Service Manualmidea.com.ge/uploads/client/Uploads/Catalogues/Service... · 2018. 12. 19. · Midea...
Transcript of Service Manualmidea.com.ge/uploads/client/Uploads/Catalogues/Service... · 2018. 12. 19. · Midea...
Commercial Air Conditioners
R410A
Series
MV6-252WV2GN1-E
MV6-280WV2GN1-E
MV6-335WV2GN1-E
MV6-400WV2GN1-E
MV6-450WV2GN1-E
MV6-500WV2GN1-E
MV6-560WV2GN1-E
MV6-615WV2GN1-E
MV6-670WV2GN1-E
MV6-730WV2GN1-E
MV6-785WV2GN1-E
MV6-850WV2GN1-E
MV6-900WV2GN1-E
Service
Manual
V6 VRF 50Hz
1
CO
NTEN
TS
CONTENTS
Part 1 General Information ............................................................................ 3
Part 2 Component Layout and Refrigerant Circuits ................................... 11
Part 3 Control ............................................................................................... 33
Part 4 Field Settings ..................................................................................... 49
Part 5 Electrical Components and Wiring Diagrams .................................. 55
Part 6 Diagnosis and Troubleshooting ......................................................... 69
V5 X VRF 50Hz
2
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
V6 VRF 50Hz
3
Part 1
- Ge
ne
ral Info
rmatio
n
Part 1
General Information
1 Indoor and Outdoor Unit Capacities .................................................. 4
2 External Appearance ............................................................................ 6
3 Outdoor Unit Combinations ................................................................ 8
4 Combination Ratio ............................................................................... 9
V6 VRF 50Hz
4
Mid
ea
V6
Se
rie
s En
gin
ee
rin
g D
ata
Bo
ok
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
1.1.1 Standard indoor units
Table 1-1.1: Standard indoor unit abbreviation codes
Abbreviation
code Type
Abbreviation
code Type
Q1 One-way Cassette T1 High Static Pressure Duct
Q2 Two-way Cassette G Wall-mounted
Q4C Compact Four-way Cassette DL Ceiling & Floor
Q4 Four-way Cassette F Floor Standing
T2 Medium Static Pressure Duct Z Console
Table 1-1.2: Standard indoor unit capacity range
Capacity Capacity
index Q1 Q2 Q4C Q4 T2 T1 G DL F Z
kW HP
1.8 0.6 18 18 — — — — — — — 18 —
2.2 0.8 22 22 22 22 — 22 — 22 — 22 22
2.8 1 28 28 28 28 28 28 — 28 — 28 28
3.6 1.25 36 36 36 36 36 36 — 36 36 36 36
4.5 1.6 45 45 45 45 45 45 — 45 45 45 45
5.6 2 56 56 56 — 56 56 — 56 56 56 —
7.1 2.5 71 71 71 — 71 71 71 71 71 71 —
8.0 3 80 — — — 80 80 80 80 80 80 —
9.0 3.2 90 — — — 90 90 90 90 90 90 —
10.0 3.6 100 — — — 100 — — — — — —
11.2 4 112 — — — 112 112 112 — 112 — —
14.0 5 140 — — — 140 140 140 — 140 — —
16.0 6 160 — — — — — 160 — 160 — —
20.0 7 200 — — — — — 200 — — — —
25.0 9 250 — — — — — 250 — — — —
28.0 10 280 — — — — — 280 — — — —
40.0 14 400 — — — — — 400 — — — —
45.0 16 450 — — — — — 450 — — — —
56.0 20 560 — — — — — 560 — — — —
1.1.2 Fresh air processing unit
Table 1-1.3: Fresh air processing unit capacity range
Capacity 12.5kW 14kW 20kW 25kW 28kW
Capacity index 125 140 200 250 280
1.2 Heat recovery ventilator Table 1-1.4: Heat recovery ventilator capacity range
Capacity 200m3/h 300m
3/h 400m
3/h 500m
3/h 800m
3/h 1000m
3/h 1500m
3/h 2000m
3/h
V6 VRF 50Hz
5
Part 1
- Ge
ne
ral Info
rmatio
n
1.3 Outdoor Units Table 1-1.5: Outdoor unit capacity range
