Integrator Series AC DrivesAC690+ Series AC Drive AC Drives 1 HP - 1500 HP
Description �e AC690+ Series is a single range of AC drives designed to meet the requirements of all variable speed applications from simple single motor speed control through to the most sophisticated integrated multi-drive systems.
�e heart of the AC690+ is a highly advanced 32-bit microprocessor based motor control model. �is provides an exceptional dynamic performance platform to which can be added a host of communications and control options, enabling you to tailor the drives to meet your exact requirements.
�e AC690+ is available in 380-500V 3-phase 1 to 1500 HP and 220V-240V 1 to 60 HP, including single phase input for 1 to 3 HP.
Modes of OperationThe AC690+ can be user configured for different modes of operation:
Open-loop (volts/frequency) control
This mode is ideal for basic motor speed control, or multiple motors driven in parallel. The quick set-up menu and plain language display ensures the quickest and easiest, trouble free start up.
Sensorless vector control
High starting torque and tight speed regulation is provided by a sophisticated MRAS (Model Reference Adaptive System) motor control strategy. MRAS provides accurate speed simulation (without the need for any speed measuring transducer) by continually modelling the motor.
Closed-loop vector control
Full closed-loop flux vector performance can be achieved with the AC690+ by simply adding an encoder feedback ‘technology box’. This provides 100% continuous full load standstill torque plus a highly dynamic speed loop (up to 45 Hz bandwidth); more than sufficient for the most demanding of applications.
Line Regenerative
Some applications require full four quadrant operation or extensive braking capabilities. The AC690+ series offers an energy efficient alternative to dynamic braking resistors in its Active Front End (AFE) unit. The AFE allows regenerative power to be returned to the grid safely and efficiently, and at unity power factor. The AC690+ AFE can also be used for situations that require ultra-low harmonics. An AFE package is offered, complete with LCL filter and other required components. See page 35 for details.
AC
690+
30
Encoder feedback option with encoder technology box
The AC 690+ is converted from open-loop control to high performance closed-loop control by simply adding the plug-in encoder feedback technology box.
High performance systems expansion module
The optional add-on “systems” expansion module is available for more advanced applications and includes phase locking between drives and register control. It fits behind the main control board and provides the following functionality:
5 configurable digital Inputs/ outputsConverts existing 4 analog inputs to high resolution (12 bit plus sign)2 encoder inputs2 high speed register mark inputs
Integrated function blocks
Winder Control
Process PID
Raise/Lower
Spinning Load Start
Open standard fieldbus communications
The AC690+ has a host of communication technology box options allowing seamless multi-vendor integration into networked systems using the most common industrial fieldbus communications protocols :
Mechanical protection options to
suit all environments
A choice of mechanical protection options allows the drive to be mounted in a variety of different operating environments.
IP20 – for mounting inside an electrical enclosure.
IP40/NEMA 1 – The optional top cover, with cable gland plate enables the drive to be directly wall or
IP54 – Ideal for mounting in aggressive environments. Higher levels of protection are available as a special build option on request. A multitude of control options can be added to the drive using our Packaged Drive service.
Through-panel mounting - This option allows the drive to be mounted with the major heat producing components and heatsink outside the enclosure, keeping the electronics clean and cool. (Frames C,D, and E)
Programming/Operator controls
The AC690+ HMI keypad comes standard with the drive, and provides access to all of the drive’s functions in a logical and intuitive manner. The readout is backlit and displays all functions in plain language and engineering units. The HMI can be mounted on the drive itself, or alternatively it can be supplied loose, with a mounting kit, for mounting remotely on a panel door, for example.
