Power Quality &
Synchronisation
Ben Kemink
2FORESIGHT
INNOVATIONQUALITY
Power Quality
What is the Quality of the Power Measurement?
3FORESIGHT
INNOVATIONQUALITY
Subjects Covered
1. Definition of Electrical Power
2. The meaning of “T”
3. Should we select the Voltage or the Current input channel for Synchronization?
4. Is an Observation Time an alternative for “T”?
4FORESIGHT
INNOVATIONQUALITY
Power Quality
Before discussing quality of power,
lets have a look at how do we
define the measurement of electrical power?
5FORESIGHT
INNOVATIONQUALITY
Traditional
CONSTANT AVERAGE=0
Applied Voltage : u(t) = Upk.sin(t)
Resulting Current : i(t) = pk.sin(t+)
Amplitude=UrmsxIrms
p(t) = u(t) . i(t) =
= ½ . Upk . Ipk . cos( ) - ½ . Upk . Ipk . cos(2t+ )
6FORESIGHT
INNOVATIONQUALITY
Definition of Average Power
dt.)t(1 T
0average p
TP
The most difficult task for the power meter is to find the period time T correctly!
Especially with distorted signals this can be very difficult.
7FORESIGHT
INNOVATIONQUALITY
Traditional 50Hz
Amplitude=Urms x Irms
Vpk
Ipk
Pavg
Tp
Ti
Tu
8FORESIGHT
INNOVATIONQUALITY
Zero Crossing?
9FORESIGHT
INNOVATIONQUALITY
The zero crossing lasts at least for one acquisition interval. An uncertainty caused by time resolution.
Δt = resolution of Tperiod
10
FORESIGHTINNOVATION
QUALITY
Current input channel is used for synchronization.
11
FORESIGHTINNOVATION
QUALITY
What if the period is longer than the acquisition memory of the power meter?
12
FORESIGHTINNOVATION
QUALITY
A too low Display Update Rate will not detect changes of short duration despite a high acquisition speed.
13
FORESIGHTINNOVATION
QUALITY
Power Quality is first of all related to an accurate Power Measurement
Factors that influence the total error for power are:
Amplitude Frequency of the fundamental of the input signal Crest Factor of the input signal (BW) Crest Factor setting of the Power Meter Power Factor Temperature Use of filters Acquisition interval Acquisition Clock Stability
Correct Detection of Period Time “T”
14
FORESIGHTINNOVATION
QUALITY
There is enough energy. The challenge is how to control it!
For Example:If of 1 gram uranium all atoms split, the heat
developed (energy) can make a water basin, 6 x 6 x 5 meter filled with water of 0 degrees Celsius, boil.
Source: Van Barnsteen naar Kernchemie, Dr. K.K. Darrow
15
FORESIGHTINNOVATION
QUALITY
Three ways to control Electrical Power
1. The current is manipulated. Example: Switched Power Supplies, Resistors.
2. The voltage is manipulated.
Example: Pulse Width Modulated Power Inverters, Frequency Converters, Soft-starters, Thyristor Controlled Power Supplies, Inductive Cooking.
3. Both the voltage and the current are manipulated.
Example:Electronic Ballasts for Lighting
16
FORESIGHTINNOVATION
QUALITY
1. Current Manipulation
Voltage
Current
Example: Switching Power Supply
17
FORESIGHTINNOVATION
QUALITY
1. Current Manipulation
Voltage
Current
Power
example: Switching Power Supply, Voltage, Current & Power Harmonics
18
FORESIGHTINNOVATION
QUALITY
2. Voltage Manipulation
example: Inductive Cooking
19
FORESIGHTINNOVATION
QUALITY
2. Voltage Manipulation
example: 3-Phase Frequency Inverter Output
20
FORESIGHTINNOVATION
QUALITY
2. Voltage Manipulation
example: Soft starter
21
FORESIGHTINNOVATION
QUALITY
3. Voltage & Current Manipulation
WT1600
example: Lighting Industry, electronic ballast
22
FORESIGHTINNOVATION
QUALITY
3. Voltage & Current Manipulation
example: 50kHz Electronic Ballast for TL
23
FORESIGHTINNOVATION
QUALITY
Design engineers are very creative.
Summary
Today electric power consumption is controlled by high speed (switching) electronics.
To limit the negative side effects for others, new regulations are issued frequently to set new guidelines for design.
The definition of the average electric power has not changed, but the selection of the true repetition time T (period) requires special attention.
The power meter should allow the user to select the appropriate synchronisation source for the measurement calculations.
24
FORESIGHTINNOVATION
QUALITY
The power meter should allow the user to select the synchronisation source for the measurement calculations.
25
FORESIGHTINNOVATION
QUALITY
THANK YOU