VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... ·...

25
B.INDONESIA УКРАЇНСЬКА РУССКИЙ БЪЛГАРСКИ ΕΛΛΗΝΙΚΆ PORTUGUÊS NEDERLANDS ITALIANO DEUTSCH ESPAÑOL FRANÇAIS ENGLISH – VRF System Air Conditioner – R410A Models Model No. Indoor Units Type Indoor Unit Type Rated Capacity 15 22 28 36 45 56 M1 Slim Low Static Ducted S-15MM1E5A S-22MM1E5A S-28MM1E5A S-36MM1E5A S-45MM1E5A S-56MM1E5A ENGLISH Read through the Installation Instructions before you proceed with the installation. In particular, you will need to read under the “IMPORTANT!” section at the top of the page. FRANÇAIS Lisez les instructions d’installation avant de commencer l’installation. En particulier, vous devez lire la section “IMPORTANT!” en haut de la plage. ESPAÑOL Lea las Instrucciones de instalación antes de proceder con la instalación del equipo. En concreto, deberá leer detenidamente la sección “¡IMPORTANTE!” situada al principio de la página. DEUTSCH Lesen Sie die Einbauanleitung, bevor Sie mit der Installation beginnen. Insbesondere die Hinweise im Abschnitt “WICHTIG!” oben auf der Seite müssen unbedingt gelesen werden. ITALIANO Leggere le Istruzioni di installazione prima di procedere con l’installazione. Prestare particolare attenzione alla sezione “IMPORTANTE!” all’inizio della pagina. NEDERLANDS Lees de installatie-instructies zorgvuldig door voor u begint met de installatie. U moet vooral het gedeelte waar “BELANGRIJK!” boven staat heel goed lezen. PORTUGUÊS Leia cuidadosamente as instruções de instalação antes de prosseguir com a instalação. Em particular, é necessário ler as informações na secção “IMPORTANTE!” na parte superior da página. ΕΛΛΗΝΙΚΆ Διαβάστε τις Οδηγίες εγκατάστασης πριν συνεχίσετε με την εγκατάσταση. Συγκεκριμένα, θα χρειαστεί να διαβάσετε την ενότητα «ΣΗΜΑΝΤΙΚΟ!» στο πάνω μέρος της σελίδας. БЪЛГАРСКИ Прочетете инструкциите за инсталиране преди да продължите с инсталирането. В частност, ще трябва да прочетете раздела „ВАЖНО!“ в горната част на страницата. РУССКИЙ Перед выполнением установки прочтите инструкцию по установке. В частности, вам следует прочесть раздел «ВАЖНО!» вверху страницы. УКРАЇНСЬКА Перш ніж продовжити встановлення, прочитайте вказівки зі встановлення. Зокрема, обов’язково прочитайте розділ «ВАЖЛИВО!» вгорі сторінки. B.INDONESIA Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara khusus, Anda perlu membaca bagian “PENTING!” di bagian atas halaman. for Refrigerant R410A INSTALLATION INSTRUCTIONS F616496 AMP Air Conditioning www.ampair.co.uk | [email protected]

Transcript of VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... ·...

Page 1: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

B.IN

DONE

SIA

УКРА

ЇНСЬ

КАРУ

СС

КИЙ

БЪЛГ

АРСК

ИΕΛ

ΛΗΝ

ΙΚΆ

PO

RTU

GU

ÊS

NED

ERLA

ND

SIT

AL

IAN

OD

EU

TS

CH

ES

PA

ÑO

LF

RA

AIS

EN

GL

ISH

– VRF System Air Conditioner –

■R410A ModelsModel No.

Indoor Units

Type Indoor Unit TypeRated Capacity

15 22 28 36 45 56

M1 SlimLowStaticDucted S-15MM1E5A S-22MM1E5A S-28MM1E5A S-36MM1E5A S-45MM1E5A S-56MM1E5A

ENGLISHReadthroughtheInstallationInstructionsbeforeyouproceedwiththeinstallation.Inparticular,youwillneedtoreadunderthe“IMPORTANT!”sectionatthetopofthepage.

FRANÇAISLisezlesinstructionsd’installationavantdecommencerl’installation.Enparticulier,vousdevezlirelasection“IMPORTANT!”enhautdelaplage.

ESPAÑOLLealasInstruccionesdeinstalaciónantesdeprocederconlainstalacióndelequipo.Enconcreto,deberáleerdetenidamentelasección“¡IMPORTANTE!”situadaalprincipiodelapágina.

DEUTSCHLesenSiedieEinbauanleitung,bevorSiemitderInstallationbeginnen.InsbesonderedieHinweiseimAbschnitt“WICHTIG!”obenaufderSeitemüssenunbedingtgelesenwerden.

ITALIANOLeggereleIstruzionidiinstallazioneprimadiprocedereconl’installazione.Prestareparticolareattenzioneallasezione“IMPORTANTE!”all’iniziodellapagina.

NEDERLANDSLeesdeinstallatie-instructieszorgvuldigdoorvoorubegintmetdeinstallatie.Umoetvooralhetgedeeltewaar“BELANGRIJK!”bovenstaatheelgoedlezen.

PORTUGUÊSLeiacuidadosamenteasinstruçõesdeinstalaçãoantesdeprosseguircomainstalação.Emparticular,énecessáriolerasinformaçõesnasecção“IMPORTANTE!”napartesuperiordapágina.

ΕΛΛΗΝΙΚΆΔιαβάστε τις Οδηγίες εγκατάστασης πριν συνεχίσετε με την εγκατάσταση.Συγκεκριμένα, θα χρειαστεί να διαβάσετε την ενότητα «ΣΗΜΑΝΤΙΚΟ!» στο πάνω μέρος της σελίδας.

БЪЛГАРСКИПрочетете инструкциите за инсталиране преди да продължите с инсталирането.В частност, ще трябва да прочетете раздела „ВАЖНО!“ в горната част на страницата.

РУССКИЙПеред выполнением установки прочтите инструкцию по установке.В частности, вам следует прочесть раздел «ВАЖНО!» вверху страницы.

УКРАЇНСЬКАПерш ніж продовжити встановлення, прочитайте вказівки зі встановлення.Зокрема, обов’язково прочитайте розділ «ВАЖЛИВО!» вгорі сторінки.

B.INDONESIABacalahseluruhPetunjukPemasangansebelumAndamelakukanpemasangan.Secarakhusus,Andaperlumembacabagian“PENTING!”dibagianatashalaman.

forRefrigerantR410A

INSTALLATION INSTRUCTIONS

F616496

II_F616496_EU_L_2.indb 1 2014-10-24 13:53:46

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 2: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

2

IMPORTANT! Please Read Before StartingThisairconditionermustbeinstalledbythesalesdealerorinstaller.Thisinformationisprovidedforuseonlybyauthorizedpersons.

For safe installation and trouble-free operation, you must:● Carefullyreadthisinstructionbookletbeforebeginning.● Followeachinstallationorrepairstepexactlyasshown.● Thisairconditionershallbeinstalledinaccordancewith

NationalWiringRegulations.● Paycloseattentiontoallwarningandcautionnotices

giveninthismanual.

WARNINGThissymbolreferstoahazardorunsafepracticewhichcanresultinseverepersonalinjuryordeath.

CAUTIONThissymbolreferstoahazardorunsafepracticewhichcanresultinpersonalinjuryorproductorpropertydamage.

If Necessary, Get HelpTheseinstructionsareallyouneedformostinstallationsitesandmaintenanceconditions.Ifyourequirehelpforaspecialproblem,contactoursales/serviceoutletoryourcertifieddealerforadditionalinstructions.

In Case of Improper InstallationThemanufacturershallinnowayberesponsibleforimproperinstallationormaintenanceservice,includingfailuretofollowtheinstructionsinthisdocument.

SPECIAL PRECAUTIONS

WARNING WARNING When Wiring

WARNING

Risk of Electric Shock

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.

