
device fails, the ISOMETER® asks whether it should search for channels and then automatically determines all channels refer to “Alarm messages” from page 79.
4
Active insulation fault locationfor 1 cycle
(insulation measurement)
Active insulation fault locationcontinuously
Insulation faultstill present
Manual startManual start.he device retains the riginal mode setting
The device retains the original mode setting
Mode: 1 cycleMode: autoIf one bus measuringagain. Also
Settingsettings
0.1 (2.1.2) Modeo locate insulation faults, select one of the three available modes for insulation fault cation.
•Manual In manual mode, the insulation fault location does not start auto-matically. If you start the insulation fault location, it remains active without considering the insulation resistance and the alarm mes-sage of the ISOMETER®.
•auto In auto mode, the insulation fault location starts automatically as soon as the response value of alarm 2 of the ISOMETER® has fallen below the preset value. The insulation fault location is cyclically interrupted for an insulation measurement. If the insulation fault still exists after the interruption, the insulation fault location starts again. The insulation fault location only stops if alarm 2 is inactive. If a new insulation fault appears, the insulation fault location restarts auto-matically.
•1 cycle In 1-cycle mode, the insulation fault location starts automatically as soon as the response value of alarm 2 of the ISOMETER® has fallen below the preset value. The insulation fault location is stopped after one cycle. If the insulation fault still exists after the interruption, the insulation fault location does NOT start again. If a new insulation fault appears, the insulation fault location restarts automatically for one cycle.
Inactive insulation fault location(insulation measurement)
New insulation faultMode: auto/1 cycle No insulation fault
10.1 (2.1.3) Using a poIf you would like to use a potion fault location process w
10.1 (2.2) Scanning chaFor a successful insulation fmined. Indicate if you woul
Also refer to “Commissionin
Do not carlocation, si
•on Ins
•off Ins
If the triggvated in thed at this m
•Cancel Ab
•Start St
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1DthSh
…
Nle
1Uo
Ifp
ring channel, you must activate it.nnel you would like to activate and configure.
lection point using the and buttons. Confirm your se-tivate the selected measuring channel using the button ptions.
ansformer (CT)rmer.
10.1 (2.4.1.2) CT monitoringT monitoring. alarm is signalled as soon as a fault occurs on a current trans-nel (short circuit or interruption).
l measuring channels are selected.
channel is selected.
e current selection is inverted.
single channel is selected.
/WR…/WS…//WS8000
AB
monitoring is activated e current transformers are monitored).
monitoring is deactivated e current transformers are not monitored).
5
The values indicated in the group settings are not the values of the individ-ual EDS but the factory settings or the last adjusted values in theISOMETER®. To see the values of the individual EDS, please navigate to themenu points “10.1 (2.5) Channel” to “10.1 (2.8) Device”.
Activate or deactivate the CIf CT monitoring is active, anformer of an activated chan
•on CT(th
•off CT(th
Settingsettings
0.1 (2.3) Activating channelsuring initial commissioning all channels are inactive. Before configuring the channels ey must be activated in this menu.
elect which measuring channels you would like to activate. Multiple selection is possible ere.
avigate to the required selection point using the and buttons. Confirm your se-ction by pressing "OK". The selected channels are activated with the button.
0.1 (2.4) Group settingsse group settings to adjust the settings for several EDS or EDS channels simultaneously r to read out settings.
you would like to make settings for each EDS or each EDS channel individually, then lease refer to the menus from “10.1 (2.5) Channel” to “10.1 (2.8) Device”.
•Select all All measuring channels are selected.
•No selection No channel is selected.
•Invert selection The current selection is inverted.
•Channel 1(BS 2/1)
A single channel is selected.
•Channel 12 (BS 2/12)
10.1 (2.4.1) ChannelBefore configuring a measuSelect which measuring cha
Navigate to the required selection by pressing "OK". Acand navigate to its setting o
10.1 (2.4.1.1) Current trSet the used current transfo
•Select all Al
•No selection No
•Invert selection Th
•Channel 1 (BS 2/1)
A
•Channel 2 (BS 2/2)
•Channel 3 (BS 2/3)
•Type A W…W
•Type AB W…
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1Sa(r
1Sa
1In
ould like to configure.
lay can be activated or deactivated. This only applies to the cyclic device self test.
ing modean be adapted to the application.
All relays are selected.
No relay is selected.
The current selection is inverted.
A single relay is selected.
The manual test checks the switching function of the relay.
The manual test does not check the switching function of the relay.
Normally closed- N/C operation contacts11-12-14 / 21-22-24 (in fault-free condition, the alarm relay is energised).
Normally opened - N/O operation contacts 11-12-14 / 21-22-24 (in fault-free condition, the alarm relay is de-energised).
6
Settingsettings
0.1 (2.4.1.3) IΔL Response valueet the response value for I∆L (main alarm for insulation fault location) between 200 µA nd 10 mA. The response value must be below the set locating current efer to 7.2.6 “Setting EDS current” on page 35).
0.1 (2.4.1.4) IΔn Response valueet the response value for I∆n (alarm for residual current measurement) between 100 mA nd 10 A.
0.1 (2.4.2) Outputs this menu, the settings for the outputs of the EDS can be made.
The permissible response value and the response sensitivity depend onthe connected EDS (EDS440… or EDS441…).
The permissible response value and the response sensitivity depend onthe connected EDS (EDS440… or EDS441…).
•Relays
•Buzzer
•Dig. output
CAUTION
CAUTION
10.1 (2.4.2.1) RelaysSelect the relays that you w
10.1 2.4.2.1.1 TESTThe functional test of the remanual test and not to the
10.1 2.4.2.1.2 OperatThe relay operating mode c
•Select all
•No selection
•Invert selection
•Relay 1 (BS 2/1)
•Relay 2 (BS 2/2)
•on
•off
•N/C
•N/O
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1Uo
S
1R
1R
1
would like to configure.
hich the buzzers should be triggered.
”.
n 1tion 1”.
n 2tion 1”.
n 3tion 1”.
tput the EDS that you would like to configure.
he digital outputs of the EDS selected before.
ll buzzers are selected.
o buzzer is selected.
he current selection is inverted.
single buzzer is selected.
ll digital outputs are selected.
o digital output is selected.
•Invert selection The current selection is inverted.
single digital output is selected.
7
0.1 2.4.2.1.4 Function 2efer to “10.1 2.4.2.1.3 Function 1”.
0.1 2.4.2.1.5 Function 3efer to “10.1 2.4.2.1.3 Function 1”.
0.1 (2.4.2.2) Buzzer
•Common alarm The status of the output changes on the occurrence of any alarms and fault messages (I∆L alarm, I∆n alarm, connection and device fault).
Now make the settings for t
•Dig. output 1(BS 2/1)
A
Settingsettings
0.1 2.4.2.1.3 Function 1p to three functions can be assigned to one output. The functions are linked to an OR perator:
et the function for the outputs:
•off The function is not used.
•I∆L The status of the output changes if an insulation fault is detected (EDS function) on one of the measuring channels.
•I∆N The status of the output changes if the residual current (RCM func-tion) is exceeded.
•Device fault The status of the output changes in the event of an internal device fault.
•Connection fault The status of the output changes when one of the following measur-ing current transformer connection faults occurs:• Measuring current transformer defective• Power supply cable interrupted• Power supply cable short-circuited
•Insulation fault location active
The buzzer signals active insulation fault location can only be set for buzzer).
≥ 1 Response
Function 1
Function 2
Function 3
Select the buzzers that you
Now assign the events on w
10.1 2.4.2.2.1 TESTRefer to “10.1 2.4.2.1.1 TEST
10.1 2.4.2.2.2 FunctioRefer to “10.1 2.4.2.1.3 Func
10.1 2.4.2.2.3 FunctioRefer to “10.1 2.4.2.1.3 Func
10.1 2.4.2.2.4 FunctioRefer to “10.1 2.4.2.1.3 Func
10.1 (2.4.2.3) Digital ouSelect the digital outputs of
•Select all A
•No selection N
•Invert selection T
•Buzzer 1 (BS 2/1)
A
•Select all A
•No selection N
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1Tto
1R
1R
1R
1S
N
digital input can be set to the following values. For a descrip-s, refer to “Mode” on page 48. The following can be selected:
r a switch-on signal can be set between 100 milliseconds and on of the operating modes, refer to “Mode” on page 48.
r a switch-off signal can be set between 100 milliseconds and on of the operating modes, refer to “Mode” on page 48.
ings
n event is carried out on the rising edge of the digital input (low to igh).
n event is carried out on the falling edge of the digital input (high o low).
igital input without function.
evice self test.
eset of fault and alarm messages.
ll devices are selected.
•No selection No device is selected.
he current selection is inverted.
8
ow make the settings for the digital inputs of the EDS selected before. •Invert selection T
•BS bus 2 (1-12)
Settingsettings
0.1 2.4.2.3.1 TESThe functional test of the digital output can be activated or deactivated. This only applies the manual test and not to the cyclic device self test:
0.1 (2.4.2.4) Function 1efer to “10.1 2.4.2.1.3 Function 1”.
0.1 (2.4.2.5) Function 2efer to “10.1 2.4.2.1.3 Function 1”.
0.1 (2.4.2.6) Function 3efer to “10.1 2.4.2.1.3 Function 1”.
0.1 (2.4.3) Dig. inputelect the digital inputs of the EDS that you would like to configure:
•on The manual test changes the status of the digital output.
•off The manual test does not change the status of the digital output.
•Select all All digital inputs are selected.
•No selection No digital input is selected.
•Invert selection The current selection is inverted.
•Dig. input 1 (BS 2/1)
A single digital input is selected.