Capacity Model Name Combination Type
8HP MV6-252WV2GN1 /
10HP MV6-280WV2GN1 /
12HP MV6-335WV2GN1 /
14HP MV6-400WV2GN1 /
16HP MV6-450WV2GN1 /
18HP MV6-500WV2GN1 /
20HP MV6-560WV2GN1 /
22HP MV6-615WV2GN1 /
24HP MV6-670WV2GN1 /
26HP MV6-730WV2GN1 /
28HP MV6-785WV2GN1 /
30HP MV6-850WV2GN1 /
32HP MV6-900WV2GN1 /
34HP MV6-950WV2GN1 12HP+22HP
36HP MV6-1015WV2GN1 14HP+22HP
38HP MV6-1065WV2GN1 16HP+22HP
40HP MV6-1120WV2GN1 12HP+28HP
42HP MV6-1175WV2GN1 20HP+22HP
44HP MV6-1230WV2GN1 22HP+22HP
46HP MV6-1285WV2GN1 22HP+24HP
48HP MV6-1345WV2GN1 22HP+26HP
50HP MV6-1400WV2GN1 22HP+28HP
52HP MV6-1460WV2GN1 26HP+26HP
54HP MV6-1515WV2GN1 26HP+28HP
56HP MV6-1570WV2GN1 28HP+28HP
58HP MV6-1635WV2GN1 28HP+30HP
60HP MV6-1685WV2GN1 28HP+32HP
62HP MV6-1750WV2GN1 30HP+32HP
64HP MV6-1800WV2GN1 32HP+32HP
66HP MV6-1850WV2GN1 12HP+22HP+32HP
68HP MV6-1915WV2GN1 14HP+22HP+32HP
70HP MV6-1965WV2GN1 16HP+22HP+32HP
72HP MV6-2020WV2GN1 12HP+28HP+32HP
74HP MV6-2075WV2GN1 20HP+22HP+32HP
76HP MV6-2130WV2GN1 22HP+22HP+32HP
78HP MV6-2185WV2GN1 22HP+24HP+32HP
80HP MV6-2245WV2GN1 22HP+26HP+32HP
82HP MV6-2300WV2GN1 22HP+28HP+32HP
84HP MV6-2360WV2GN1 26HP+26HP+32HP
86HP MV6-2415WV2GN1 26HP+28HP+32HP
88HP MV6-2470WV2GN1 28HP+28HP+32HP
90HP MV6-2535WV2GN1 28HP+30HP+32HP
92HP MV6-2585WV2GN1 28HP+32HP+32HP
94HP MV6-2650WV2GN1 30HP+32HP+32HP
96HP MV6-2700WV2GN1 32HP+32HP+32HP
Notes: 1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.
V6 VRF 50Hz
6
Mid
ea
V6
Se
rie
s En
gin
ee
rin
g D
ata
Bo
ok
2 External Appearance
2.1 Indoor Units
2.1.1 Standard indoor units
Table 1-2.1: Standard indoor unit appearance
One-way Cassette Two-way Cassette
Q1
Q2
Compact Four-way Cassette Four-way Cassette
Q4C
Q4
Medium Static Pressure Duct High Static Pressure Duct
T2
T1
Wall-mounted Ceiling & Floor
G
DL
Floor Standing Console
F
Z
2.1.2 Fresh air processing unit
Table 1-2.2: Fresh air processing unit appearance
Fresh Air Processing Unit
FA
2.2 Heat Recovery Ventilator Table 1-2.3: Heat recovery ventilator appearance
Heat Recovery Ventilator
V6 VRF 50Hz
7
Part 1
- Ge
ne
ral Info
rmatio
n
2.3 Outdoor Units
2.3.1 Single units
Table 1-2.4: Single outdoor unit appearance
8/10/12HP
(with single fan)
14/16HP
(with single fan)
18/20/22HP
(with dual fans)
24/26/28/30/32HP
(with dual fans)
2.3.2 Combinations of units
Table 1-2.5: Combination outdoor unit appearance
34HP 36/38HP 40HP
42/44HP 46/48/50HP 52/54/56/58/60/62/64HP
66HP 68/70HP 72HP
74/76HP 78/80/82HP 84/86/88/90/92/94/96HP
V6 VRF 50Hz
8
Mid
ea
V6
Se
rie
s En
gin
ee
rin
g D
ata
Bo
ok
3 Outdoor Unit Combinations
Table 1-3.1: Outdoor unit combinations
System capacity Number
of units
Modules1 Outdoor branch
joint kit2 kW HP 8 10 12 14 16 18 20 22 24 26 28 30 32
25.2 8 1
—
28.0 10 1
33.5 12 1
40.0 14 1
45.0 16 1
50.0 18 1
56.0 20 1
61.5 22 1
67.0 24 1
73.0 26 1
78.5 28 1
85.0 30 1
90.0 32 1
95.0 34 2
FQZHW-02N1E
101.5 36 2
106.5 38 2
112.0 40 2
117.5 42 2
123.0 44 2
128.5 46 2
134.5 48 2
140.0 50 2
146.0 52 2
151.5 54 2
157.0 56 2
163.5 58 2
168.5 60 2
175.0 62 2
180.0 64 2
185.0 66 3
FQZHW-03N1E
191.5 68 3
196.5 70 3
202.0 72 3
207.5 74 3
213.0 76 3
218.5 78 3
224.5 80 3
230.0 82 3
236.0 84 3
241.5 86 3
247.0 88 3
253.5 90 3
258.5 92 3
265.0 94 3
270.0 96 3
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible. 2. For systems with two or more outdoor units, outdoor branch joints (sold separately) are required.