•Donotsupplypowertotheunituntilallwiringandtubingarecompletedorreconnectedandchecked.

•Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagramandtheseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancauseaccidental injury or death.

•Connectallwiringtightly.Loosewiringmaycauseoverheatingatconnectionpointsandapossiblefirehazard.

•Provideapoweroutlettobeusedexclusivelyforeachunit.

•Provideapoweroutletexclusivelyforeachunit,andfulldisconnectionmeanshavingacontactseparationinallpolesmustbeincorporatedinthefixedwiringinaccordancewiththewiringrules.

•Topreventpossiblehazardsfrominsulationfailure,theunitmustbegrounded.

•ThisequipmentisstronglyrecommendedtobeinstalledwithEarthLeakageCircuitBreaker(ELCB)orResidualCurrentDevice(RCD).Otherwise,itmaycauseelectricalshockandfireincaseofequipmentbreakdownorinsulationbreakdown.

When Transporting

Becarefulwhenpickingupandmovingtheindoorandoutdoorunits.Getapartnertohelp,andbendyourkneeswhenliftingtoreducestrainonyourback.Sharpedgesorthinaluminumfinsontheairconditionercancutyourfingers.

When Installing…

Selectaninstallationlocationwhichisrigidandstrongenoughtosupportorholdtheunit,andselectalocationforeasymaintenance.…In a RoomProperlyinsulateanytubingruninsidearoomtoprevent“sweating”thatcancausedrippingandwaterdamagetowallsandfloors.

WARNINGCAUTIONKeepthefirealarmandtheairoutletatleast1.5mawayfromtheunit.

…In Moist or Uneven LocationsUsearaisedconcretepadorconcreteblockstoprovideasolid,levelfoundationfortheoutdoorunit.Thispreventswaterdamageandabnormalvibration.…In an Area with High WindsSecurelyanchortheoutdoorunitdownwithboltsandametalframe.Provideasuitableairbaffle.

II_F616496_EU_L_2.indb 2 2014-10-24 13:53:47

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 3: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

3

EN

GL

ISH

…In a Snowy Area (for Heat Pump-type Systems)Installtheoutdoorunitonaraisedplatformthatishigherthandriftingsnow.Providesnowvents.…At least 2.5 mIndoorunitofthisairconditionershallbeinstalledinaheightofatleast2.5m.…In laundry roomsDonotinstallinlaundryrooms.Indoorunitisnotdripproof.

When Connecting Refrigerant Tubing

WARNINGWARNING• Whenperformingpipingworkdonot

mixairexceptforspecifiedrefrigerant(R410A)inrefrigerationcycle.Itcausescapacitydown,andriskofexplosionandinjuryduetohightensioninsidetherefrigerantcycle.

• Refrigerantgasleakagemaycausefire.• Donotaddorreplacerefrigerant

otherthanspecifiedtype.Itmaycauseproductdamage,burstandinjury,etc.

• Ventilatetheroomwell,intheeventthatisrefrigerantgasleaksduringtheinstallation.Becarefulnottoallowcontactoftherefrigerantgaswithaflameasthiswillcausethegenerationofpoisonousgas.

• Keepalltubingrunsasshortaspossible.

• Usetheflaremethodforconnectingtubing.

• Applyrefrigerantlubricanttothematchingsurfacesoftheflareanduniontubesbeforeconnectingthem,thentightenthenutwithatorquewrenchforaleak-freeconnection.

• Checkcarefullyforleaksbeforestartingthetestrun.

• Donotleakrefrigerantwhilepipingworkforaninstallationorre-installation,andwhilerepairingrefrigerationparts.Handleliquidrefrigerantcarefullyasitmaycausefrostbite.

When Servicing

• TurnthepowerOFFatthemainpowerbox(mains)beforeopeningtheunittocheckorrepairelectricalpartsandwiring.

• Keepyourfingersandclothingawayfromanymovingparts.

• Cleanupthesiteafteryoufinish,rememberingtocheckthatnometalscrapsorbitsofwiringhavebeenleftinsidetheunitbeingserviced.

WARNINGWARNING• Thisproductmustnotbe

modifiedordisassembledunderanycircumstances.Modifiedordisassembledunitmaycausefire,electricshockorinjury.

• Donotcleaninsidetheindoorandoutdoorunitsbyusers.Engageauthorizeddealerorspecialistforcleaning.

• Incaseofmalfunctionofthisappliance,donotrepairbyyourself.Contactthesalesdealerorservicedealerforrepair.

WARNINGCAUTION• Donottouchtheairinletorthe

sharpaluminumfinsoftheoutdoorunit.Youmaygetinjured.

• Ventilateanyenclosedareaswheninstallingortestingtherefrigerationsystem.Escapedrefrigerantgas,oncontactwithfireorheat,canproducedangerouslytoxicgas.

• Confirmafterinstallationthatnorefrigerantgasisleaking.Ifthegascomesincontactwithaburningstove,gaswaterheater,electricroomheaterorotherheatsource,itcancausethegenerationofpoisonousgas.

Others

WARNINGCAUTION• Donotsitorstepontheunit,you

mayfalldownaccidentally.• Donottouchtheairinletorthe

sharpaluminumfinsoftheoutdoorunit.Youmaygetinjured.

• DonotstickanyobjectintotheFANCASE.Youmaybeinjuredandtheunitmaybedamaged.

NOTICE

TheEnglishtextistheoriginalinstructions.Otherlanguagesaretranslationsoftheoriginalinstructions.

II_F616496_EU_L_2.indb 3 2014-10-24 13:53:49

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 4: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

4

IMPORTANT! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

PleaseReadBeforeStarting

1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1-1. ToolsRequiredforInstallation(notsupplied)

1-2. AccessoriesSuppliedwithUnit

1-3. TypeofCopperTubeandInsulationMaterial

1-4. AdditionalMaterialsRequiredforInstallation

2. SELECTING THE INSTALLATION SITE . . . . . . . . . . . . . . 6

IndoorUnit

3. HOW TO INSTALL THE INDOOR UNIT . . . . . . . . . . . . . . . 7

■ SlimLowStaticDuctedType(TypeM1). . . . . . . . . . . . . . .7

3-1. RequiredMinimumSpaceforInstallationandService

3-2. PreparationsBeforeInstallation

3-3. ForBottomIntake

3-4. InstallingtheDuct

3-5. SuspendingtheIndoorUnit

3-6. InstallingtheDrainPipe

3-7. CheckingtheDrainage

4. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

4-1. GeneralPrecautionsonWiring

4-2. RecommendedWireLengthandWireDiameterforPowerSupplySystem

4-3. WiringSystemDiagrams

5. HOW TO PROCESS TUBING . . . . . . . . . . . . . . . . . . . . . 16

5-1. ConnectingtheRefrigerantTubing

5-2. ConnectingTubingBetweenIndoorandOutdoorUnits

5-3. InsulatingtheRefrigerantTubing

5-4. TapingtheTubes

5-5. FinishingtheInstallation

Page

6. HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH-SPEC WIRED REMOTE CONTROLLER (OPTIONAL PART) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

NOTE

RefertotheOperatingInstructionsattachedtotheoptionalTimerRemoteControlleroroptionalHigh-specWiredRemoteController.

7. HOW TO INSTALL WIRELESS REMOTE CONTROLLER RECEIVER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

NOTE

RefertotheOperatingInstructionsattachedtotheoptionalWirelessRemoteControllerReceiver.

8. EXTERNAL STATIC PRESSURE SETTING . . . . . . . . . . 19

8-1. HowtoSetonPCBoard

8-2. OperatingtheTimerRemoteController(CZ-RTC2)

8-3. OperatingtheHigh-specWiredRemoteController(CZ-RTC3)

9. APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

■ NamesofParts

■ CareandCleaning

IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Page

CONTENTS

II_F616496_EU_L_2.indb 4 2014-10-24 13:53:49

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 5: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

5

EN

GL

ISH

1. GENERALThisbookletbrieflyoutlineswhereandhowtoinstalltheairconditioningsystem.Pleasereadovertheentiresetofinstructionsfortheindoorandoutdoorunitsandmakesureallaccessorypartslistedarewiththesystembeforebeginning.

