Powerwave 33 ENG WEB 290509
Transcript of Powerwave 33 ENG WEB 290509
8/3/2019 Powerwave 33 ENG WEB 290509
http://slidepdf.com/reader/full/powerwave-33-eng-web-290509 1/6
P O W E R W A V E 3 3Master your energy challenge
8/3/2019 Powerwave 33 ENG WEB 290509
http://slidepdf.com/reader/full/powerwave-33-eng-web-290509 2/6
P O W E R WA V E 3 3 6 0 - 2 0 0 K V A
Technical SpeciicationsPowerWave 33 60-200 kVA
GENERAL DATA
Output Rated Power kVA 60 80 100 120 160 200
Topology True double conversion on-line (VFI-SS-111)
Parallel confgurations Distributed Parallel Architecture DPA™ (standard up to 10 units, more on request)
Static and Maintenance Bypass standard
Accessibility Front access only or service and maintenance (no need or side or top access)
Efciency (Double Conversion) Up to 95.5%
Audible Noise With 100% Load <65 <69INPUT DATA
Nominal Voltage 3x380/220V+N, 3x400/230V+N, 3x415/240V+N
Voltage Tolerance (Re . to3x400/230V) % For loads <100% (-23%, +15%), <80% (-30%, +15%), <60% (-40%, +15%)
Frequency Hz 35 – 70
Power Factor 0.99 (electrically regulated)
Current Distortion THDI % < 3.5 @ 100% load (sinewave)
Inrush Current Sot start
Cabling Hardwired
OUTPUT DATA
Voltage V 3x380/220V+N, 3x400/230V+N, 3x415/240V+N
Voltage Tolerance % +/- 1% (linear load), +/- 3% (non-linear load)
Voltage Tolerance (Load Jumps 0-100-0%) % +/- 4%Frequency Hz 50 or 60
Frequency Tolerance % +/- 0.1% (ree-running), +/- 4% (with mains, adjustable)
Crest Factor 3 : 1
Overloading Capability % 125% / 10 min., 150% / 60 s.
Permissible Unbalanced Load % 100% (all 3 phases regulated independently)
COMMUNICATIONS
Power Management Display (PMD) With LCD, Mimic Diagram, Control
Communication port (Smart Port) Serial RS 232, Sub-D9 and USB (standard)
Communication port (Dry Port) Volt-ree contacts (standard)
SNMP Yes (optional)
Shutdown and Monitoring Sotware Yes (Wavemon) (optional)
Emergency Power O (EPO) YesSTANDARDS
Saety IEC/EN 62040-1-1, IEC/EN 60950-1
Electromagnetic Compatibility IEC/EN 61000-6-4 (product standard IEC/EN 62040-2 limit A (C2 UPS))
IEC/EN 61000-6-2 (product standard IEC/EN 62040-2 Criterion A (C2 UPS))
IEC/EN 61000-4-2, IEC/EN 61000-4-3, IEC/EN 61000-4-4, IEC/EN 61000-4-5, IEC/EN 61000-4-6
Perormance IEC/EN 62040-3
Product Certifcation CE – GOST by TUV
Degree o protection IP 20
Manuacturing ISO 9001:2000, ISO 14001:2004
Country o origin Switzerland
MECHANICAL DATA
Dimensions (WxHxD) mm 550x1820x750 850x1820x750Dimension with battery enclosures (WxHxD) mm 970 (or 1180)x1820x750
Weight (Without batteries) kg 230 240 245 280 290 310 S p e c i f i c a t i o n
s a r e s u b j e c t t o c h a n g e w i t h o u t n o t i c e .
8/3/2019 Powerwave 33 ENG WEB 290509
http://slidepdf.com/reader/full/powerwave-33-eng-web-290509 3/6
P O W E R WA V E 3 3 6 0 - 2 0 0 K V A
PowerWave 33, Newave’s latest three-phase UPS system,
delivers the best combination o energy eiciency and overallpower perormance in the industry. Oering both intelligent
energy management and maximum power protection
PowerWave 33 helps you to use less energy, generate less
CO2, take up less space and provide signiicant cost savings.