Integrator Series AC Drive AC690+ Series AC Drive
AC Drives 1 HP - 1500 HP
Features
31
Vector control with / without encoder feedback
Power ratings 1 HP - 1500 HP
Pre-programmed application Macros
Programmable over communications Programming identical to DC590+ DC drive
Variable torque ratings
Class B EMC filters
Technical SpecificationPower Supply 380-460V (±10%) 3-phase 1 to 1500 HP
380-500V (±10%) 3-phase 2.2 to 110kW
220-240V (±10%) 1-phase 1 to 3 HP
220-240V (±10%) 3-phase 1 to 60 HP
Operating
Temperature
Constant torque - 0-45°C (40°C with IP40 cover)
Derate 2% per degree C to 50°C max (Frame B-F)
Derate 1% per degree C to 50°C max (Frame G-J)
Derate 1.5% per degree C to 50°C max (Frame K)
Altitude Maximum altitude: 1000m (Derate by 1% for every
100m above 1000m to 2000m maximum)
Overload Constant torque: 150% for 60 seconds, 180% for
1 second
Variable torque: 110% for 60 seconds
Output Frequency Volts/Hertz mode: 0-1000 Hz
Sensorless Vector mode: 0-120 Hz
Closed Loop Vector mode: 0-300 Hz
Switching Frequency Frame B: 3,6 or 9kHz
Frame C, D, E and F: 3 or 6kHz
All with audibly silent switching frequency
Dynamic Braking Each drive can be fitted with an internal dynamic
brake switch
Frame B and C: standard
Frame D,E and F: optional
Analog Inputs 4 Configurable, 10 bits (13 bits with optional
system card). 0-10V, 0-±10V, 0-20mA, 4-20mA
Analog Outputs 3 Configurable, 10 bits. 0-10V, 0-±10V, 0-20mA,
4-20mA
Digital Inputs 7 Configurable, nominal 24VDC (30VDC max)
Digital Outputs 3 Configurable, relay contacts 3A/230 VAC
Reference Supplies +10VDC, -10VDC, +24VDC
Motor Thermistor
InputYes
Integrator Series AC DriveAC690+ Integrator Series AC Drive
AC Drive 1 HP - 1500 HP
Function Block
Programming
Function block programming allows a
tremendously flexible control structure to be
created with ease. An almost infinite combination
of user functions can be realized often alleviating
the need for an external PLC. However, the drive
is pre-configured so it can be used straight from
the box as a standard AC drive without further
adjustment.
Analog Functions If So, summing, subtractor, multiplier, divider, if
higher then lower then If, Counter, Timer
Boolean Functions Not, And, Nand, Or, Nor, Xor, Trigger, Flip-Flop
Application Macros Simple speed control, Forward/Reverse, Raise/
Lower, Process PID, Preset speeds, Winder
control.
6901 Operator
Keypad
The 6901 keypad is designed for setting-up,
configuring and operating the AC690+ drive. The
intuitive menu navigation and parameter display
is simple and easy to use. Main features:
Remote mounting capability on front of
enclosure
Backlit display
Multilingual 2x16 alphanumeric display
Customizable display
Local Control: Speed setpoint, Start/Stop,
Jog and Direction
Password protection
Quick set-up mode
Systems Expansion
Module
The optional systems expansion module allows
for advanced applications such as phase locking
between drives and register control.
Key features include:
5 Additional user configurable Inputs /
Outputs
4 High resolution analog inputs (12 bits
plus sign)
2 Additional encoder inputs
2 High speed register mark inputs
Encoder slave repeater
AC
690+
32
Standards�e AC690+ series meets the following standards when installed in accordance with the relevant product manual.
CE Marked to EN50178 (Safety, Low Voltage Directive)CE Marked to EN61800-3 (EMC Directive)UL Listed to US safety standard UL508C.cUL Listed to Canadian standard C22.2 #14.
Specifications
Energy Savings
Fast return on investment in pump and fan applications
Improved power factor
Flux vector control with or without encoder andV/F control
Reduced harmonics through 12 or 18 pulsecoupling
Improved HVAC control
6 pulse
Model
Power Rating Constant torque : 600 - 1500 HP
Variable torque : 700 - 1600 HP
Supply Voltage 380-460Vac (±10%) 3-phase
Disconnect Switch Standard
Input inductance Standard for limiting harmonic