•Dig. input 2 (BS 2/2)
10.1 (2.4.3.1) ModeThe operating mode for thetion of the operating mode
10.1 (2.4.3.2) t(on)The response time t(on) afte300 seconds. For a descripti
10.1 (2.4.3.3) t(off)The response time t(off) afte300 seconds. For a descripti
10.1 (2.4.3.4) Function
10.1 (2.4.4) Device sett
•Active high Ah
•Active low At
•off D
•TEST D
•RESET R
•Select all A
S
iso685-D-P_D00170_03_M_XXEN/07.20175
1
A
1
C
f the ISOMETER® is synchronised with the measurement tech- bus or the BS bus. This allows a more reliable detection of the event of disturbances. e.g. by variable-speed drives, rectifiers, actuators, noise fil-nics.
oryorarily can be saved.
can be configured. Also refer to “10.1 (2.4.1) Channel”.
d channel. This name will also be displayed on the gateways an be edited via these as well.
ynchronisation via BS bus or BB bus. The EDS only searches for insu-ation faults if the insulation fault location has been started. Less ime is needed for the insulation fault location as with the setting auto".
o synchronisation (e.g. if there is no BS bus or BB bus).he EDS continuously searches for insulation faults.
er mode is set to "auto", the use of a portable EDS must be acti-e menu “10.1 (2.1.3) Using a portable EDS” = "on"), since the measure-od is correspondingly adjusted at this menu point.
fter eliminating the cause of fault, alarm messages remain stored ntil a RESET is carried out. This function applies to alarm and device
ault messages.
he EDS exits the alarm mode as soon as the cause of fault is liminated.
9
10.1 (2.5) ChannelIn this menu, each channel
10.1 (2.5.1) NameEnter a name for the selecteand in the web server and c
Settingsettings
0.1 (2.4.4.1) System type
djust the EDS to the IT system to be monitored.
0.1 (2.4.4.2) Frequency
onfigure the mains frequency of the IT system to be monitored.
Settings made to this menu point will only have an effect on connectedEDS460 and NOT on EDS44… devices.
•DC DC system
•AC Single-phase AC system
•3AC 3AC system
Settings made to this menu point will only have an effect on connectedEDS460 and NOT on EDS44… devices.
•50 Hz
•60 Hz
•400 Hz
•DC
10.1 (2.4.4.3) TriggerThe locating current pulse onology in the EDS via the BBlocating current pulse in theDisturbances can be causedters, PLCs, or control electro
10.1 (2.4.4.4) Fault memFaults that only occur temp
•Com Slt"
•auto NT
If the triggvated in th(menu itemment meth
•on Auf
•off Te
S
iso685-D-P_D00170_03_M_XXEN/07.20176
1R
1R
1R
1In
1S
.
1R
1R
1R
1R
1Refer to “10.1 2.4.2.1.3 Function 1”.
1In
1R
1R
2tion 1”.
3tion 1”.
puttput can be configured. igital output”.
”.
1tion 1”.
2tion 1”.
3tion 1”.
put can be configured. Therefore, select a digital input.
e”.
.
”.
tion”.
0
0.1 (2.6.2) Buzzer this menu, each buzzer can be configured. Also refer to “10.1 (2.4.2.2) Buzzer”.
0.1 (2.6.2.1) TESTefer to “10.1 2.4.2.1.1 TEST”.
0.1 (2.6.2.2) Function 1efer to “10.1 2.4.2.1.3 Function 1”.
Refer to “10.1 (2.4.3.1) Mod
10.1 (2.7.2) t(on)Refer to“10.1 (2.4.3.2) t(on)”
10.1 (2.7.3) t(off)Refer to “10.1 (2.4.3.3) t(off)
10.1 (2.7.4) FunctionRefer to “10.1 (2.4.3.4) Func
Settingsettings
0.1 (2.5.2) Current transformer monitoringefer to “10.1 (2.4.1.2) CT monitoring”.
0.1 (2.5.3) Response value IΔLefer to “10.1 (2.4.1.3) I∆L Response value”.
0.1 (2.5.4) Response value IΔnefer to “10.1 (2.4.1.4) I∆n Response value”.
0.1 (2.6) Outputs this menu, each output can be configured. Also refer to “10.1 (2.4.2) Outputs”.
0.1 (2.6.1) Relayselect the relay that you would like to configure.
..
0.1 (2.6.1.1) TESTefer to “10.1 2.4.2.1.1 TEST”.
0.1 (2.6.1.2) Operating modeefer to “10.1 2.4.2.1.2 Operating mode”.
0.1 (2.6.1.3) Function 1efer to “10.1 2.4.2.1.3 Function 1”.
0.1 (2.6.1.4) Function 2efer to “10.1 2.4.2.1.3 Function 1”.
0.1 (2.6.1.5) Function 3
•Relay 1 (BS 2/1)
10.1 (2.6.2.3) Function Refer to “10.1 2.4.2.1.3 Func
10.1 (2.6.2.4) Function Refer to “10.1 2.4.2.1.3 Func
10.1 (2.6.3) Digital outIn this menu, each digital ouAlso refer to “10.1 (2.4.2.3) D
10.1 (2.6.3.1) TESTRefer to “10.1 2.4.2.3.1 TEST
10.1 (2.6.3.2) Function Refer to “10.1 2.4.2.1.3 Func
10.1 (2.6.3.3) Function Refer to “10.1 2.4.2.1.3 Func
10.1 (2.6.3.4) Function Refer to “10.1 2.4.2.1.3 Func
10.1 (2.7) InputsIn this menu, each digital in
10.1 (2.7.1) Mode
•Dig. input 1 (BS 2/1)
•Dig. input 2 (BS 2/2)
S
iso685-D-P_D00170_03_M_XXEN/07.20176
1
1R
1R
1T
1Tthu
n start a manual test reset, reset alarm messages and start an
lts detected by the ISOMETER® are displayed. For a detailed to “History memory” on page 40:
sllows you to configure the basic settings for the ISOMETER®:
isplayed by the ISOMETER®. For example, you can set the lan-
anual device test
eset of fault and alarm messages
ll recorded measurements are discarded and a new measurement s started
tarting and stopping the insulation fault location
verview of faults that have occurred
eset the history memory
•English
1
•...
Settingsettings
0.1 (2.8) Device
0.1 (2.8.1) Triggerefer to “10.1 (2.4.4.3) Trigger”.
0.1 (2.8.2) Fault memoryefer to “10.1 (2.4.4.4) Fault memory”.
0.1 (2.9) Servicehe service menu can only be accessed by Bender Service staff.
0.1 (3.0) Data measured valueshe ISOMETER® stores certain measured values for a specific period of time. You can view ese data at the "Data meas. values" menu point. Navigate through the different views
sing the and buttons:
•isoGraph data Displays the insulation resistance and chronological sequence. See “Data - isoGraph” on page 39.
•Insulation data Displays the current insulation resistance, the minimum insulation resistance measured and the system leakage capacitance.
•IT system data Displays the system phase-to-phase voltages and the mains fre-quency (r.m.s. values)
•IT system data Displays the system phase-to-earth voltages
•EDS data Displays I∆L and I∆n in % and ampere. Use the and buttons to switch between the two options.
•EDS data Displays the locating current for Insulation fault location
10.1 (4.0) ControlIn the control menu, you cainitial measurement:
10.1 (5.0) HistoryIn the history menu, the faufunctional description, refer
10.1 (6.0) Device settingThe device settings menu a
10.1 (6.1) LanguageChoose the language to be dguages:
•TEST M
•RESET R
•Start initial measurement
Ai
•EDS S
•History O
•Delete R
•German
S
iso685-D-P_D00170_03_M_XXEN/07.20176
1Inis
1Bh
1S
1S
ing to Central European regulation.
format you can set the current date.
te) format you want to be displayed:
nchronise the current time via NTP. You have to configure the is function (see “NTP server” on page 62).
P server.
TC (coordinated world time). For Germany, set +1 for winter-er time (MESZ).
onnection of other devices to the ISOMETER® in the interface
DST or CEST, changing between summer time and normal timee on the date of the official time change.
ay, month, year
onth, day, year
ynchronisation via NTP server is activated.
ynchronisation via NTP server is deactivated.
2
Central European summer time begins on each last Sunday in March at 02:00 CEST by setting the clock forward by one hour from 2:00 to 03:00. Central European summer time always ends on the last Sun-day in October at 03:00 CEST by setting the clock back one hour from 3:00 to 2:00.
10.1 (6.3) InterfaceSet the parameters for the cmenu:
Settingsettings
0.1 (6.2) Clock the clock menu you can set the display format of time and date for the ISOMETER® o685:
0.1 (6.2.1) Timeased on the selected time format you can set the current time to display 24-hour or 12-our notation (am/pm).
0.1 (6.2.2) Format (time)elect the appropriate time format to be displayed:
0.1 (6.2.3) Summer timeummer time can be considered in the following settings:
•12 h 12-hour notation am/pm
•24 h 24-hour notation
•off No automatic change between summer time and standard time.
•DST Daylight Saving TimeAutomatic change between summer and standard time according to North American regulation.North American summer time begins on each second Sunday in March at 02:00 local time by setting the clock forward by one hour from 2:00 to 03:00 local time. Summer time always ends the first Sun-day in October at 03:00 local time by setting the clock back one hour from 3:00 to 2:00.
•CEST Central European Summer TimeAutomatic change between summer time and standard time accord-
10.1 (6.2.4) DateBased on the selected date
10.1 (6.2.5) Format (daSelect the appropriate date
10.1 (6.2.6) NTPSelect if you would like to syNTP server in order to use th
10.1 (6.2.7) NTP serverSet the IP address of the NT
10.1 (6.2.8) UTCSet the time according to Utime (MEZ) and +2 for summ
When set tois only don
•dd.mm.yy d
•mm-dd-yy m
•on S
•off S
S
iso685-D-P_D00170_03_M_XXEN/07.20176
1Spth
1SE
1SWthmre
1S
1S
10.1 (6.3.2.4) Std. GWIfstco
1IfCo
nistrator in case you have questions about the configuration
munication with other devices via BCOM.r to “BCOM” on page 65.
amenetwork in which the devices are located. In order to guaran- to communicate via BCOM, all devices must have the same
dress of the network in which the devices are located. The de- subsystems with the same or different subsystem addresses. he ISOnet functions, the devices must have the same subsys-
dressh device must have a different address to distinguish it from nsure correct communication.
s between 100 ms…10 s.es the maximum permissible time for a device to respond.
ut time in the ISOnet, the fault message "Failure address" is
bscription92 min.
rvals at which the ISOMETER® sends messages to e.g. a gateway. tion alarms or substantial value changes) are always sent imme-
TCPion with other devices via Modbus TCP.
refer to “Modbus TCP” on page 65.
