    1/24

    Air Quality Expert

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    2/24

    Our management system is certi ed ISO 9001: 2008.Therefore, ATAs products are all marked.We ensure that each product: is tested at our factory before shipping, consists of components carefully selected according to quality and performance requirements, can be installed on the site by a quali ed technician respecting all our protocols, has a unique serial number allowing traceability during its life cycle.

    Fields of activityHospital

    Aerospace

    Laboratories

    Microelectronic components production

    Quality

    WorldwideHaving a solid reputation in hospitals and clinics in France, ATA also carries almost 40% of itsturnover for export in nearly 30 countries . An extensive network of partners around the globeguarantees fast and exible after-sales service to users worldwide.

    Over 20 years of experience in Air HandlingReliability and Performance

    Since 1987 ATA has gained rich experience indesigning and marketing of air handling unitsfor all areas where infection risk tends to occur.ATA proposes a range of hygienic productswhich corresponds to all requirements of hospi-tal and industrial sectors.

    ATA s solutions are developed by an engineer-ing department having more than 20 years ofexpertise. Services proposed by ATA, such asaudit, technical assistance and training, ensureits customers to get the most from new equip-ment.

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    3/24

    Hygienic Air Handling Units CLINICAIR aredesigned and developed to ensure, withaccuracy and continuity, the quality of airin terms of particulate and bacteriologicalclass,temperature, humidity, pressure in area swhere air contamination control is the majorissue.

    ATA offers 3 ranges (CLN1b, CLN3 and CLN4) including more than 100 models with partialrecycling or 100% fresh air operation mode,duct connections placed at the top, bottom,front, side. Sound traps on op tion depending onmodels, etc...

    CLINICAIR Range

    4

    2

    8

    Presentation

    Princ iple of operation

    Advantages

    Detailed description

    Presentation

    Applications

    Detailed description

    Principle of operation

    Advantages of the CLN Range

    Tec hnical DataLaminar Flow C eilings

    Presentation

    ApplicationsDetailed description

    Principle of operation

    2

    2

    2

    3

    8

    9

    10

    14

    15

    1618

    4

    56

    14

    Clinicair 1b

    Clinicair 3

    Clinicair 4

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    4/24

    2

    Advantages

    Principle of operationVersion with plenum Version with Laminar Flow Ceiling

    CLINICAIR 1b is an attractive plug & play solution dedicatedto control a ir quality in operating theatres or other risk area s.

    Top of c lass in reducing airborne diseases, CLINICAIR 1b will proveits ef ciency by the combined action of BIOXIGEN decontami-nation system and HEPA H14 ltration (99,995% particle reduc-tion up to 0,3 microns (MPPS). They provide fast bacteriologicaland pa rtic le decontamination kinetics. The PCO3 control systempermanently regulates working parameters, in particular provid-ing accurate temperature control.

    Appreciated for its assembling quality and performance level,

    CLINICAIR 1b complies with high-level requirements for a setupwithin the operating theatre and, therefore, represents an idealsolution to ght against airborne infections.

    clinica ir 1b

    Air ow: 1500 to 2500m3/h. Air supply plenum. Filtration : G4 + F7 at air intake - H14 at air supply. Bioxigen dec ontamination system having

    ba cteric ida l, fungicidal, virucidal effec t on livingparticles.

    Regulation system providing constant air ow. High performance microprocessor. Remarkable sound insulation.

    Reduced dimensions : 1200mm x 700mm x 1950mm (2400mm with plenum) /500 kg.

    Can be completely integrated into the wall(fresh air supply possible a t the top , at the sideor at the ba ck).

    Single inlet motorised impeller module with lowpower consumption (EEF1).

    Front access for maintenance.

    For more details see: Tec hnical Data p.16

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    5/24

    3

    Detailed description

    Tight self-supporting metallicstructure.

    White painted (RAL 9010) interior. White pa inted (RAL 9010) double

    skin panels made of 15/10 stainlesssteel with high density (40 kg/m3)glass wool providing heat and noiseinsulation.

    RAL 9010 cover panels on 4 sides. Fresh air connec tion 200mm at

    the top, side or back. Adjustable feet.

    HEPA H14 ltration (low pressure drop lter made ofpolypropylene).

    Integrated pre- ltration. 2 steps of G4 + F7 type (low pressure drop lter made of

    polypropylene). Filters placed before cooling and heating coils.

    Copper tubes and aluminium ns with 2.5 mm minimumspacing.

    Multiple venturi circuits. Condensate tray mad e o f 316L stainless steel. Condensate d rain pipe ( 1) to the o uter casing

    (front, side or back).

    Frame and c asing

    Power supply 400V N+T 50Hz. Switch cabinet contains: - Switches and thermal cut-offs. - Regulation with microprocessor - LCD display on control

    panel.