1-1. Tools Required for Installation (not supplied)1. Flatheadscrewdriver

2. Phillipsheadscrewdriver

3. Knifeorwirestripper

4. Tapemeasure

5. Carpenter’slevel

6. Sabresaworkeyholesaw

7. Hacksaw

8. Corebits

9. Hammer

10. Drill

11. Tubecutter

12. Tubeflaringtool

13. Torquewrench

14. Adjustablewrench

15. Reamer(fordeburring)

1-2. Accessories Supplied with Unit

Part Name Figure Q’ty Remarks

Washer 8 Forsuspensionfitting

Flareinsulator

2 Forgaspipe/liquidpipeconnection

2 Forgaspipe/liquidpipeconnection

Clamper 4 Forflare/draininsulatingconnection

DrainhoseL=131

1 Forunit&PVCpipeconnection

Hoseband 1 Fordrainhoseconnection

Drainhoseinsulation 2 Fordrainpipeconnection

Clamper1 Forpowersupplycode

Besuretofixthepowersupplycordwiththeclamper.

Short-circuitconnection 1

Forhighstaticpressure(Locatedonthebackoftheelectricalcomponentboxlid.)

•Use3/8”(M10)forsuspensionbolts.•Suspensionboltsandnutsarefieldsupply.

1-3. Type of Copper Tube and Insulation MaterialIfyouwishtopurchasethesematerialsseparatelyfromalocalsource,youwillneed:

1. Deoxidizedannealedcoppertubeforrefrigeranttubing.

2. Foamedpolyethyleneinsulationforcoppertubesasrequiredtopreciselengthoftubing.Wallthicknessoftheinsulationshouldbenotlessthan5/16”(8mm).

3. Useinsulatedcopperwireforfieldwiring.Wiresizevarieswiththetotallengthofwiring.Referto4.ELECTRICALWIRINGfordetails.

CAUTION

Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.

1-4. Additional Materials Required for Installation1. Refrigeration(armored)tape

2. Insulatedstaplesorclampsforconnectingwire(Seeyourlocalcodes.)

3. Putty

4. Refrigerationtubinglubricant

5. Clampsorsaddlestosecurerefrigeranttubing

6. Scaleforweighing

II_F616496_EU_L_2.indb 5 2014-10-24 13:53:51

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 6: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

6

2. SELECTING THE INSTALLATION SITE Indoor Unit

AVOID:● areaswhereleakageofflammablegasmaybeexpected.● placeswherelargeamountsofoilmistexist.● directsunlight.● locationsnearheatsourceswhichmayaffectthe

performanceoftheunit.● locationswhereexternalairmayentertheroomdirectly.

Thismaycause“condensation”ontheairdischargeports,causingthemtosprayordripwater.

● locationswheretheremotecontrollerwillbesplashedwithwateroraffectedbydampnessorhumidity.

● installingtheremotecontrollerbehindcurtainsorfurniture.● locationswherehigh-frequencyemissionsaregenerated.

DO:● selectanappropriatepositionfromwhicheverycornerofthe

roomcanbeuniformlycooled.● selectalocationwheretheceilingisstrongenoughto

supporttheweightoftheunit.● selectalocationwheretubinganddrainpipehavethe

shortestruntotheoutdoorunit.● allowroomforoperationandmaintenanceaswellas

unrestrictedairflowaroundtheunit.● installtheunitwithinthemaximumelevationdifference

aboveorbelowtheoutdoorunitandwithinatotaltubinglength(L)fromtheoutdoorunitasdetailedintheinstallationmanualpackedwiththeoutdoorunit.

● allowroomformountingtheremotecontrollerabout1m(3.3ft.)offthefloor,inanareathatisnotindirectsunlightnorintheflowofcoolairfromtheindoorunit.

● Theelevation(SlimLowStaticDucted)betweenthebottomunitandthefloorsurfaceshouldbeatleast2.4m(8feet).

● Iftheelevation(SlimLowStaticDucted)betweenthemislessthan2.4m(8feet),installafilteroraprotectivedevice(fieldsupply)nottotouchtheelectricalpartsorfanwithhands.

2.4m(8feet)ormore

Floor

Fig. 2-1

II_F616496_EU_L_2.indb 6 2014-10-24 13:53:51

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 7: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

7

EN

GL

ISH

564

3. HOW TO INSTALL THE INDOOR UNIT

■ Slim Low Static Ducted Type (Type M1)

3-1. Required Minimum Space for Installation and Service

● Thisairconditionerisusuallyinstalledabovetheceilingsothattheindoorunitandductsarenotvisible.Onlytheairintakeandairoutletportsarevisiblefrombelow.

● Theminimumspaceforinstallationandserviceisshowninthediagram.(Fig.3-1)

● *Hdimensionmeanstheminimumheightoftheunit.● Selectthe*Hdimensionsuchthatadownwardslopeofat

least1/100isensuredasindicatedin“3-6. Installing the Drain Pipe”.

● Thediagramshowsthedetaileddimensionsoftheindoorunit.(Fig.3-2)

Fig. 3-1

Fig. 3-2

Unit:mm1 Refrigeranttubingjoint(narrowtube)

2 Refrigeranttubingjoint(widetube)

3 Upperandbottomdrainport(O.D.26mm)

4 Suspensionlug

5 Powersupplyoutlet(ø17)

6 Flangeforairoutletduct

7 Coverplate

8 Electricalcomponentbox

9 Filter

0Inter-unitcontrolwiringandcontrolwiringforgroupcontroloutlet(ø15)

! Remotecontrolwiringoutlet(ø15)

824(Suspensionboltpitch)

Flangeforairoutletduct

Min.100mmormoreforbottomairintake

8

6

4

7

1

2

5

10

119

3

145

6922996

750

640

194

38

37

150

6626

27

2830

81

33

153

150200

301080

143

238

44

126

680

2215

523

40 1412

015

14

70423 23132 220 220 132

14

84

640 (160x4)

824

2-ø3.1(Hole)

10-ø3.1(Hole)

*FilterUninstalled

(Flangeforairoutletduct)

5-ø3.1(Hole)

(Suspensionboltpitch)

Inspectionaccess(450x450)

(Fieldsupply)

Waterinlet

Fla

nge

for

air

outle

tduc

t56

4(S

uspe

nsio

nbo

ltpi

tch)

Ceiling

Unit:mm

Refrigeranttubing

Min.650ormore

Inspectionaccess

450x450

Electricalcomponentbox

Min.200ormore

Min.20ormore

200

Min.20ormore *H=

Min

.240

Min

.20

0or

m

ore

II_F616496_EU_L_2.indb 7 2014-10-24 13:53:52

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 8: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

8

3-2. Preparations Before Installation(1)Confirmthepositionalrelationshipbetweentheunitand

suspensionbolts.(Fig.3-3)

● Installtheinspectionopeningonthecontrolboxsidewheremaintenanceandinspectionofthecontrolboxanddrainpumpareeasy.Installtheinspectionopeningalsointhelowerpartoftheunit.

70080

0

A

Airdischarge Airintake

Ceiling

Unit:mm

(Inspectionaccess)

AllowviewAInspectionaccess

(Fieldsupply)

Fig. 3-3

(2)Makesuretherangeoftheunit’sexternalstaticpressureisnotexceeded.(Seethetechnicaldocumentationfortherangeoftheexternalstaticpressuresetting.)

(3)Opentheinstallationhole.(Pre-setceilings)

●Oncetheinstallationholeisopenedintheceilingwheretheunitistobeinstalled,passrefrigerantpiping,drainpiping,inter-unitcontrolwiring,andremotecontrollerwiringtotheunit’spipingandwiringholes.See“5. HOW TO PROCESS TUBING”,“3-6. Installing the Drain Pipe”and“4. ELECTRICAL WIRING”.