3
a standard gateway is used, enter the IP address here. Ensure that the IP address of the andard gateway suits the subnet mask, so that the ISOnet function can operate rrectly.
0.1 (6.3.2.5) DNS server a DNS server is used, enter the server's IP address.ontact your network administrator in case you have questions about the configuration f the DNS server.
This time defines the inteSevere alarms (e.g. insuladiately.
10.1 (6.3.4) ModbusSettings for communicatFor further information,
Settingsettings
0.1 (6.3.1) Write accesset whether the device can be parameterised externally via Modbus or web server. Dis-laying and reading out data via Modbus and web server is always possible, regardless of is setting.
0.1 (6.3.2) Ethernetet the parameters for communication with other devices via the Ethernet interface. The thernet interface can be used for communication with Modbus, web server and BCOM.
0.1 (6.3.2.1) DHCPelect whether you want to use automatic address assignment via your DHCP server. hen the automatic IP address assignment is activated, the IP address, subnet mask and e standard gateway are assigned automatically. When the automatic IP address assign-ent is deactivated, you have to make these settings manually in the menu. The IP add-ss can be viewed in the “Info“ menu (see “Info” on page 64).
0.1 (6.3.2.2) IPet the appropriate IP address for the ISOMETER®.
0.1 (6.3.2.3) SNet the appropriate subnet mask.
•Allow Allow external parameter setting.
•Deny Refuse external parameter setting.
•on Activate automatic IP address assignment.
•off Deactivate automatic IP address assignment.
10.1 (6.3.2.6) DomainEnter the domain.Contact your network admiof the domain.
10.1 (6.3.3) BCOMSet the parameters for comFor further information, refe
10.1 (6.3.3.1) System nSet the system name of the tee that all devices are ablesystem name.
10.1 (6.3.3.2) SubsystemConfigure the subsystem advices can communicate withEXCEPTION: In order to use ttem address.
10.1 (6.3.3.3) Device adAssign a device address. Eacanother in the system and e
10.1 (6.3.3.4) TimeoutSet the timeout for messageThis time specification definWhen exceeding the timeoshown.
10.1 (6.3.3.5) TTL for suSet a time between 1 s…10
S
iso685-D-P_D00170_03_M_XXEN/07.20176
1C
1SF
1S
1A
1AIfd
1Um
1E
1D
ng you can open the ISOMETER®'s commissioning wizard again.
vice settings can be saved or device settings already saved
e accessed by Bender Service staff.
ttings can be viewed in the Info menu. Navigate through the and buttons:
e ISOMETER® saves your device settings.
e ISOMETER® restores your initial device settings.
vice name, serial number, article number
ftware version measurement technique, ftware version HMI
lected profile, selected system type
cating current injector (PGH), locating current, ulation fault location mode
e, date, summer time
address, DHCP status, MAC address
address of the device
4
•on Password query active
•off Password query inactive
•BS bus BS
Settingsettings
0.1 (6.3.4.1) Port 502hoose whether Modbus TCP should be used:
0.1 (6.3.5) BS buset the parameters for communication with other devices via the Bender sensor bus.or further information, refer to “BS bus” on page 69.
0.1 (6.3.5.1) Addresselect an address between 1 and 90 for the Bender sensor bus.
0.1 (6.4) Displaydjust the display brightness for the ISOMETER® in the display menu:
0.1 (6.4.1) Brightnessdjust the display brightness between 0 % and 100 % in steps of 10. no button is pressed on the display for 15 minutes, the brightness of the display is re-uced. If now a button is pressed, the normal brightness is restored.
0.1 (6.5) Passwordse the password function to protect the device parameters against unauthorised adjust-ent. The default password is 0000.
0.1 (6.5.1) Passwordnter an individual four-digit password.
0.1 (6.5.2) Statusecide if the password query should be used:
•on Modbus TCP can be used for communication with other devices.
•off Modbus TCP cannot be used for communication with other devices.
10.1 (6.6) CommissioniIn the commissioning menu
10.1 (6.7) Data backupIn the data backup menu decan be restored.
10.1 (6.8) ServiceThe service menu can only b
10.1 (7.0) InfoThe ISOMETER®'s current sedifferent views using the
•Save Th
•Restore Th
•Device De
•Software Soso
•Measurement-technique
Se
•EDS LoIns
•Clock Tim
•Ethernet IP
iso685-D-P_D00170_03_M_XXEN/07.2017
1
1TB
1BAbF
a
1M
ADm Tinb
rated web server which displays ISOMETER® data and data of EDS) comfortably on every PC via a web browser. to read out measured values and parameterise the
llowing functions:
nformation (e.g. device type, software version, etc.)
device settings.
essages.
bus information of the individual parameters.
rfaces in use.
ent measured values.
resentation of the insulation resistance (isoGraph).
lisation without any programming.
ter setting of the device and the connected EDS.
edition options of device and measuring channel texts.
ific events for fast support by Bender Service
65
A maximum of 5 TCP/IP connections can be used simultaneously.
In order to be able to parameterise the device externally via Modbus, themenu item "Allow" must have been set in the "Write access" menu (see“Write access” on page 63).
Device communication1. Device communication
1.1 Ethernet interfacehe Ethernet interface can be used for communication with Modbus, web server and COM.
1.2 BCOMCOM is intended for communication between Bender devices via Ethernet.ll devices that communicate via BCOM must have the same system name. Devices cane organised in subsystems. Each device requires an individual device address. or more information regarding BCOM, refer to the BCOM manual (D00256)
t http://www.bender.de/manuals.
1.3 Modbus TCP odbus is an international widely used protocol for data transfer between devices.
ll measured values, messages and parameters are stored in virtual register addresses. ata can be read out with a read command on the register address. With a write com-and, data can be written into a register address.he register addresses of the individual measured values und parameters can be found the manual "iso685-D Annex A" with the title "ISOMETER® iso685 device family - Mod-
us settings" at http://www.bender.de/manuals.
When address 0 has been set for communication via BCOM the device canbe accessed via the network (e.g. for parameter setting, etc.) but it cannotcommunicate with other devices.
11.4 Web serverThe ISOMETER® has an integany associated devices (e.g.The web server can be usedISOMETER®s and the EDS.
The web server offers the fo
• Visualisation
• Indication of device i
• Indication of current
• Indication of alarm m
• Indication of the Mod
• Indication of the inte
• Overview of the curr
• Detailed graphic rep
• Fast and simple visua
• Parameter setting
• Easy and fast parame
• Easy assignment and
• Maintenance
• Data storage of spec
D
iso685-D-P_D00170_03_M_XXEN/07.20176
. irst level)
ice menu (first level)
tion of general device information.
tion of an overview of alarm values and measured values.tion of the settings. Settings can be changed here.
tion of alarm messages.
te and deactivate the indication of the Modbus information by ing or deselecting the selection box for the question "Display addi-Modbus information for each parameter?".
1
2
3
4
6
Device communicationevice communication
A maximum of 5 TCP/IP connections can be used simultaneously.
Only one device may access the web server at the same time. If several de-vices try to access the web server it may result in timeouts.
The write access is deactivated by default in the device menu (= Deny). Tobe able to set parameters via the web server the write access must first beactivated in the device menu (= Allow) (see “Write access” on page 63).
Use the web server preferably with the following web browsers: Google Chrome, Mozilla Firefox or Internet Explorer.
If you deactivate EDS channels via the web server, no settings can bemade simultaneously on the EDS channels. The settings of deactivatedchannels cannot be changed.
Web server device menu (f
Legend for web server dev
1 START Indica
2 DEVICEIndicaIndica
3 ALARMS Indica
4PARAMETER ADDRESSES
Activaselecttional
D
iso685-D-P_D00170_03_M_XXEN/07.20176
W
10
evice communication
7
eb server user interface
5
6 9
78
D
iso685-D-P_D00170_03_M_XXEN/07.20176
L
8
Device communicationevice communication
egend for user interface
5
Main menu of the web server (first level)• START (1)• DEVICE (2)• ALARMS (3)• PARAMETER ADDRESSES (4)Refer to “Web server device menu (first level)” on page 66.
6 MenuISOMETER® and EDS settings.Adjust device settings here.
7 Info
• Indication of device information regarding software, measurement technique, Ethernet and BS bus address.
• Indication of Modbus information for the individual parameters.To be able to see this information, the selection box at PARAMETER ADDRESSES (4) for the question "Display additional Modbus informa-tion for each parameter?" must be activated.
8System OK/alarms
Indication of the system status "System OK" (green button) and "Alarms" (red button).If there are pending alarms, click on the red button or go to menu point "ALARMS" (3) to obtain further information.
9Alarm/meas.values
Overview of alarm values and measured values.
10 i symbol Click on the "i" symbol on the right side to obtain further information regarding measured values.
D
iso685-D-P_D00170_03_M_XXEN/07.20176
1TsoBtr(d
MThe BS bus works according to the master-slave principle. This means that the measuring dreteuto
AAwu
es tricts the cable length to 1200 m and requires a daisy chain devices on the BS bus is only limited by the BS bus master. ables for bus cabling. For example, cable type J-Y(St)Y ield must have a single-ended connection to earth. The BS oth ends with terminating resistors (120 Ω, 0.25 W). The ter-
ected in parallel to the terminals A and B. Some devices fea- resistors and can be activated or deactivated via the "R"
or the BS bus is a double-terminated bus topology. The length to 1 m. These branch lines do not have to be terminated.
ng resistor activated via switch on device (ON) or external terminat-r between terminals A and B
2 Slave Terminating resistor deactivated via switch on device (OFF)
ng resistor activated via switch on device (ON) or external terminat-r between terminals A and B
rst and last device in one line may be terminated. Therefore,evices.
