    Circuit Breakers

    MCCB | ELCB | MCB | RCBO

    T e c h n i c a l C a t a l o g u e

  • 7/30/2019 Circuit Braker

    2/62

    general overview ... 2

    feature

    - company profile ... 6

    MCCB

    - NF series circuit breaker, double repulsion breaking method ... 7

    - double number of copper contacts, materials of the NF series ... 8- method of installation, MCCB cross sectional area,

    positive indication & operation ... 9- suitability for isolation, compliance with standards ... 10

    - selection | quick & easy selection table ... 11- power distribution | technical details ... 12

    - ambient temperature ... 16- characteristic curves | NF series ... 17

    - physical dimensions & mounting holes | NF series ... 22- accessories | phase insulation barriers,

    electrical accessories & shunt trip ... 30

    - accessories | under voltage device ... 31- accessories | signal switches, rotary handle ... 32

    - accessories | rotary handle ... 33- mounting position | internal accessory ... 35

    - internal resistance & power loss ... 36- short circuit table | DC voltage ... 39

    - selection table | motor circuit protection ... 40- motor selection ... 41

    - installation safety distance requirement ... 43- terminal-tightening torque ... 44

    - terminal-cable & copper busbar connection data ... 45

    ELCBs

    - EG series | with overload & short circuit protection ... 46

    - EG series | operating characteristics & dimensions ... 48

    MCBs

    - BHQ series | fixed type ... 52- BHP series | plug-in type ... 53

    - BHQ & BHP | operating characteristics & dimensions ... 54

    RCBOs

    - EQ series | fixed type ... 56

    - EP series | plug-in type ... 57- EQ & EP series | dimensions & operating characteristics ... 58

    ordering codes ... 60

    contents

  • 7/30/2019 Circuit Braker

    3/62

    M C C B

    g e n e r a l o v e r v i e w

    NF series

    2

    The NF series MCCBs are available from 50AF to 1200AF.

    Pole sizes from 1 to 4 are available for the various models.

    All NF series MCCBs are suitable for isolation.

    250AF

    NF-250GP NF-250MANF-250HA NF-250L

    10kA (3P)25kA (1P to 4P)50kA (1P to 4P)65kA (3P)

    50AF

    NF-50MA

    10kA (2P & 3P)

    100AF

    NF-100GP NF-100MANF-100HA NF-100L

    10kA (2P & 3P)

    25kA (1P to 4P)50kA (1P to 4P)65kA (3P)

  • 7/30/2019 Circuit Braker

    4/62

    3

    400AF

    NF-400GP NF-400LNF-400HA

    25kA (3P & 4P)50kA (3P & 4P)65kA (3P)

    600AF & 800AF

    NF-600GP NF-800GPNF-600HA NF-800HANF-600L NF-800L

    25kA (3P & 4P)

    50kA (3P & 4P)65kA (3P)

    1200AF

    NF-1200HA

    50kA (3P & 4P)

  • 7/30/2019 Circuit Braker

    5/62

    g e n e r a l o v e r v i e w

    ELCB: EG series | with overload & short circuit protection

    4

    100AF

    EG-100MA EG-100HA

    25kA (3P & 4P)

    50kA (3P & 4P)

    250AF

    EG-250MA EG-250HA

    25kA (3P & 4P)

    50kA (3P & 4P)

    Accessories

    shunt trip under voltage trip signaling switches rotary handle

  • 7/30/2019 Circuit Braker

    6/62

    100AF

    BHP-1

    6kA (1P)

    100AF

    BHP-2

    6kA (2P)

    100AF

    BHP-3

    6kA (3P)

    100AF

    BHQ-1

    6kA (1P)

    100AF

    BHQ-2

    6kA (2P)

    100AF

    BHQ-3

    6kA (3P)

    5

    MCB: BHQ & BHP series

    RCBO: EQ & EP series | with overload &short circuit protection

    50AF

    EP-1

    10kA (1P)

    50AF

    EP-2

    10kA (2P)

    50AF

    EP-3

    10kA (3P)

    50AF

    EQ-1

    10kA (1P)

    50AF

    EQ-2

    10kA (2P)

    50AF

    EQ-3

    10kA (3P)

  • 7/30/2019 Circuit Braker

    7/62

    company profile

    Since our inception in 1974, our company specializes in manufacturing low

    voltage circuit breakers and have a reputation of producing products of

    consistent quality and high reliability.

    Our manufacturing facilities are certified to the international quality standards of

    ISO 9001, while our products are certified by ASTA Certification Services UK.

    With such high standards, our range of circuit breakers are able to meet your

    highest demands for quality, safety and reliability.

    f e a t u r e

    6

  • 7/30/2019 Circuit Braker

    8/62

    NF series circuit breakers

    The demand for economical and high performance circuit

    breakers is ever increasing in the global market. The NF

    series circuit breakers provide a simple and reliable

    solution to meet this global demand where quality,

    performance and compliance are required.

    The NF series circuit breakers have been engineeredto provide effective protection to low voltage power

    distribution systems. The NF series is a complete range

    of MCCBs from 10A to 1200A with 1, 2, 3 and 4 pole

    versions. An extensive range of electrical accessories is

    also available.

    double repulsion breaking method

    The double repulsion method uses areverse-loop of current (I) flowing in

    essentially opposite directions (see figure).

    This creates a repulsion action and results

    in a greater opening force (Fm) between

    the fixed and moving contacts. This force

    also assists to rapidly extinguish the arc,

    thereby causing the moving contacts to

    open faster. A faster breaking time is

    achieved with this design.

    7

    Fm Fmopening

    moving contacts

    fixed contact

    M C C B

  • 7/30/2019 Circuit Braker

    9/62

    M C C B

    double number of contact coppers

    For the NF600 and above circuit breakers,

    double moving contacts are used instead

    of a single contact. This additional moving

    contact improves the short circuit breaking

    performance and reduces contact wear.

    materials of the NF series

    8

    The design of the NF series circuit breakers makes itsuitable to be used in hot and humid climates. The

    material used for the circuit breaker casing

    consists of synthetic resins reinforced with

    glass fibers. Furthermore, the metal parts

    used in the breakers are chemically treated

    to protect against corrosion. The external

    copper terminals are tin-plated to prevent

    oxidation.

    double moving

    contacts in NF1200

  • 7/30/2019 Circuit Braker

    10/62

    method of installation

    The NF series circuit breakers

    can be installed in vertical or

    horizontal position without any

    impact on its performance or

    de-rating of characteristics.

    MCCB cross sectional area

    positive indication & operation

    9

    horizontal vertical

    The circuit breaker operating handle is designed to indicate the exact position of

    its moving contacts. Its trip-free operating mechanism cannot indicate that the

    breaker is ON if the moving contacts are in the OFF position. If the breaker trips

    due to an electrical fault or overload the handle will be in between the ON and

    OFF position. This is the TRIP position. To switch the breaker ON after tripping,

    the handle position must be switched toOFF

    position first and so to reset thebreaker and then switch to the ON position.

    BA

    FD E

    C

    Parts Index for cross-sectional area of MCCB

    A MCCB casing made of high-impact BMC material reinforced with

    glass fibres, providing a safe and strong housing in the event of

    breaking high-fault currents.

    B Trip-free mechanism ensuring positive operation and isolation

    suitability. Designed for long service life and high number of

    operating cycles. Metal parts in mechanism are chemically treated to

    withstand harsh tropical weather conditions.C Arc chutes with predefined steel plates arrangement, provide high

    breaking capabilities.

    D Fixed and moving contacts utilizing the reverse loop current

    method, creates a repulsion force thus rapidly extinguishing the arc.

    E Common trip mechanism to ensure breaking of all poles even when

    the fault occurs at a particular pole.

    F Trip release consists of thermal (bi-metal) and magnetic devices

    suitable for use in AC or DC supply voltages.

  • 7/30/2019 Circuit Braker

    11/62

    M C C B

    suitability for isolation

    In compliance with IEC 60947-2 standard, NF series

    circuit breaker guarantees no leakage currents and over-

    voltage withstand between the supply and load terminals

    when its moving contacts are in the open position.

    compliance with standards

    10

    The NF series circuit breakers have been designedto meet international standards, complying with the

    following standards:

    1. IEC 60947-2: International Electro Committee

    Standard

    2. BSEN 60947-2: British Standard European Norm

    3. JIS C 8201-2: Japan Industrial Standard

    4. GB 14048-2: China Standard

    5. CNS 14816-2: Taiwan Standard

    6. CE: Conformity European

    test trip button isolation

  • 7/30/2019 Circuit Braker

    12/62

    selection | quick & easy table

    65502510

    NF-50MA

    NF-100GP

    NF-100MA NF-100LNF-100HA

    NF-100GP

    NF-250GP NF-250MA NF 250HA NF-250L

    NF-400GP NF-400HA NF-400L

    NF-600GP NF-600HA NF-600L

    NF-800GP NF-800HA NF-800L

    NF-1200HA

    RatedCurrent

    In (A)

    10

    15

    20

    30

    40

    50

    60

    75

    80

    100

    125

    150

    160

    175

    200

    225

    250

    250

    300

    350

    400

    500

    600

    700

    800

    1000

    1200

    Interrupting Capacity Icu (kA) Sym at 415 Vac

    11

  • 7/30/2019 Circuit Braker

    13/62

    Rated Short CircuitBreaking Capacity: (kA)