V6 VRF 50Hz
9
Part 1
- Ge
ne
ral Info
rmatio
n
4 Combination Ratio
Table 1-5.1: Indoor and outdoor unit combination ratio limitations
Type Minimum
combination ratio
Maximum combination ratio
Standard indoor units only
Fresh air processing units only
Fresh air processing units and standard indoor units together
V6 Series outdoor units 50% 130% 100% 100%1
Notes: 1. When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30%
of the total capacity of the outdoor units and the combination ratio must not exceed 100%.
Table 1-5.2: Combinations of Indoor and outdoor units
Outdoor unit capacity Sum of capacity indexes of connected indoor units (standard
indoor units only)
Sum of capacity indexes of connected indoor units (fresh air processing units and standard
indoor units together)
Maximum number of connected indoor
units kW HP
Capacity index
25.2 8 252 126 to 327.6 126 to 252 13 28.0 10 280 140 to 364 140 to 280 16 33.5 12 335 167.5 to 435.5 167.5 to 335 20 40.0 14 400 200 to 520 200 to 400 23 45.0 16 450 225 to 585 225 to 450 26 50.0 18 500 250 to 650 250 to 500 29 56.0 20 560 280 to 728 280 to 560 33 61.5 22 615 307.5 to 799.5 307.5 to 615 36 67.0 24 670 335 to 871 335 to 670 39 73.0 26 730 365 to 949 365 to 730 43 78.5 28 785 392.5 to 1020.5 392.5 to 785 46 85.0 30 850 425 to 1105 425 to 850 50 90.0 32 900 450 to 1170 450 to 900 53 95.0 34 950 475 to 1235 475 to 950 56
101.5 36 1015 507.5 to 1319.5 507.5 to 1015 59 106.5 38 1065 532.5 to 1384.5 532.5 to 1065 63 112.0 40 1120 560 to 1456 560 to 1120
64
117.5 42 1175 587.5 to 1527.5 587.5 to 1175 123.0 44 1230 615 to 1599 615 to 1230 128.5 46 1285 642.5 to 1670.5 642.5 to 1285 134.5 48 1345 672.5 to 1748.5 672.5 to 1345 140.0 50 1400 700 to 1820 700 to 1400 146.0 52 1460 730 to 1898 730 to 1460 151.5 54 1515 757.5 to 1969.5 757.5 to 1515 157.0 56 1570 785 to 2041 785 to 1570 163.5 58 1635 817.5 to 2125.5 817.5 to 1635 168.5 60 1685 842.5 to 2190.5 842.5 to 1685 175.0 62 1750 875 to 2275 875 to 1750 180.0 64 1800 900 to 2340 900 to 1800 185.0 66 1850 925 to 2405 925 to 1850 191.5 68 1915 957.5 to 2489.5 957.5 to 1915 196.5 70 1965 982.5 to 2554.5 982.5 to 1965 202.0 72 2020 1010 to 2626 1010 to 2020 207.5 74 2075 1037.5 to 2697.5 1037.5 to 2075 213.0 76 2130 1065 to 2769 1065 to 2130 218.5 78 2185 1092.5 to 2840.5 1092.5 to 2185 224.5 80 2245 1122.5 to 2918.5 1122.5 to 2245 230.0 82 2300 1150 to 2990 1150 to 2300 236.0 84 2360 1180 to 3068 1180 to 2360 241.5 86 2415 1207.5 to 3139.5 1207.5 to 2415 247.0 88 2470 1235 to 3211 1235 to 2470 253.5 90 2535 1267.5 to 3295.5 1267.5 to 2535 258.5 92 2585 1292.5 to 3360.5 1292.5 to 2585 265.0 94 2650 1325 to 3445 1325 to 2650 270.0 96 2700 1350 to 3510 1350 to 2700
Combination ratio = Sum of capacity indexes of the indoor units
Capacity index of the outdoor units
V6 VRF 50Hz
10
Mid
ea
V6
Se
rie
s En
gin
ee
rin
g D
ata
Bo
ok
V6 VRF 50Hz
11
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components ....................................................... 12
2 Piping Diagrams .................................................................................. 16
3 Refrigerant Flow Diagrams .................................................................. 22
V6 VRF 50Hz
12
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
1 Layout of Functional Components
8/10/12HP Figure 2-1.1: 8/10/12 layout of functional components
Legend
No. Parts name
1 Compressor
2 Discharge temperature switch