2
2
2
2 2
2 2
2
3
9
evice operates as the MASTER, while all sensor devices operate as SLAVES. The master is sponsible for the communication that is necessary for the measuring function. The mas-r also provides the required bus bias voltage for the operation of the BS bus. The meas-
ring device on the BS bus is the master and has address 1. All sensor devices connected the BS bus require unique addresses.
ddresses and address ranges on the BS busddress 1 is assigned to the master. All sensor devices receive unique addresses starting ith address 2, assigned in consecutive order without gaps. In the event of a device fail-re, a maximum gap of 5 addresses is permissible.
3 SlaveTerminatiing resisto
Only the ficheck all d
CAUTION
Device communicationevice communication
1.5 BS bushe BS bus is used to extend Bender measuring devices (e.g. ISOMETER®) with Bender sen-
r devices (e.g. EDS). It is an RS-485 interface with a specially developed protocol for ender devices. On the BS bus, the transmission of alarm messages takes priority over the ansmission of all other messages. For further information, refer to the BS bus manual ocument number: D00278) at www.bender.de/manuals.
aster-slave principle
When connecting more than ten EDS44…-L to the BS bus, the wiring mustbe shockproof.
When using interface converters, a galvanic separation is required.
The compatibility of the BS bus and the BMS bus is restricted!
An ISOMETER® can administer a maximum of 255 EDS channels. There-fore, if an EDS has 12 channels, a maximum of 21 EDS devices can be con-nected via BS bus and BB bus (max. 2).
CAUTION
CAUTION
RS-485 specifications/cablThe RS-485 specification resconnection. The number ofUse twisted pair, shielded cn x 2 x 0.8 is suitable. The shbus must be terminated at bminating resistors are connture integrated terminatingbutton.
Cable routing The optimum cable routing fof the branch line is limited
Bus topology examples:
Termination
1 MasterTerminatiing resisto
2
2
23 2
3
iso685-D-P_D00170_03_M_XXEN/07.2017
1
1AsucaFre
1
CcFthto
ST(s(sFtoF
1TF
pping the insulation fault location can be started and stopped via different interfaces:
e insulation fault location, which runs continuously. If the uously, it measures until it is manually stopped via the short- elements and device buttons” on page 19).
rding start and stop conditions of the insulation fault loca-de” on page 54.
70
Insulation fault location2. Insulation fault location
2.1 General descriptionn additional function of the ISOMETER® in combination with the EDS is the selective in-lation fault location. The insulation faults detected in the IT system by the ISOMETER® n be located by means of an EDS and a measuring current transformer.
or further information regarding the function principle of the insulation fault location, fer to 3.4 “Insulation fault location” on page 14.
2.2 Required settings for insulation fault location
onnecting and commissioning the system consisting of ISOMETER® and EDS orrectly. or further information regarding the connection of the EDS, refer to 6.11 “Connecting e EDS to the ISOMETER®” from page 27, at “Commissioning flow chart” on page 33 and the corresponding manual of the EDS.
etting locating current and EDS mode.hese settings can be made either during initial commissioning ee 7.2 “Initial commissioning” from page 34) or in the device menu of the ISOMETER® ee 10.1 (2.0) “EDS (insulation fault location)” from page 53).or further information regarding the locating current for insulation fault location, refer 10.1 (2.1.1) “Current” on page 53.
or further information regarding EDS modes, refer to 10.1 (2.1.2) “Mode” on page 54.
2.3 Indication on the displayhe active insulation fault location is indicated on the display of the ISOMETER®.or further information, refer to 8.7 “Initial measurement” from page 40.
12.4 Starting and stoThe insulation fault location
• Shortcut button "EDS" Manually starts/stops thdevice is started contincut button (see “Display
• Device menu
• Modbus
• Web server
• Digital input
For further information regation, refer to 10.1 (2.1.2) “Mo
iso685-D-P_D00170_03_M_XXEN/07.2017
d IT systems1
1WnITu
IfcuITin
1
OMETER® can be isolated from the IT system and the measur-ated. Therefore, the function of the digital input in use has to
his function is selected, the connectors L1/+, L2, L3/- are de- isolating switches, the measuring function stops and the fol- the display: "Device inactive. Device separated". set when the cause of the fault has been eliminated (Reset
er selected, first the connection to the IT system is restored new measuring cycle for the insulation monitoring starts. disconnect the second ISOMETER® selectively in coupled IT tact of the coupling switch.
IT-System 2
Adr.3Adr.3
Adr.1
PE
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
71
Special functions for couple3. Special functions for coupled IT systems
3.1 Particularities when monitoring coupled IT systemshen using ISOMETER®s in IT systems, make sure that only one active ISOMETER® is con-
ected in each interconnected system. If several ISOMETER®s are to be connected to the system, ensure that only one ISOMETER® is active in the IT system via system isolation sing the digital input or Ethernet (ISOnet function).
IT systems are interconnected via coupling switches, make sure that ISOMETER®s not rrently used are disconnected from the IT system and deactivated.
systems coupled via diodes or capacitances may also influence the insulation monitor-g process so that a central control of the different ISOMETER®s is required.
3.2 System isolation via digital input with two coupled systems
In order to deactivate the ISOMETER® via one of the digital inputs, the cou-pling switch must have a free contact.
If IT systems are interconnected via coupling switches, one ISOMETER® al-ways remains inactive. Insulation fault location in the IT system of the in-active ISOMETER® is only possible when the associated EDS are in automode (see “Setting EDS mode” on page 34). In addition, insulation faultlocation with a portable EDS must be activated for the active ISOMETER®(setting: Use portable EDS = on, see “Using a portable EDS” on page 54).
Via the X1 connector, the ISing functions can be deactivbe set to "Device inactive". If the digital input used for tactivated via internal systemlowing message appears onStored fault messages are refunction). If the digital input is no longand afterwards, an entirely This function can be used tosystems via the auxiliary con
IT-System 1
PE
Adr.1
d IT systemsS
iso685-D-P_D00170_03_M_XXEN/07.20177
1Tin
Afterwards, it participates again in the measuring interconnection.
number of devices in an ISOnet interconnection: 20 devices
IT-System 2
PE
Adr.3
OM dr.1
BCOM Adr.2
BS-Bus
Adr.1
Adr.3
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
2
The IP address of the standard gateway must suit the subnet mask, so thatthe ISOnet function can operate correctly.
Special functions for couplepecial functions for coupled IT systems
3.3 System isolation via ISOnethe ISOnet function ensures via an Ethernet connection that only one ISOMETER® of the terconnection is active when several ISOMETER®s are connected to an IT system.
For several ISOMETER®s to be able to measure in the same ISOnet inter-connection, the settings for the BCOM system name and the BCOM sub-system have to be the same. Only the device address has to be different. Ifthis is not taken into account, the ISOnet function will not work.
If the ISOnet function is deactivated in an ISOMETER® in an ISOnet inter-connection, it will measure continuously and will not forward measuringcommands to the next device in the interconnection.
In comparison to a solution with coupling switches and function input,the response time will be extended because the measurement in the IT sys-tem is not carried out continuously.
The addresses of the ISOMETER®s in the ISOnet interconnection can be se-lected at will. The addresses do not have to be subsequent but they haveto differ from each other.
If in addition to the ISOnet interconnection the digital inputs are wiredand a device is deactivated via a digital input, the device will forward themeasuring authorisation until the signal at the digital input disappears.
CAUTION
Maximum
IT-System 1
PE
Adr.1
BCA
BS-Bus
d IT systemsS
iso685-D-P_D00170_03_M_XXEN/07.20177
FIShAgco
Acointhnrait
Iffa
Ifh
IT-System 2
IT-System 3
PE
PE
EthernetSWITCH
COM Adr.1
BCOM Adr.2
BCOM Adr.3
COM dr.4
BS-Bus
Adr.1
Adr.3Adr.3
Adr.3 BS-Bus
Adr.1
Adr.3
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
I L I nISOSCAN®
EDS440
76 5
3
4
2
01
5
34 2
01
9
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
121110987
1 2 3 4 5 6
I∆L
I∆n
3
Special functions for couplepecial functions for coupled IT systems
or the ISOnet function, the following settings are made in the menu: Alarm settings -> ONet -> ISONet = BCOM. The ISOnet function of all ISOMETER®s existing in the system as to be activated and the number of devices has to be determined. lso the parameters of the Ethernet (DHCP on or IP address, subnet mask and default ateway) and BCOM have to be set so that the devices in the ISOnet interconnection can
mmunicate with each other.
fter starting the system, the devices initialise. The initialisation phase ends when the nfigured number of devices has been reached. Then, the device starts with a measur-g cycle at the lowest address. When an ISOMETER® has finished one measuring cycle, e authorisation for insulation measurement is forwarded to the ISOMETER® with the
ext higher address. While one ISOMETER® is measuring, all other ISOMETER®s are sepa-ted from the system via internal system isolation switches. By limiting to one subsystem
is possible to have several ISOnet interconnections running in one system.
a single device fails, the remaining ISOMETER®s continue the ISOnet operation. For the ilure of one device, two scenarios are possible:
• A device fails during the measuring procedure.After timeout, another device takes over the measuring function. In this way, all devices monitor each other.
• The device fails in the inactive mode.When forwarding the measuring authorisation, the device is skipped and the next device carries out the measurement.
a device that has failed before returns, it is taken into the interconnection again and will ave its turn during the next run.