    Rated Service Short CircuitBreaking Capacity: I cs = % I cu

    600V

    DC

    400V

    500V

    440V

    415V

    380V

    230V

    IEC 60947-2

    M C C B

    p o w e r d i s t r i b u t i o n

    12

    technical details | electrical characteristicsNF-100NF-50

    50AF 100AF

    NF-250

    250AF

    10 15 2030 40 50

    2 3

    600

    8

    MA

    5

    7.510

    10

    10

    15

    25

    5

    50

    7.5

    10

    15

    25

    5

    A

    2

    20000

    model Code

    Ampere Frame (AF)

    Rated Current: In (A)at Ambient Temp 50C

    Number of Poles Available

    Rated Insulation Voltage: U i(V)

    Rated Impulse withstandVoltage: U imp (kV)

    Rated Ultimate Short CircuitBreaking Capacity: I cu (kA)

    10 15 20 30 4050 60 75 80 100

    1 2 3 4

    690

    8 8 8 8

    GP MA HA L

    5 10 10 35

    7.5 15 40 5010 25 50 65

    10 25 50 65

    10 25 50 65

    15 30 60 100

    25 50 85 125

    5 10 20 40

    50 50 50 50

    690

    8 8 8 8

    GP MA HA L

    5 10 10 35

    7.5 15 40 5010 25 50 65

    10 25 50 65

    10 25 50 65

    15 30 60 100

    25 50 85 125

    5 10 20 40

    50 50 50 50

    7.5 10 30 50

    10 22 50 65

    15 30 50 100

    25 50 85 125

    7.5 10 30 50

    10 22 50 65

    15 30 50 100

    25 50 85 125

    5 10 20 40

    A A A A

    2 2 2 2

    15000

    125 150 160 175200 225 250

    3 4

    5 10 20 40

    A A A A

    2 2 2 2

    15000

    690V

    250V

    Suitable for Isolation

    Utilization Category

    Pollution Degree

    No. of Electrical Operations

    440V

    380V

    220V

    JIS C 8201-2(sym)

    DC

    250V

    Notes: - denotes available.

  • 7/30/2019 Circuit Braker

    14/62

    Notes: - denotes available.

    Rated Short CircuitBreaking Capacity:(kA)

    Rated Service Short CircuitBreaking Capacity: I cs = % I cu

    600V

    DC

    400V

    500V

    440V

    415V

    380V

    230V

    IEC 60947-2

    13

    technical details | electrical characteristicsNF-600 & NF-800NF-400

    400AF 800AF

    NF-1200

    1200AF

    1000 1200

    3 4

    690

    8

    HA

    10

    4050

    50

    50

    60

    85

    40

    50

    30

    50

    50

    85

    40

    A

    3

    8000

    model Code

    Ampere Frame (AF)

    Rated Current: In (A)at Ambient Temp 50C

    Number of Poles Available

    Rated Insulation Voltage: U i(V)

    Rated Impulse withstandVoltage: U imp (kV)

    Rated Ultimate Short CircuitBreaking Capacity: I cu (kA)

    250 300350 400

    3 4

    690

    8 8 8

    GP HA L

    10 10 35

    22 40 5025 50 65

    25 50 65

    25 50 65

    30 60 100

    50 85 125

    20 40 40

    50 50 50

    690

    8 8 8

    GP HA L

    10 10 35

    22 40 5025 50 65

    25 50 65

    25 50 65

    30 60 100

    50 85 125

    20 40 40

    50 50 50

    18 30 50

    25 50 65

    30 50 100

    50 85 125

    18 30 50

    25 50 65

    30 50 100

    50 85 125

    20 40 40

    A A A

    3 3 3

    11000

    500 600700 800

    3 4

    20 40 40

    A A A

    3 3 3

    11000

    690V

    250V

    Suitable for Isolation

    Utilization Category

    Pollution Degree

    No. of Electrical Operations

    440V

    380V

    220V

    JIS C 8201-2(sym)

    DC

    250V

  • 7/30/2019 Circuit Braker

    15/62

    mechanical characteristics

    M C C B

    p o w e r d i s t r i b u t i o n

    14

    technical details

    NF-100NF-50

    50AF 100AF

    NF-250

    250AF

    model Code

    Ampere Frame (AF)

    Fixed thermal,Fixed Magnetic 10 x Ith

    Fixed thermal,

    Adjustable Magnetic

    thermomagnetic trip release

    MARated Ultimate Short Circuit

    Breaking Capacity: I cu (kA)GP MA HA L GP MA HA L

    1 2 3 42 3

    50 75

    130 130

    68 68

    90 90

    110 110

    25

    42 60 90 120

    155 155 155 155

    68 68 68(80) 68

    90 90 90(102) 90

    132 132 132 132

    29.5 30 30

    1 3 4

    48 105 140

    165 165 165

    68 68(80) 68

    92 92(104) 92

    126 126 126

    35 35 35

    M5 clampterminal screw

    25000

    Number of Poles (P)

    Type of Terminals

    No of Mechanical Operations

    M8 screw

    20000

    M8 screw

    20000

    0.4 0.5Weight (kg) 0.5 0.7 1.0(1.2) 1.4 0.7 1.5(1.6) 1.9

    Shunt Trip Device

    Under Voltage Trip Device

    Auxiliary Switch

    Alarm Switch

    Auxiliary + Alarm Switch

    Rotary Handle

    accessories

    Notes: All L-type breakers are only available in the 3-pole version; ( ) denotes for L-type.

    - denotes available; however, all accessories are not available for 1-pole models.

    aa

    a

    b

    c

    ca

    bb

    ON

    OFF

    a

    aa

    ca

    bbb

    c

    (mm)

  • 7/30/2019 Circuit Braker

    16/62

    mechanical characteristics

    15

    technical details

    NF-600 & NF-800NF-400

    400AF 800AF

    NF-1200

    1200AF

    model Code

    Ampere Frame (AF)

    Fixed thermal,Fixed Magnetic 10 x Ith

    Fixed thermal,

    Adjustable Magnetic

    thermomagnetic trip release

    GP HA LRated Ultimate Short CircuitBreaking Capacity: I imp (kA)

    GP HA L HA

    Shunt Trip Device

    Under Voltage Trip Device

    Auxiliary Switch

    Alarm Switch

    Auxiliary + Alarm Switch

    Rotary Handle

    accessories

    Notes: All L-type breakers are only available in the 3-pole version; ( ) denotes for L-type.

    - denotes available.

    25000No of Mechanical Operations 20000 20000

    5.5(6.0) 7.2Weight (kg) 10.0(11) 12.0 15.0 19.0

    3 43 4

    140 196

    257 257

    103 103

    155 155

    194 194

    44 44

    210 280

    275 275

    103 103

    155 155

    243 243

    70 70

    3 4

    210 280

    400 400

    103 103

    155 155

    370 370

    70 70

    M12 Bolt

    Number of Poles (P)

    Type of Terminals M12 Bolt M12 Bolt

    aa

    a

    b

    c

    ca

    bb

    ON

    OFF

    a

    aa

    ca

    bbb

    c

    (mm)

  • 7/30/2019 Circuit Braker

    17/62

    10

    15

    20

    30

    40

    50

    60

    75

    80

    100

    125

    150

    160

    175

    200

    225

    250

    300

    350

    400

    500

    600

    700

    800

    1000

    1200

    M C C B

    a m b i e n t t e m p e r a t u r e

    The NF series circuit breakers are able to operate in temperatures between 25 to 70C. The nominal current

    of circuit breakers are rated 100% at 50C. Please refer to the table below for temperature derating.

    1-Pole, 2-Pole, 3-Pole and 4-Pole

    30C25C 40C35C 50C45C 60C55C 70C65CIn (A)

    11.2 10.9

    16.8 16.4

    22.4 21.8

    33.6 32.7

    42.2 41.8

    52.8 52.3

    63.3 62.7

    79.1 78.4

    84.4 83.6

    105.5 104.5

    138.1 136.3

    165.8 163.5

    176.8 174.4

    193.4 190.8

    221.0 218.0

    248.6 245.3

    282.5 275.0

    339.0 330.0

    395.5 385.0

    452.0 440.0

    557.5 547.5

    669.0 657.0

    763.0 749.0

    872.0 856.0

    1110.0 1090.0

    1308.0 1272.0

    10.8 10.5

    16.2 15.8

    21.6 21.0

    32.4 31.5

    41.4 41.0

    51.8 51.3

    62.1 61.5

    77.6 76.9

    82.8 82.0

    103.5 102.5

    134.4 131.3

    161.3 157.5

    172.0 168.0

    188.1 183.8

    215.0 210.0

    241.9 236.3

    270.0 262.5

    324.0 315.0

    378.0 367.5

    432.0 420.0

    537.5 522.5

    645.0 627.0

    735.0 728.0

    840.0 832.0

    1070.0 1045.0

    1260.0 1248.0

    10.3 10.0

    15.5 15.0

    20.6 20.0

    30.9 30.0

    40.4 40.0

    50.5 50.0

    60.6 60.0

    75.8 75.0

    80.8 80.0

    101.0 100.0

    128.8 125.0

    154.5 150.0

    164.8 160.0

    180.3 175.0

    206.0 200.0

    231.8 225.0

    257.5 250.0

    309.0 300.0

    360.5 350.0

    412.0 400.0

    512.5 500.0

    615.0 600.0

    714.0 700.0

    816.0 800.0

    1025.0 1000.0

    1224.0 1200.0

    9.8 9.6

    14.7 14.4

    19.6 19.2

    29.4 28.8

    38.4 37.2

    48.0 46.5

    57.6 55.8

    72.0 69.8

    76.8 74.4

    96.0 93.0

    122.5 118.8

    147.0 142.5

    156.8 152.0

    171.5 166.3

    196.0 190.0

    220.5 213.8

    243.8 236.3

    292.5 283.5

    341.3 330.8

    390.0 378.0

    485.0 475.0

    582.0 570.0

    686.0 672.0

    784.0 768.0

    970.0 945.0

    1176.0 1140.0

    9.4 9.2

    14.1 13.8

    18.8 18.4

    28.2 27.6

    36.6 36.0

    45.8 45.0

    54.9 54.0

    68.6 67.5

    73.2 72.0

    91.5 90.0

    116.3 111.3

    139.5 133.5

    148.8 142.4

    162.8 155.8

    186.0 178.0

    209.3 200.3

    231.3 222.5

    277.5 267.0

    323.8 311.5

    370.0 356.0

    465.0 450.0

    558.0 540.0

    658.0 644.0

    752.0 736.0

    920.0 900.0

    1128.0 1104.0

    16

  • 7/30/2019 Circuit Braker

    18/62

    tripping curve temperature characteristic

    tripping curve temperature characteristic

    NF-50MA | characteristic curves

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Opera

    tingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Operating Characteristics