●Afteropeningtheceilinghole,makesureceilingislevelifneeded.Itmightbenecessarytoreinforcetheceilingframetopreventshaking.Consultanarchitectorcarpenterfordetails.

3-3. For Bottom IntakeForbottomintake,replacethecoverplateandFrameFilterAssynetintheprocedureshowninthediagram.

(1)Removetheframefilterassy.Removethecoverplate.(Fig.3-4)

Airintake

FrameFilterAssy

Coverplate

Airdischarge

Dummyhole

Fig. 3-4

(2)Refertothediagramtoattachthecoverplateandframefilterassyinthedirectionofthearrow.(Fig.3-5)Note:Attachthecoverplatewiththedummyholesdownward.

Dummyhole

Coverplate

Airdischarge

Airintake

FrameFilterAssy

Fig. 3-5

(3)Attachtheframefilterassy(supplied)inthemannershowninthediagram.(Fig.3-6)

Mainunit

FrameFilterAssy

Incaseofbottomside Incaseofbackside

AttachtheFrameFilterAssytothemainunitwhilepushingthetipofthelatchesinthedirectionofthearrow.

Fig. 3-6

II_F616496_EU_L_2.indb 8 2014-10-24 13:53:53

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 9: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

9

EN

GL

ISH

3-4. Installing the DuctConnecttheductsuppliedinthefieldasshowninFig.3-7.

Flange(Fieldsupply)

Rectangularsolidduct(Fieldsupply)

Insulationmaterial(Fieldsupply)

Connectionscrew(x10)

Airinletside Airoutletside

Mainunit

Flange

Fig. 3-7

Air inlet side

• Attachtheductandintake-sideflange(fieldsupply).• Connecttheflangetothemainunitwith10-ø3.1(Hole)

screws.• Wraptheintake-sideflangeandductconnectionareawith

aluminumtapeorsomethingsimilartopreventairescaping.

CAUTION

When attaching a duct to the intake-side, be sure to attach an air filter inside the air passage on the intake-side. (Use an air filter whose dust collecting efficiency is at least 50% in a gravimetric technique.)The included filter is not used when the intake duct is attached.

Air outlet side

• Connecttheductaccordingtotheairoutsideoftheoutlet-sideflange.

• Wraptheoutlet-sideflangeandtheductconnectionareawithaluminumtapeorsomethingsimilartopreventairescaping.

CAUTION

●Besuretoinsulatetheducttopreventcondensationfromforming.(Material:glasswoolorpolyethylenefoam,25mmthick)

●Useelectricinsulationbetweentheductandthewallwhenusingmetalductstopassmetallathsofthenetorfenceshapeormetalplatingintowoodenbuildings.

●Besuretoexplainaboutthewayofmaintainingandcleaninglocalprocurements(airfilter,grille[bothairoutletandsuctiongrille],etc.)toyourcustomer.

3-5. Suspending the Indoor UnitDependingontheceilingtype:

• Insertsuspensionboltsasshowninthediagram.(Fig.3-8)or

• Useexistingceilingsupportsorconstructasuitablesupportasshowninthediagram.(Fig.3-9)

Hole-in-anchorHole-in-plug

Suspensionbolt(M10or3/8”)(fieldsupply)

ConcreteInsert

Ceilingtiles

Ceilingsupport

Fig. 3-8 Fig. 3-9

WARNING

It is important that you use extreme care in supporting the indoor unit inside the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.

(1)Whenplacingtheunitinsidetheceiling,determinethepitchofthesuspensionboltsreferringtothedimensionaldataasshowninFig.3-1.Tubingmustbelaidandconnectedinsidetheceilingwhensuspendingtheunit.Iftheceilingisalreadyconstructed,laythetubingintopositionforconnectiontotheunitbeforeplacingtheunitinsidetheceiling.

(2)ScrewinthesuspensionboltsallowingthemtoprotrudefromtheceilingasshowninFig.3-8.(Cuttheceilingmaterial,ifnecessary.)

(3)Threadthe3hexagonalnutsand2washers(fieldsupply)ontoeachofthe4suspensionboltsasshowninFig.3-10and3-11.Use1nutand1washerfortheupperpart,and2nutsand1washerforthelowerpart,sothattheunitwillnotfalloffthesuspensionlugs.

Nutsandwashers(useforupperandlower)

Suspensionbolt

Doublenuts

Suspensionlug

Notch

Fig. 3-10Suspensionbolt

Hexagonalnut

Doublenuts

Fig. 3-11

II_F616496_EU_L_2.indb 9 2014-10-24 13:53:54

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 10: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

10

(4)Adjusttheheightoftheunit.

(5)Checktheunitishorizontallylevel.

CAUTION

●Makesuretheunitisinstalledlevelusingaleveloravinylhosefilledwithwater.Inusingavinylhoseinsteadofalevel,adjustthetopsurfaceoftheunittothesurfaceofthewateratbothendsofthevinylhoseandadjusttheunithorizontally.(Onethingtowatchoutforinparticularisiftheunitisinstalledsothattheslopeisnotinthedirectionofthedrainpiping,thismightcauseleaking.)(Fig.3-12)

Level

Vinylhose

Fig. 3-12

(6)Tightentheuppernut.

3-6. Installing the Drain Pipe(1)PreparestandardhardPVCpipeVP20(O.D.26mm)forthe

drainandusethesuppliedhosebandtopreventwaterleaks.(Fig.3-13)ThePVCpipemustbepurchasedseparately.Thetransparentdrainpartontheunitallowsyoutocheckdrainage.

(45°)

Unitdrainport Hoseband(supplied)

Drainhose(supplied)

Donotuseadhesive.AdherewithPVCadhesive.

Draininsulator(supplied)

VinyltapeDraininsulator

Vinyltape

Hoseband

DraininsulatorHoseband

Unit:mm

HardPVCpipe(VP20notsupplied)

Fig. 3-13

CAUTION

●Attachsothatthehosebandfastenerisonthesideofthedrainport.(Fig.3-13)

●Attachthehosebandssothateachisapproximately5to25mmfromtheendofthesupplieddrainhose.(Fig.3-13)

●Do not use adhesive at the drain connection port on the indoor unit.

● Insert the drain pipe until it contacts the socket, as shown in the figure above, then secure it tightly with the hose band.

●Do not use the supplied drain hose bent at a 90° angle. (The maximum permissible bend is 45°.)

NOTE

Makesurethedrainpipehasadownwardgradient(1/100ormore)andthattherearenowatertraps.

CAUTION

●Do not install an air bleeder as this may cause water to spray from the drain pipe outlet. (Fig. 3-14)

Airbleeder

Prohibited

Fig. 3-14

●Make sure that the drain port is not a downward gradient from the joint section (may lead to abnormal noise). (Fig. 3-15)

● If it is necessary to increase the height of the drain pipe, the section directly after the connection port can be raised a maximum of 500 mm. Do not raise it any higher than 500 mm, as this could result in water leaks. (Fig. 3-15)

Atleast1/100

Good

300mmorless(notadownwardgradient)

500mmorless

Fig. 3-15

II_F616496_EU_L_2.indb 10 2014-10-24 13:53:55

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 11: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

11

EN

GL

ISH

●Do not install the pipe with an upward gradient from the connection port. This will cause the drain water to flow backward and leak when the unit is not operating. (Fig. 3-16)

Upwardgradient

Prohibited

Fig. 3-16

●Do not apply force to the piping on the unit side when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connection to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 3-17)

Supportpieces

Fig. 3-17

3-7. Checking the DrainageAfterwiringanddrainpipingarecompleted,usethefollowingproceduretocheckthatthewaterwilldrainsmoothly.Forthis,prepareabucketandwipingclothtocatchandwipeupspilledwater.

(1)Connectpowertothepowerterminalboard(R,Sterminals)insidetheelectricalcomponentbox.