IT-System 1
IT-System 4
PE
PE
B
BA
BS-Bus
Adr.1
BS-Bus
Adr.1
iso685-D-P_D00170_03_M_XXEN/07.2017
quency changes.r all systems primarily with constant mains frequencies and ing inverters and dynamic frequency control, select Inverter
easurement voltage to ±10 V in control systems with lower ce the impact by the ISOMETER® on sensitive switching ele-
of a very fast measuring time, e.g. as required for generator file can be used to support fast fault location in an IT sys-ble for AC systems containing DC components.
acitances, e.g. ship applications, the impact of leakage sult can be significantly reduced by selecting this profile.
h dynamic frequency control by inverters in the range 10 to easurement with respect to the measuring time and quality.
w-frequency control in the range of up to 1…460 Hz and ng extraneous DC voltages due to dynamic load conditions tion monitoring can be optimised using this profile.
nt customer-specific measurement settings. If no settings the profile has the same parameters and technical specifi-.
74
14. Device profilesAdjustment to different applications can be carried out very easily by selecting a device profile.
Response times see “Diagrams” on page 75.
Nominal system voltage Mains frequency
System leakage capacitance
Measuring voltage Description
Power circuits AC 0…690 V/DC 0…1000 V
15…460 Hz 0…150 µF ±50 V
Main circuits without dynamic freThe universal profile is suitable foextraneous DC voltages. When us> 10 Hz or Inverter < 10 Hz.
Control circuits AC 0…230 V/DC 0…230 V
15…460 Hz 0…150 µF ±10 VThis profile is used to reduce the mnominal voltages in order to reduments.
Generator AC 0…690 V 50…60 Hz 0…5 µF ±50 VThis profile allows the realisation monitoring. Furthermore, this protem. The generator profile is suita
High capacitance AC 0…690 V/DC 0…1000 V
15…460 Hz 0…1000 µF ±50 VFor systems with high leakage capcapacitances on the measuring re
Inverter > 10 Hz AC 0…690 V/DC 0…1000 V
10…460 Hz 0…20 µF ±50 VThis profile is used for systems wit460 Hz in order to optimise the m
Inverter < 10 Hz AC 0…690 V/DC 0…1000 V
1…460 Hz 0…20 µF ±50 VFor systems involving extremely lovery low and continuously changiin an IT system, continuous insula
Customized – – – –Allows Bender Service to implemeare made by Bender service, thencation as the Powercircuits profile
iso685-D-P_D00170_03_M_XXEN/07.2017
7515. Diagrams
15.1 Response time profile power circuits
15.2 Response time profile control circuits
Ce ≤ 150 µF
Ce ≤ 50 µF
Ce ≤ 20 µF
Ce ≤ 5 µF
Ce ≤ 1 µF
Response time as a function of the response value (Ran) and system leakage capacitance (Ce) according to IEC 61557-8 (Un = AC 690 V, fn = 50 Hz)
1
10
100
100001000100101
Resp
onse
tim
e [s
ec]
Response value Ran [kΩ]
Ce ≤ 150 µF
Ce ≤ 50 µF
Ce ≤ 20 µF
Ce ≤ 5 µF
Ce ≤ 1 µF
Response time as a function of the response value (Ran) and system leakage capacitance (Ce) according to IEC 61557-8 (Un = AC 230 V, fn = 50 Hz)
1
10
100
100001000100101
Resp
onse
tim
e [s
ec]
Response value Ran [kΩ]
D
iso685-D-P_D00170_03_M_XXEN/07.20177
1
1
iagrams
6
5.3 Response time profile generator
5.4 Response time profile high capacitance
Ce ≤ 5 µF
Ce ≤ 1 µF
Response time as a function of the response value (Ran) and system leakage capacitance (Ce) according to IEC 61557-8 (Un = AC 690 V, fn = 50 Hz)
0,1
1
10
100001000100101
Resp
onse
tim
e [s
ec]
Response value Ran [kΩ]
Ce ≤ 1000 µF
Ce ≤ 500 µF
Ce ≤ 150 µF
Ce ≤ 50 µF
Ce ≤ 20 µF
Ce ≤ 5 µF
Ce ≤ 1 µF
Response time as a function of the response value (Ran) and system leakage capacitance (Ce) according to IEC 61557-8 (Un = AC 690 V, fn = 50 Hz)
10
100
1000
100001000100101
Resp
onse
tim
e [s
ec]
Response value Ran [kΩ]
D
iso685-D-P_D00170_03_M_XXEN/07.20177
1
1
iagrams
7
5.5 Response time profile inverter > 10 Hz
5.6 Response time profile inverter < 10 Hz
Ce ≤ 20 µF
Ce ≤ 5 µF
Ce ≤ 1 µF
Response time as a function of the response value (Ran) and system leakage capacitance (Ce) according to IEC 61557-8 (Un = AC 690 V, fn = 50 Hz)
1
10
100
100001000100101
Resp
onse
tim
e [s
ec]
Response value Ran [kΩ]
1
10
100
10 100 500 1000 5000 10000
Resp
onse
tim
e [s
ec]
Response value Ran [KΩ]
Response time as a function of the response value (Ran) and system leakagecapacitance (Ce) according to IEC 61557-8 (Un = AC 690 V, fn = 50 Hz)
Ce 20 μF
Ce 5 μF
Ce 1μF
D
iso685-D-P_D00170_03_M_XXEN/07.20177
1
1
iagrams
8
5.7 Response time DC alarm
5.8 Relative uncertainty
0,1
1
10
100
1000
0,1 1 10 100
system leakage capacitance [µF]
resp
onse
tim
e [s
ec]
Typical response time for DC alarm for RF =100KΩ depending onsystem profile and system leakage capacitance
Power circuit
Control circuit
High capacitance
Inverter >10Hz
Inverter <10Hz
Generator
Ce
0.1 1 10 100 1000 10000 100000
Relative uncertainty as a function of the response value (Ran) and system leakage capacitance (Ce) according to IEC 61557-8 (Un = AC 690 V, fn = 50 Hz)
0 %
90 %
80 %
70 %
60 %
50 %
40 %
30 %
20 %
10 %
100 %
Response value Ran [kΩ]
Ope
rati
ng u
ncer
tain
ty [%
]
Ce ≤ 1000 µF
Ce ≤ 1 µF
iso685-D-P_D00170_03_M_XXEN/07.2017
Reference LED indicators
stem and, if nec-“Functional descrip-tion” on page 13
ALARM 1 lights
nitored “Functional descrip-tion” on page 13
ALARM 2 lights
the IT system “Connection” on page 21 & menu setting“System type” on page 47
ALARM 1 + ALARM 2 flash alternately
E) “Connection” on page 21
ALARM 1 + ALARM 2 flash in common mode
SERVICE lights up
quency in the
e characteristics
“Device profiles” on page 74 &“Profile” on page 47
evice
“DHCP” on page 63
“Clock” on page 62
SERVICE lights up
“System isolation via ISOnet” on page 72
79
16. Alarm messages
16.1 Alarm messages of the ISOMETER®
Alarm message Description Measures
Insulation faultAn insulation fault exists. The insulation resistance falls below the response value Ran1.
• Observe insulation resistance in the monitored syessary, eliminate fault.
• Reset fault message by pressing the reset button
Insulation faultAn insulation fault exists. The insulation resistance falls below the response value Ran2.
• If necessary, locate insulation fault using the EDS• Eliminate insulation fault in the system being mo• Reset fault message by pressing the reset button
Check L1-L2-L3 for cor-rect connection!
No low-resistance connection between the line con-ductors
• Check the wiring of terminals L1/+, L2 and L3/- to• Press the test button• Check mains voltage• Check fuses• Check set system type
Check E-KE connections for interruptions!
No low-resistance connection between terminals E and KE to earth (PE)
• Check the wiring of terminals E and KE to earth (P• Press the test button
Service mode active! The device is in maintenance condition • Contact Bender Service
The profile does not suit the application!
Wrong profile selected for this application• Check measured system capacitance or mains fre
Info menu• Select another profile taking into consideration th
No DHCP server found! Connection problem at the Ethernet interface• Check cable connection at the Ethernet interface• Check the DHCP server's availability• Check the DHCP's interface configuration in the d
Check time and date! Time and date have not been set yet• Set local time and date
(in case of voltage failure a buffer for three days)
Load on X1 too high! Sum of the external loads on X1 is too high• Check load at X1.+, X1.Q1 and X1.Q2• Check ambient temperature
Device error x.xx Internal device fault• Press the TEST button• Switch the supply voltage off and on• Contact Bender Service
Num.ISOnet devicesThe configured number of devices does not match the number of devices that are actually included in the ISOnet interconnection.
• Check settings• Check Ethernet connection
A
iso685-D-P_D00170_03_M_XXEN/07.20178
“System isolation via ISOnet” on page 72
“System isolation via ISOnet” on page 72
“BS bus” on page 69 and “Scanning channels” on page 54
nESET button, the
ervice.“Current” on page 53
ntppear or occurs
“Setting EDS cur-rent” on page 35
omponents.“DC alarm” on page 46
Reference LED indicators
larm messages
0
Failure addressOne device of the ISOnet interconnection is not accessible
• Check Ethernet connection• Check device function
Disturbance ISOnet
General fault at ISOnet, which is not covered by "Num.ISOnet devices" and "Failure address". For exam-ple, sending messages can fail or another device can-not process a message.
• Check Ethernet connection• Check device function• Switch OFF and switch ON the power supply
Start search for EDS channels now?
A device on the BS bus has failed or cannot be detected. The ISOMETER® searches automatically for channels.
• Test wiring of terminals A, B to X1 of all devices• Start search for EDS channels now
Malfunction overcurrent
The locating current for the insulation fault location is higher than the set limit value. The insulation fault loca-tion is aborted and the insulation resistance measure-ment is continued even if an insulation fault is still active. The insulation fault location is only restarted when the alarm message has been reset and there still exists an insulation fault.
• Reset fault message by pressing the RESET butto• If the fault does not disappear after pressing the R
device is defective. In this case, contact Bender S
Overtemperature PGHThe locating current injector in the ISOMETER® has heated up. The ISOMETER® stops the locating current injector until it cools down and then restarts it.