    Frame size: 50AF

    10A 15A 20A 30A 40A 50A

    Max

    Min

    300250

    200

    150

    1008070

    10 20 30 40 50 60

    Operatingtime

    Currentrating(%)

    Ambient temperature ( C)

    Rated ambient 50 C

    Ratedambient

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Operating Characteristics

    Frame size: 100AF

    10A 15A 20A 30A 40A

    50A 60A 75A 80A 100A

    Max

    Min

    Time delay tr ip I nst an tane ous tr ip

    130

    120

    110

    90

    100

    10 20 30 40 50 6080

    Rated ambient 50 C

    Currentrating

    (%)

    Ambient temperature ( C)

    Ratedambient

    10A~30A

    40A~100A

    NF-100GP, MA & HA | characteristic curves

    17

    M C C B

    c h a r a c t e r i s t i c s

  • 7/30/2019 Circuit Braker

    19/62

    NF-250GP, MA & HA | characteristic curves

    NF-400GP & HA | characteristic curves

    18

    M C C B

    c h a r a c t e r i s t i c s

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Opera

    tingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Operating Characteristics

    Frame size: 250AF

    125A 150A 160A 175A

    200A 225A 250A

    Max

    Min

    Time delay tr ip I ns tant aneous t ri p

    Max. Total

    interrupting time

    130

    120

    110

    100

    90

    10 20 30 40 50 60 7080

    Rated ambient 50 C

    Currentrating(%)

    Ambient temperature ( C)

    Ratedambient

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Operating Characteristics

    Frame size: 400AF

    250A 300A 350A 400A

    Max

    Min

    Max. Total

    interrupting time

    Time delay tr ip I nst an tane ous tr ip

    130

    120

    110

    90

    100

    10 20 30 40 50 60 7080

    Rated ambient 50 C

    Currentrating(%)

    Ambient temperature ( C)

    Ratedambient

    tripping curve temperature characteristic

    tripping curve temperature characteristic

  • 7/30/2019 Circuit Braker

    20/62

    19

    NF-600/800GP & HA | characteristic curves

    NF-1200HA | characteristic curves

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Opera

    tingtime

    100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Max

    Min

    Operating Characteristics

    Frame size: 600AFrame size: 800A

    500A 600A 700A 800A

    Time delay trip Instantaneous trip

    800AF

    600AF

    Max. Total

    interrupting time

    tripping curve

    130

    120

    110

    100

    90

    10 20 30 40 50 60 7080

    Rated ambient 50 C

    Currentrating(%)

    Ambient temperature ( C)

    Ratedambient

    600AF

    800AF

    temperature characteristic

    240

    120

    60

    20

    106

    4

    2

    140

    20

    10

    64

    2

    1

    0.60.4

    0.2

    0.10.06

    0.02

    0.01

    Operatingtime

    Multiple of rated current

    1.5 2 3 4 5 6 7 8 10 15 20 30 4 0 50 80 100

    Second

    Minute

    InItr

    Low High

    1000A 3000A25%

    In: Rated current(A)Itr: Instantaneous

    trip current

    3600A25%

    6000A10%

    7200A10%1200A

    Mix: value

    Max: value

    Adjustable

    Instantaneoustripping

    setting range

    Max total fault

    clearing time

    tripping curve

    130

    120

    110

    100

    90

    10 20 30 40 50 60 7080

    Rated ambient 50 C

    Currentrating(%)

    Ambient temperature ( C)

    R

    atedambient

    1000AF

    1200AF

    temperature characteristic

  • 7/30/2019 Circuit Braker

    21/62

    NF-100L | characteristic curves

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Opera

    tingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Max

    Min

    Operating Characteristics

    Frame size: 100AF

    10A 15A 20A 30A 40A

    50A 60A 75A 80A 100A

    Time delay t ri p I ns tant aneo us t ri p

    NF-250L | characteristic curves

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Max

    Min

    Operating Characteristics

    Frame size: 250AF

    125A 150A 160A 175A

    200A 225A 250A

    Max. Total

    interrupting time

    Time delay t ri p I nst an tane ous tr ip

    tripping curve

    tripping curve

    20

    M C C B

    c h a r a c t e r i s t i c s

  • 7/30/2019 Circuit Braker

    22/62

    21

    NF-400L | characteristic curves

    NF-600L, 800L | characteristic curves

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Opera

    tingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Max

    Min

    Operating Characteristics

    Frame size: 400AF

    250A 300A 350 400A

    LtrIn

    250A

    300A

    350A

    400A

    175025%

    210025%

    245025%

    280025%

    400010%

    480010%

    560010%

    640010%

    Lo Hi

    Adjustment

    range 400AF Max. Total

    interrupting time

    Time delay t ri p I nst an taneo us t ri p

    tripping curve

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Max

    Min

    Operating Characteristics

    Frame size: 600AFFrame size: 800AF

    500A 600A 700A 800A

    Inst. trip adjustment

    range (4 steps)

    Controlsetting

    600

    Lo2

    3HiLo23Hi

    500100800

    11001400280350100550750950280

    800

    Inst tripcurrent(%)

    600AF 800AF

    Adjustment

    range 800AF

    Adjustment

    range 600AF

    Max. Total

    interrupting time

    Time delay trip Instantaneous trip

    tripping curve

  • 7/30/2019 Circuit Braker

    23/62

    NF-50MA | front connection

    22

    M C C B p h y s i c a l d i m e n s i o n s

    & m o u n t i n g h o l e s

    CLCL

    CL

    50

    22

    75

    25

    50

    130

    110

    50

    Mounting hole

    Trip button

    Insulation barrier (removable)

    84

    4

    .5

    50

    4 72

    90

    68

    61

    27

    Screw24

    8.

    5

    110 R

    1

    52

    CLCL

    CL

    2522.5

    50 70M4 Screw

    or 5mm

    CL CL

    CL

    BreakerBreaker

    2-pole 3-pole

    2-pole 3-pole

  • 7/30/2019 Circuit Braker

    24/62

    NF-100GP, MA & HA | front connection

    23

    CL

    CLCL

    CL

    60

    22

    90

    30

    50

    155

    134

    60

    Mounting hole

    Tripbutton

    Insulation barrier

    (removable)

    Neutral pole

    30

    90

    120

    50

    155

    134

    102

    4.5

    50

    4 72

    90

    68

    61

    27

    Screw24

    8.

    5

    N

    R1 5

    2

    CLCL

    CL

    3028

    57M4 Screw

    or 5mm

    132

    CL

    30

    CL CL

    CL

    Breaker Breaker

    86

    Breaker

    2-pole 3-pole

    2-pole 3-pole

    4-pole

    4-pole

  • 7/30/2019 Circuit Braker

    25/62

    24

    NF-250GP, MA & HA | front connection

    M C C B p h y s i c a l d i m e n s i o n s

    & m o u n t i n g h o l e s

    CL

    CL

    N

    70

    100

    120

    4.5

    50

    144

    165

    100

    30

    105

    1404 72

    92

    68

    61

    45

    Screw

    22

    105

    Mounting

    hole

    Trip

    button

    Insulation

    barrier

    (removable)

    Neutral

    pole

    24

    8.5

    CL CL CL

    126

    52

    35100

    32.5

    Breaker

    35

    R1CL

    M4 Screw

    or 5mm

    Breaker

    3-pole

    3-pole

    4-pole

    4-pole

  • 7/30/2019 Circuit Braker

    26/62

    25

    NF-400GP & HA | front connection

    CL

    CL

    14

    M12 bolt

    Neutral pole

    Mounting

    hole

    Trip

    button

    Insulation barrier

    (removable)Conductor

    110

    51

    112

    140

    1

    02

    39

    39

    5 107

    155

    103

    97

    44

    44

    94.5

    8

    CL

    CL 28

    185

    196

    56

    168

    2

    57

    43

    16

    N

    12.5

    47

    7

    CL CL

    CLCL

    M6 screw

    or 7mm

    Breaker

    4444

    194 CL

    CL

    Breaker

    118

    R692

    3-pole 4-pole

    3-pole

    4-pole

  • 7/30/2019 Circuit Braker

    27/62

    NF-600/800GP & HA | front connection

    26

    M C C B p h y s i c a l d i m e n s i o n s

    & m o u n t i n g h o l e s

    Mounting hole

    Trip button

    Insulation barrier

    (removable)