(2)Removetheeyeletcapandthroughtheopening,slowlypourabout500ccofwaterintothedrainpantocheckdrainage.

(3)Shortthecheckpin(CHK)ontheindoorcontrolboardandoperatethedrainpump.Checkthewaterflowthroughthetransparentdrainportandseeifthereisanyleakage.(Fig.3-19)

CAUTION

Be careful since the fan will start when you short the pin on the indoor control board.

(4)Whenthecheckofdrainageiscomplete,openthecheckpin(CHK)andremounttheinsulatoranddraincapontothedraininspectionport.

Waterinlet

Wiringport

Eyeletcap

Fig. 3-18

Indoor control board

TP6

CN11

2

CN11

1

CN11

0

WHT YE

L

RED

TP3

EMG

CN06

2CH

K

CN06

3DI

SP

CN06

4

CN073

TEST

EXCTFILTER

OC RCCN044 CN040 CN041

FAN-

TAP TP

1

IC010

IC001

T5A E250V

JP001

JP04

0

Checkpin(CHK:CN062)

Fig. 3-19

II_F616496_EU_L_2.indb 11 2014-10-24 13:53:56

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 12: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

12

4. ELECTRICAL WIRING

4-1. General Precautions on Wiring (1) Beforewiring,confirmtheratedvoltageoftheunitasshownonitsnameplate,thencarryoutthewiringcloselyfollowingthewiring

diagram.

WARNING

(2) ThisequipmentisstronglyrecommendedtobeinstalledwithEarthLeakageCircuitBreaker(ELCB)orResidualCurrentDevice(RCD).Otherwise,itmaycauseelectricalshockandfireincaseofequipmentbreakdownorinsulationbreakdown.EarthLeakageCircuitBreaker(ELCB)mustbeincorporatedinthefixedwiringinaccordancewiththewiringregulations.TheEarthLeakageCircuitBreaker(ELCB)mustbeanapproved10-16A,havingacontactseparationinallpoles.

(3) Topreventpossiblehazardsfrominsulationfailure,theunitmustbegrounded.

(4) Eachwiringconnectionmustbedoneinaccordancewiththewiringsystemdiagram.Wrongwiringmaycausetheunittomisoperateorbecomedamaged.

(5) Donotallowwiringtotouchtherefrigeranttubing,compressor,oranymovingpartsofthefan.

(6) Unauthorizedchangesintheinternalwiringcanbeverydangerous.Themanufacturerwillacceptnoresponsibilityforanydamageormisoperationthatoccursasaresultofsuchunauthorizedchanges.

(7) Regulationsonwirediametersdifferfromlocalitytolocality.Forfieldwiringrules,pleaserefertoyourLOCALELECTRICALCODESbeforebeginning.

Youmustensurethatinstallationcomplieswithallrelevantrulesandregulations.

(8) Topreventmalfunctionoftheairconditionercausedbyelectricalnoise,caremustbetakenwhenwiringasfollows:

●Theremotecontrolwiringandtheinter-unitcontrolwiringshouldbewiredapartfromtheinter-unitpowerwiring.

●Useshieldedwiresforinter-unitcontrolwiringbetweenunitsandgroundtheshieldonbothsides.

(9) Ifthepowersupplycordofthisapplianceisdamaged,itmustbereplacedbyarepairshopdesignatedbythemanufacturer,becausespecial-purposetoolsarerequired.

4-2. Recommended Wire Length and Wire Diameter for Power Supply System

Indoor unit

Type(B) Power supply Time delay fuse or

circuit capacity2.5 mm2

M1 Max.130m 10-16A

Control wiring(C) Inter-unit

control wiring (between outdoor and indoor units)

(D) Remote control wiring

(E) Control wiring for group control

0.75mm2

(AWG#18)Use shielded wiring*

0.75mm2

(AWG#18)0.75mm2

(AWG#18)

Max.1,000m Max.500m Max.200m(Total)

NOTE

*Withring-typewireterminal.

II_F616496_EU_L_2.indb 12 2014-10-24 13:53:56

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 13: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

13

EN

GL

ISH

4-3. Wiring System Diagrams

NOTE(1) RefertoSection“4-2.RecommendedWireLength

andWireDiameterforPowerSupplySystem”fortheexplanationof“B”,“C”,“D”and“E”intheabovediagram.

(2) Thebasicconnectiondiagramoftheindoorunitshowstheterminalboards,sotheterminalboardsinyourequipmentmaydifferfromthediagram.(Fig.4-2)

(3) RefrigerantCircuit(R.C.)addressshouldbesetbeforeturningthepoweron.

(4) RegardingR.C.addresssetting,refertotheinstallationinstructionssuppliedwiththeremotecontrollerunit(optional).Autoaddresssettingcanbeexecutedbyremotecontrollerautomatically.Refertotheinstallationinstructionssuppliedwiththeremotecontrollerunit(optional).

L N U1 U2 R1 R2

6Pterminalboard

Type M1

Powersupply

Remotecontrol

line

Unitcontrol

line

Fig. 4-2

Fig. 4-1

U2

U1

R2

R1

L

N

R2

R1

R2

R1

R2

R1

2

1

2

1

U2

U1

L

N

U2

U1

L

N

U2

U1

L

N

2

1

2

1

2

1

D

E

C

B

LN

LN

LN

LN

2

1

B

B

B

C

D

D

C

2

1

L1L2L3N

2

1

L1L2L3N

CL1

L2

L3

N

L1

L2

L3

N

U2

U1

Powersupply220/230/240V~50/60Hz

Powersupply220/230/240V~50/60Hz

Powersupply220/230/240V~50/60Hz

Powersupply220/230/240V~50/60Hz

Remotecontroller

Remotecontroller

Remotecontroller

WHTBLK

WHTBLK

WHTBLK

Ground

Ground

Ground

Ground

Ground

GroundInter-outdoor-unitcontrolwiring

Ground

Ground Ground

OutdoorunitINVunit

Powersupply380/400/415V,3N~,50Hz

ex.)TypeMF2

Powersupply380/400/415V,3N~,50Hz

OutdoorunitINVunit

Ground

Ground

Ground

Ground

Ground

Ground

Indoorunit(No.1)

Indoorunit(No.2)

Indoorunit(No.n)

Indoorunit(No.3)

Groupcontrol:

II_F616496_EU_L_2.indb 13 2014-10-24 13:53:57

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 14: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

14

CAUTION

(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug.

(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-3)

Outdoorunit Outdoorunit Outdoorunit

Indoorunit Indoorunit Indoorunit Indoorunit

Prohibited

Prohibited

Indoorunit

Fig. 4-3

(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting. (Fig. 4-4)

Fig. 4-4

(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.

CentralController

Outdoorunit

Outdoorunit

Indoorunit

Indoorunit

Indoorunit Indoorunit Indoorunit

Indoorunit Indoorunit

Indoorunit Indoorunit

Outdoorunit

:Branchpoint

Mor

eth

an2

mr

equi

red

Fig. 4-5

Outdoorunit IndoorunitIndoorunit

IndoorunitIndoorunitNOBranchpoint

(5) Use shielded wires for inter-unit control wiring (C) and ground the shield on both sides, otherwise misoperation from noise may occur. (Fig. 4-6) Connect wiring as shown in Section “4-3. Wiring System Diagrams”.

Fig. 4-6

(6) • Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 or 3 *1.5 mm2 flexible cord. Type designation 60245 IEC57 (H05RN-F, GP85PCP etc.) or heavier cord.

• Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to CENELEC (HAR) rating specifications) or use the cables based on IEC standard. (60245 IEC57, 60245 IEC66)

WARNING

Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also occur. Therefore, ensure that all wiring is tightly connected.

Whenconnectingeachpowerwiretotheterminal,followtheinstructionson“Howtoconnectwiringtotheterminal”andfastenthewiresecurelywiththeterminalscrew.