• If necessary, reduce the maximum locating curre• Contact Bender Service if the fault does not disa
more frequently
DC offset voltage There is a DC offset voltage in the system. • Check insulation fault and eliminate fault of DC c
Undervoltage Operating outside the specified supply voltage range • Check supply voltage
Overvoltage Operating outside the specified supply voltage range • Check supply voltage
Alarm message Description Measures
A
iso685-D-P_D00170_03_M_XXEN/07.20178
1
A
Reference LED indicators
nate it.
ers “Scanning channels” on page 54 &“Activating chan-nels” on page 55
t and eliminate
larm messages
1
6.2 Alarm messages of the EDS
dditionally, read the operating manual of the EDS.
Alarm message Description Measures
Insulation fault location disturbed!
Interferences during insulation fault locationPossible causes:• Low-frequency residual currents• External magnetic fields
• Identify interference sources and eliminate them
insulation fault x mA
If an insulation fault is located, the message Insulation fault 5 mA appears on the display. The level of the locat-ing current gives information regarding the faulty out-going circuit. The higher the locating current, the lower the insulation resistance on the detected channel.
• Determine cause of the insulation fault and elimi
Interference CT connec-tion
A measuring current transformer has not been con-nected correctly or does not work.
• Check wiring of the measuring current transform• Check device function• Start new search for EDS channels• Deactivate channel without CT
CT short circuit
Connection fault of CTsPossible causes:• Measuring current transformer defective• Power supply cable short-circuited
• Replace defective measuring current transformer• Check cables
Residual currentThe set response value of the residual current has beenexceeded on one channel.
• Determine cause of the exceeded residual currenfault.
iso685-D-P_D00170_03_M_XXEN/07.2017
1
P
R
R
R
DDFC
S
SP
T
S
D
D
M
F
D
MF
D
onN/C operationIns. alarm 1Connection faultoff
onN/C operationIns. alarm 2Device faultConnection fault
off
192.168.0.5255.255.255.0system-1-01
ISOnet off
auto10 mA
Value
82
Mode (Operating mode) Active highFunction Deactivate device
Digital outputs
Digital output 1
Function 1 Common alarm EDS
Function 2 offFunction 3 off
EDS
ModeCurrent
Factory settings7. Factory settings
arameter Value
esponse values/alarms
esponse value Ran1 (ALARM 1) 40 kΩ
esponse value Ran2 (ALARM 2) 10 kΩ
C alarm offC-offset voltage for DC alarm 65 V
ault memory offoupling monitoring on
ystem
ystem type 3ACrofile Power circuits
ime response
tart-up delay Tstart-up 0 s
igital inputs
igital input 1
ode (Operating mode) Active high
unction Test
igital input 2
ode (Operating mode) Active lowunction Reset
igital input 3
Switching elements
Relay 1
TestOperating modeFunction 1Function 2Function 3
Relay 2
TestOperating modeFunction 1Function 2Function 3
Interfaces
DHCP
IP addressNet maskBCOM addressDevice address BS bus
ISOnet
Parameter
iso685-D-P_D00170_03_M_XXEN/07.2017
1
1InDe
RaOvRa
Ra
PoPoPr
Vo
IC4 / IC5 ............................................................................................................................................................................... AC 2,2 kV
.......................................................................................................................... ≤ 12 W/45 VA
....................................................................................................................................... DC 24 V
...................................................................................................................... DC -20…+25 %
................................................................................................. AC 0…690 V; DC 0…1000 V
.................................................................................... AC/DC 0…600 V (for UL applications)
............................................................................................................................AC/DC +15 %
.......................................................................................................................... DC, 1…460 Hzge fn = 0.1…4 Hz .................................................................. U~ max = 50 V/Hz² *(1+ fn²)
...........................................................................................................................1 kΩ…10 MΩ
...........................................................................................................................1 kΩ…10 MΩ) ............................................................................profile dependent, ±15 %, at least ±1 kΩ.................................................................................................................... 25 %, at least 1 kΩ
= 10 kΩ) and Ce = 1 μF according to IEC 61557-8 ................................................................................................................................................ profile dependent, typ. 4 s (see diagrams).................................................................................profile dependent, typ. 2 s (see diagram).................................................................................................................................. 0…120 s
........................................................profile dependent, ±10 V, ±50 V (see profile overview)
....................................................................................................................................≤ 403 μA
....................................................................................................................................≥ 124 kΩ
....................................................................................................................................≤ 1200 VCe........................................................................................... profile dependent, 0…1000 μFtion (EDS):
........................................................................................................1/1.8/2.5/5/10/25/50 mA
Measuring range fn ................................................................................................................................................................ 10…460 Hz.........................................................................................................................±1 % ±0.1 Hz.........................................................................................................................AC 25…690 V........................................................................................... AC 25…690 V; DC 25…1000 V.......................................................................................................................... AC/DC > 10 V..............................................................................................................................±5 % ±5 V.............................................................................................................................0…1000 μF........................................................................................................................ ±10 % ±10 μF......................................................................................................................DC, 30…460 Hzf Ce ..........................................depending on the profile and coupling mode, typ. > 10 kΩ
83
Supply voltageSupply via A1/+, A2/-:Supply voltage range Us ...............................................................................................................................................AC/DC 24…240 VTolerance of Us..................................................................................................................................................................... -30…+15 %Maximum permissible input current of Us .................................................................................................................................... 650 mAFrequency range of Us ................................................................................................................................................. DC, 50…400 Hz 1)
Tolerance of the frequency range of Us................................................................................................................................. -5…+15 %Power consumption, DC................................................................................................................................................................ ≤ 12 WPower consumption, typically 50/60 Hz .......................................................................................................................... ≤ 12 W/21 VA
Tolerance measurement of fn....................Voltage range measurement of fn.............Measuring range Un ..................................Voltage range measurement of Un ...........Tolerance measurement of Un...................Measuring range Ce ...................................Tolerance measurement of Ce ...................Frequency range measurement of Ce........Min. insulation resistance measurement o
Technical data8. Technical data
8.1 Tabular datasulation coordination according to IEC 60664-1/IEC 60664-3finitions:
Measuring circuit (IC1)............................................................................................................................................. (L1/+, L2, L3/-)Supply circuit (IC2)................................................................................................................................................................... A1, A2Output circuit 1 (IC3)...........................................................................................................................................................11, 12, 14Output circuit 2 (IC4)...........................................................................................................................................................21, 22, 24Control circuit (IC5) .................................................................................................................................... (E, KE), (X1, ETH, X3, X4)
ted voltage....................................................................................................................................................................................1000 Vervoltage category ............................................................................................................................................................................... IIIted impulse voltage:
IC1 / (IC2-5) ................................................................................................................................................................................. 8 kVIC2 / (IC3-5) ................................................................................................................................................................................. 4 kVIC3 / (IC4-5) ................................................................................................................................................................................. 4 kVIC4 / IC5 ........................................................................................................................................................................................ 4 kV
ted insulation voltage:IC1 / (IC2-5) .............................................................................................................................................................................1000 VIC2 / (IC3-5) ...............................................................................................................................................................................250 VIC3 / (IC4-5) ...............................................................................................................................................................................250 VIC4 / IC5 ......................................................................................................................................................................................250 V
llution degree for accessible parts on the outside of the device housing (Un < 690 V)..................................................................... 3llution degree for accessible parts on the outside of the device housing (Un >690 < 1000 V)........................................................ 2otective separation (reinforced insulation) between:
IC1 / (IC2-5) ....................................................................................................................................Overvoltage category III, 1000 VIC2 / (IC3-5) ......................................................................................................................................Overvoltage category III, 300 VIC3 / (IC4-5) .......................................................................................................................................Overvoltage categoryIII, 300 VIC4 / IC5 .............................................................................................................................................Overvoltage category III, 300 V
ltage test (routine test) according to IEC 61010-1:IC2 / (IC3-5) ........................................................................................................................................................................ AC 2,2 kVIC3 / (IC4-5) ........................................................................................................................................................................ AC 2,2 kV
Power consumption, typically 400 Hz ...Supply via X1:Supply voltage Us.....................................Tolerance of Us .........................................
IT system being monitoredNominal system voltage range Un ...........................................................................Tolerance of Un.........................................Frequency range of Un .............................Max. AC voltage U~ in the frequency ran
Response valuesResponse value Ran1 (alarm 1) ................Response value Ran2 (alarm 2) ................Relative uncertainty (acc. to IEC 61557-8Hysteresis ..................................................
Time responseResponse time tan at RF = 0.5 x Ran (Ran ..................................................................Response time DC alarm at Ce = 1 μF.....Start-up delay Tstart-up.............................
Measuring circuitMeasuring voltage Um.............................Measuring current Im...............................Internal resistance Ri ,Zi ...........................Permissible extraneous DC voltage Ufg ...Permissible system leakage capacitance Measuring circuit for insulation fault locaLocating current IL ...................................
Measuring ranges
T
iso685-D-P_D00170_03_M_XXEN/07.20178
DInDi
LONPGSEALAL
InCaCaToToTo....
DNuOpFuVoTo
DNOpFu..