    110

    32

    32

    32

    15

    70

    210

    280

    87

    87

    102

    14

    8

    275

    14

    40

    140

    210

    CL CL

    CL

    14

    M12bolt

    Neutral

    pole

    N

    600A frame 8

    800A frame 12

    600A frame 44

    800A frame 46

    600A frame 8

    15

    5

    94.5

    97

    103

    107

    155

    800A frame 12

    600A frame 14

    800A frame 46

    Conductor

    243

    92

    70

    CL CL

    CLCL

    CLCL

    Breaker

    Breaker

    70

    R6

    51

    172

    M6 Screw

    or 7mm

    3-pole 4-pole

    3-pole

    4-pole

  • 7/30/2019 Circuit Braker

    28/62

    NF-1200HA | front connection

    27

    Mounting hole

    Trip

    button

    Insulation barrier

    (removable)

    110

    32

    32

    20

    70

    210

    280

    87

    87

    102

    14

    8

    400

    14

    40

    140

    210

    CL CL

    CL

    14

    M12bolt

    Neutral

    pole

    N

    17

    46

    15

    5

    94.5

    97

    103

    107

    155

    17

    46

    Conductor

    40

    370

    92

    70

    CL CL

    CLCL

    CLCL

    Breaker

    Breaker

    70

    R6

    51

    172

    M6 Screw

    or 7mm

    3-pole

    4-pole

    3-pole 4-pole

  • 7/30/2019 Circuit Braker

    29/62

    28

    NF-100L | front connection

    NF-250L | front connection

    CL

    60

    134

    132

    155

    50

    22

    90

    Mounting hole

    Trip button

    Insulation barrier

    (removable)

    102

    4.5

    50

    4 84

    102

    80

    73

    27

    Screw24

    8.5

    CL CL

    52

    86

    30

    M4 Screw

    or 5mm

    R1

    Breaker

    CL

    70

    1

    44

    1

    65

    100

    22

    105

    Mounting hole

    Trip button

    Insulation barrier

    (removable)

    1

    02

    4.5

    5

    0

    4 84

    104

    80

    73

    45

    Screw24

    8.5

    126

    CL CL

    52

    100

    35

    R1

    M4 Screw

    or 5mm

    Breaker

    M C C B p h y s i c a l d i m e n s i o n s

    & m o u n t i n g h o l e s

    3-pole

    3-pole

    3-pole

    3-pole

  • 7/30/2019 Circuit Braker

    30/62

    NF-400L | front connection

    NF-600/800L | front connection

    CLCL CL

    CL

    CLCL

    14

    M12 bolt

    M6 Screw

    or 7mm

    Mounting

    hole

    Trip

    button

    Insulation barrier

    (removable)

    Conductor

    Breaker110

    51

    28

    112

    140

    44118

    R6

    257

    102

    39

    92

    39

    5 107

    155

    103

    97

    44

    44

    94.5

    8

    194

    43

    16

    12.5

    7

    47

    Mounting hole

    Trip

    button

    Insulation barrier

    (removable)

    110

    87

    275

    32

    15

    243

    92

    87

    14

    40

    140

    210

    CL

    CL 102

    14

    8

    600A frame 8

    800A frame 12

    600A frame 44

    800A frame 46

    600A frame 8

    15

    5

    94.5

    97

    103

    107

    155

    800A frame 12

    600A frame 14

    800A frame 46

    Conductor

    70

    CL

    CL CL

    CLBreaker

    R6

    172M6 Screw

    or 7mm

    29

    3-pole

    3-pole

    3-pole

    3-pole

  • 7/30/2019 Circuit Braker

    31/62

    phase insulation barriers

    Inter phase barriers are provided as standard. The use

    of the inter phase barriers is

    necessary to increase the

    clearance distances between

    phases to prevent electrical

    faults during the operation

    of the circuit breaker.

    electrical accessories & shunt trip

    All electrical accessories supplied for the breaker are pre-

    wired. Accessories such as Shunt Trip, Under Voltage Trip,

    Alarm Switch, Auxiliary Switch and combination Alarm and

    Auxiliary Switch can be fitted into the breaker accessory

    compartments. Please refer to the table in page 31 for the

    accessories installation guide.

    Shunt Trip Device

    The Shunt Trip device opens the circuit breaker by means

    of an electrical signal. Voltages between 70% and 110% of

    the coil voltage rating will operate the shunt trip device.

    All Shunt Trip devices are factory fitted with a cut-off

    supply switch.30

    M C C B

    a c c e s s o r i e s

    baModel

    NF-50 59 59

    NF-100 59 59

    NF-250 62 100

    NF-400 95 116

    NF-600 95 116

    NF-800 top95 116

    NF-1200 95 116

    a

    bdimensions of phase

    barrier insulators in mm

  • 7/30/2019 Circuit Braker

    32/62

    < 15 < 15 < 15 8 to 15 8 to 15 8 to 15

    under voltage trip device

    31

    The Under Voltage Trip device will open the circuit breaker contacts when the supply

    voltage to the coil drops below 70% of its voltage rating.

    After tripping, the circuit breaker can be closed manually

    again when the supply voltage is 85% of its coil voltage

    rating or more.

    The Under Voltage Trip device is always energized duringnormal conditions when supply voltage is healthy.

    NF-1200NF-600NF-400NF-250NF-100NF-50

    Coil Power Consumption (VA)50 / 60 Hz

    Coil Voltage

    200 200120 20 (100V)

    50 (200V)

    120 120

    200 200

    200 200

    120 (330V)

    170 (450V)

    200

    10

    8 to 15

    NF-800

    200

    200

    200

    200

    10 70

    120

    10

    120 120

    50

    AC 110 - 240

    AC 100 - 450

    AC 200 - 240

    AC 380 - 450

    AC 380 - 550

    DC 100 - 125

    AC Coil Voltage Consump (VA) Trip Time (ms)Model

    5 < 30

    5 5 to 30

    380-415 440-480

    400-440

    100-110 200-220

    100-110 200-220

    5 5 to 30

    5 6 to 35

    400-440

    380-450

    100-110 200-220

    100-120 200-240

    NF-250 & below

    NF-400

    NF-800

    NF-1200

    Trip Time (ms)

    Note: Other voltages can be supplied on demand.

  • 7/30/2019 Circuit Braker

    33/62

    signaling switches

    The Signaling switches allow the breaker

    status information to be obtained remotely.

    The signaling switch consists of several dry

    contacts with both normally open (N.O.) and

    normally closed (N.C.) positions.

    Auxiliary Switch - Provides breaker ON and

    OFF status information.

    Alarm Switch - Provides breaker TRIP status

    information.

    Auxiliary + Alarm Switch - Provides breaker

    ON, OFF and TRIP status information.

    rotary handle | mechanism

    32

    M C C B

    a c c e s s o r i e s

    The breaker mounted rotary handle mechanism allows the user to easily switch thebreaker ON by a rotating action.

    The rotary handle mechanism is equipped with a safety device that prevents the

    panel door from being open when the breaker is in ON position. A bypass screw is

    provided for manual intervention when breaker is in ON position.

    Pad locking facility is available on the rotary handle. The handle can be pad locked

    when the breaker is in OFF position.

    Please refer to the above

    circuit diagram for the switch

    terminal codes in order to

    obtain different contact

    positions, such as N.O. and

    N.C. to suit the application.

    Auxiliary Switch

    Alarm Switch

    AXa

    AXbAXc

    ALa

    ALbALc

  • 7/30/2019 Circuit Braker

    34/62

    DrillingPlan

    ExternalDimensions

    Figure Dimensions (mm)Mounting

    ScrewsType Breaker Type

    Noof

    Pole

    a

    b

    c

    d

    e

    e

    A B C D

    95

    105

    117

    107

    119

    183

    25

    30

    44

    70

    111

    132

    (116)

    35126

    (145)

    194

    243

    M4 x 0.7

    screw

    or 5

    M6

    screwor 7

    (X)

    breakersmounting

    screws (2pcs)

    (Y) operating

    handle

    mounting

    screws (2pcs)

    (X) (Y)

    breakers

    mounting

    screws (4pcs)

    AC-NF-RHN0

    AC-NF-RHN1

    AC-NF-RHN2

    AC-NF-RHN3

    AC-NF-RHN4

    NF-50MA

    NF-100GP MA HA

    NF-100L

    EG-100MA HA

    NF-250GP MA HA

    NF-250L

    EG-250MA HA

    NF-400GP HA L

    NF-600GP HA LNF-800GP HA L

    NF-1200HA

    3P

    3P

    4P

    3P

    4P

    3P 4P

    3P

    4P

    rotary handle | external dimensions

    104

    45

    104

    Panel thickness1.2~3.2

    A 2

    150

    50

    20

    150

    130

    Panel thickness

    Extension handle

    (option)

    1.2~3.2A 2

    rotary handle | drilling plan

    78

    78

    F

    Center of breaker

    112

    1

    12

    F

    Center of breakerbreaker

    DB

    C

    (x) (Y)

    (Y) (X)

    90

    11

    8

    CL CL

    33

    Figure (a)

    Figure (c) Figure (d) Figure (e)

    Note All rotary handles are supplied with M4 x 0.7 screws and self-tapping 5mm screws.

    Figure (b)

  • 7/30/2019 Circuit Braker

    35/62

    rotary handle | appearance

    M C C B

    a c c e s s o r i e s

    34

    A direct rotating operating handle has a standard safety device which prevents the

    breaker from closing as long as the cover is open. It indicates the tripping of the

    breaker even in ON-lock position, but only in cases when a single padlock (35mm)

    is used. The degree of protection, in accordance with IEC529, is IP3X (or IP5X with

    provision of dustproof packing).