    Switch cabinet and controls

    Air supply filtration

    Air intake filtration

    Air supply plenum

    Cooling coil (11 kW)

    3-step elec tric heater.

    Speed regulator maintainingconstant air ow in line withlter clogging degree.

    Single inlet motorised impellermodule with low power

    consumption (EEF1).

    Remote assistance Fresh air fan Laminar ow ceiling

    Filter clogging c ontrolledby air pressure switches.

    Integrated probes. PC O3 control system with

    energy economy mode.Heating (9 kW)

    FansOptions

    Control*

    *

    clinicair 1b

    Decontamination system havingbactericidal, fungicidal, virucidaleffec t on living pa rtic les.

    Bioxigen

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    6/24

    4clinicair 3

    CLINICAIR 3 range meets high-level requirements ofhyper aseptic environments offering nominal air owfrom 1000 to 20000 m3/h and external pressure up to1500 Pa (for more details see Tec hnical Data p. 16 ).Various models are available: with chilled-water, hot-water coils or electric heaters.

    CLINICAIR 3 range offers innovative hygienic aircon-ditionning solutions for operating theatres and other

    sensitive areas within the hospital. It complies with the most demanding standards: NFS 90-351 july 2003 and EN 1886. CLINICAIR 3 concept allows installation close to the area and offers signi -cant savings in terms of c onstruction, installation and operating costs. CLINICAIR 3 is a c ompacthygienic air handling unit which integrates all necessary components: control system, electricalcabinet, humidi er, condensate drain pipe, etc...

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    7/24

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    8/24

    6

    Detailed description

    Frame made of 40mm aluminium pro les assembled with aluminium corner joints. Double skin panels made of 15/10 - 8/10 stainless steel with high-density (40 kg/m3) glass wool

    providing heat and noise insulation. Panel locking with high compression self-wedging system and seals. Soundproof RAL 9010 panels, satin nish on all 4 sides with high ef ciency foam. Removable condensate tray made of 316L stainless steel with rigid siphon. 316L stainless steel diamond-shaped bottom. Ad justable feet (40mm).

    Noise level control often involvesthe installation of sound traps at airintake and air supply (on request).

    Copper tubes and aluminium ns with a minimum spacing of 2.0 mm. Multiple venturi circuits. 2 or 3-way proportiona l control valve (water chilled coil). Condensate droplet separator preventing any water priming. Removable condensate tray made of 316L stainless steel. Condensate d rain pipe to the outer casing ( 1). Elec tric hea ter with stainless steel heating rods and 2 safety thermostats.

    Integrated pre-filtration. One or two-stage filtration (on request): G4 + F5/F7. Filters positioned before coo ling and heating c oils. G4 filter with antifreeze damper installed at fresh air

    supply (on request).

    Frame and c asing

    Sound traps

    Cooling & Heating c oils

    Air intake filtration

    clinicair 3

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    9/24

    7

    Pressure gauges for monitoring of lterclogging a t the air intake and air supply.

    Speed regulator maintaining constant air ow in line with lter clogging degree. Single inlet motorised impeller module with low power

    consumption (EEF1).

    Filter clogging c ontrolled byair pressure switch.

    Detection of low air ow byalarm pressure switch.

    Remote assistanc e Electric hea ter in plac e of or

    in add ition to hot water coil Water lter with drain cock to protect

    control valve (chilled-water or hot- water models)

    Ma nual or motorised dampers Condensate pump Water sensor alarm Low pressure drop lters made of

    polypropylene Recovery coil

    3-phase power supply:400 V N+T 50Hz.

    Switch cabinet contains: - Switches and thermal cut-offs. - Regulation with microprocessor.

    LCD display on control panel. - 3, 4 or 5 probes ac cording to the

    model (rec ycling or fresh air) andregulation type.

    F9 ltration. H13 lter on request.

    Pressure gauges

    Fans

    Pressure switches

    Options

    Switch cabinet and controls

    Air supply ltration

    Electrode steam humidi er for automatic steam

    generation. Microprocessor control providing: - Overall performance - Proportional steam control Stainless steel steam ramp.

    Humidifier

    clinicair 3

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    10/24

    8clinicair 4

    CLINICAIR 4 is a compact hygienic air handling unit,integrating all the components necessary for high-quality air handling for all hospital departments.

    The unit can either be installed in technical premisesor outside the building allowing substantial savingsin terms of installation, maintenance and operatingcosts.

    CLINICAIR 4 range offers innovative a ir handling solu-tions for operating rooms and other risk area s within the hospital and complies with NFS 90-351J uly2003 standard. Appreciated for its assembling qua lity and performanc e level, CLINICAIR 4 repre-sents an alternative solution in ghting against airborne infections in operating rooms.