VoAnalogue Output (M+)NuOpFuCuVoTo
...............................................................................................web server/Modbus TCP/BCOM
....................................................................................................... 10/100 Mbit/s, autodetect
..................................................................................................................................... < 100/s
....................................................................................................................................≤ 100 m
........................................................................................................................................... RJ45
.......................................................................................................DHCP/manual 192.168.0.5
.......................................................................................................................... 255.255.255.0
................................................................................................................................system-1-0
..........................................................................................................communication interface
.......................................................................................................................................... ≤ 20
.................................................................................................................................RS-485/BS
............................................................................................................................... 9.6 kBaud/s
..................................................................................................................................≤ 1200 mnected to PE................................................................... recommended: J-Y(St)Y min. 2x0.8................................................................................................................. terminals X1.A, X1.Bd at the end of the transmission path..............................120 Ω, can be connected internally.......................................................................................................................................1…90
.............................................................................................................. 2 changeover contacts
.................................................................................................. N/C operation/N/O operations. alarm 1, Ins. alarm 2, connection fault, DC- alarm 4), DC+ alarm 4), symmetrical alarm,mon alarm, measurement complete, device inactive, DC offset alarm, common alarm EDSs. alarm 1, Ins. alarm 2, connection fault, DC- alarm 4), DC+ alarm 4), symmetrical alarm,mon alarm, measurement complete, device inactive, DC offset alarm, common alarm EDSg conditions, number of cycles.................................................................................... 10.000
................................................................................ AC-13 / AC-14 / DC-12 / DC-12 / DC-12Rated operational voltage .............................................................................................................. 230 V / 230 V / 24 V / 110 V / 220 V
................................................................................................... 5 A / 3 A / 1 A / 0.2 A / 0.1 A.......................................................................................................................................... 250 V.......................................................................................................................................... 160 V............................................................................................................ 1 mA at AC/DC ≥ 10 V
4
mber ...................................................................................................................................................................................................... 1erating mode................................................................................................................................ linear, midscale point 28 kΩ/120 kΩnctions ...........................................................................................................................................................insulation value, DC offsetrrent ........................................................................................0…20 mA (< 600 Ω), 4…20 mA (< 600 Ω), 0…400 μA (< 4 kΩ)ltage........................................................................................................................................ 0…10 V (> 1 kΩ), 2…10 V (> 1 kΩ)lerance .........................................................................................................................................................................................±20 %
Rated operational current ........................Rated insulation voltage ≤ 2000 m NN .Rated insulation voltage ≤ 3000 m NN .Minimum contact rating ..........................
Technical dataechnical data
isplaydication ....................................................................................................................... graphic display 127 x 127 pixels, 40 x 40 mm 2)
splay range measured value .........................................................................................................................................0.1 kΩ…20 MΩ
EDs (operation LED) ............................................................................................................................................................................greenH ON ............................................................................................................................................................................................. yellowRVICE ............................................................................................................................................................................................. yellowARM 1 ........................................................................................................................................................................................... yellowARM 2 ........................................................................................................................................................................................... yellow
-/Outputs (X1-Interface)ble length X1 (unshielded cable)............................................................................................................................................... ≤ 10 mble length X1 (shielded cable, shield connected to earth (PE) on one end, recommended: J-Y(St)Y min. 2x0,8) ............. ≤ 100 mtal max. supply output current via X1.+/X1.GND for each output..........................................................................................max. 1 Atal max. supply output current via A1/A2 on X1.............................................................................................................. max. 200 mAtal max. supply output current via A1/A2 on X1 between 16,8 V and 40 V ..........................................................................................................................................................................................................................ILmaxX1 = 10mA + 7mA/V * Us – n * PBB / 24V 3)
.......................................................................................................................................... (negative values are not allowed for ILmaxX1)igital Inputs (I1, I2, I3)
mber ...................................................................................................................................................................................................... 3erating mode, adjustable................................................................................................................................... active high, active lownctions ............................................................ off, test, reset, deactivate device, start initial measurement, insulation fault locationltage...........................................................................................................................................Low DC -3…5 V, High DC 11…32 Vlerance Voltage...........................................................................................................................................................................± 10 %
igital Outputs (Q1, Q2)Number ................................................................................................................................................................................................... 2erating mode, adjustable.................................................................................................................................................active, passivenctions ......................................... off, Ins. alarm 1, Ins. alarm 2, connection fault, DC- alarm 4), DC+ alarm 4), symmetrical alarm,
....................................device fault, common alarm, measurement complete, device inactive, DC offset alarm, common alarm EDSltage.............................................................................................................................passive DC 0…32 V, active DC 0/19.2…32 V
InterfacesField bus:Interface/protocol .....................................Data rate....................................................Max. amount Modbus requests ...............Cable length .............................................Connection ................................................IP address ..................................................Network mask...........................................BCOM address ...........................................Function ....................................................ISOnet:Number ISOnet devices ............................Sensor bus:Interface/protocol .....................................Data rate....................................................Cable length .............................................Cable: twisted pair, one end of shield conConnection ................................................Terminating resistor at the beginning anDevice address, BS bus .............................
Switching elementsNumber of switching elements................Operating mode........................................Contact 11-12-14 ........................... off, In...................................... device fault, comContact 21-22-24 ........................... off, In...................................... device fault, comElectrical endurance under rated operatinContact data acc. to IEC 60947-5-1:Utilisation category...................................
T
iso685-D-P_D00170_03_M_XXEN/07.20178
EEMAmOpTrLoClStTrLoClStTrLoAr
CCoScNoTiCoStrigfleMMMMPuNoCoStripping length............................................................................................................................................................................... 10 mmrigfleMPuNoCoStrig
e ..................................................................................................................... 0.25…1.5 mm²eve .............................................................................................................. 0.25…0.75 mm²
................................................................................................................continuous operation................................................display oriented, cooling slots must be ventilated vertically 6)
s .........................................................................................................................................IP40............................................................................................................................................IP20
................................................................................................................................... IEC 60715....................................................................................................... 3 x M4 with mounting clip........................................................................................................................... polycarbonate.............................................................................................................................................V-0.............................................................................................................................................. 64................................................................................................................... 108 x 93 x 110 mm..................................................................................................................................... < 510 g
rom the standard versionements .....................................................................................max. 3 A (for UL applications)
...........................................................................................................................-40…+70 °C......................................................................................... -40…+65 °C (for UL applications)............................................................................................................................-40…+85 °C...........................................................................................................................-40…+70 °Co IEC 60721:................................................................... 3K5 (condensation and formation of ice possible)cc. to IEC 60721:........................................................................................................................................... 3M7
ion of X1 must be insulated. Only permanently installed devices which at least have over- connected.ture range -25…+55 °C.
n = Number of BB bus devicese
environment, this product may cause radio interference. In this case, the user may be re-
t 0 ° (display-oriented, cooling slots must be ventilated vertically).°, the max. working temperature is reduced by 10 °C.°, the max. working temperature is reduced by 20 °C.
5
id/flexible .......................................................................................................................................................................0.2…2.5 mm²xible with ferrules, with/without plastic sleeve ..........................................................................................................0.25…2.5 mm²ultiple conductor, flexible with TWIN ferrule with plastic sleeve..................................................................................0.5…1.5 mm²sh-wire terminals X1:minal current................................................................................................................................................................................. ≤ 8 Anductor sizes.........................................................................................................................................................................AWG 24-16ripping length............................................................................................................................................................................... 10 mmid/flexible .......................................................................................................................................................................0.2…1.5 mm²
PBB [Watt] = Power of a BB bus devic4) For Un ≥ 50 V only.5) This is a class A product. In a domestic
quired to take corrective actions.6) Recommendation: Devices mounted a
For devices mounted at an angle of 45For devices mounted at an angle of 90
Technical dataechnical data
nvironment/EMCC ................................................................................................................................................................................. IEC 61326-2-4 5)
bient temperatures:erating temperature........................................................................................................................................................ -25…+55 °C
ansport.............................................................................................................................................................................. -40…+85 °Cng-term storage .............................................................................................................................................................. -40…+70 °Cassification of climatic conditions acc. to IEC 60721:ationary use (IEC 60721-3-3) ....................................................................................3K5 (except condensation and formation of ice)ansport (IEC 60721-3-2) .................................................................................................................................................................. 2K3 ng-term storage (IEC 60721-3-1) ................................................................................................................................................... 1K4 assification of mechanical conditions acc. to IEC 60721:ationary use (IEC 60721-3-3) ...........................................................................................................................................................3M4ansport (IEC 60721-3-2)...................................................................................................................................................................2M2ng-term storage (IEC 60721-3-1) ...................................................................................................................................................1M3ea of application ............................................................................................................................................................... ≤ 3000 m NN
onnectionnnection type...................................................................................................pluggable screw-type terminal or push-wire terminalrew-type terminals:minal current............................................................................................................................................................................... ≤ 10 A
ghtening torque.......................................................................................................................................... 0.5…0.6 Nm (5…7 lb-in)nductor sizes.........................................................................................................................................................................AWG 24-12ripping length................................................................................................................................................................................. 7 mmid/flexible .......................................................................................................................................................................0.2…2.5 mm²xible with ferrules, with/without plastic sleeve ..........................................................................................................0.25…2.5 mm²ultiple conductor, rigid.......................................................................................................................................................0.2…1 mm²ultiple conductor, flexible ...............................................................................................................................................0.2…1.5 mm²ultiple conductor, flexible with ferrule without plastic sleeve .......................................................................................0.25…1 mm²ultiple conductor, flexible with TWIN ferrule with plastic sleeve..................................................................................0.5…1.5 mm²sh-wire terminals:minal current............................................................................................................................................................................... ≤ 10 Anductor sizes.........................................................................................................................................................................AWG 24-12
flexible with ferrule without plastic sleevflexible with TWIN ferrule with plastic sle
OtherOperating mode........................................Mounting (0°)..........................................Degree of protection internal componentDegree of protection terminals ................DIN rail mounting acc. to.........................Screw fixing...............................................Enclosure material ....................................Flammability class ....................................ANSI code .................................................Dimensions (W x H x D)............................Weight ......................................................
Option "W" data different fRated operational current of switching elAmbient temperatures:Operating temperature...............................................................................................Transport ..................................................Long-term storage....................................Classification of climatic conditions acc. tStationary use (IEC 60721-3-3) ..............Classification of mechanical conditions aStationary use (IEC 60721-3-3) .............
1) At a frequency > 200 Hz, the connectvoltage category CAT2 (300V) may be
2) Indication limited outside the tempera3) Us [Volt] = supply voltage ISOMETER®
T
iso685-D-P_D00170_03_M_XXEN/07.20178
1DTm
1T
s
and vibration resistance 3K5, 3M7; -40…+70 °C
pply voltage US Art. No.
24…240 V; 50…400 HzC 24…240 V
B91067030
24…240 V; 50…400 HzC 24…240 V
B91067030W
24…240 V; 50…400 HzC 24…240 V
B91067230
24…240 V; 50…400 HzC 24…240 V
B91067230W
voltage US* Response value Art. no.