    The use of the

    rotary handle

    mechanism

    increases the IP

    rating of the breaker

    The figure above shows the relationship

    between the hinge and breaker viewed

    from the load side of the breaker.

    X1 X2

    H H

    Right hingeLeft hinge

    Front panel

    Operating handle

    Breaker

    Left hingeX1

    Left hingeH

    Center of hinge & Breaker

    Type

    0 or more(5H + 100)

    or more

    0 or more(8H + 100)

    or more

    Right hingeX2

    Right hingeH

    Less than 10

    10 or more

    170 or more

    (5H + 120) or more

    0 or more (4H + 70) or more

    AC-NF-RHN0 to

    AC-NF-RHN2

    AC-NF-RHN3 to

    AC-NF-RHN4

  • 7/30/2019 Circuit Braker

    36/62

    M C C B

    35

    mounting position | internal accessory

    NF-1200HA

    NF-600/800GP HA L

    NF-400GP HA L

    NF-250GP MA HA L

    NF-100GP MA HA L

    NF-50MA

    MCCB models

    Accessories

    R1 & 2 R1 & 2

    R1 & 2 R1 & 2

    R1 & 2 R1 & 2

    R1 & 2 R1 & 2

    R1 & 2 R1 & 2

    R1 & 2 R1 & 2

    L1, L2, L3 L1, L2, L3

    L1, L2, L3 L1, L2, L3

    L1, L2, L3 L1, L2, L3

    L1 & L2 L1, L2

    L1 & L2 L1, L2

    L1 & L2 L1, L2

    L1 & L2

    L1 & L2

    L1 & L2

    L1 & L2

    L1 & L2 L1 & L2

    Shunt TripCoil

    (STC)

    Under VoltageTrip (UVT)

    Auxiliary Switch(AUS)

    Alarm Switch(ALS)

    Auxiliary +Alarm Switch

    (AAS)

    Notes

    1) It is NOT possible to install both UVT and STC in the same MCCB.

    2) For NF600 onwards, it is possible to install up to a maximum of 4 Auxiliary. Switches or 2 Alarm switches.

    3) UVT requires a voltage module that is installed on the right side lead wire terminal.

    L R

    MCCBfront view

    L = Left compartment; R = Right Compartment

    Accessory compartment

    slot markings

    1234

    4321

    right side

    left side

  • 7/30/2019 Circuit Braker

    37/62

    NF-250MA

    LossW

    Resistance

    u

    NF-100MA

    LossW

    Resistance

    u

    8700

    6200

    3570

    1980

    1480

    1.6 7200 0.7

    2.0 6700 1.5

    2.5 6000 2.4

    3.2 3100 2.8

    3.4 1990 3.1

    3.7 1480

    1200

    1100

    980

    770

    3.7

    4.3

    6.2

    6.5

    7.7

    575 9.0

    11.8

    12.1

    14.6

    16.9

    525

    395

    365

    335

    NF-800GP

    internal resistance & power loss

    LossW

    Resistance

    u

    NF-600GP

    LossW

    Resistance

    u

    NF-400GP

    LossW

    Resistance

    u

    NF-250GP

    LossW

    Resistance

    u

    NF-100GP

    LossW

    Resistance

    u

    NF-50MA

    Resistance

    uLossW

    Type

    In A

    10A 60000 6.0

    58000 1.3

    45000 1.8

    32000 2.9

    19000 3.0

    1650

    1175

    1120

    1010

    820

    4.1

    4.2

    6.3

    7.1

    8.2

    450 7.0

    9.0

    10.7

    12.4

    13.2

    196 12.3

    162 14.6

    148 18.1

    120 19.2

    100

    90

    25.0

    32.4

    70

    60

    34.3

    38.4

    400

    350

    310

    260

    15A

    20A

    30A

    40A

    50A

    60A

    75A

    80A

    100A

    125A

    150A

    10.94259.7380160A

    175A

    200A

    225A

    250A

    300A

    350A

    400A

    500A

    600A

    700A

    800A

    36

    M C C B

    15600

  • 7/30/2019 Circuit Braker

    38/62

    M C C B

    NF 1200HA

    internal resistance & power loss

    LossW

    Resistanceu

    NF 800HA

    LossW

    Resistanceu

    NF 600HA

    LossW

    Resistanceu

    NF 400HA

    LossW

    Resistanceu

    NF 250HA

    LossW

    Resistanceu

    NF 100HA

    LossW

    Resistanceu

    Type

    In A

    31500

    33500

    17000

    8500

    6000

    3300

    3.2

    7.5

    6.8

    7.7

    9.6

    8.2

    2000 7.2

    1500

    1200

    8.4

    8.8

    950 9.5

    775 12.1

    725 16.3

    595 18.1

    575 23.0

    535 27.0

    251 15.7

    188 16.9

    188 23.0

    138 22.1

    220 51.0

    210 75.6

    120 58.8

    105 67.2

    55 55.0

    45 64.8

    37

    10A

    15A

    20A

    30A

    40A

    50A

    60A

    75A

    80A

    100A

    125A

    150A

    160A

    175A

    200A

    225A

    250A

    300A

    350A

    400A

    500A

    600A

    700A

    800A

    1000A

    1200A

    680 17.4

  • 7/30/2019 Circuit Braker

    39/62

    internal resistance & power lossNF 800L

    LossW

    Resistanceu

    NF 600L

    LossW

    Resistanceu

    NF 400L

    LossW

    Resistanceu

    NF 250L

    LossW

    Resistanceu

    NF 100L

    LossW

    Resistanceu

    Type

    In A

    38

    31500

    33500

    17500

    9000

    7000

    4500

    3.2

    7.5

    7.0

    8.1

    11.2

    11.3

    2200 7.9

    1800

    1500

    10.1

    11.2

    1350 13.5

    775 12.1

    725 16.3

    595 18.1

    575 23.0

    535 27.0

    290 18.1

    195 17.5

    185 22.7

    175 28.0

    220 51.0

    210 75.6

    120 58.8

    105 67.2

    10A

    15A

    20A

    30A

    40A

    50A

    60A

    75A

    80A

    100A

    125A

    150A

    680 17.4160A

    175A

    200A

    225A

    250A

    300A

    350A

    400A

    500A

    600A

    700A

    800A

    M C C B

  • 7/30/2019 Circuit Braker

    40/62

    DC voltage | time constant 10ms or below

    M C C B d c s h o r t

    c i r c u i t t a b l e

    Model Pole 48V Icu/Ics 125V Icu/Ics 250V Icu/Ics 400V Icu/Ics 550V Icu/Ics 600V Icu/Ics

    NF-50MA2

    3

    40 / 20

    40 / 20

    41 / 20

    42 / 20

    40 / 20

    NF-100GP

    1

    2

    3

    NF-100MA

    NF-100HA

    NF-100L

    NF-250GP

    NF-250MA

    NF-250HA

    1

    2

    3

    4

    1

    2

    3

    4

    3

    1

    2

    3

    4

    1

    2

    3

    4

    3

    1

    2

    3

    NF-250L

    NF-400GP

    NF-400HA

    NF400L

    NF-600 /

    NF-800GP

    NF-600 /

    NF-800HA

    NF-800L

    NF-1200HA

    3

    4

    3

    4

    3

    3

    4

    3

    4

    3

    3

    4

    50 / 25

    50 / 25

    50 / 25

    50 / 25

    100 / 50

    100 / 50

    100 / 50

    100 / 50

    150 / 75

    50 / 25

    50 / 25

    50 / 25

    50 / 25

    100 / 50

    100 / 50

    100 / 50

    100 / 50

    150 / 75

    40 / 20

    40 / 20

    40 / 20

    80 / 40

    80 / 40

    100 / 50

    100 / 50

    150 / 75

    80 / 40

    80 / 40

    100 / 50

    100 / 50

    150 / 75

    100 / 50

    100 / 50

    15 / 8

    15 / 8

    15 / 8

    15 / 8

    15 / 8

    30 / 15

    30 / 15

    30 / 15

    30 / 15

    80 / 40

    80 / 40

    80 / 40

    80 / 40

    100 / 50

    30 / 15

    30 / 15

    30 / 15

    30 / 15

    80 / 40

    80 / 40

    80 / 40

    80 / 40

    100 / 50

    15 / 8

    15 / 8

    15 / 8

    40 / 20

    40 / 20

    80 / 40

    80 / 40

    100 / 50

    40 / 20

    40 / 20

    80 / 40

    80 / 40

    100 / 50

    80 / 40

    80 / 40

    7.5 / 4

    7.5 / 4

    7.5 / 5

    7.5 / 6

    7.5 / 7

    15 / 8

    15 / 8

    15 / 8

    15 / 8

    40 / 20

    40 / 20

    40 / 20

    40 / 20

    50 / 25

    15 / 8

    15 / 8

    15 / 8

    15 / 8

    40 / 20

    40 / 20

    40 / 20

    40 / 20

    50 / 25

    7.5 / 4

    7.5 / 4

    7.5 / 4

    20 / 10

    20 / 10

    40 / 20

    40 / 20

    50 / 25

    20 / 10

    20 / 10

    40 / 20

    40 / 20

    50 / 25

    40 / 20

    40 / 20

    6 / 3

    6 / 3

    10 / 5

    10 / 5

    25 / 13

    25 / 13

    35 / 18

    10 / 5

    10 / 5

    25 / 13

    25 / 13

    35 / 18

    6 / 3

    13 / 8

    13 / 8

    25 / 13

    25 / 13

    35 / 18

    13 / 8

    13 / 8

    25 / 13

    25 / 13

    35 / 18

    25 / 13

    25 / 13

    8 / 4

    18 / 9

    8 / 4

    18 / 9

    10 / 5

    18 / 9

    10 / 5

    18 / 9

    18 / 9

    8 / 4

    18 / 9

    8 / 4

    18 / 9

    10 / 5

    18 / 9

    10 / 5

    18 / 9

    18 / 9

    39

  • 7/30/2019 Circuit Braker

    41/62

    Interrupting Capacity Icu (kA) Sym

    motor circuit protection

    M C C B

    s e l e c t i o n t a b l e

    65

    NF-100L

    NF-250L

    NF-400L

    NF-800L

    50

    NF-100HA

    NF-250HA

    NF-400GP NF-400HA

    NF-600HA

    NF-800HA

    25

    NF-100MA

    NF-250MA

    10

    NF-50MA

    NF-100GP

    NF-250GP

    NF-600GP

    NF-800GP

    MotorCapacity

    [kW at 400/440]