Even a small eciency percentage dierence can generate signicant
savings in operating costs during the UPS lie cycle.
Cost savings calculated based on a 0.10 Euro/kWh including
air conditioning/ventilation costs.
Dierence o
efciency 2% 3% 4%
Load (kW) 3 years 7 years 3 years 7 years 3 years 7 years
100 8’240 19’227 12’495 29’154 16’841 39’297
500 41’200 96’140 62’475 145’770 84’205 196’485
1000 82’400 192’270 124’950 291’540 168’410 392’970
COST SAVINGS (Euros)
Facing continuous energy cost increases, Inormation
Technology (IT) Managers can no longer ignore the
savings o using a highly ecient UPS. PowerWave 33 has
been specically developed to meet the challenges o today’s IT inrastructures maximising energy cost savings
while ensuring the highest level o power protection
availability. PowerWave 33’s exceptional design supports
all organisation’s requirements to build and operate
energy-ecient and environmentally riendly data
centres. Cost savings rom using Newave’s high eciency
UPS oten equal the cost o energy or power and
cooling within a ew years.
PowerWave 33 is a double conversion UPS topology
and is available rom 60 to 200 kVA. PowerWave 33
supplies clean, uninterruptible power and delivers the
perormance according to your needs – whether you
are implementing power protection equipment or
data centres, banking, telecommunication, healthcare
systems, industrial automation equipments and others.
Furthermore, the PowerWave 33’s small ootprint not
only acilitates easy installation but also saves space or
uture growth.
Master your energy challenge
8/3/2019 Powerwave 33 ENG WEB 290509
http://slidepdf.com/reader/full/powerwave-33-eng-web-290509 4/6
Overall Power Perormance
Built in batteries or up to 100 kVA
PowerWave 33 is compatible with a wide range o battery autonomies.
Furthermore the ripple-ree and temperature controlled battery chargers
protect your batteries and extend their lie time perormance. PowerWave
33 is available with integrated enclosures to accommodate batteries or
60, 80 and 100 kVA power ranges. Front access acilitates installation and
service o batteries.
Near to unity Input power actor
The near to unity input power actor (sinewave) o PowerWave 33 reduces
the input installation costs by using smaller cable sections and smaller use
sizes. Accordingly the use o additional phase compensating devices is not
needed which consequently keeps the overall UPS eciency high.
Load in %
0.960.985 0.99 0.99
Input THDi in %
Load in %
9
6
4,5
3,52
4
6
8
10
Low input harmonic distortion (THDi)
PowerWave 33 is capable o keeping the Total Input Harmonic Distor tion
(THDi) at a low level (3.5% at 100% load). Newave’s unique technology
neutralizes the emission o harmonics at the input o the UPS, provides
greater reliability o operations or circuit breakers and extends the overall
lie o the equipment.
Low harmonic distortions saves unnecessary oversizing o gen-sets, cabling
and circuit breakers, avoids extra heating o input transormers and extends
the overall lie time o all input components.
Fully rated output power (Blade Friendly)
PowerWave 33 is rated at an output o 0.9 leading and
delivers ully rated active power or applications in the
wide range o 0.9 leading to 0.73 lagging. In other words
PowerWave 33 does not require de-rating within the
mentioned range and is ully optimised or a wide range
o IT and industrial loads and applications.
High efciency and minimum cost o ownership
With a transormer-less design and the Energy Saving Inverter Switching
(ESIS) Technology, PowerWave 33 delivers high eciency at par tial and
rated loads (up to 95.5 %). This level o eciency reduces dramatically the
Total Cost o Ownership o the UPS during its lie cycle. In addition to lower
operating costs, PowerWave 33 extends batter y run times and the lie o
components. Overall power perormance is thereore very much increased.
