10Gig Fiber

download 10Gig Fiber

of 15

Transcript of 10Gig Fiber

  • 8/22/2019 10Gig Fiber

    1/15

    10 GbE fiberWhy it is different

  • 8/22/2019 10Gig Fiber

    2/15

    2

    CONFIDENTIAL

    Agenda

    What is the difference for LOMM fiber

    Understanding what happens in the fiber

    Design and Specification for 10GbE fiber

    Plug-n-Play Topologies

    Installation

    Testing

    Future

  • 8/22/2019 10Gig Fiber

    3/15

    Leviton 10GbE the Fiber Future

  • 8/22/2019 10Gig Fiber

    4/15

    4

    CONFIDENTIAL

    What is the difference for LOMM fiber

    The transmitter

    VCSEL (Vertical Cavity Surface Emitting Laser). A VCSEL laser light source emits atthe 850 nm wavelength and it is capable of a high data rate.

    An LED and VCSEL emit light differently. In technical terms, the launch conditionsbetween these two light sources are different.

    The LED emits light relatively uniformly over the entire face of the multimode fibercore.

    A VCSEL source emits light in a narrow beam, which shines bright in the center ofthe fiber core and quickly dims as it moves away from the center; it does notilluminate the core near the cladding interface.

    This difference in launch conditions results in different loss measurements. The lossmeasured with a LED is typically greater than the loss measured with a VCSEL.

  • 8/22/2019 10Gig Fiber

    5/15

    5

    CONFIDENTIAL

    Understanding what happens in the fiber

    10-Gigabit Ethernet (10-GbE) -A version of Ethernet with a nominal data rate of 10 Gbit/s, agigabit per second (Gbit/s or Gbps) = 1,000,000,000 (10^9) bits per second, 10GbE over fiberis specified by IEEE 802.3. Gigabit Ethernet uses digital signaling. The fiber optic version of

    this is 1000BASE-SX.Laser-optimized 50/125 m multimode fiber Multimode fiber cable that is specificallydesigned for 850 nm operation at 1 Gb/s and higher. TIA/EIA-492-AAAC specifies mechanical,geometric and optical characteristics for laser-optimized 50/125 m multimode fiber. This fiberhas been fully adopted into TIA/EIA-568-B.3 and IEC-11801

    Differential Mode Delay (DMD)A light pulse launched from a VCSEL will have differentmode groups and will, in general, have different propagation times. This results in bandwidthreduction and limiting of the distance for 10-GbE transmission. However as you can see fromthe following figures, the effect is minimized by use of laser optimized 50 m multimode fiber.

  • 8/22/2019 10Gig Fiber

    6/15

    6

    CONFIDENTIAL

    Understanding what happens in the fiber

    The methodology of measuring DMD uses a single-mode pulse ( 5 m spot size) whichis scanned across the 50/125 m laser-optimized multimode fiber core in at most 2 mincrements. Figure X is an illustration of this methodology.

  • 8/22/2019 10Gig Fiber

    7/15

    7

    CONFIDENTIAL

    Understanding what happens in the fiber

    Effective Modal Bandwidth (EMB)

    The Fiber bandwidth measurement technique to ensure 50/125-m laser-optimizedmultimode fiber will reliably support 10-GbE transmission.

    Calculated Effective Modal Bandwidth (EMBc)

    The main purpose of the EMBc calculation is to ensure that a fibers effective modalbandwidth will meet the10-Gbits/sec requirement of 2000 MHzkm with anyconforming laser.

    Minimum Calculated Effective Modal Bandwidth (minEMBc)

    The second method of predicting EMB from DMD.

    DMD Mask

    Is the translating of DMD data into an EMB prediction.

    Return loss

    Is the power of the optical signal that returns towards the optical source against thedirection of signal propagation. Contributors to return loss are Fresnel reflections(back reflected light due to interfaces at mated connectors and mechanical splices)and Rayleigh back scattering (scattered light due to intrinsic fiber properties).

    Bit Error Rate (BER)

    Is the number of bit errors per unit time compared to the total number of bitstransmitted per unit time. Error free propagation of bits of data through the fiberlink is the ultimate design goal of the MMF and connectors in a 10-GbE optical link.

  • 8/22/2019 10Gig Fiber

    8/15

    8

    CONFIDENTIAL

    Design and Specification for 10GbE fiber

    Design of a 10-GbE fiber solution should start with the fiber.

    The selection of the optical properties of fiber should alsobe carried over to the fiber patch cords and also to the

    connector if you will be using a pre-polished connector or

    manufactured terminated cabling.