    MotorFull-load

    Current [A]

    MCCBIn [A]

    0.37

    0.55

    0.75

    1.1

    1.5

    2.2

    3

    4

    5.5

    7.5

    11

    15

    18.5

    22

    30

    37

    45

    55

    75

    90

    110

    132

    160

    200

    250

    290

    315

    355

    1.1

    1.5

    1.9

    2.8

    3.5

    5

    6.6

    8.6

    11.5

    15

    22

    29

    36

    42

    56

    68

    83

    98

    135

    158

    193

    232

    282

    349

    430

    520

    545

    610

    10

    10

    10

    10

    10

    10

    15

    15

    20

    30

    40

    40

    50

    60

    75

    100

    125

    150

    200

    225

    250

    300

    350

    400

    600

    700

    700

    800

    40

    3-phase motor |400V 440V 50 / 60Hz

  • 7/30/2019 Circuit Braker

    42/62

    Motor Full-Load Current (A)

    3 415VRated Current (A)

    Wire Size (mm2)

    Rated Current (A)

    Wire Size (mm2)

    Wire Size (mm2)

    Rated Current (A)

    Motor Full-Load Current (A)

    3 220V

    motor selection | direct-online-starter

    1.1 2.1

    10

    2

    0.65

    10

    2

    0.58

    10

    2

    10

    2

    1.2

    10

    2

    1.1

    10

    2.4 3.3 4.4 5.9 8.4 11 13.6 2015.5

    10

    2

    1.4

    10

    2

    1.3

    10

    10 10 15 20 30 30 5030

    2 2 2 2 2 5.5 5.55.5

    1.9 2.5 3.4 4.8 6.4 7.9 11.59

    10 10 10 10 15 15 20 30

    2 2 2 2 2 2 5.55.5

    1.8 2.4 3.2 4.5 5.9 7.3 10.57.7

    10 10 10 10 15 15 2015

    2 2 2 2 2 2 2 2 5.52

    MotorRatings

    5.543.732.21.51.10.750.550.370.18kW

    HP 1/4 1/2 3/4 1 1.5 2 3 4 5 5.5 7.5

    41

    Motor Full-Load Current (A)

    3 380V

    Motor Full-Load Current (A)

    3 415VRated Current (A)

    Wire Size (mm2)

    Rated Current (A)

    Wire Size (mm2)

    Wire Size (mm2)

    Rated Current (A)

    Motor Full-Load Current (A)

    3 220V

    26.5 38

    60

    14

    15

    30

    5.5

    14

    30

    5.5

    75

    22

    22

    50

    8

    20.5

    50

    50 61

    100

    38

    29

    60

    14

    27

    60

    100

    38

    36

    75

    22

    33

    75

    8 14 22

    71 97

    125

    60

    41

    100

    38

    38

    75

    150

    60

    56

    100

    38

    52

    100

    22 38

    120 145

    175

    80

    70

    150

    60

    65

    125

    200

    100

    84

    125

    60

    77

    125

    60 60

    180 240

    225

    125

    104

    150

    80

    95

    150

    400

    200

    143

    200

    100

    130

    175

    80

    290

    500

    200

    170

    225

    125

    154

    200

    100100

    MotorRatings

    9075554537302218.515117.5kW

    HP 10 15 20 25 30 40 50 60 75 100 125

    Motor Full-Load Current (A)

    3 380V

    Short Circuit protection of electric motors

    The NF series circuit breakers are suitable to combine with motor starters. As defined in IEC 60947-4

    standards, the starter switching device, usually a magnetic contactor, must be coordinated with the

    equipment capable of providing short circuit protection for circuit wiring/cables.

    The common starting methods for asynchronous squirrel-cage induction motors which the NF series can be

    used in combination are the direct-online-starters and star-delta-starters.

    The following selection tables, illustrating the above, shows the suitable breaker ratings that can

    accommodate motor starting currents. When more than one motor is connected to a branch circuit, the

    sum of the motor rated current equals to the rated current of the breaker.

    Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and

    the starting current is less than 6 times of motor full load current.

  • 7/30/2019 Circuit Braker

    43/62

    Motor Full-Load Current (A)

    3 380V

    Motor Full-Load Current (A)

    3 415V

    RatedCurrent (A)

    Wire Size (mm2)

    RatedCurrent (A)

    Wire Size (mm2)

    Wire Size (mm2)

    RatedCurrent (A)

    Motor Full-Load Current (A)

    3 220V

    motor selection | direct-online-starter

    motor selection | star-delta-starter

    M C C B

    349 411

    600

    200

    202

    400

    150

    185

    300

    150

    700

    325

    238

    400

    200

    218

    400

    500 625 780 980

    800

    325

    290

    500

    200

    260

    500

    360 450 570

    600 800 1000

    200 325 325

    330 415 520

    600 700 800

    200 200 200 325 325

    MotorRatings

    315250200160132110kW

    HP 150 180 220 270 340 420

    42

    Motor Full-Load Current (A)

    3 415V

    RatedCurrent (A)

    Wire Size (mm2)

    RatedCurrent (A)

    Wire Size (mm2)

    Wire Size (mm2)

    RatedCurrent (A)

    Motor Full-Load Current (A)

    3 220V

    20 28.5

    50

    8

    11.5

    30

    3.5

    10.5

    30

    3.5

    50

    8

    15

    30

    5.5

    14

    30

    5.5

    38 50

    75

    22

    22

    50

    8

    20.5

    50

    8

    100

    22

    29

    60

    14

    27

    60

    14

    61 71

    125

    38

    35

    75

    22

    33

    75

    22

    150

    38

    41

    100

    38

    41

    100

    22

    97 120

    200

    60

    56

    100

    38

    52

    100

    38

    225

    60

    70

    150

    50

    65

    150

    50

    145 180

    300

    80

    84

    175

    50

    77

    175

    50

    240

    400

    100

    143

    225

    80

    130

    225

    80

    400

    80

    104

    225

    60

    95

    200

    60

    MotorRatings

    75554537302218.515117.55.5kW

    HP 7.5 10 15 20 25 30 40 50 60 75 100

    Motor Full-Load Current (A)

    3 380V

    Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and

    the starting current is less than 6 times of motor full load current.

  • 7/30/2019 Circuit Braker

    44/62

    43

    110

    Motor Full-Load Current (A)

    3 415VRated Current (A)

    Wire Size (mm2)

    Rated Current (A)

    Wire Size (mm2)

    Wire Size (mm2)

    Rated Current (A)

    Motor Full-Load Current (A)

    3 220V

    motor selection | star-delta-starter

    290

    500

    150

    170

    300

    100

    154

    300

    80

    MotorRatings

    90kW

    HP 125

    Motor Full-Load Current (A)

    3 380V

    349

    600

    150

    202

    400

    125

    185

    300

    100

    150

    160

    411

    800

    200

    238

    400

    125

    218

    400

    125

    132

    180

    500

    1000

    250

    290

    600

    150

    260

    400

    150

    220

    NF 50

    NF 100-250

    NF 400-600

    NF 800-1200

    Insulation, Insulated Barsor Painted Sheetmetal (mm)

    installation | safety distance requirementsOperating

    VoltageModel

    25

    50

    75

    80

    A

    40

    50

    50

    55

    100

    100

    B1

    40

    50

    50

    55

    100

    100

    B2

    Bare/UnpaintedSheetmetal (mm)

    25

    30

    80

    90

    A

    45

    55

    100

    100

    B1

    45

    55

    100

    100

    B2

    U

  • 7/30/2019 Circuit Braker

    45/62

    NF-800

    NF-50

    NF-100

    NF-250

    NF-400

    NF-600

    NF-1200

    NF-50

    NF-100

    NF-250

    NF-400

    NF-600

    NF-800

    NF-1200

    tightening range* Nm Bolt/Screw

    To ensure the correct operation of the MCCB, it is essential to make a proper

    cable or busbar termination to the MCCB. It is recommended that the

    supplied screws be used to connect the cables or busbars to the breaker

    terminals and tightened to the torque, as shown in the table below.