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    11/24

    Robert Debr Hospital in Pa ris. Bone marrow transplant c enter

    Applications

    ATA has equipped with CLINICAIR solution100% of high risk departments within public andprivate hospitals and clinics:

    operating theatres, intensive care units, hemodialysis services, cardiac intensive care units, induction rooms, MRI rooms, coronarography rooms, tomography rooms, angiography rooms, endoscopy rooms, delivery rooms, recovery rooms, ophthalmologic laser,

    cytotoxic products, cell therapy laboratories, hospital sterilisation.

    electronics, food-processing, pharmaceutical, aerospace.

    ATA has also installed its air treatmentunits in the following industrial sectors:

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    12/24

    10

    Detailed description

    Frame made of 70mm aluminium pro les assembledwith aluminium corner joints.

    Double skin panels made of 15/10 - 8/10 stainlesssteel with hig h-density (45 kg/m3) glass wool providinghea t and noise insu lation.

    Panel locking with high compression self-wedging system.

    Electrode steam humidi erfor automatic steamgeneration. Microproc essor co ntrol

    providing: - Overall performance. - Prop ortional steam control. Stainless steel steam ramp. Heating o f technical c ompartment in

    the winter to avoid freezing.

    3-phase power supply: 400 V N+T 50Hz Switch cabinet contains: - Switches and thermal cut-offs. - Regulation with microprocessor.

    LCD display on control panel.- 3, 4 or 5 probes ac cording to the model (rec ycling orfresh air) and regulation type.

    Filter c logging c ontrolled byair pressure switch.

    Detection of low air ow byalarm pressure switch.

    Frame and c asing

    Humidifier

    Switch cabinet and controls

    Pressure switches

    Sound traps

    clinicair 4

    Noise level control often involvesthe installation of sound traps at airintake and air supply. Noise level at1,5 meters: 40 dB (A) +/- 3dB (A).

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    13/24

    11

    F9 ltration. H13 lter on request.

    Integrated pre- ltration. One or two-stage ltration (on request): G4 + F5/F7. Filters located before cooling and heating coils.

    Copper tubes and aluminium ns with a minimum spacing of 2.0 mm.

    Multiple venturi circuits. 3-way propo rtional co ntrol valve (standard) or 2-way valve on request. Condensate d rop let separator made of 316L stainless steel preventing any

    water priming. Removable condensate tray made of 316L stainless steel. Condensate d rain pipe to the outer casing ( 1). Integrated condensate pump (option).

    Copper tubes and aluminium ns. Multiple venturi circuits. 3-way propo rtional co ntrol valve (standard) or 2-way valve on request. Electric hea ter in plac e of or in addition to hot water coil (option).

    Pressure gauges are used for themonitoring of lter clogging at theair intake and air supply.

    Male connectors. Connection at the bottom.

    Speed regulator to maintain constant air ow in line with lter cloggingdegree.

    Single inlet motorised impeller module with low energy consumption (EEF1).

    Integrated motorised dampers at the air intake, air supply or fresh air.

    Air supply filtration

    Air intake filtration

    Cooling coil

    Heating c oil

    Remote assistanc e Electric hea ter in plac e of or

    in add ition to the hot water coil Water lter with drain cock to protect

    control valve (chilled-water or hot- water models) Water sensor alarm

    OptionsPressure gauges

    Chilled / hot water connection

    Fans

    Damper with servo motor

    clinicair 4

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    14/24

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    15/24

    13

    Technical Data & Advantagesof CLINICAIR Range

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    16/24

    14

    Fresh airOutgoing air

    Air supplyAir intake

    Principle of operation CLINICAIR 3

    Principle of operation CLINICAIR 4

    Fresh air

    Air supplyAir intake

    Outgoing air

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    17/24

    Selection of the best equipment to optimize energy consumption

    Low construction and installation costs

    User comfort

    Health and Safety

    Easy maintenanc e

    Up to 75% technical oorspace reduction compared to an equivalentair handling unit.

    Reduction of duct network. Plug & Play solution.

    Allows construction phasing (e.g: frame height of the CLINICAIR 3 enablesthe tting through a standard door).

    Adapts to speci c constraints of any type of the building.

    Remarkable noise level control (e.g: double panels with sound attenuationof -31 dBA and -21 dBA for the CLINICAIR 3).

    Easy access to working parameters. Easy lter clogging control with external pressure gauges.

    Quick return to activity due to reduced installation time. Allows refurbishment of the area without stopping a ctivity.

    C ross contamination reduction due to double skin c asing with remarkabletightness (e.g: CLINICAIR 3 is classi ed L1 for negative pressure and L2 forpositive pressure according to EN 1886 standard).

    Diamond-shaped stainless steel c ondensate tray to a void water stagnation. CLINICAIR 1b or 3 can be lifted upon the ba seboa rd to prevent dust

    accumulation. Batteries with no risk of water carry-over.

    Easy access from front panels allowing quick maintenance. Building management system.