95.595
94.5
Load in %
100
98
96
92
90
95.5
Efciency in %
LEADING LAGGING
c o s ϕ
= 0, 6
c o s ϕ
= 0 , 7 c o
s ϕ = 0 , 8
c o s ϕ
= 0 , 9
c o s ϕ
=
1
c o s ϕ
= 0 , 9
5
kW (%)
c o s ϕ
= 0 , 9
5
c o s ϕ = 0 , 9
c o s ϕ = 0 , 8
5
c o s ϕ
= 0 , 8 c o s ϕ = 0 , 6
0
20
40
60
80
100
120
140
using 40 batte ry b lo cks using 50 batt er y block s
8/3/2019 Powerwave 33 ENG WEB 290509
http://slidepdf.com/reader/full/powerwave-33-eng-web-290509 5/6
Advanced scalable architecture
Connectivity
Newsetservice tool
SMS
Wavemon
Wavemonmonitoring
ShutdownCommand
Server Web browser monitoring
Newave Watch
PSTN
LAN/WAN
GSM
USB/RS232
I additional capacity or redundancy is needed,
up to 10 independent UPS units can be
mounted in parallel. Correspondingly, a single
system o parallel mounted UPS units candeliver a maximum power capacity o up to
2000 kVA. In all parallel congurations, each
PowerWave 33 unit operates independently
but is securely synchronised with the
others. This scalable architecture keeps the
purchasing and operating costs o your
power protection solutions exceptionally
low. As your power requirements grow, the
UPS grows with you - thanks to its fexible
scalability – even in the most conned spaces.
Your benets are lower capital commitment,
cost-eective expansion and minimal spaceoccupancy.
• Modem GSM / Fixnet or remote monitoring
(*NewavewatchTM)
Newave service center/engineer
*NewavewatchTM is a redundant remote
surveillance system and service o Newave
which complements Newave’s “Continuous
Power Protection Availability” concept.
NewavewatchTM supports Newave’s service
engineers with early detection/ identication
o anomalies, 24/365 monitoring, analysis and
diagnosis capabilities and reporting unctions.Facility managers are oered real preventive
maintenance and get rid o important
consequences or even downtimes.
PowerWave 33 is equipped with several
connection/interace types which can be
used or local and remote monitoring, status
signaling, control, maintenance and even
FirmWare upgrade. For these operations a
specic interace is oreseen or the inter-
connection o several parallel UPS.
The interaces are:
• USB, RS232 or maintenance and upgrade
Newave Service Engineer
• Dry contacts (out) or status signalslocal facility management & control
• Dry contacts (in) or external commands
local facility management & control
• LAN adapter (SNMP, MODBUS,
PROFIBUS) or monitoring
local facility management and control
PSTN
LAN/WAN
➥
Modems
LAN
Dry Contacts
8/3/2019 Powerwave 33 ENG WEB 290509
http://slidepdf.com/reader/full/powerwave-33-eng-web-290509 6/6 R e v . 2 -
0 8 / 0 8
ABBAcerAEG SVSAmerican British RacingAmerican ExpressAnsar AlmojahedinARGE NS LötschbergAXA InsuranceBank Renaissance Moscow
Bank Vontobel AGBarclays Bank Basijian InstituteBasler VersicherungBBC (British Broadcasting Corp.)BelgorodenergoBetty BarclayBlaupunktBLS Lötschbergbahn AGBNFL (British Nuclear Fuels Ltd.)Boehringer IngelheimBritish Airport Authority (BAA)British CouncilBritish TelecomBürgerspital St. GallenCable and WirelessCambridge UniversityCaterpillarCentral Bank o Russian Federation
CepsaCoca ColaCore TelecomCorreos de EspañaCredit SuisseDachserDaimler AGDanossDeutsche PostDNAEADSEDEKAEDP (Electricity o Portugal)ElisaEnoEterraFujitsuGestamp CorporationGlaxo Smith Kline