current
Output Choke Standard
Operator Panel 6901 operator keypad mounted on
enclosure door
12 pulse
Model
(option)
Harmonics Reduced harmonic current
Power Rating Constant torque : 600 - 1000 HP
Variable torque : 700 - 1500 HP
Supply Voltage 380-460Vac (±10%) 3-phase
Disconnect Switch Standard
Input Transformer (not included in the enclosure)
optional 2 secondaries U/D
Output Choke Standard
Operator Panel 6901 operator keypad mounted on
enclosure door
18 pulse
Model
(option)
Harmonics Total harmonic distortion (current) in
accordance with limits of
IEEE 519 (1992)
Power Rating Constant torque : 900 - 1500 HP
Variable torque : 1000 - 1600 HP
Supply Voltage 380-460Vac (±10%) 3-phase
Disconnect Switch Standard
Input Transformer (not included in the enclosure)
optional 3 secondaries phase shifted
by 20°
Output Choke Standard
Operator Panel 6901 operator keypad mounted on
enclosure door
Integrator Series AC Drive AC690+ Series AC Drive
K-Frame 600 HP - 1500 HP
Constant Torque ratings provide 150% overload for 60 seconds. Variable Torque ratings provide 110% overload for 60 seconds
To add System Expansion Module (page 44) change last character in part number from “N” to “S”
Electrical Characteristics
AC690+ Integrator Series AC Drive
Part Number Phases Frame
Constant Torque Variable Torque
Inductance Braking
Module Power
(HP/kW)
Output
Current (A)
Power
(HP/kW)
Output
Current (A)
690+0001/230/1BN1 1 B 1/.75 4.0 - - No
Yes
690+0002/230/1BN1 1 B 2/1.5 7.0 - - No
690+0003/230/1BN1 1 B 3/2.2 10.5 - - No
690+0001/230/1BN 3 B 1/.75 4.3 - - No
690+0002/230/1BN 3 B 2/1.5 8 - - No
690+0003/230/1BN 3 B 3/2.2 10.5 - - DC
690+0005/230/1BN 3 B 5/4 16 - - DC
690+0007/230/1BN 3 C 7.5/5.5 22 - - DC
690+0010/230/1BN 3 C 10/7.5 28 - - DC
690+0015/230/1NN 3 D 15/11 42 20/15 54 DC No
690+0015/230/1BN 3 D 15/11 42 20/15 54 DC Yes
690+0020/230/1NN 3 D 20/15 54 25/18.5 68 DC No
690+0020/230/1BN 3 D 20/15 54 25/18.5 68 DC Yes
690+0025/230/1NN 3 D 25/18.5 68 25/18.5 68 DC No
690+0025/230/1BN 3 D 25/18.5 68 25/18.5 68 DC Yes
690+0030/230/1NN 3 E 30/22 80 40/30 104 DC No
690+0030/230/1BN 3 E 30/22 80 40/30 104 DC Yes
690+0040/230/CNN 3 F 40/30 104 50/37 130 AC No
690+0040/230/CBN 3 F 40/30 104 50/37 130 AC Yes
690+0050/230/CNN 3 F 50/37 130 60/45 154 AC No
690+0050/230/CBN 3 F 50/37 130 60/45 154 AC Yes
690+0060/230/CNN 3 F 60/45 154 75/55 192 AC No
690+0060/230/CBN 3 F 60/45 154 75/55 192 AC Yes
Power Supply 220-240V (±10%) 50/60 Hz
Part Number Phases Frame
Constant Torque Variable Torque
Inductance
Braking
ModulePower
(HP/kW)
Output
Current (A) Power
(HP/kW)
Output
Current (A)
400V 460V 400V 460V
690+0001/460/1BN 3 B 1/.75 2.5 2.5 - - - - Yes
690+0002/460/1BN 3 B 2/1.5 4.5 4.5 - - - - Yes
690+0003/460/1BN 3 B 3/2.2 5.5 5.5 - - - - Yes
690+0005/460/1BN 3 B 5/4 9 9 - - - - Yes
690+0007B/460/1BN 3 B 7.5/5.5 12 11 - - - - Yes
690+0010B/460/1BN 3 B 10/6 14 14 - - - - Yes
690+0015/460/1BN 3 C 15/11 23 21 20/15 30 27 DC Yes
690+0020C/460/1BN 3 C 20/15 30 27 25/18.5 37 34 DC Yes
690+0025/460/1NN 3 D 25/18.5 38 38 30/22 45 45 DC No
690+0025/460/1BN 3 D 25/18.5 38 38 30/22 45 45 DC Yes
690+0030/460/1NN 3 D 30/22 45 45 40/30 59 52 DC No
690+0030/460/1BN 3 D 30/22 45 45 40/30 59 52 DC Yes
690+0040D/460/1NN 3 D 40/30 59 52 50/37.5 73 65 DC No
690+0040D/460/1BN 3 D 40/30 59 52 50/37.5 73 65 DC Yes
Power Supply 380-460V (±10%) 50/60 Hz 3-phase
33
AC
690+
34
Part Number Phases Frame
Constant Torque Variable Torque
Inductance Braking
Module
Power
(HP/kW)
Output
Current (A)
Power
(HP/kW)
Output
Current (A)
400V 460V 400V 460V
690+0050/460/1NN 3 E 50/37 73 73 60/45 87 87 AC No
690+0050/460/1BN 3 E 50/37 73 73 60/45 87 87 AC Yes
690+0060/460/1NN 3 E 60/45 87 87 75/55 105 100 AC No
690+0060/460/1BN 3 E 60/45 87 87 75/55 105 100 AC Yes
690+0075/460/CNN 3 F 75/55 105 100 100/75 145 125 AC No
690+0075/460/CBN 3 F 75/55 105 100 100/75 145 125 AC Yes
