Datapoints Profiles
PCLPCLPCLPCL
PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2
CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
2/23
Schneider Electric 2- CS&P – Datapoints Profiles – E01
• Content
Generalities
Inputs Profiles
Outputs Profiles
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
3/23
Schneider Electric 3- CS&P – Datapoints Profiles – E01
• Content
Generalities
Inputs Profiles
Outputs Profiles
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
4/23
Schneider Electric 4- CS&P – Datapoints Profiles – E01
Supervision Profiles … What are Supervision DataPoint?
xPS
MV
xCT
FSS, SBMC dependency
Few acquisition options
State labels
Archive&Logging / state
Interlock Boolean / state
Alarm / state
SPS, SPS_Profile
DPS, DPS_Profile
MPS, MPS_Profile
MV, MV_Profile
Counter, Counter_Profile
FOR
• SCE Profiles : Input Profiles
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
5/23
Schneider Electric 5- CS&P – Datapoints Profiles – E01
Control Profiles … What are Control DataPoint?
xPC
SetPoint
DE / SBO
Few acquisition options
State labels
Archive&Logging on event
Interlock Boolean / state
Alarm on Negative Ack.
SPC, SPC_Profile
DPC, DPC_Profile
SetPoint, SetPoint_Profile
FOR
• SCE Profiles : Output Profiles
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
6/23
Schneider Electric 6- CS&P – Datapoints Profiles – E01
• Content
Generalities
Inputs Profiles
Outputs Profiles
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
7/23
Schneider Electric 7- CS&P – Datapoints Profiles – E01
Single, Double, Multi Point Status : General Tab
Allow FSS on DPYes/No
Allow SBMC on DP(Yes/No)
when bay has SBMC ON : SBMC Substitutes values to RCP by: - SPS : Set/Reset/Suppressed - DPS : Jammed/Open/Close/Suppressed
- MPS : Undefined/Suppressed
Toggling Filtering for SPS, DPSYes/No
Initial Status
For software info => status at start-up
No
No
Never use Motion
• xPS Profiles (1)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
8/23
Schneider Electric 8- CS&P – Datapoints Profiles – E01
Single, Double, Multi Point Status : State Labels tab : Alarms / Log Print
All Invalid States or FSS Label
SPS : Set/Reset
DPS : Jammed/Open/Close/Undefined MPS : 1 among N( Open/Close
R/L => Remote/Local MPS N and associate DP impact labels
1) Labels are Business Languagedependant
• xPS Profiles (2)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
9/23
Schneider Electric 9- CS&P – Datapoints Profiles – E01
State by State, archiving policy
For OI :- No Archive, No logging = nothing in SQLHistorian database
- Archive only = all states in VTQ(states/values) SQL Historian databasetables (Trend Viewer) - Archive & Logging = all states in VTQ(states/values) SQL Historian databasetables + states marked with “Logging” inEvents SQL database table (Event Viewer+ Archive viewer + printer)
Single, Double, Multi Point Status : State Treatment Tab
Relation “has events logged on” for SOEprinting
For C264 :- Archive & Logging = Archivemeans stored in event list (2048
events in memory) & Loggingmeans displayed in event list of
front face (200 events).
• xPS Profiles (3)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
10/23
Schneider Electric 10- CS&P – Datapoints Profiles – E01
Single, Double, Multi Point Status : Interlock tab : Boolean value by state
Note : For MPS, no convention => depends on context of use
SPS Set and Reset Boolean value in all PSL and
interlocking :
convention : SET=TRUE, RESET=FALSE
DPS Jammed, Open and Closed Boolean valuein all PSL and interlocking :convention : CLOSED=TRUE, OPEN=FALSE,JAMMED=INVALID,UNDEFINED=INVALID
• xPS Profiles (4)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
11/23
Schneider Electric 11- CS&P – Datapoints Profiles – E01
Single, Double, Multi Point Status : Alarm tab, Alarm definition state by state
Alarm GenerationAppearance/Appearance disappearance
1 / 2 alarms
Alarmed state or not
Spurious SPS is Set and never reset
Alarm not generatedif state follow control (RFI SBUS)
Delay before alarm generation(if DP reset for example)
Gravity 1->5Audibility (klaxon)
Alarms are acknowledged byoperator, but clearing can be
manual or automatic
Relation “has alarm events
logged on” for alarm printing
• xPS Profiles (5)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
12/23
Schneider Electric 12- CS&P – Datapoints Profiles – E01
Measurement Values : General tab
Allow FSS on MVYes/No
Allow SBMC on MV(Yes/No) when bay in SBMC ON: Substitutes values by Suppressed
MV value display on OIMimic
No # after decimal.