    terminal-tightening torque

    M C C B

    44

    Cable size mm2 ScrewModel

    terminals for cable lugs connection

    M5 screw Pan head

    M8 screw Screw

    1.8 ~ 2.0 N/A

    2.5 ~ 3.5 N/A

    1.6

    Min Max I II Size Type

    22

    1.6 50

    M8 screw Screw

    M12 bolt x 2 Bolts

    2.5 ~ 3.5 N/A

    N/A 10 ~ 14

    38 150

    150 2 x 100

    M12 bolt x 2 Bolts

    N/A N/A

    N/A 10 ~ 14

    N/A N/A

    2 x 150 2 x 200

    N/A N/A

    N/A N/AN/A N/AN/A N/A

    tightening range* kgf-cm Bolt/ScrewCopper busbar size mm2

    Model

    terminals for copper busbar connection

    M5 screw

    M8 screw

    1.8 ~ 2.0 N/A

    2.5 ~ 3.5 N/A

    5

    Max t = Max w = I II Size

    12.5

    5 16.5

    M8 screw

    M12 bolt x 2

    2.5 ~ 3.5 N/A

    N/A 10 ~ 14

    7 23

    8 25

    M12 bolt x 2

    M12 bolt x 2

    N/A 10 ~ 14

    N/A 10 ~ 14

    8 40

    10 44

    M12 bolt x 2N/A 10 ~ 1417 44

    * Note

    Copper busbar

    Caution

    1) Do not over tighten. If the tightening torque isexceeded, bolts/screws and copper bars may

    be damaged.2) Failure to secure a terminal connection may

    cause an electrical fault. Make sure all

    terminal connections are tightly secured.

    w

    t

  • 7/30/2019 Circuit Braker

    46/62

    terminal-cable & copper busbar sizes

    M C C B

    c o n n e c t i o n d a t a

    ISO Square(mm2)

    CNS StandardSquare (mm2)

    UL StandardAWG or kcmil at 75C

    MCCBRated Current

    In (A)

    8 In > 0 1 1.6 14 AWG

    14 AWG

    14 AWG

    12 AWG

    10 AWG

    10 AWG

    8 AWG

    6 AWG

    4 AWG

    3 AWG

    2 AWG

    1 AWG

    1/0 AWG

    2/0 AWG

    3/0 AWG

    4/0 AWG

    250 MCM

    300 MCM

    350 MCM

    500 MCM

    2 x 3/0 AWG

    2 x 250 MCM

    2 x 350 MCM

    3 x 300 MCM

    2 x 250 MCM

    2 x 350 MCM

    3 x 300 MCM

    2.0

    2.0

    2.0

    5.5

    8

    14

    22

    38

    38

    38

    50

    60

    80

    100

    100

    125

    150

    200

    200

    250

    1.5

    2.5

    2.5

    4

    6

    10

    16

    25

    35

    35

    50

    50

    70

    95

    95

    120

    150

    185

    185

    240

    2 x 150

    2 x 185

    2 x 240

    2 x (30 x 5)

    2 x (40 x 5)

    2 x (50 x 5)

    2 x 150

    2 x 185

    2 x 240

    2 x (30 x 5)

    2 x (40 x 5)

    2 x (50 x 5)

    12 In > 8

    15 In > 12

    20 In > 15

    25 In > 20

    32 In > 25

    50 In > 32

    65 In > 50

    85 In > 65

    100 In > 85

    115 In > 100

    130 In > 115

    150 In > 130

    175 In > 150

    200 In > 175

    225 In > 200

    250 In > 225

    275 In > 250

    300 In > 275

    350 In > 300

    400 In > 350

    500 In > 400

    630 In > 500

    800 In > 630

    500 In > 400

    630 In > 500

    800 In > 630

    45

  • 7/30/2019 Circuit Braker

    47/62

    1.1 1.3 1.1 1.3Weight kgaa

    CNS 5422(Asym/sym) kA

    IEC 60947-2CNS 14816-2

    (Icu/Ics) kA

    Rated Breaking capacity

    E L C B

    46

    EG series | with overload & short circuit protection100100

    EG-100MA EG-100HA

    3

    230-380-415 (Multi-voltage type)

    30-100-300 (selectable) 30-100-300 (selectable)

    0.04 0.04

    button button

    10 15 20 30 40

    50 60 75 80 100

    10 15 20 30 40

    50 60 75 80 100

    1 2W

    1 3W

    3 3W

    3 4W

    1 2W

    1 3W

    3 3W

    3 4W

    4 3 4

    Ampere Frame (AF)

    Model Code

    Supply System

    Number of Pole (P)

    Rated Operational Voltage: Ue Vac

    Rated Current: In (A)at Ambient Temp 50C

    Rated ResidualOperating Current

    In (mA)

    Max Operating Timeat 5 In (Sec)

    Residual OperatingCurrent Indication System

    Instantaneous

    Type

    Type: ACCharacteristics for DC Components

    25 / 22

    35 / 30

    60 / 50

    25 / 13

    25 / 13

    50 / 25

    90

    155

    80

    102

    132

    30

    155

    80

    102

    132

    30

    120

    60 / 50

    60 / 50

    100 / 85

    50 / 25

    50 / 25

    85 / 43

    90 120

    AC 440V

    AC 380V

    AC 220V

    AC 415V

    AC 380V

    AC 230V

    a

    b

    c

    ca

    bb

    ON

    OFF

    a

    aa

    ca

    bbb

    c

    (mm)

    Type: AC

  • 7/30/2019 Circuit Braker

    48/62

    1.6 1.8 1.6 1.8Weight kgaa

    CNS 5422(Asym/sym) kA

    IEC 60947-2CNS 14816-2

    (Icu/Ics) kA

    Rated Breaking capacity

    E L C B

    47

    EG series | with overload & short circuit protection250250

    EG-250MA EG-250HA

    3

    230-380-415 (Multi-voltage type)

    30-100-300 (selectable) 30-100-300 (selectable)

    0.04 0.04

    button button

    125 150 160

    175 200 225 250

    125 150 160

    175 200 225 250

    1 2W

    1 3W

    3 3W

    3 4W

    1 2W

    1 3W

    3 3W

    3 4W

    4 3 4

    Ampere Frame (AF)

    Model Code

    Supply System

    Number of Pole (P)

    Rated Operational Voltage: Ue Vac

    Rated Current: In (A)at Ambient Temp 50C

    Rated ResidualOperating Current

    In (mA)

    Max Operating Timeat 5 In (Sec)

    Residual OperatingCurrent Indication System

    Instantaneous

    Type

    Characteristics for DC Components

    25 / 22

    35 / 30

    60 / 50

    25 / 13

    25 / 13

    50 / 25

    105

    165

    80

    104

    126

    35

    165

    80

    104

    126

    35

    140

    60 / 50

    60 / 50

    100 / 85

    50 / 25

    50 / 25

    85 / 43

    105 140

    AC 440V

    AC 380V

    AC 220V

    AC 415V

    AC 380V

    AC 230V

    a

    b

    c

    ca

    bb

    ON

    OFF

    a

    aa

    ca

    bbb

    c

    (mm)

    Type: AC Type: AC

  • 7/30/2019 Circuit Braker

    49/62

    EG series | operating characteristics: EG-100MA & EG-100HA

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    EG-100MA, EG-100HA

    Frame size: 100AFRated current:

    10A 15A 20A 30A 40A

    50A 60A 75A 80A 100A

    Max

    Min

    Time delay tr ip I ns tant aneous t ri p

    EG series |

    130

    120

    110

    100

    90

    15 20 30 40 50 6080

    Rated ambient 50 C

    Currentrating(%)

    Ambient temperature ( C)

    Ratedambient

    10A~30A

    40A~100A

    Residual Current% of rated residual current48

    E L C B c h a r a c t e r i s t i c s

    temperature & operatingcharacteristics for instantaneous type

  • 7/30/2019 Circuit Braker

    50/62

    EG series | operating characteristics: EG-250MA & EG-250HA

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    EG-250MA, EG-250HA

    Frame size: 250AFRated current:

    125A 150A 160A 175A

    200A 225A 250A

    Max

    Min

    Time delay tr ip I ns tant aneous t ri p

    Max Total

    Interrupting time.

    EG series |

    130

    120

    110

    100

    90

    10 20 30 40 50 60 7080

    Rated ambient 50

    C

    Currentrating(%)

    Ambient temperature ( C)

    Ratedambient

    Residual Current% of rated residual current 49

    E L C B c h a r a c t e r i s t i c s

    temperature & operatingcharacteristics for instantaneous type

  • 7/30/2019 Circuit Braker

    51/62

    EG series | front connection: EG-100MA & EG-100HA

    CL

    CL

    N

    60

    50

    12

    0

    4.5

    5013

    4

    15

    5

    30

    90

    120

    4 84

    102

    80

    73

    27

    Screw

    22

    90

    Mounting hole

    Trip button

    Insulation barrier

    (removable)

    Neutral pole

    24

    8.

    5

    CL CL CL

    132

    52

    3086

    28

    4-pole

    Breaker3-pole

    30

    M4 Screw

    or 5mm

    R1CL

    Breaker

    50

    E L C B d i m e n s i o n s

    3-pole 4-pole

  • 7/30/2019 Circuit Braker

    52/62

    EG series | front connection: EG-250MA & EG-250HA

    CL

    CL

    N

    70

    100

    102

    4.

    5

    501

    44

    165

    35

    105

    140

    4 84

    104

    80

    73

    45

    Screw

    22

    105

    Mounting hole

    Trip button

    Insulation barrier

    (removable)

    Neutral pole

    24

    8.