690+0100/460/CNN 3 F 100/75 145 130 125/90 165 156 AC No
690+0100/460/CBN 3 F 100/75 145 130 125/90 165 156 AC Yes
690+0125/460/CNN 3 F 125/90 180 156 150/110 205 180 AC No
690+0125/460/CBN 3 F 125/90 180 156 150/110 205 180 AC Yes
690+0150/460/CNN 3 F 150/90 180 180 150/110 205 180 AC No
690+0150/460/CBN 3 F 150/90 180 180 150/110 205 180 AC Yes
690+0175/460/CNN 3 G 175/110 216 216 200/132 260 260 External No
690+0175/460/CBN 3 G 175/110 216 216 200/132 260 260 External Yes
690+0200/460/CNN 3 G 200/132 250 250 250/150 302 302 External No
690+0200/460/CBN 3 G 200/132 250 250 250/150 302 302 External Yes
690+0250/460/CNN 3 G 250/160 316 316 300/180 361 361 External No
690+0250/460/CBN 3 G 250/160 316 316 300/180 361 361 External Yes
690+0300/460/CNN 3 G 300/180 361 361 350/220 420 420 External No
690+0300/460/CBN 3 G 300/180 361 361 350/220 420 420 External Yes
690+0350/460/CNN 3 H 350/220 420 420 400/250 480 480 External No
690+0350/460/CBN 3 H 350/220 420 420 400/250 480 480 External Yes
690+0400/460/CNN 3 H 400/250 480 480 450/300 545 545 External No
690+0400/460/CBN 3 H 400/250 480 480 450/300 545 545 External Yes
690+0450/460/CNN 3 H 450/280 520 520 500/315 590 590 External No
690+0450/460/CBN 3 H 450/280 520 520 500/315 590 590 External Yes
690+0500/460/CNN 3 J 500/315 590 590 550/355 650 650 External No
690+0500/460/CBN 3 J 500/315 590 590 550/355 650 650 External Yes
690+K0600/460/2G/N 3* K 600 - 685 700 - 798 AC No
690+K0600/460/2G/B 3* K 600 - 685 700 - 798 AC Yes
690+K0700/460/2H/N 3* K 700 - 798 800 - 912 AC No
690+K0700/460/2H/B 3* K 700 - 798 800 - 912 AC Yes
690+K0800/460/2H/N 3* K 800 - 988 900 - 1120 AC No
690+K0800/460/2H/B 3* K 800 - 988 900 - 1120 AC Yes
690+K0900/460/3G/N 3** K 900 - 1028 1000 - 1197 AC No
690+K0900/460/3G/B 3** K 900 - 1028 1000 - 1197 AC Yes
690+K1000/460/2J/N 3* K 1000 - 1120 1100 - 1235 AC No
690+K1000/460/2J/B 3* K 1000 - 1120 1100 - 1235 AC Yes
690+K1000/460/3H/N 3** K 1000 - 1197 1200 - 1368 AC No
690+K1000/460/3H/B 3** K 1000 - 1197 1200 - 1368 AC Yes
690+K1300/460/3H/N 3** K 1300 - 1482 1500 - 1681 AC No
690+K1300/460/3H/B 3** K 1300 - 1482 1500 - 1681 AC Yes
690+K1500/460/3J/N 3** K 1500 - 1681 1600 - 1852 AC No
690+K1500/460/3J/B 3** K 1500 - 1681 1600 - 1852 AC Yes
Power Supply 380-460V (±10%) 50/60 Hz 3-phaseElectrical Characteristics AC690+ Integrator Series AC Drive
*12-Pulse Input Optional
**18-Pulse Input Optional
For frame “K” drives, please specify whether constant torque or variable torque when ordering
Constant Torque ratings provide 150% overload for 60 seconds. Variable Torque ratings provide 110% overload for 60 seconds
To add System Expansion Module (page 44) change last character in part number from “N” to “S”
35
Recovers wasted energy
No braking resistor/No maintenance
Ultra-low harmonics, meeting the
requirements of IEEE 519
High power factor (cos ø ~ 1)
DescriptionMany applications depend on the drive for braking torque as well as motoring torque. While dynamic braking with a resistor can be effective for lighter or lower duty cycle braking, some applications demand more braking performance
dynamic braking using a resistor is wasteful of energy, as the
an Active Front End (AFE) configuration, energy from the load is returned back to the power grid at unity power factor, providing extremely effective and controllable braking, as well as energy efficiency.
Applications that can benefit from line regeneration include hoists and lifts, centrifuges, continuous web processes, and dynamometer test stands. An AFE may also be used in applications that require ultra-low harmonics.
This cost effective AFE package includes pre-charge circuit and LCL filter.
4 Quadrant Power ModuleAC690+ Integrator Series AC Drive
Active Front End Units 10 HP - 500 HP
Illustration shows typical panel including AC690+ with AFE and additional system components.
