Frankfurt (Germany), 6-9 June 2011
RT3b – André Smit, Siemens USA
U.S. Distribution Feeder Automation Pilot Project We have developed a peer-to-peer feeder
automation system using WiMAX and IEC61850 During the project we needed to develop new
protection settings for the feeder We found that conventional settings of
coordinated overcurrent relays was not possible The relay setting groups could not be adapted to
all the different operating scenarios we faced We needed to find a solution that was less
complicated with better performance
Frankfurt (Germany), 6-9 June 2011
Overcurrent protection operate and trip Utility receives a fault notification from a
customer experiencing an outage Trouble desk dispatches a line crew to locate
and isolate the fault Crew restores service to unaffected sections of
line Crew effects repairs and restores feeder to
normal operation Outage time could be measured in hours
André Smit – U.S. – RT3b
Traditional Feeder Operation
Frankfurt (Germany), 6-9 June 2011
Automation of the Distribution Feeder
FLISR Fault Location, Isolation, and Service
Restoration
Circuit Breaker Recloser Switch
Frankfurt (Germany), 6-9 June 2011
Feeder Automation Pilot Project
Frankfurt (Germany), 6-9 June 2011
Automating the Distribution Feeder
Operational Features to Consider Change open point based on loading Isolate line sections for maintenance Transfer to healthy source
Circuit Breaker Recloser
Frankfurt (Germany), 6-9 June 2011
Different curve shapes to deal with
Relay protecting power transformer does not have same shape curve as fuse designed to protect small distribution feeder load
Frankfurt (Germany), 6-9 June 2011
Affect when lowering the Isc
The effect of moving 50 setting to indicate what happens when Isc is low.Little room to coordinate with 51 element. Cannot coordinate with 50 elementas a higher Isc will cross both lines and both relays will trip.
Frankfurt (Germany), 6-9 June 2011
Affect without low Isc being a factor
If low Isc not a factor, more space to coordinate with 51 element and still stay above fuse.
Frankfurt (Germany), 6-9 June 2011
3 Reclosers with Tolerance Affect
Typical TCC curve showing high and low tolerances. (Used ±5% on pickup & time.)Not considering CT tolerance. Illustrates need for space between curves.
Frankfurt (Germany), 6-9 June 2011
1 Recloser
Only one recloser easy to fit between max fuse and feeder main breaker.Better coordination (more space) between all four devices.
Frankfurt (Germany), 6-9 June 2011
One set of TCC curves of 16 setsUsing four total setting groups
150 A
2189 A
360 A
2189 A
312 A
1357 A
256 A
1308 A
200 A
890 A
1386 A
KEL 69KV T1B-OC
ComponentName P1 50/51 Manufacturer SIEMENS7SJ62/63/64, TOC ANSI 7SJ64X CT Ratio 600 / 5 ASettings Phase 51 (0.5-20.0 x CTR) 3 (360A) ANSI Extremely Inv. 2.58 50-1 (0.5-175 x CTR) 7.92 (950.4A) 50-1 Delay (0-60 Sec) 0.1
ComponentName P2 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.39 (312A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 1.15 (920A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P3 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.32 (256A) ANSI Extremely Inv. 0.45 50-1 (0.05-50.0 x CTR) 0.78 (624A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P4 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.25 (200A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 0.5 (400A) 50-1 Delay (0-60 Sec) 0.15
MAX FU 1-2
KEL 69KV T1B-OC
ComponentName P1 50/51 Manufacturer SIEMENS7SJ62/63/64, TOC ANSI 7SJ64X CT Ratio 600 / 5 ASettings Phase 51 (0.5-20.0 x CTR) 3 (360A) ANSI Extremely Inv. 2.58 50-1 (0.5-175 x CTR) 7.92 (950.4A) 50-1 Delay (0-60 Sec) 0.1
ComponentName P2 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.39 (312A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 1.15 (920A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P3 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.32 (256A) ANSI Extremely Inv. 0.45 50-1 (0.05-50.0 x CTR) 0.78 (624A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P4 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.25 (200A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 0.5 (400A) 50-1 Delay (0-60 Sec) 0.15
MAX FU 1-2
TCC Name: BKR KEL 69KV THRU TO OPEN P5 Current Scale x 1 Reference Voltage: 25000 March 31, 2011 9:54 PM Siemens Energy Automation, Wendell, NCExisting devices shown for reference. Instantaneous enabled only during reclose cycle. P1 50-1 delay is 0.10 sec due to longer opening time for breaker vs. recloser.