4…240V 2…10mA B 9108 0201
4…240V 2…10mA B 9108 0201W
4…240V 2…10mA B 9108 0202
4…240V 2…10mA B 9108 0202W
4…240V 0,2…1mA B 9108 0204
4…240V 0,2…1mA B 9108 0204W
EDS441-L-4 AC/DC 24…240V 0,2…1mA B 9108 0205
4…240V 0,2…1mA B 9108 0205W
4…240V 0,2…1mA B 9108 0207
4…240V 0,2…1mA B 9108 0207W
6
* Absolute values
EDS441W-L-4 AC/DC 2
EDS441-LAB-4 AC/DC 2
EDS441W-LAB-4 AC/DC 2
Technical dataechnical data
8.2 Option Wevices with the suffix "W“ feature increased shock and vibration resistance.he electronics is covered with a special varnish to provide increased protection againstechanical stress and moisture.
8.3 Standards and certificationshe ISOMETER® has been developed in compliance with the following standards:
• DIN EN 61557-8 (VDE 0413-8):2015-12
• IEC 61557-8:2014-12
• IEC 61557-8:2014/COR1:2016
• DIN EN 61557-8 Ber 1 (VDE 0413-8 Ber 1):2016-12
• DIN EN 61557-9 (VDE 0413-9):2015-10
• IEC 61557-9:2014-12
Combination of ISOMETER® sensor variant with FP200:The requirements of Option "W" will only be fulfilled when the ISOMETER®sensor variant is mounted on DIN rail and connected to the FP200 via thepatch cable.Refer also to the quick-start guide FP200 (Document number D00169).
18.4 Ordering detail
* Option W: Increased shock
Insulation fault locators
Type Su
iso685-D-PACD
iso685W-D-P*ACD
Combinationiso685-S-P + FP200
ACD
Combinationiso685W-S-P + FP200W*
ACD
Type Supply
EDS440-S-1 AC/DC 2
EDS440W-S-1 AC/DC 2
EDS440-L-4 AC/DC 2
EDS440W-L-4 AC/DC 2
EDS441-S-1 AC/DC 2
EDS441W-S-1 AC/DC 2
T
iso685-D-P_D00170_03_M_XXEN/07.20178
A
* **
ts
and vibration resistance 3K5, 3M7; -40…+70 °C
Type Art. No.
nts
20 mAere)
7204-1421 B986763
9604-1421 B986764
9620-1421 B986841
tingFP200 B91067904
FP200W B91067904W
200)
Supply voltage:AC 24…240 V; 50…400 HzDC 24…240 V
B91067130
200)
Supply voltage:AC 24…240 V; 50…400 HzDC 24…240 V
B91067130W
7
Technical dataechnical data
ccessories
included in the scope of delivery If the “transparent front cover 144x72 (IP65)” is used, the cutout in the control cabinet must be increased in height from 66 mm to 68 mm (+ 0.7 / -0 mm).
Description Art. No.
iso685 mechanical accessories comprising: terminal cover and 2 mounting clips*
B91067903
iso685 plug kit, screw terminals* B91067901
iso685 plug kit, with push-wire terminals B91067902
Transparent cover 144x72 (IP65) for FP200 ** B 98060005
BB bus 6TE connector(Necessary for the connection of the ISOMETER®s with an EDS44…-L)
B98110001
Suitable system componen
* Option W: Increased shock** SKMP = midscale point
Description
Suitable measuring instrumeSKMP**: 28 kΩ,120 kΩCurrent values: 0…400 µA, 0…(for more information, click h
Display for front panel moun
iso685-S-P(only in combination with FP
iso685W-S-P*(only in combination with FP
iso685-D-P_D00170_03_M_XXEN/07.2017
er-internal device bus).
other (RS-485 interface).
a a server.
until the button is pressed again, which stops the
, the insulation fault location starts and stops due
TER® are coupled, this function ensures via an
ng current for insulation fault location. This locat-ted by the EDS.
or the insulation fault location is generated.
The BCOM communication takes place within this
s. A typical subsystem are also "non BCOM-capa-
out measured values and for parameter setting.
88
19. Glossary
• BB busThe BB bus is an interface which enables Bender devices to communicate with each other (BendThe BB bus can be used with an ISOMETER® and one or more EDS44…-S.
• BCOM Protocol for communication between Bender devices via an IP-based network.
• BS bus The Bender sensor bus is an interface which enables Bender devices to communicate with each
• DHCP Dynamic Host Configuration Protocol. It is used to assign the network configuration to Clients vi
• EDS Insulation fault locator for fault location in an IT system.
• EDS buttonThe shortcut button "EDS" manually starts the insulation fault location, which runs continuouslyprocess immediately.(refer also to “Display elements and device buttons” on page 19).
• EDS modeThe insulation fault location can be carried out in three different modes. Depending on the modeto different conditions (see also “Mode” on page 54).
• ISOnetOnly one ISOMETER® may exist in an isolated system. If several networks monitored by an ISOMEEthernet connection that only one ISOMETER® is actively measuring.
• Modbus TCP Modbus is an international widely spread protocol for data transfer.
• PGHPGH stands for locating current injector. The locating current injector generates a periodic locatiing current is detected by the measuring current transformers connected to the EDS and evalua
• "PGH ON" LED The "PGH ON" LED flashes during insulation fault location. It indicates that the locating current f
• System (BCOM)The system is the entire installation that is visible for the customer and defined by the customer.system. Naturally, different systems can exist independently in one network.
• Subsystem (BCOM)The subsystem structures parts of the system as units defined by the customer, e.g. all PQ deviceble" devices that are hidden behind a proxy.
• Web server A web server presents the device functions graphically. The web server can be used for reading
iso685-D-B_D00177_05_M_XXDE/07.2017
InAAA
BBBCBBu
Bu
CCC
CCC
EEDS 88
Device settings 58Inputs 58Outputs 56
Ethernet interface 25
FFunction description
Insulation fault location 14ISOMETER 12, 13ISOnet 72
GGlossary 88
HHazards when handling the device 10History memory 40
IInitial measurement 40, 61Inputs
EDS 58Inputs ISOMETER 48Insulation fault location 14, 70
EDS button 19PGH ON LED 19Response value I∆L 56Response value I∆n 56Test current 53
Insulation resistanceActivate/deactivate measurement 47
Intended use 10Interfaces 62
BB bus 27
89
MENU 19OK 19RESET 19TEST 19
ttons 19
haracteristic curves 75ommissioning 33
Commissioning wizard 33, 34Initial commissioning 33Recommissioning 34
ommunication interfaces 65ompatibility 15onnection
3(N)AC system 23AC system 23BB bus 27
DHCP 63, 88Diagrams 75Dimensions 16Display 19, 37
Data - isoGraph 39Fault display (active) 37Fault display (inactive) 38Fault memory 39History memory 40Initial measurement 43Insulation fault location 42Limit values for R(an) 37Measuring pulse 42Signal quality of the measurement 37Standard display 37
Display elements 19
dex
ccessories 87larm
Alarm 1 13Alarm 2 13Reset alarm message 61Settings 46
B bus 27, 88OM 65, 88
S bus 69, 88ttonDATA 19EDS 19ESC 19Info 19
Connection requirements 21Connectors 18DC system 24Ethernet interface 25Relay 1 interface (11 12 14) 26Relay 2 interface (21 22 24) 26Supply voltage 25X1 interface 24
Control circuits 74Coupled IT systems 71Coupling monitoring 47
DDate 34, 62
Setting the date 34, 62Device buttons 19Device profiles 34, 47
90 iso685-D-B_D00177_05_M_XXDE/07.2017
In
IS
LLE
MMMM
MMMMMMM
NNN
SSafety instructions 8Self test 14Service menu 61, 64Set language 34, 61Set system type of the system to be monitored34Setting the time 34, 62Settings 46
Basic settings 61Signal quality of the measurement 37Start-up delay 47Supply voltage 83System leakage capacitance 11, 12, 74
TTechnical data 83Test
Manual test 61Self test 14
WW (W option) 86Warranty 12Web server 65, 88
ains frequency 74ains voltage 11easured values 61
View measured values 61easuring pulse 42enu 43inimum current rectifier 22inimum distance 21odbus TCP 88odbus/TCP 65ounting
DIN rail mounting 21Screw mounting 20
ominal system voltage 74, 83ominal voltage 21
Product description 12Profiles
Description 74Overview 74Set profile 34, 47
Protective earth conductor (PE) 21
RResponse time
Profile control circuits 75Profile generator 76Profile high capacitance 76Profile inverter 10 Hz 77Profile power circuits 75Relative uncertainty 78
Response value 12, 83I∆L 56Set Ran1, Ran2 35
dex
BCOM 63, 65BS bus 69Ethernet 63, 65Modbus TCP 63Modbus/TCP 65Web server 65X1 24
Onet 72, 88
Ds 19ALARM 1 19ALARM 2 19ON 19PGH ON 19, 88SERVICE 19
Normal operation 37
OOperating controls 19Operating mode 48Operation
Commissioning 22, 33Commissioning EDS 36
Option W 86Ordering information 86Outputs
EDS 56ISOMETER 49
PPassword 64PGH 88
iso685-D-B_D00177_05_M_XXDE/07.2017
N
91
otes
Photos: Bender archive.
Customer serviceService hotline: 0700-BenderHelp (Telephone und Fax)Carl-Benz-Straße 8 • 35305 Gruenberg • Germany
Tel.: +49 6401 807-760Fax: +49 6401 807-629
E-Mail: [email protected]: http://www.bender.de BENDER Group
Bender GmbH & Co. KGPostbox 1161 • 35301 Gruenberg • GermanyLondorfer Straße 65 • 35305 Gruenberg • Germany
Tel.: +49 6401 807-0Fax: +49 6401 807-259
E-Mail: [email protected]: www.bender.de