3 High pressure switch
4 High pressure sensor
5 Oil separator
6 Four-way valve
7 Heat exchanger
8 Electronic expansion valve (EXV)
9 Low pressure switch
10 Fan motor
11 Fan
12 Stop valve (liquid side)
13 Stop valve (gas side)
14 Plate heat exchanger
1556
7
8
12 13 14
11
9
10
3 4 2 1
V6 VRF 50Hz
13
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
14/16HP Figure 2-1.2: 14/16 layout of functional components
Legend
No. Parts name
1 Compressor
2 Discharge temperature switch
3 High pressure switch
4 High pressure sensor
5 Oil separator
6 Four-way valve
7 Heat exchanger
8 Electronic expansion valve (EXV)
9 Low pressure switch
10 Fan motor
11 Fan
12 Stop valve (liquid side)
13 Stop valve (gas side)
14 Plate heat exchanger
15 Accumulator
1556
7
8
12 13 14
11
9
10
34 2 1
V6 VRF 50Hz
14
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
18/20/22HP Figure 2-1.3: 18/20/22 layout of functional components
Legend
No. Parts name
1 Compressor
2 Discharge temperature switch
3 High pressure switch
4 High pressure sensor
5 Oil separator
6 Four-way valve
7 Heat exchanger
8 Electronic expansion valve (EXV)
9 Low pressure switch
10 Fan motor
11 Fan
12 Stop valve (liquid side)
13 Stop valve (gas side)
14 Plate heat exchanger
15 Accumulator
1556
7
8
12 13 14
11
9
10
34 2 1
V6 VRF 50Hz
15
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
24/26/28/30/32HP Figure 2-1.4: 24/26/28/30/32 layout of functional components
Legend
No. Parts name
1 Compressor
2 Discharge temperature switch
3 High pressure switch
4 High pressure sensor
5 Oil separator
6 Four-way valve
7 Heat exchanger
8 Electronic expansion valve
(EXV)
9 Low pressure switch
10 Fan motor
11 Fan
12 Stop valve (liquid side)
13 Stop valve (gas side)
14 Plate heat exchanger
15 Accumulator
155 46
7
8
9
12 13 14
11
9
10
3 2 1
V6 VRF 50Hz
16
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2 Piping Diagrams
8/10/12HP
Figure 2-2.1: 8/10/12HP piping diagram
Legend
No. Parts name
No. Parts name
1 Compressor 14 Plate heat exchanger
2 Discharge temperature switch 15 Accumulator
3 High pressure switch 16 Heat exchanger cooling electric control box
4 High pressure sensor T3 Heat exchanger temperature sensor
5 Oil separator T4 Outdoor ambient temperature sensor
6 Four-way valve T6A Plate heat exchanger inlet temperature sensor
7 Heat exchanger T6B Plate heat exchanger outlet temperature sensor
8 Electronic expansion valve (EXV) T7C1 Compressor A discharge temperature sensor
9 Low pressure switch T7C2 Compressor B discharge temperature sensor
10 Fan motor SV4 Oil return valve
11 Fan SV5 Fast defrosting (in heating) and unloading (in cooling) valve
12 Stop valve (liquid side) SV6 Refrigerant bypass EXV valve
13 Stop valve (gas side) SV8A Compressor A vapor injection valve
7
115 129
3
2
45
6
1110
9
14
8
8
13
EXVA
EXVC
E SC
T3
T4
T6B
T7C1
T7C
2
T6A
SV8A SV
4
SV5
SV6
16
V6 VRF 50Hz
17
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
14/16HP
Figure 2-2.2: 14/16HP piping diagram
Legend
No. Parts name
No. Parts name
1 Compressor 15 Accumulator
2 Discharge temperature switch 16 Heat exchanger cooling electric control box
3 High pressure switch T3 Heat exchanger temperature sensor
4 High pressure sensor T4 Outdoor ambient temperature sensor
5 Oil separator T6A Plate heat exchanger inlet temperature sensor
6 Four-way valve T6B Plate heat exchanger outlet temperature sensor
7 Heat exchanger T7C1 Compressor A discharge temperature sensor