Part Number Phases Frame
Nominal
Power
(HP)
Dimensions
(in)
AFE-13-LCL 3 B 13 22 x 18
AFE-26-LCL 3 C 26 28 x 22
AFE-45-LCL 3 D 45 33 x 27
AFE-85-LCL 3 E 85 46 x 34
AFE-125-LCL 3 F 125 46 x 34
AFE-167-LCL 3 F 167 46 x 34
AFE-200-LCL* 3 G 200 79 x 47 x 24
AFE-300-LCL* 3 G 300 79 x 47 x 24
AFE-350-LCL* 3 G 350 79 x 47 x 24
AFE-400-LCL* 3 H 400 79 x 47 x 24
AFE-500-LCL* 3 H 500 79 x 47 x 24
* Provided in NEMA 12 force ventilated cabinet with fans and filters
M
BI-DIRECTIONAL POWER FLOW
LCL Filter
Active
Front End Inverter
AC
690+
36
ModelDimensions (in/mm) Mounting Centers (in/mm) Weight
(lb/kg)H W D W2 H2 H1 W1 G
Frame B 9.17/233 6.95/177 7.13/181 - - 8.78/223 5.12/130 - 4.3/1.95
Frame C 13.7/348 7.91/201 8.19/208 - - 13.19/335 5.91/150 - 9.3/4.22
Frame D 17.8/453 9.92/252 9.65/245 - - 13.32/440 5.91/150 - 17.4/7.89
Frame E 26.3/669 10.1/257 12.28/312 - - 24.80/630 5.91/150 - 32.5/14.74
Frame F 28.3/720 10.1/257 13.74/349 - - 27.56/700 5.91/150 - 41.0/18.60
Frame G 41/1042 17.9/455 18.31/465 26.57/675 8.86/225 11.81/300 16.54/420 0.63/16 202/100
Frame H 46.3/1177 22.5/570 18.31/465 31.69/805 14.17/360 11.81/300 21.10/536 0.63/16 276/125
Frame J 50.7/1288 26.6/1177 18.31/465 32.48/825 13.11/333 11.81/300 25.24/641 0.63/16 388/176
Frame K - 685A, 798A, 988A,
and 1120A ratings79/2000 128/3251 24/610 - - - - - -
Frame K - 1028A, 1197A,
1482A, and 1681A ratings79/2000 176/4470 24/610 - - - - - -
Frame G,H,J Frame K
DimensionsAC690+ Integrator Series AC Drive
Dimensions
37
AC690+ HVAC SeriesEnergy Saving AC Drives
Features�e HVAC series was designed for applications including air handling units, cooling towers, chilled water pumping, and other related uses. Ranging from 1 HP to 150 HP, this series o!ers a compact and easy to install package, including specialized con-"gurations with power disconnect switch and built-in contactor bypass circuit.
Save energy on many applications with the HVAC series. When used to replace louvers, dampers, or throttling valves, the drive allows more controllable $ow by adjusting the speed of the mo-
cubic rate, and you will see this in your power bill! Contact your Parker territory manager for a free payback analysis. Check with your local power utility for information on rebates or incentives!
HVAC Series Benefits:Soft Mechanical Starting & Stopping
Lower Peak Demand on Startup
Repeatable Flow
Building Automation Interfacing
Overspeed Protection
Reduced Noise
Less Maintenance
Coordinated Supply & Return
Contactor Bypass included
Line Disconnect Switch Included
All-inclusive drive package for easy installation
and wiring
Flexible Control:Four analog inputs with selectable levels (V or mA)
Hand/Off/Auto switch
Two Analog Outputs for speed or load
Three Programmable Relay outputs
Dedicated digital input for purge - overrides “stop” signal from the network
Variable Torque V/Hz curve shape parameter
Up to 8 preset speeds
Current limit, adjustable to 110% of rating
Programmable Sleep Mode
AC
690+
38
Intuitive Display Panel Indicator lights for drive status
Industrial-grade switches for control modes
‘Hand/Off/Auto’ selection
‘Drive/Bypass’ selection with ‘Test’ mode
Main Power Disconnect
Communications Options Johnson Metasys N2
Echelon LonWorks
Modbus RTU
Siemens Apogee P1
Ethernet
Canbus
Devicenet