51 pickup markersLargest downstream fuseFeeder main breaker and three reclosers
50 active only during reclose
Match curvesto data
by color
Upstream Transformer or Bus Main Breaker
Frankfurt (Germany), 6-9 June 2011
One set of TCC curves of 16 setsUsing four total setting groups
150 A
2189 A
360 A
2189 A
312 A
1357 A
256 A
1308 A
200 A
890 A
1386 A
KEL 69KV T1B-OC
ComponentName P1 50/51 Manufacturer SIEMENS7SJ62/63/64, TOC ANSI 7SJ64X CT Ratio 600 / 5 ASettings Phase 51 (0.5-20.0 x CTR) 3 (360A) ANSI Extremely Inv. 2.58 50-1 (0.5-175 x CTR) 7.92 (950.4A) 50-1 Delay (0-60 Sec) 0.1
ComponentName P2 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.39 (312A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 1.15 (920A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P3 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.32 (256A) ANSI Extremely Inv. 0.45 50-1 (0.05-50.0 x CTR) 0.78 (624A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P4 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.25 (200A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 0.5 (400A) 50-1 Delay (0-60 Sec) 0.15
MAX FU 1-2
KEL 69KV T1B-OC
ComponentName P1 50/51 Manufacturer SIEMENS7SJ62/63/64, TOC ANSI 7SJ64X CT Ratio 600 / 5 ASettings Phase 51 (0.5-20.0 x CTR) 3 (360A) ANSI Extremely Inv. 2.58 50-1 (0.5-175 x CTR) 7.92 (950.4A) 50-1 Delay (0-60 Sec) 0.1
ComponentName P2 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.39 (312A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 1.15 (920A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P3 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.32 (256A) ANSI Extremely Inv. 0.45 50-1 (0.05-50.0 x CTR) 0.78 (624A) 50-1 Delay (0-60 Sec) 0.15
ComponentName P4 50/51 Manufacturer SIEMENS7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 ASettings Phase 51 (0.05-2.5 x CTR) 0.25 (200A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 0.5 (400A) 50-1 Delay (0-60 Sec) 0.15
MAX FU 1-2
TCC Name: BKR KEL 69KV THRU TO OPEN P5 Current Scale x 1 Reference Voltage: 25000 March 31, 2011 9:54 PM Siemens Energy Automation, Wendell, NCExisting devices shown for reference. Instantaneous enabled only during reclose cycle. P1 50-1 delay is 0.10 sec due to longer opening time for breaker vs. recloser.
51 pickup markersLargest downstream fuseFeeder main breaker and three reclosers
50 active only during reclose
Match curvesto data
by color
Upstream Transformer or Bus Main Breaker
Frankfurt (Germany), 6-9 June 2011
Difficulties in Coordinating Feeder Reclosers are in series on feeder and not located
on branches Segments have different types of loads Curves for transformers are not as steep Demand changes by time of day and season and
differently for each segment Melt/time characteristics for distribution fuses do
not fit closely with substation transformer protection upstream
Original system designed without new switching points
Frankfurt (Germany), 6-9 June 2011
Difficulties in Coordinating Feeder High source impedance + long line = very low fault
currents Substations located at the ends of the line, so source
impedance is usually high; a long feeder—the best candidate for automation—adds to the impedance
Severe limits caused by existing minimum current settings and low short circuit current (Isc)
Low available Isc limits use of 50, or 50 with definite time Must include considerable allowance for high-impedance
branch line faults causing Isc to be even lower Inrush current could be five times nominal current,
therefore precluding the use of 50 element when Isc is low
Frankfurt (Germany), 6-9 June 2011
How do we deal with these difficulties to protect an Automated Feeder?
Setting Sheets
Frankfurt (Germany), 6-9 June 2011
Our Solution Detect and isolate faults with a differential (87L) function Activate a 50/51 overcurrent curve on one device end and
reclose on fault
87
87
Relay 1
87
87
Relay 2
87
87
Relay 3
Diff Zone Diff Zone
PrimarySwitch 1
PrimarySwitch 2
PrimarySwitch 3
Frankfurt (Germany), 6-9 June 2011
PerformanceDirect Fiber WiMAX
30 msec 80 msec
Frankfurt (Germany), 6-9 June 2011
Automating the Distribution Feeder Locate using 87L
Isolate using 87L & Restore
Reclose using 50/51
Restore
Frankfurt (Germany), 6-9 June 2011
New Protection for Automated Feeders
Transformer
Feeder Breaker
ReclosersFastSelectiveUncomplicated Minimal Disruption for customers
Frankfurt (Germany), 6-9 June 2011
Questions
Top Related