8 Electronic expansion valve (EXV) T7C2 Compressor B discharge temperature sensor
9 Low pressure switch SV4 Oil return valve
10 Fan motor SV5 Fast defrosting (in heating) and unloading (in cooling) valve
11 Fan SV6 Refrigerant bypass EXV valve
12 Stop valve (liquid side) SV7 Refrigerant bypass indoor units valve
13 Stop valve (gas side) SV8A Compressor A vapor injection valve
14 Plate heat exchanger
2
1 15 129
3
45
6
1110
7
14
8 8
8
13
EXVA EXVB
EXVC
ES
CT3
T4
T7C1
T7C
2
T6B
T6A
SV8A SV
4
SV7
SV5
SV6
16
V6 VRF 50Hz
18
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
18/20/22HP
Figure 2-2.3: 18/20/22HP piping diagram
Legend
No. Parts name
No. Parts name
1 Compressor 15 Accumulator
2 Discharge temperature switch 16 Heat exchanger cooling electric control box
3 High pressure switch T3 Heat exchanger temperature sensor
4 High pressure sensor T4 Outdoor ambient temperature sensor
5 Oil separator T6A Plate heat exchanger inlet temperature sensor
6 Four-way valve T6B Plate heat exchanger outlet temperature sensor
7 Heat exchanger T7C1 Compressor A discharge temperature sensor
8 Electronic expansion valve (EXV) T7C2 Compressor B discharge temperature sensor
9 Low pressure switch SV4 Oil return valve
10 Fan motor SV5 Fast defrosting (in heating) and unloading (in cooling) valve
11 Fan SV6 Refrigerant bypass EXV valve
12 Stop valve (liquid side) SV8A Compressor A vapor injection valve
13 Stop valve (gas side) SV8B Compressor B vapor injection valve
14 Plate heat exchanger SV9 Compressor B pressure balance valve
7
1 1 15 129
34 5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6B
T6
A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
16
V6 VRF 50Hz
19
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
24/26/28HP
Figure 2-2.4: 24/26/28HP piping diagram
Legend
No. Parts name
No. Parts name
1 Compressor 15 Accumulator
2 Discharge temperature switch 16 Heat exchanger cooling electric control box
3 High pressure switch T3 Heat exchanger temperature sensor
4 High pressure sensor T4 Outdoor ambient temperature sensor
5 Oil separator T6A Plate heat exchanger inlet temperature sensor
6 Four-way valve T6B Plate heat exchanger outlet temperature sensor
7 Heat exchanger T7C1 Compressor A discharge temperature sensor
8 Electronic expansion valve (EXV) T7C2 Compressor B discharge temperature sensor
9 Low pressure switch SV4 Oil return valve
10 Fan motor SV5 Fast defrosting (in heating) and unloading (in cooling) valve
11 Fan SV6 Refrigerant bypass EXV valve
12 Stop valve (liquid side) SV8A Compressor A vapor injection valve
13 Stop valve (gas side) SV8B Compressor B vapor injection valve
14 Plate heat exchanger SV9 Compressor B pressure balance valve
7
11 15 15 129
34 5
6
1110
1110
14
8
8
8 SV6
13
EXVBEXVA
EXVC
ES C T3
T4
T6B
T6A
SV8
A
SV8
B
SV4
SV9
SV5
T7C1 T7C2
2 2
16
V6 VRF 50Hz
20
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
30/32HP
Figure 2-2.5: 30/32HP piping diagram
Legend
No. Parts name
No. Parts name
1 Compressor 16 Heat exchanger cooling electric control box
2 Discharge temperature switch T3 Heat exchanger temperature sensor
3 High pressure switch T4 Outdoor ambient temperature sensor
4 High pressure sensor T6A Plate heat exchanger inlet temperature sensor
5 Oil separator T6B Plate heat exchanger outlet temperature sensor
6 Four-way valve T7C1 Compressor A discharge temperature sensor
7 Heat exchanger T7C2 Compressor B discharge temperature sensor
8 Electronic expansion valve (EXV) SV4 Oil return valve