Controlnet
Profibus
Modbus+
HVAC3 units include contactor bypass and fused disconnect
Part Number Voltage Frame
Variable Torque
Nominal
Power (HP)
Output
Current (A)
HVAC3/0001/230/N 208/230 B 1 4
HVAC3/0002/230/N 208/230 B 2 7
HVAC3/0003/230/N 208/230 B 3 10.5
HVAC3/0005/230/N 208/230 B 5 16.5
HVAC3/0007/230/N 208/230 C 7.5 25
HVAC3/0010/230/N 208/230 C 10 40
HVAC3/0015/230/N 208/230 D 15 52
HVAC3/0020/230/N 208/230 D 20 63
HVAC3/0025/230/N 208/230 E 25 80
HVAC3/0030/230/N 208/230 E 30 104
HVAC3/0040/230/N 208/230 F 40 125
HVAC3/0050/230/N 208/230 F 50 154
HVAC3/0060/230/N 208/230 F 60 185
HVAC3/0001/460/N 460 B 1 2.4
HVAC3/0002/460/N 460 B 2 4.5
HVAC3/0003/460/N 460 B 3 5
HVAC3/0005/460/N 460 B 5 8.5
HVAC3/0007/460/N 460 B 7.5 11
HVAC3/0010/460/N 460 B 10 14
HVAC3/0015/460/N 460 C 15 21
HVAC3/0020/460/N 460 C 20 27
HVAC3/0025/460/N 460 C 25 34
HVAC3/0030/460/N 460 D 30 45
HVAC3/0040/460/N 460 D 40 52
HVAC3/0050/460/N 460 D 50 65
HVAC3/0060/460/N 460 E 60 80
HVAC3/0075/460/N 460 E 75 105
HVAC3/0100/460/N 460 F 100 125
HVAC3/0125/460/N 460 F 125 150
HVAC3/0150/460/N 460 F 150 180
AC690+ HVAC SeriesEnergy Saving AC Drives
For information on Type 1 and Type 2 HVAC units, please consult factory
For 208/230V units, VT rating is for 208V. 230V units are rated at constant torque
39
Option Description Frame Part Number Page
Operator Keypad
AC690+ (removable) B - K 6901/00/G
43Advanced operator keypad (removable) B - K 6911/01/00/G
Remote mounting kit B - K 6052/00
Keypad Blanking Cover B - K LA500326U001 44
Communication Cards
Ethernet Modbus/TCP and Ethernet IPB 6053/ENET/00
40
C - K 6055/ENET/00
ControlNetB 6053/CNET/00
C - K 6055/CNET/00
Modbus PlusB 6053/MBP/00
C - K 6055/MBP/00
DeviceNetB 6053/DNET/00
C - K 6055/DNET/00
RS485 / ModbusB 6053/EI00/00
C - K 6055/EI00/00
Profibus-DPB 6053/PROF/00
C - K 6055/PROF/00
CANopen DS402B 6053/CAN/00
C - K 6055/CAN/00
LonWorksB 6053/LON/00
C - K 6055/LON/00
LinkB 6053/LINK/00
C - K 6055/LINK/00
Apogee P1 (HVAC Series)B 6053/APOG/00
C - K 6055/APOG/00
Metasys N2 (HVAC Series)B 6053/JMET/00
C - K 6055/JMET/00
Speed Feedback / Systems Module
HTTL Encoder CardB LA467461
41C - K 6054-00
Systems Expansion Module B - K Specified in drive part number (S) 42
Other Options and Accessories
Dynamic Braking Resistors All See table 44
Filters and Reactors All See table 112
IP40 Cover for Wall Mounting (Included standard with all
part numbers ending in 1BN or 1NN)
B LA467452
C LA465034U002
D LA465048U002
E LA465058U002
DSE Lite Programming Software All DSE-Lite 106
Through-panel mount bracket assembly
C LA465034U003
43D LA465048U003
E LA465058U003
HMI Operator interace 3 to 15” All See TS8000 section 107
Conformal Coating B - F /083 43
Vent Kit F LA466717U003 44
Accessories and OptionsAC690+ Integrator Series AC Drive
AC
690+
40
Communication CardsAC690+ Integrator Series AC Drive
Ethernet Communications Interface
*Part Number: 6053/ENET/00 and 6055/ENET/00
Supported Protocols Modbus/TCP and Ethernet IP
Communication Speed 10/100M bits/s
Station Address Selectable via switch or Internet Explorer
Suitable for AC690+ version 4.7+
Description The selection of available AC690+ communication “technol-ogy boxes” allow the flexibility to be connected to the most common industry standard fieldbuses.