    Internet connec tion for ATA remote tec hnical assistance.

    Single inlet motorised impeller unit with low energy consumption (EEF1). Polypropylene lters with low pressure drop (for CLINICAIR 1b and as an

    option for CLINICAIR 3 and 4). Free-cooling regulation. Optimized coil and frame sizing to reduce air pressure drop.

    Advantages of CLINICAIR Range

    Minimized inconvenience

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    18/24

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    19/24

    17

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    20/24

    18laminar air flow ceilings

    ATA Air Flow Ceiling The range of ATA Laminar Air Flow Ceilings ensures ef cient protection against contaminationwhich c an oc cur during invasive acts and caused by airborne inert or living partic les.

    ATA Laminar Air Flow Ceilings are available in square, rectangular, oc tagonal or round shapes in

    order to suit any room layout and answer speci c requirements to create a clean zone aroundthe patient, medical staff and medical devices. The ceilings are mainly used with CLINICAIR AirHandling Units, but can be also adapted to another AHU.

    The units are dedicated to operating rooms in order to ght airborne infections and meet ISO 5standard (compliance with EN ISO 14644-1) as well as to the pharmaceutical industry.

    ATA has developed two ranges which correspond to different standards:- NFS 90-351 Range:rec tangular, square, octogonal ceilings (on request)

    - DIN 1946 Range:rec tangular, round, octogonal c eilings

    Advantages

    Example: CLINICAIR

    3 with ATA Laminar Air Flow C eiling

    Easy installation and lter replacement Easy tting Various shapes Adaptable with all types of Air Handling Units

    Rectangular / SquareRound Oc togonal

    Fresh airOutgoing air

    Air supplyAir intake

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    21/24

    19 laminar air flow c eilings

    Technical Data

    NFS - 90 - 351 range

    Frame made of 15/10 electro galvanized metal sheet with epoxy RAL 9010 or stainless steel(AISI 304L or AISI 316L).

    Air distribution through metallic grille or stretched fabric . Lateral duct connections. HEPA H14 ltration (ULPA 15 optional). Metal lateral ap ron to stop induc tion (height 100 mm) with epoxy paint (transpa rent apron optional). Central passage for surgical light.

    Measuring connection for Emery testing and/or lter pressure drop measuring. Possibility to add Bioxigen ionisation system: bactericidal, fungucidal, virucidal action.

    X horizontal lter integrated to LAF, air distribution through perforated metallic grille or stretched fabric* 70 mm thickness for 350 mm height and above - initial pressure drop 100 Pa @ 0.25m/s air distribution through stretched fabric, sideway ltration

    Metallic frame made of aluminum with Epoxy Ral 9010 white paint. Air distribution through double stretched fabric. Lateral duc t connec tions. HEPA H13 ltration. Transparent anti-induction lateral apron.

    Central passage for surgical light. Measuring connection for Emery testing and/or lter pressure drop measuring. LED or standard lighting.

    DIN 1946 range

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    22/24

    20

    In order to obtain suitable air quality it is important to take into account the speci ties of the areaand the objectives in terms of particulate and bacteriological cleanliness class, and to de ne thefollowing parameters:

    Air diffusion method, Filtration ef ciency, Air ow rates and conditions (temperature and humidity) at the air supply, air intake, fresh air

    and outgoing air, Noise level allowing users to work in comfortab le conditions.

    Despite the fact that various individua l approaches exist as to the choice of air handling units tobe installed, everyone agrees that only the performant hygienic equipment will be ef cient ineradication of microorganisms (bacteria, viruses, mold, yeast...) using inert air particles to movearound and develop.

    Therefore, designers, manufacturers and users, as well as maintenance teams will ensure, at theirrespective levels, that performant hygienic equipment is selected to achieve the objectives;that it is installed respecting good prac tices; that it is commissioned and maintained in good op-erating c onditions according to the supplier protocols.

    ATA commits to design and deliver the best solution according to the building characteristics andthe activities concerned.

    ATA is an Expert in Air Quality who will provide you with:

    an objective rec ommendation a s to the solution to implement, a strong commitment to selec t performant hygienic equipment, an assistance of a quali ed technician in equipment commissioning, a technical training (ATA is an approved training c enter), a remote assistance to provide problem-free operation.

    In hospital eld, the ght against airborne diseases remains the priority for all healthactors around the world.

    For over the last 25 years ATA has made it a priority to become one of the main actorsin this market and to be recognized today as one of the leading experts in risk area airhandling.

    ATA Commitment

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    23/24

    Other products in ATA Range:

    Mobile Air Treatment Units:

    Protected Environment Transport Chambers:Air Diffusion Ceilings:

    Laminar Air Flow Ceilings:

  • 8/10/2019 Centrale Sali de Operatie Clinicair_ENG

    24/24