Shieldedwire

Ground Ground

II_F616496_EU_L_2.indb 14 2014-10-24 13:53:58

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 15: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

15

EN

GL

ISH

Strandedwire

Ringpressureterminal

ScrewandSpecialwasher

Ringpressureterminal

Terminalboard

Ringpressureterminal

ScrewSpecialwasher

Wire

Wire

Insulationtape

8mm

Insulationtape

Shieldmesh

Shieldmesh

Str

ip1

0m

m

Fig. 4-7 Fig. 4-8

Fig. 4-9

Fig. 4-10

Fig. 4-11

Fig. 4-12

How to connect wiring to the terminal

■ Examples of shield wires(1) Removecablecoatnottoscratchbraidedshield.(Fig.4-9)

(2) Unbraidthebraidedshieldcarefullyandtwisttheunbraidedshieldwirestightlytogether.Insulatetheshieldwiresbycoveringthemwithaninsulationtubeorwrappinginsulationtapearoundthem.(Fig.4-10)

(3) Removecoatofsignalwire.(Fig.4-11)

(4) AttachringpressureterminalstothesignalwiresandtheshieldwiresinsulatedinStep(2).(Fig.4-12)

■ Wiring samples

ClamperinsidetheboxforRemoteControlWiringandInter-unitControlWiring

UsethisscrewwhenconnectingtheshieldfortheInter-unitcontrolwiringtoground.

Functionalgroundscrew(ExternalElectronicExpansionValveKitandScheduleTimer)

Protectivegroundscrew(ExternalSolenoidValveKitfor3WAY)

ClamperonthefrontsideforPowerSupply

ClampingClip

Inter-unitControlWiring

WireSaddle

PowerSupply

WireSaddle

PowerSupply

SuppliedClamper*

*Routethepowersupplycordthroughtheringofthesuppliedwiresaddleandclampthecord.

RemoteControlWiring

Inter-unitControlWiring

RemoteControlWiring

Type M1

■ For stranded wiring(1) Cutthewireendwithcuttingpliers,

thenstriptheinsulationtoexposethestrandedwiringabout10mmandtightlytwistthewireends.(Fig.4-7)

(2) UsingaPhillipsheadscrewdriver,removetheterminalscrew(s)ontheterminalboard.

(3) Usingaringconnectorfastenerorpliers,securelyclampeachstrippedwireendwitharingpressureterminal.

(4) Placetheringpressureterminal,andreplaceandtightentheremovedterminalscrewusingascrewdriver.(Fig.4-8)

II_F616496_EU_L_2.indb 15 2014-10-24 13:54:00

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 16: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

16

5. HOW TO PROCESS TUBING

5-1. Connecting the Refrigerant Tubing

Use of the Flaring Method

Manyofconventionalsplitsystemairconditionersemploytheflaringmethodtoconnectrefrigeranttubesthatrunbetweenindoorandoutdoorunits.Inthismethod,thecoppertubesareflaredateachendandconnectedwithflarenuts.

Flaring Procedure with a Flare Tool

(1) Cutthecoppertubetotherequiredlengthwithatubecutter.Itisrecommendedtocutapprox.30–50cmlongerthanthetubinglengthyouestimate.

(2) Removeburrsateachendofthecoppertubingwithatubereamerorfile.Thisprocessisimportantandshouldbedonecarefullytomakeagoodflare.Besuretokeepanycontaminants(moisture,dirt,metalfilings,etc.)fromenteringthetubing.(Figs.5-1and5-2)

AfterBefore

Deburring

Coppertubing

Reamer

Fig. 5-1 Fig. 5-2

NOTE

Whenreaming,holdthetubeenddownwardandbesurethatnocopperscrapsfallintothetube.(Fig.5-2)

(3) Removetheflarenutfromtheunitandbesuretomountitonthecoppertube.

(4) Makeaflareattheendofthecoppertubewithaflaretool.(Fig.5-3)

Flarenut

Coppertubing

FlaretoolFig. 5-3

NOTE

Agoodflareshouldhavethefollowingcharacteristics:

● insidesurfaceisglossyandsmooth● edgeissmooth● taperedsidesareofuniformlength

Caution Before Connecting Tubes Tightly

(1) Applyasealingcaporwater-prooftapetopreventdustorwaterfromenteringthetubesbeforetheyareused.

(2) Besuretoapplyrefrigerantlubricant(etheroil)totheinsideoftheflarenutbeforemakingpipingconnections.Thisiseffectiveforreducinggasleaks.(Fig.5-4)

Applyrefrigerantlubricant.

Fig. 5-4

(3) Forproperconnection,aligntheuniontubeandflaretubestraightwitheachother,thenscrewontheflarenutlightlyatfirsttoobtainasmoothmatch.(Fig.5-5)

FlarenutUnion

Fig. 5-5

● Adjusttheshapeoftheliquidtubeusingatubebenderattheinstallationsiteandconnectittotheliquidtubingsidevalveusingaflare.

5-2. Connecting Tubing Between Indoor and Outdoor Units

(1) Tightlyconnecttheindoor-siderefrigeranttubingextendedfromthewallwiththeoutdoor-sidetubing.

Indoor Unit Tubing Connection

Indoor unit type 15 22 28 36 45 56

Gastubing(mm) ø12.7

Liquidtubing(mm) ø6.35

(2) Tofastentheflarenuts,applyspecifiedtorque.

● Whenremovingtheflarenutsfromthetubingconnections,orwhentighteningthemafterconnectingthetubing,besuretouse2adjustablewrenchesorspanners.(Fig.5-6)Iftheflarenutsareover-tightened,theflaremaybedamaged,whichcouldresultinrefrigerantleakageandcauseinjuryorasphyxiationtoroomoccupants.

Outdoorunit

Torquewrench

SpannerIndoorunit

Fig. 5-6

II_F616496_EU_L_2.indb 16 2014-10-24 13:54:01

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 17: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

17

EN

GL

ISH

● Fortheflarenutsattubingconnections,besuretousetheflarenutsthatweresuppliedwiththeunit,orelseflarenutsforR410A(type2).Therefrigeranttubingthatisusedmustbeofthecorrectwallthicknessasshowninthetablebelow.

Tube diameter Tightening torque(approximate) Tube thickness

ø6.35(1/4") 14–18N·m{140–180kgf·cm} 0.8mm

ø12.7(1/2") 49–61N·m{490–610kgf·cm} 0.8mm

Becausethepressureisapproximately1.6timeshigherthanconventionalrefrigerantpressure,theuseofordinaryflarenuts(type1)orthin-walledtubesmayresultintuberupture,injury,orasphyxiationcausedbyrefrigerantleakage.

● Inordertopreventdamagetotheflarecausedbyover-tighteningoftheflarenuts,usethetableaboveasaguidewhentightening.

● Whentighteningtheflarenutontheliquidtube,useanadjustablewrenchwithanominalhandlelengthof200mm.

5-3. Insulating the Refrigerant Tubing

Tubing Insulation

● Thermalinsulationmustbeappliedtoallunitstubing,includingdistributionjoint(fieldsupply).

*Forgastubing,theinsulationmaterialmustbeheatresistantto120°Corabove.Forothertubing,itmustbeheatresistantto80°Corabove.

Insulationmaterialthicknessmustbe10mmorgreater.IftheconditionsinsidetheceilingexceedDB30°CandRH70%,increasethethicknessofthegastubinginsulationmaterialby1step.

Two tubes arranged together

Liquidtubing Gastubing

Insulation

Fig. 5-7

Insulation of the flare nuts

Attachtheflareinsulator(supplied)justlikewrappingaroundtheflarenut(supplied).Matchthebothslitsofflareinsulatorsforgasandliquidtubesfacingupward.Tightlyattachtheendoftheflareinsulatorstothetubecradlewithoutanyspace.Thenclamptheflareinsulatorwiththeclampersabout20mmawayfrombothends.