Devicenet Communications Interface
*Part Number: 6053/DNET/00 and 6055/DNET/00
Supported ProtocolsDeviceNet Drive Profile Drive – Group 2 slave
only
Station AddressDeviceNet Drive Profile Drive – Group 2 slave
only
Suitable for Drives AC690+
CANopen Communications Interface
*Part Number: 6053/CAN/00 and 6055/CAN/00
Profile DS402
Supported Messages SDO, PDO, NMT, SYNC
Communication Speed20K, 50K, 125K, 250K, 500K, 1M bits/s
selectable
Station Address Selectable via Switch
Suitable for AC690+
RS485/Modbus Communications Interface
*Part Number: 6053/EI00/00 and 6055/EI00/00
Supported Protocols Modbus RTU, EI Bisynch ASCII
Cabling RS485 2 or 4 wire
Communication Speed 300 to 115200 bits/s
Station Address Selectable via Software
Suitable for AC690+ version 4.7+
ControlNet Communications Interface
*Part Number: 6053/CNET/00 and 6055/CNET/00
Supported Messages Polled I/O
Station Address Selectable via Software
Suitable for AC690+ version 4.7+
Modus Plus Communications Interface
*Part Number: 6053/MBP/00 and 6055/MBP/00
Supported Protocols Modbus Plus
Cabling RS485 2 or 4 wire
Communication Speed 1 M bits/s
Station Address Selectable via Software
Suitable for AC690+ version 4.7+
Profibus-DP Communications Interface
*Part Number: 6053/PROF/00 and 6055/PROF/00
Supported Protocols Profibus-DP
Communication Speed Automatically Detected
Station Address Selectable via Software
Suitable for AC690+ version 1.x+
LonWorks
*Part Number: 6053/LON/00 and 6055/LON/00)
Supported Protocols LonWorks
Deliveredwith a resource file compatible with
LonMaker software (or equivalent)
Suitable for AC690+ HVAC Series version 5.1+
SSD Link
*Part Number: 6053/LINK/00 and 6055/LINK/00)
Supported Protocols Parker SSD LINK
Cabling Fiber Optic
Network speed 2.7 MBaud
Suitable for AC690+
FeaturesCommunications cards can be factory installed into
the drive, or purchased separately for installation on-site
Dimensions H x W x D : 127mm x 76.2mm x 25.4mm
LED indication of network and card status
* Refer to page 39 for details of drive frame compatibility
Apogee P1 (HVAC Series only)
*Part Number: 6053/APOG/00 and 6055/APOG/00)
Supported Protocols Apogee P1
Suitable for AC690+ HVAC Series
Metasys N2 (HVAC Series only)
*Part Number: 6053/JMET/00 and 6055/JMET/00)
Supported Protocols Johnson Controls N2
Suitable for AC690+ HVAC Series version 4.6+
41
HTTL Encoder Feedback CardAC690+ Integrator Series AC Drive
DescriptionThe HTTL Encoder Feedback Card allows an incremental encoder to be connected to the AC690+ AC drive, allowing users to take full advantage of the integrated torque control and speed regulation functionality.
The HTTL Encoder Feedback card has the following features:
Adjustable isolated 10 - 20V encoder power output
SpecificationsMaximum Input
Frequency
250kHz
Receiver current
consumption
≤10mA per channel
Input Format 2-channels in quadrature, clock / direction,
or clock only
De-phasing >1µs
Differential Input Voltage 10 - 30V Maximum
Encoder Power Maximum Load:
Card LA467461: 200mA or 2W
Housing 6054-00: 250mA or 2.5W
Voltage 10-20V software adjustable.
AC690+ Frames C-K DrivesAC690+ Frame B Drives
Installation and cabling
Part Number Compatible Drives
LA467461 AC690+ Frame B (690-xxxxxxB...) drives
6054-00 AC690+ Frames C - K drives
Part Numbers
AC
690+
42
System Expansion ModuleAC690+ Integrator Series AC Drive
DescriptionWith the System Expansion Module, the AC690+ can be used in more sophisticated applications, or where a small amount of automation is required to be used in conjunction with the drive.
The following features are available:
Analog Inputs AIN1-4 are become high resolution (12 bit plus sign)5 isolated I/O points, configurable as either inputs or outputsVariable isolated output power for encodersMaster encoder inputs
Slave encoder output retransmission (Isolated HTTL): A, A/,
External Power Supply
An external 1 Amp 24VDC (±10%) supply must be connected to the card.
How to Order
Change last character of drive part number from “N” to “S”.