U to display unit
No
No
• MV Profile (1)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
13/23
Schneider Electric 13- CS&P – Datapoints Profiles – E01
Measurement Values : State Labels tab AlarmsLog Print
IED disconnectedBoard acquisition saturated
Digital Measurement coding
error
4-20mA DC input when
under 4mA
Threshold violation
• MV Profile (2)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
14/23
Schneider Electric 14- CS&P – Datapoints Profiles – E01
State by State, archiving policy
For OI :- No Archive, No logging = nothing in SQLHistorian database
- Archive only = all states in VTQ(states/values) SQL Historian databasetables ( Trend Viewer ) - Archive & Logging = all states in VTQ(states/values) SQL Historian databasetables + states marked with “Logging” inEvents SQL database table (Event Viewer+ Archive viewer + printer)
Measurement Values : State Treatment Tab
Note : - Archive only for valid => value will be available for trend viewer - Archive & Logging for SelfCheckFault and Unknown to store acquisition errors
• MV Profile (3)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
15/23
Schneider Electric 15- CS&P – Datapoints Profiles – E01
Measurement Values : Interlocking tab
Note : Goal is use MV associated status in PSL.No convention => depends on context of use
• MV Profile (4)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
16/23
Schneider Electric 16- CS&P – Datapoints Profiles – E01
Measurement Values : Alarm Management tab
Alarm GenerationAppearance/Appearance disappearance
1 / 2 alarms
Alarmed state or not
Delay before alarm generationGravity 1->5
Audibility (klaxon)
Alarms are acknowledged byoperator, but clearing can be
manual or automatic
• MV Profile (5)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
17/23
Schneider Electric 17- CS&P – Datapoints Profiles – E01
Measurement Values : Mean Value tab cf. PS06
Reference hour :- Hour of day for min/max/average values
calculation - Daily mean values stored in monthlyVTQ table for 15 months
Reference day :- Day of month for min/max/average
values calculation - Monthly mean values stored in yearlyVTQ table for about 5 years
Daily
Monthly
Yearly
.csv VTQ tables
SQLHISTORIAN
Event
SQLHISTORIAN
VTQ35 days storing
15 months storing
5 years storing
• MV Profile (6)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
18/23
Schneider Electric 18- CS&P – Datapoints Profiles – E01
Single, Double CounTer: Status… Like MV Except
Pulse valuemultiplicative coefficient
Counter over max value
Double Counter invalidity
• Counter Profile
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
19/23
Schneider Electric 19- CS&P – Datapoints Profiles – E01
• Content
Generalities
Inputs ProfilesOutputs Profiles
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
20/23
Schneider Electric 20- CS&P – Datapoints Profiles – E01
Single, Double Point Control: General tab
Define SBUS control sequencein one or two steps :In DE : Client send control to Server Server send back Ack to Client
In SBO : - Step Selection
kept by Server with Time Out[0..600](s)
- Step Execution
SBO Many => transformer
Note : At PACiS OI Level, DE/SBO pop-up.DE with SBO popup = Control is DE appearing in SBO-like popup
• xPC Profiles (1)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
21/23
Schneider Electric 21- CS&P – Datapoints Profiles – E01
Single, Double Point Control: use and labelsSet Point => no order
Usage :Some controls are using only one“channel” e.g. Master Trip Reset
Labels “status” for control sendlogging, alarms, popup buttons
On Control
• xPC Profiles (2)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
22/23
Schneider Electric 22- CS&P – Datapoints Profiles – E01
Single, Double Point Control: interlocking and FBD tab
PSL status on control False/True
Note : Goal is use xPC associated status in PSL.
• xPC Profiles (3)
-
8/20/2019 L2 V4 03 Datapoints Profiles E 01
23/23
Schneider Electric 23- CS&P – Datapoints Profiles – E01
Single, Double Point Control: Alarm on NACK
Alarm on control Yes/No
Clearing Acknowledged alarms
Delay [0..120] Gravity [1..5] Klaxon [Yes/No] + Relation
V4.7
• xPC Profiles (4)