Flareinsulator(forgastube)

Flareinsulator(forliquidtube)

Tubecradle

Facingupward

Liquidtubing

Gastubing

Insulator(notsupplied) Withoutanyspace

Tubecradle

Indoorunitside

Outdoorunitside

About20mmAbout20mm

Clamper

ClamperFlarenut(supplied)

Fig. 5-8

NOTE

Tightentheclamperstopreventanycondensationthatmayoccurasthecoppertubingisexposed.

Insulation material

Thematerialusedforinsulationmusthavegoodinsulationcharacteristics,beeasytouse,beageresistant,andmustnoteasilyabsorbmoisture.

CAUTION

After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.Never grasp the drain or refrigerant connecting outlets when moving the unit.

II_F616496_EU_L_2.indb 17 2014-10-24 13:54:02

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 18: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

18

5-4. Taping the Tubes(1) Atthistime,therefrigeranttubes(andelectricalwiring

iflocalcodespermit)shouldbetapedtogetherwitharmoringtapein1bundle.Topreventcondensationfromoverflowingthedrainpan,keepthedrainhoseseparatefromtherefrigeranttubing.

(2) Wrapthearmoringtapefromthebottomoftheoutdoorunittothetopofthetubingwhereitentersthewall.Asyouwrapthetubing,overlaphalfofeachprevioustapeturn.

(3) Clampthetubingbundletothewall,using1clampapprox.eachmeter.(Fig.5-9)

NOTE

Donotwindthearmoringtapetootightlysincethiswilldecreasetheheatinsulationeffect.Alsoensurethatthecondensationdrainhosesplitsawayfromthebundleanddripsclearoftheunitandthetubing.

5-5. Finishing the InstallationAfterfinishinginsulatingandtapingoverthetubing,usesealingputtytosealofftheholeinthewalltopreventrainanddraftfromentering.(Fig.5-10)

InsulatedtubesDrainhose

Clamp

Applyputtyhere

Tubing

Fig. 5-9

Fig. 5-10

6. HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH-SPEC WIRED REMOTE CONTROLLER (OPTIONAL PART)

NOTE

RefertotheOperatingInstructionsattachedtotheoptionalTimerRemoteControlleroroptionalHigh-specWiredRemoteController.

7. HOW TO INSTALL WIRELESS REMOTE CONTROLLER RECEIVER

NOTE

RefertotheOperatingInstructionsattachedtotheoptionalWirelessRemoteControllerReceiver.

II_F616496_EU_L_2.indb 18 2014-10-24 13:54:02

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 19: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

19

EN

GL

ISH

8. EXTERNAL STATIC PRESSURE SETTINGChooseoneofthemethods(selectionof“a”,“b”,“c”withintherangeofdottedlineasshownintheflowchartbelow)andmakesettings.a. Nosettingchanges:

Whenusingasitisfactorypresetatshipment.(Ifresettingafterexternalstaticpressuresettingonce,itmightbedifferentfromfactorypreset.)

b. Manualsetting(onPCB):

Thisisstaticpressuresettingexceptingfactorypresetatshipment.Dipswitchselectmethod.

c. Manualsetting(bywiredremotecontroller):

Staticpressuresettingexceptingfactorypresetatshipment.

Flow of External Static Pressure

NOTE

(1) RefertoTable8-2andFig.8-2fordetailsontherelationshipbetweenthevalueofitemcode“5d”andtheexternalstaticpressure.

(2) Whensetingroupcontrol(connectingmultipleindoorunitswithonewiredremotecontroller),seteachindoorunittoitemcode“5d”.Whenamendingthesettingafterselecting[b.Manualsetting](duetoairflowpathchanges,etc.),itisnecessarytocancel[b.Manualsetting](switchingOFFpositions).When[b.Manualsetting]hasnotbeencancelled,[c.Manualsetting]willbeactivatedifselected,but[b.Manualsetting]takesprecedencewhenthepowerisswitchedbackonafterpoweroutages,etc.

CAUTION

● Make sure the external static pressure is in a range of specifications. Then proceed the external static pressure setting. Improper settings can cause noise, a shortage of airflow volume and water leakage. Refer to Fig. 8-2 for the external static pressure setting range.

● Be sure to set the [External Static Pressure Setting] once again after amending the airflow path for the duct or air outlet after setting the external static pressure.

Startofexternalstaticpressuresetting

Isitdesignedandinstalledatthesettingline

atshipmentonPQlinedrawing?

Operatingbywiredremote

controller

Selectionmethodsofexternalstaticpressuresetting

No

NoYes

Yes

a. No setting changes

b. Manual setting(SettingonPCB)

SettingswitchesofTP3Refertosection"8-1.HowtosetonPCBoard".

c. Manual settingItemcode5d:Setting3

(*Note1)(*Note2)

Refertosection8-2.or8-3.

Completionofexternalstaticpressuresetting

II_F616496_EU_L_2.indb 19 2014-10-24 13:54:03

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 20: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

20

8-1. How to Set on PC Board1. Turnoffthepowerbreakertohaltthesupplyofelectricityto

thePCboard.

2. Openthecoveroftheelectricalboxandconfirmthatthereis

theindoorunitcontrolPCboardinit.

Whenusingwithhighstaticpressuremode,settheindoorunit

controlPCboardasshowninFig.8-1.

3. Connecttheshortcircuitconnectortotheshortcircuitpin

TP3(2P:Yellow)oftheindoorunitcontrolboard.

● Inthecaseofwiredremotecontrolsetting,donotuse

theshortcircuitconnector.

Table 8-2 Setting the external static pressure

Indoorunit Itemcode15 22 28 36 45 56

Externalstaticpressureoftheratedairflowvolume(Pa)

10 15 15

30 30 40

6

2

1 5 1 4

3

NOTE: Failuretosetthisparametermayresultindecreasedairflowandcondensation.

8-2. Operating the Timer Remote Controller (CZ-RTC2)

8-2-1. How to set the external static pressure1. Pressandholddownthe , and buttons

simultaneouslyfor4ormoreseconds.

( ,theUnitNo.,ItemCodeandDetailedDatawill

blinkontheLCDdisplay.)

2. Theindoorunitnumbersinthegroupcontrolwillbe

sequentiallydisplayedwhenevertheUnitSelectbuttonis

pressed .

Onlythefanmotorfortheselectedindoorunitwilloperate

duringthistime.

3. Specifythe“ ”itemcodebypressingthe

/ buttonsforthetemperaturesetting

buttonsandconfirmthevalues.

(“ ”setatshipment)

4. Pressthe / buttonsforthetimetoamendthe

valuesforthesetdata.

RefertoTable8-2andFig.8-2andselectavalue“ ”.

5. Pressthe button.

Thedisplaywillstopblinkingandremainilluminated.

6. Pressthe button.Thefanmotorwillstopoperatingand

theLCDdisplaywillreturntothenormalstopmode.

TP6

CN11

2

CN11

1

CN11

0

WHT YE

L

RED

TP3

EMG

CN06

2CH

K

CN06

3DI

SP

CN06

4

CN073

TEST

EXCTFILTER

OC RCCN044 CN040 CN041

FAN-

TAP TP

1

IC010

IC001

T5A E250V

JP001

JP04

0

TP6 TP3 TP1

IndoorUnitcontrolPCboard

Fig. 8-1

CZ-RTC2

White Yellow Red

Table 8-1 External static pressure

Type 15 22 28 36 45 56

Standard(Pa)(shipment) 10 15 15

Highstaticpressure(Pa) 30 30 40

II_F616496_EU_L_2.indb 20 2014-10-24 13:54:08

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 21: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

21

EN

GL

ISH

8-3. Operating the High-spec Wired Remote Controller (CZ-RTC3)

How to set the external static pressure1. Keeppressingthe , and buttons

simultaneouslyfor4ormoreseconds.

The“Maintenancefunc”screenappearsontheLCD

display.

Maintenance func1. Outdoor unit error data2. Service contact3. RC setting mode4.Test run

Sel. Page [ ] Confirm

20:30 (THU)

2. Pressthe or buttontoseeeachmenu.If

youwishtoseethenextscreeninstantly,pressthe

or button.