HenkelHiltonHoneywellHSBCHyattIBERIAIBMIntelInterouteIran InsuranceIran Telecom (TCI)IXEurope (Switzerland) AGKaraarin Bank LekkerlandLloyds TSBLonza AGLUKOILManor AGMehiläinen
MeridienMeteorological OfceMetropolitano de LisboaMigros Ostschweiz
Mobile TeleSystems (MTS)MobistarMotorolaNATs (National Air Trafc control)NestlèNokian RenkaatNovartis Consumer Health Schweiz AGNufeld HospitalsO2
Océ (Schweiz) AGOlviOracle CorporationOSCE KosovaOsuuspankkikeskusOutokumpuOxord UniversityPaulanerPortugal TelecomProcter & GambleRabo Bank Radio Televisión EspañolaREFER (Protuguese Railways)REPSOL-YPFRittalRitzRohde & SchwarzRolex SAROS Telecom
Roshal’s medical clinicRoyal Bank o ScotlandRoyal ScandinaviaRussian RailwaysSampo PankkiSchiphol AirportSchweiz. Bundesbahnen SBBScottish PowerSheratonSiemens Schweiz AGSoudronic AGStora EnsoStudienzentrum GerzenseeSwiss RailwaySwiss ReinsuranceT-mobileTechnionTechnische BetriebeTedjarat Bank
Telekurs Services AGTescoThalesTiebauamt NidwaldenTool-TempUnifed Energy System o RussiaUnited Bank o Switzerland (UBS)UPM-KymmeneWaitroseVAPOVeikkausWilliamsWinterthur-Assurance p.a. wincasaVneshtorgbank Vnukovo Airport MoscowVodaoneWolseleyvon Moos Stahl AGVR-Rata
Ziegler Papier AGZurichZürcher Kantonalbank
Subsidiaries
Austria
Newave Österreich GmbHUngargasse 36A-1030 WienÖsterreichTel. +43 (1) 710 96 70 16Fax +43 (1) 710 96 70 12
Brazil
Newave South America LTDARua Clodomiro Amazonas No. 1422Suite 68BR-04537-002 - São PauloTel. +55 11 3045 0809Fax +55 11 3045 [email protected]
Finland
Newave Finland OYNiittlyäntie 5 (postal)Läkkisepänkuja 6 (visiting)FIN-00620 HelsinkiTel. +358 9 751 46 100Fax +358 9 751 46 [email protected]
Germany
Newave USV Systeme GmbHSummerside Ave. C 207Baden Airpark D-77386 RheinmünsterTel. +49 7229 1866-0Fax +49 7229 [email protected]
www.newave-usv.de
Hong Kong & China
Newave Energy Hong Kong ltdRoom 2506, West Tower, Shun Tak CentreHK-168-200 Connaught RoadCentralTel. [email protected]
with branch ofce in China:
Newave Energy (Jiangmen) Limited9/F Kawa House, 49 Jiangshe Road, Jiangmen, GuangDong, ChinaPostal Code: 529000
Tel. +86 750 3680239Fax +86 750 3680229ino @newave.cn.comwww.newave.com.cn
India
Newave Energy India Private Limited102/103 Tanishka, Akurli Road,Near Big Bazar, Kandivali EastIN-400 101 MumbaiTel. +91 (22) 42179292Fax +91 (22) 42179200
Italy
NEWAVE ItaliaVia Vincenzo Ussani, 90I-00151 RomaTel. +39 06 87451674Fax. +39 06 [email protected]
Spain
Newave España SAArturo Soria 329 1 DES-28033 MadridTel. +34 (91) 768 22 22Fax +34 (91) 383 21 [email protected]
Switzerland
ServiceNet AGIndustriestrasse 5CH-5432 Neuenho Tel. +41 56 416 01 01Fax +41 56 416 01 [email protected]
with branch ofce in Biel:
Am Wald 36
CH-2504 BielSwitzerlandTel. +41 32 366 60 30Fax +41 32 366 60 [email protected]
The Netherlands
Newave UPS Systems BVStephensonweg 9NL-4207 HA GorinchemTel. +31 183 64 6474Fax +31 183 62 [email protected]
Newave Energy Holding SA
Via Luserte Sud 9CH-6572 Quartino
Switzerland
Tel. +41 91 850 29 29Fax +41 91 840 12 [email protected]
Newave SAVia Luserte Sud 9CH-6572 QuartinoSwitzerland
Tel. +41 91 850 29 29Fax +41 91 840 12 [email protected]
References
Newave Cer tifications & Recognitions
Newave Group Companies
Head Office: Operations, Sales & Marketing