    5

    CL CL CL

    CL126

    52

    35100

    32.5

    4-pole

    Breaker3-pole

    35

    M4 Screw

    or 5mm

    R1

    Breaker

    51

    E L C B d i m e n s i o n s

    3-pole 4-pole

  • 7/30/2019 Circuit Braker

    53/62

    M C B

    BHQ series | fixed type100100100

    BHQ-1 BHQ-2 BHQ-3

    1

    220 / 415 220 / 415 220 / 415

    10

    6 / 3

    10

    6 / 3

    10

    6 / 3

    1

    25

    95

    50

    95

    75

    95

    58.5 58.5 58.5

    77.5 77.5 77.5

    100 100 100

    0 25 50

    0.15 0.31 0.46

    10 15 20 30 40

    50 60 75 80 100

    10 15 20 30 40

    50 60 75 80 100

    10 15 20 30 40

    50 60 75 80 100

    2 3

    Ampere Frame (AF)

    Model Code

    Number of Pole (P)

    Rated Voltage: Ue Vac

    Rated Current: In (A)at Ambient Temperature: 50 C

    Breaking capacity (kA)

    AC 220V

    AC 110/220V

    AC 220/415V

    DC 125V

    a

    b

    c

    ca

    bb

    aa

    kgWeight

    CNS 2931(Asym/sym) kA

    IEC 60947-2CNS 14816-2

    52

    a

    aa

    ca

    bbb

    c

  • 7/30/2019 Circuit Braker

    54/62

    BHP series | plug-in type100100100

    BHP-1 BHP-2 BHP-3

    1

    220 / 415 220 / 415 220 / 415

    10

    6 / 3

    10

    6 / 3

    10

    6 / 3

    1

    25

    74

    50

    74

    75

    74

    60.5 60.5 60.5

    77.5 77.5 77.5

    0 25 50

    0.13 0.26 0.39

    10 15 20 30 40

    50 60 75 80 100

    10 15 20 30 40

    50 60 75 80 100

    10 15 20 30 40

    50 60 75 80 100

    2 3

    Ampere Frame (AF)

    Model Code

    Number of Pole (P)

    Rated Voltage: Ue Vac

    Rated Current: In (A)at Ambient Temperature: 50 C

    Breaking capacity (kA)

    AC 220V

    AC 110/220V

    AC 220/415V

    DC 125V

    a

    b

    c

    ca

    bb

    aa

    kgWeight

    CNS 2931(Asym/sym) kA

    IEC 60947-2CNS 14816-2

    (Icu/Ics) kA

    53

    a

    aa

    b

    ca

    c

  • 7/30/2019 Circuit Braker

    55/62

    BHQ & BHP series | operating characteristics

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Type : BHQ, BHP

    Rated current:

    10A 15A 20A 30A 40A 50A

    60A 75A 80A 100A

    Min (10~50A)

    Max (10~50A)

    Max (60~100A)

    Min (60~100A)

    BHQ & BHP series | temperature characteristics

    150

    145

    140

    135

    130

    125

    120

    115

    110

    105

    100

    10 15 20 25 30 35 40 45 50 55 6095

    Rated ambient 50 C

    Currentrating

    (%)

    Ambient temperature ( C)

    10A

    Ratedambient

    15A~30A

    40A~50A

    60A~100A

    54

    M C B c h a r a c t e r i s t i c s

  • 7/30/2019 Circuit Braker

    56/62

    BHQ series | fixed type front connection

    CL

    25

    25

    50

    50

    75

    58.5

    87

    100

    113

    32

    63.5

    77.5

    Mig bracket

    Mig bracket

    M5 Screw

    (Line side & Load side)

    73

    95

    57

    BHP series | plug-in type front connection

    25

    25 25

    50 75 77.5

    60.5

    65.5

    57.

    5

    71.

    5

    74

    7.

    5

    25

    Plug-in terminal

    (Line side)

    M5 Screw

    (Load side)

    Mig SlotMig Slot

    22 47 47

    13.5

    5.5

    55

    M C B d i m e n s i o n s

    1-pole 2-pole 3-pole

    1-pole 2-pole 3-pole

  • 7/30/2019 Circuit Braker

    57/62

    IEC 60947-2CNS 14816-2

    (Icu/Ics) kA

    Rated Breaking capacity (kA)

    R C B O

    56

    EQ series | fixed type505050

    EQ-1 EQ-2 EQ-3

    1 2W

    1

    220 / 240 220 / 240 220 / 240

    30

    0.04

    30

    0.04

    30

    0.04

    Type: AC

    10 15 20

    30 40 50

    10 15 20

    30 40 50

    10 15 20

    30 40 50

    1 2W

    2

    1 2W

    1 3W

    3 3W

    3

    Ampere Frame (AF)

    Model Code

    Supply System

    Number of Pole (P)

    Rated Operational Voltage: Ue Vac

    Rated Current: In (A)at Ambient Temp 50C

    Rated Residual

    Operating CurrentIn (mA)

    Max Operating Timeat 5 In (Sec)

    Characteristics for DC Components

    InstantaneousType

    with overload &short circuit protection

    10

    10 / 5

    10

    10 / 5

    10

    10 / 5

    25

    96

    50

    96

    75

    96

    58 58 58

    77 77 77

    100 100 100

    25 50

    0.2 0.3 0.5

    AC 220/380V

    AC 110/220V

    AC 220/240V

    a

    b

    c

    ca

    bb

    aa

    kgWeight

    CNS 5422(Asym/sym) kA

    aca

    bbb

    c

    Type: AC Type: AC

  • 7/30/2019 Circuit Braker

    58/62

    EP-1 EP-2 EP-3

    57

    EP series | plug-in type505050Ampere Frame (AF)

    Model Code

    IEC 60947-2CNS 14816-2

    (Icu/Ics) kA

    Rated Breaking capacity (kA)

    1 2W

    1

    220 / 240 220 / 240 220 / 240

    30

    0.04

    30

    0.04

    30

    0.04

    10 15 20

    30 40 50

    10 15 20

    30 40 50

    10 15 20

    30 40 50

    1 2W

    2

    1 2W

    1 3W

    3 3W

    3

    Supply System

    Number of Pole (P)

    Rated Operational Voltage: Ue Vac

    Rated Current: In (A)at Ambient Temp 50C

    Rated Residual

    Operating CurrentIn (mA)

    Max Operating Timeat 5 In (Sec)

    Characteristics for DC Components

    InstantaneousType

    10

    10 / 5

    10

    10 / 5

    10

    10 / 5

    25

    83

    50

    83

    75

    83

    62 62 62

    81 81 81

    0.2 0.3 0.5

    AC 220/380V

    AC 110/220V

    AC 220/240V

    a

    b

    c

    ca

    bb

    aa

    kgWeight

    CNS 5422(Asym/sym) kA

    with overload &short circuit protection

    aca

    b

    c

    Type: AC Type: AC Type: AC

  • 7/30/2019 Circuit Braker

    59/62

    EQ & EP series | operating characteristics

    Operatingtime

    x 100% of rated current

    1 1.3 2 3 4 5 6 7 10 15 20 30 40

    Min

    Type: EQ-1, EQ-2, EQ-3,

    EP-1, EP-2, EP-3Rated current:

    10A 15A 20A 30A

    40A 50A

    4hr

    2hr

    1hr

    30min20min14min10min6min4min

    2min

    1min

    30sec20sec

    10sec

    5sec

    2sec

    1sec

    0.5sec

    0.2sec

    0.1sec

    0.05sec

    0.02sec

    0.01sec

    Max

    EQ & EP series |

    150

    145

    140

    135

    130

    125

    120

    115

    110

    105

    100

    10 15 2 0 25 30 35 40 45 50 55 60

    95

    Rated ambient 50 C

    Currentrating

    (%)

    Ambient temperature ( C)

    Ratedambient

    10A~20A

    30A~50A

    Residual Current% of rated residual current58

    R C B O c h a r a c t e r i s t i c s

    temperature & operatingcharacteristics for instantaneous type

  • 7/30/2019 Circuit Braker

    60/62

    EQ series | fixed type front connection

    EP series | plug-in type front connection

    59

    R C B O d i m e n s i o n s

  • 7/30/2019 Circuit Braker

    61/62

    ordering codes | MCCB

    60

    NF 400 HA 300A 3P STC 3

    type framesize

    breakingcapacity

    nominalcurrent

    pole accessory accessoryframesize

    Example:

    NF 400 HA 300A 3P STC 3

    400A frame size breaker with Rated Nominal

    current of 300A, 3-poles and complete with

    400A frame size Shunt trip coil.

    800AF600AF400AF250AF100AF50AF

    Frame SizeIcu

    25kA 25kA

    1200AF

    10kA 25kA10kA

    25kA10kA 25kA

    50kA 50kA 50kA50kA 50kA50kA

    65kA 65kA65kA 65kA65kA

    GP

    MA

    HA

    L

    breaking capacity, Icu @ 415V ~

    CodeItem

    STC

    UVT

    AUS

    ALS

    AAS

    RHN

    Shunt trip coil (240Vac)

    UVT (415Vac)

    Auxiliary switch

    Alarm switch

    Auxiliary + alarm switch

    Rotary handle

    accessories

    DescriptionNo of Poles

    1 phase

    2 phase

    3 phase3 phase

    + neutral

    1

    2

    3

    4

    poles

    SizeCode

    50AF

    100AF

    250AF

    400AF to 1200AF

    0

    1

    2

    3

    accessoryframe size

  • 7/30/2019 Circuit Braker

    62/62

    what is quality ?

    We define quality as products having the highest

    level of reliability, performance and design. Ouraim for quality is to meet the requirements of

    other global markets and to exceed the current

    international standards. With our in-house design

    and development team, our range of products

    are currently manufactured in accordance and

    compliance to various international standards.

    our road to quality

    Main OfficeHwa Shih Electric (M) Sdn Bhd

    25 USJ 9/5P, Subang Jaya,47620 Selangor D. E., Malaysia.Tel : 603 8023 2966Fax : 603 8023 2523Email : [email protected]