Select“8.Detailedsettings”ontheLCDdisplayandpress

the button.

Maintenance func5. Sensor info.6. Servicing check7. Simple settings8. Detailed settings

Sel. Page [ ] Confirm

20:30 (THU)

The“Detailedsettings”screenappearsontheLCDdisplay.

Selectthe“Unitno.”bypressingthe or

buttonforchanges.

Detailed settings

Unit no. Code no. Set data

103-1 0006

Sel. Next

20:30 (THU)

3. Selectthe“Codeno.”bypressingthe or

button.

Changethe“Codeno.”to“5D”bypressingthe or

button(orkeepingitpressed).

Detailed settings

Unit no. Code no. Set data

00001-3

Sel. Next

20:30 (THU)

5D

4. Selectthe“Setdata”bypressingthe or

button.

Selectoneofthe“Setdata”among“0003”accordingto

thedesiredexternalstaticpressuresettingbypressingthe

or button.

Thenpressthe button.

(Seethetablebelow.)

Thenpressthe button.

Indoorunit Itemcode15 22 28 36 45 56

5DExternalstaticpressureoftheratedairflowvolume(Pa)

10 15 15 000030 30 40 0003

5. Selectthe“Unitno.”bypressingthe or

buttonandpressthe button.

The“Exitdetailedsettingsandrestart?”(Detailedsetting-

end)screenappearsontheLCDdisplay.

Select“YES”andpressthe button.

Whenthesettingiscompleted,performthetestrunforthe

externalstaticpressuresettingdescribedin“AutoExternal

StaticPressureSettingOperation”.

Detailed settings

Unit no. Code no. Set data

101-1 0001

Sel. Next

20:30 (THU)Exit detailed settings

and restart?

NOYES

II_F616496_EU_L_2.indb 21 2014-10-24 13:54:11

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 22: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

22

L

M

M

H

L

H

(Pa)

4 5 6 7 8 9 10 11

4 5 6 7 8 9 10 11 12 5 6 7 8 9 10 11 12 13 7 8 9 10 11 12 13 14 15

0

10

20

30

40

{mm

Aq}

0

5

ML

L

MH

H

Type 15

4 5 6 7 8 9 10 11 0

10

20

30

40{m

mA

q}

0

5

ML

L

MH

H

Type 22

0

10

20

30

40

{mm

Aq}

0

5

ML

L MH

4 5 6 7 8 9 10 11 12

Type 28

{mm

Aq}

0

ML

10

20

30

40

50

0

10

20

30

40

50

60

0

5

{mm

Aq}

0

5

ML

LM

H

M

L

H

HT H

H

0

10

20

30

40

50

60{m

mA

q}

0

5

LM

L

M

H

H

Type 56Type 36 Type 45

H

Externalstaticpressure’supperlimitinhighstaticpressuremode

Standardexternalstaticpressure’supperlimit

Ext

erna

lSta

ticP

ress

ure

Ext

erna

lSta

ticP

ress

ure

(Pa)

Airflow(m3/min.)

Airflow(m3/min.)

Airflow(m3/min.)

Airflow(m3/min.)

Airflow(m3/min.)

Airflow(m3/min.)

Airflow(m3/min.)

Ext

erna

lSta

ticP

ress

ure

(Pa)

Ext

erna

lSta

ticP

ress

ure

(Pa)

Ext

erna

lSta

ticP

ress

ure

(Pa)

Ext

erna

lSta

ticP

ress

ure

(Pa)

Ext

erna

lSta

ticP

ress

ure

(Pa)

Lowerlimitairflow

Ratedexternalstaticpressureinhighstaticpressuremode

Lowerstaticpressureinhighstaticpressuremode

Ratedexternalstaticpressureatshipment

Upperlimitairflow

Fig. 8-2

II_F616496_EU_L_2.indb 22 2014-10-24 13:54:12

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 23: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

23

EN

GL

ISH

9. APPENDIX

■ Names of PartsType M1 (Slim Low Static Ducted)

Airintakesideductflange

Waterdrain

Airoutletsideductflange(rear)

Electricalbox

■ Care and Cleaning

WARNING

● For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.

● Donotpourwaterontheindoorunittocleanit.Thiswilldamagetheinternalcomponentsandcauseanelectricshockhazard.

Air intake and outlet side (Indoor unit)

Cleantheairintakeandoutletsideoftheindoorunitwithavacuumcleanerbrush,orwipethemwithaclean,softcloth.

If these parts are stained, use a clean cloth moistened withwater.Whencleaningtheairoutletside,becarefulnottoforcethevanesoutofplace.

CAUTION

● Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic parts using very hot water.

● Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.

● The internal coil and other components of outdoor unit must be cleaned regularly. Consult your dealer or service center.

Air filter

Theairfiltercollectsdustandotherparticlesfromtheairandshouldbecleanedatregularintervalsorwhenthefilterindication( )onthedisplayoftheremotecontroller(wiredtype)showsthatthefilterneedscleaning.Ifthefiltergetsblocked,theefficiencyoftheairconditionerdropsgreatly.

Type M1

Period (Dependsonfilterspecifications)

Anairfilterisnotprovidedwiththisairconditioneratthetimeofshipment.Togetcleanairandtoextendtheservicelifeoftheairconditioner,anairfiltermustbeinstalledintheairintake.Forinstallationandcleaningtheairfilter,consultyourdealerorservicecenter.

NOTE

Thefrequencywithwhichthefiltershouldbecleaneddependsontheenvironmentinwhichtheunitisused.

<How to clean the filter>1. Removetheairfilterfromtheairintakegrille.2. Useavacuumcleanertoremovelightdust.If

thereisstickydustonthefilter,washthefilterinlukewarm,soapywater,rinseitincleanwater,anddryit.

CAUTION

● Certain metal edges and the condenser fins are sharp and may cause injury if handled improperly; special care should be taken when you clean these parts.

● Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt or soot.

● The internal coil and other components must also be cleaned periodically. Consult your dealer or service center.

Care: After a prolonged idle periodChecktheindoorandoutdoorunitairintakesandoutletsforblockage;ifthereisablockage,removeit.

Care: Before a prolonged idle period

● Operatethefanforhalfadaytodryouttheinside.

● Disconnectthepowersupplyandalsoturnoffthecircuitbreaker.

● Cleantheairfilterandreplaceitinitsoriginalposition.

● Outdoorunitinternalcomponentsmustbecheckedandcleanedperiodically.Contactyourlocaldealerforthisservice.

NOTE

Should the power fail while the unit is runningIfthepowersupplyforthisunitistemporarilycutoff,theunitwillautomaticallyresumeoperationoncepowerisrestoredusingthesamesettingsbeforethepowerwasinterrupted.

IMPORTANT INFORMATION REGARDING THE REFRIGERANT USEDThisproductcontainsfluorinatedgreenhousegasescoveredbytheKyotoProtocol.Donotventgasesintotheatmosphere.

Refrigeranttype:R410AGWP

(1)value:1975

(1)GWP=globalwarmingpotential

PeriodicalinspectionsforrefrigerantleaksmayberequireddependingonEuropeanorlocallegislation.Pleasecontactyourlocaldealerformoreinformation.

Regardingtheamountofrefrigerant,seetherefrigerantchargelabelattachedtotheoutdoorunit.

II_F616496_EU_L_2.indb 23 2014-10-24 13:54:13

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 24: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

24

– NOTE –

II_F616496_EU_L_2.indb 24 2014-10-24 13:54:13

AMP Air Conditioning www.ampair.co.uk | [email protected]

Page 25: VRF System Air Conditioner –ampair.co.uk/wp-content/uploads/Media/Panasonic/VRF/... · 2018-03-27 · Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan. Secara

F616496DC0914-0PrintedinMalaysia

II_F616496_EU_L_2.indb 268 2014-10-24 13:58:24

AMP Air Conditioning www.ampair.co.uk | [email protected]