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 SW1 SW2 1 2 3 4 5 6 1 2 3 4 5 6
Exte
rna
l 0V
DIG
IO11
DIG
IO12
DIG
IO13
DIG
IO14
DIG
IO15
Exte
rna
l 24V
In
Re
fere
nc
e E
nc
od
er
A
Re
fere
nc
e E
nc
od
er
/A
Re
fere
nc
e E
nc
od
er
B
Re
fere
nc
e E
nc
od
er
/B
Re
fere
nc
e E
nc
od
er
Z
Re
fere
nc
e E
nc
od
er
/Z
En
co
de
r S
up
ply
Ou
t
Exte
rna
l 0V
Sla
ve
En
co
de
r A
Sla
ve
En
co
de
r /A
Sla
ve
En
co
de
r B
Sla
ve
En
co
de
r /B
Sla
ve
En
co
de
r Z
Sla
ve
En
co
de
r /Z
Re
pe
at
Sla
ve
En
co
de
r A
Re
pe
at
Sla
ve
En
co
de
r /A
Re
pe
at
Sla
ve
En
co
de
r B
Re
pe
at
Sla
ve
En
co
de
r /B
Re
pe
at
Sla
ve
En
co
de
r Z
Re
pe
at
Sla
ve
En
co
de
r /Z
ON ON
+24V DC Power Supply
Encoder Power Supply Select by SW1 & SW2 SW2
SW1
OFF ON
OFF 24V 18V
ON 12V 5V
Encoder Voltage Selection
43
Operator KeypadsAC690+ Integrator Series AC Drive
Features
Local motor control : start, speed, direction, diagnostics
Operator menus and parameter configuration
Quick setup menu
Password protection for parameter configuration
Standard operator keypad 6901/00/G
Multilingual English · Spanish - French · German · Italian · Portuguese · Swedish · Polish
Quick setup menuIntuitive menus allowing easy and quick setup of the drive
Auto-tuningAutomatic tuning of motor parameters ensures maximum dynamic motor performance
Diagnostics messagesDisplay input and output parameters as well as drive operating units
Drive configuration
Advanced operator keypad 6911/01/00/GFeatures
128 x 64 pixels semi-graphical resolution
RS232 and RS485 ports
Recording of paramters to keypad and restore to drive (Memory card 256Mb to 2Gb)
DescriptionThis option allows the heat sink of the drive to protrude through the back panel of an enclosure or cabinet, allowing the heat to be dissipated outside of the enclosure. This mounting configuration can generally permit the use of a smaller enclosure, or elimination of the need for air conditioning inside the enclosure. Please consult the installation manual for complete information regarding thermal management requirements for the drive or drives to be used.
Through-panel Mounting KitConformal CoatingFor environments that have dusty, humid or corrosive atmospheres, the AC690+ family can optionally be supplied with conformally coated circuit boards that improve the drive’s resistance to corrosion, thereby increasing reliability and service life. Environments that typically benefit from conformal coating include:
Water and wastewater treatment plants
Paper and pulp processing mills
Steel mills
Marine and offshore
Outdoor cranes
Wind & wave power generation
Food and chemical processing plants
AC
690+
44
Dynamic Braking Kit/Vent KitAC690+ Integrator Series AC Drive
D/B Kit includes resistor, overload, protective cage, and enclosure top or panel mounting
Part Number Voltage
Nominal
Power - CT
(HP)
Nominal
Power - VT
(HP)
Ohms Amps WattsDimensions (in)
LxWxH
LA471358 208/230 1, 2, 3, 5 - 56 1.9 202 6.5 x 1.2 x 2.4
LA471406 208/230 7.5, 10 10, 15 30 3.5 368 13.5x4x5
LA471386 208/230 15 20 15 5 375 13.5x4x5
LA471378 208/230 20, 25 25 10 8.7 757 13.5x7x5
LA471407 208/230 30 40 7 10.4 757 13.5x7x5
LA471379 208/230 40 50 6 13.7 1126 13.5x10x5
LA471380 208/230 50, 60 60, 75 4 19.4 1505 13.5x13x5
LA471356 460 1, 2, 3 1, 2, 3 100 1 100 6.5 x 1 x 1.6
LA471404 460 5, 7.5, 10 5, 7.5, 10 100 1.9 361 13.5x4x5
LA471359 460 15 20 56 3 500 13.2x1.2x2.4
LA471405 460 20 25 60 3.5 735 13.5x7x5
LA471361 460 25, 30 30, 40 30 5 750 13.5x7x5
LA471350 460 40 50 22.5 7.1 1134 13.5x10x5
LA471364 460 50 60 18 7.9 1123 13.5x10x5
LA471365 460 60 75 15 8.7 1135 13.5x10x5
LA471367 460 75, 100 100, 125 8 13.7 1502 13.5x13x5
LA471369 460 125, 150 150 6 19.4 2258 13.5x10x5
LA471370 460 200 250 3 39 4563 20x18x10
LA471372 460 250, 300 300, 350 2.25 45 4556 20x18x10
LA471375 460 350, 400, 450 400, 450, 500 1.5 55 4538 20x18x10
LA471376 460 500 550 1.2 61 4465 20x18x10
*NEMA ICS 3-301.62 Dynamic braking stop option. Minimum 100% full load
torque from base speed with 6x motor inertia, and 4 stops per hour.
Vent KitDescription For the two largest frame sizes, optional vent ducting kits is available. These kits provide a convenient means of venting hot exhaust air from the panel-mounted AC690+ drive. The kit includes a duct, attached to the top of the drive and the roof of your enclosure, and an air exhaust hood for mounting on the top of the enclosure. Mounting hardware and gasket are provided in the kit. Installation will require a rectangular hole and six mounting bolt holes to be cut through the top of your enclosure.
Part Number Description Suitable for
LA466717U004 Vent Kit AC690+ Frame E
LA466717U003 Vent Kit AC690+ Frame F
Keypad Blanking Cover
Part Number Description Suitable for
LA500326U001 Blank Cover AC690+ Frame B-J