    50/125 m laser optimized fiber for building backbone,

    campus backbone, horizontal cabling, centralized cabling anddata centers is recommended, so long as it does not exceed

    the operating range of 300m (OM3) or 550m (OM4).

    This provides the user with the ability to operate at slower

    data-rate speeds initially, while additionally offering the

    ability to migrate to higher data-rate laser-based systemsas demands for bandwidth increase.

  • 8/22/2019 10Gig Fiber

    9/15

    9

    CONFIDENTIAL

    Plug-n-Play (PNP) Topologies

    What are they?

    Most common assumptions

    Factory terminated modules through the use of a multifiber connector with breakoutkit to individual fiber connectors for discreet interconnect

    jumper cassette trunk cable cassette jumper cassette trunk cable cassette jumper

    Standard PNP issues

    Cassette system component loss @ 1.2dB

    Total path loss = 4.8dB

    Amount of discreet connections

    Future migration requires replacement of cassette or hybrid jumper

    Leviton PNP MTP Bracket solution

    Reduces component loss to 0.5dB per connection

    Reduces number of links hopsResults in total path loss of 2.0dB

    Reduces the number of discreet connections (harness vs jumper)

    Future migration via use of harness replacement

  • 8/22/2019 10Gig Fiber

    10/15

    10

    CONFIDENTIAL

    Standard PNP Topology

    Total Loss = 4.8dB

    2.2dB Over Budget

  • 8/22/2019 10Gig Fiber

    11/15

    11

    CONFIDENTIAL

    Leviton PNP Bracket Topology

  • 8/22/2019 10Gig Fiber

    12/15

    12

    CONFIDENTIAL

    Installation

    Follow the industry standards for the passive components,

    TIA/EIA-568-C, Commerc ia l Bui ld ing Telecommunicat ionsCabl ing Stand ard,

    TIA/EIA 569-A, Commerc ia l Bui ld ing Standards forTelecommun icat ions Pathw ays and Spaces, and

    TIA-942, Telecommunic at ions Infrastructu re Standard for DataCenters,

    These standards offer guidance, recommendations and a templatefor a successful solution.

    A final note on the installation of a 10-GbE fiber solution. Fiberconnector and coupler adapter cleanliness and fiber connector endface polish are the most often over looked cause of system failure tosupport a 10-Gbe solution. Make sure to thoroughly clean and

    visually inspect all connectors, couplers and patch cords.Additionally bend radius and tension placed on the fiber cable willhave a significant impact on the capacity of a fiber network tosupport a 10-GbE solution. Careful attention to installationmethodology and support hardware is a must.

  • 8/22/2019 10Gig Fiber

    13/15

    13

    CONFIDENTIAL

    Testing

    Deployment of high data-rate 10-GbE systems requires attention todetail as cabling length and attenuation requirements are more

    stringent.TIA TR-42.8 outlines in TSB-140 outlines the field testing ofoptical fiber cabling.

    This document describes field-testing of length, optical loss andpolarity in optical fiber cabling using an optical loss test set(OLTS), optical time domain reflectometer (OTDR) and a visual

    fault locator (VFL).

    The purpose of this TSB is to clarify, not replace ANSI/TIA/EIA-526-7 and ANSI/TIA/EIA-526-14-A.

    Standards, such as the IEEE802.3ae, typically specify the maximumchannel link loss as a primary link parameter. Although measured

    installed link loss is an important parameter, the link loss is not atrue indicator of whether or not a fiber is capable of supporting10Gb/s error free transmission. The most precise measure of channelperformance is bit error rate (BER) testing. At this time aneconomical field BER testing device is not available, so you mustrely on conventional link loss testing.

  • 8/22/2019 10Gig Fiber

    14/15

    14

    CONFIDENTIAL

    Future Look

    At the time of this paper, the TIA/EIA-492AAAC (850-nm laser-

    optimized, 50 m MMF) specification is being asked to review

    a new draft specification 492AAAD from the work on the TSB-

    172 Committee: TIA FO-4.2 _ TIA TR42.12. This review is

    scheduled for 02/08. This new fiber commonly know as OM4

    is being considered to handle up to 1000-GbE via 850-nm

    laser-optimized, 50 m multi-mode fiber.

    The IEEE Higher Speed Study Group (HSSG) has voted to

    approve the next standard speed for Ethernet to be 100

    Gbit/s. HSSG is currently working on developing the next

    generations of Ethernet. It is obvious that optical fiber will be

    a significant portion of that future.