9 Low pressure switch SV5 Fast defrosting (in heating) and unloading (in cooling) valve
10 Fan motor SV6 Refrigerant bypass EXV valve
11 Fan SV7 Refrigerant bypass indoor units valve
12 Stop valve (liquid side) SV8A Compressor A vapor injection valve
13 Stop valve (gas side) SV8B Compressor B vapor injection valve
14 Plate heat exchanger SV9 Compressor B pressure balance valve
15 Accumulator
7
11 1515 129
34 5
6
1110
1110
14
8 8
8
13
EXVBEXVA
EXVC
ES
C
SV6
T3
T4
T6B
T6A
SV5
SV9
SV7
SV4
SV8
A
SV8B
T7C1 T7C2
2 2
16
V6 VRF 50Hz
21
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Four-way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the heat
exchanger functions as a condenser; when open, the heat exchanger functions as an evaporator.
5. Plate heat exchanger:
In cooling mode, it can improve super-cooling degree and the super-cooled refrigerant can achieve better heat
exchange in indoor side. In heating mode, the refrigerant comes from the plate heat exchanger going to the
compressor can enhance the refrigerant enthalpy and improve the heating capacity in low ambient temperature.
Refrigerant volume in plate heat exchanger is controlled according to temperature different between plate heat
exchanger inlet and outlet.
6. Solenoid valve SV4:
Returns oil to the compressor. Opens once the compressor has run for 200 seconds and closes 600 seconds later and
then opens for 3 minutes every 20 minutes.
7. Solenoid valve SV5:
Enables fast defrosting in heating mode and unloading in cooling mode. During defrosting operation, opens to
shorten the refrigerant flow cycle and quicken the defrosting process. In cooling mode, SV5 opens when outdoor
ambient temperature is above 40oC or compressor frequency is below 41Hz.
8. Solenoid valve SV6:
Allows refrigerant to bypass the expansion valves. Opens in cooling mode when discharge temperature exceeds the
limit. Closed in heating mode and standby.
9. Solenoid valve SV7:
Allows refrigerant to return directly to the compressor. Opens when indoor air temperature is close to the set
temperature to avoid frequent compressor on/off.
10. Solenoid valve SV8A / SV8B:
Allows refrigerant from plate heat exchanger inject directly to the compressor. SV8A opens when compressor A
startup and closes when compressor A stop. SV8B delays opening when compressor B startup and closes when
compressor B stop.
11. Solenoid valve SV9:
Balances compressor B pressure. Opens before compressor B startup and closed after compressor B running for 15
seconds. Opens after compressor B stops 10s and keep opening 60s.
12. High and low pressure switches:
Regulate system pressure. When system pressure rises above the upper limit or falls below the lower limit, the high or
low pressure switches turn off, stopping the compressor. After 10 minutes, the compressor restarts.
V6 VRF 50Hz
22
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
3 Refrigerant Flow Diagrams
8/10/12HP
Cooling operation
Figure 2-3.1: 8/10/12HP refrigerant flow during cooling operation
Oil return operation in cooling mode
Figure 2-3.2: 8/10/12HP refrigerant flow during oil return operation in cooling mode
7
115
129
3
2
45
6
11
10
14
8
13
EXVA
EXVC
E SC
T3
T4
T6B
T7C1
T7
C2
T6
A
SV8A SV
4
SV5
SV6
Closed
FilterFilter
Closed
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
FilterFilter
Normal control
FilterFilter
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
Fanon
Fanoff
Fanon
Fanon
7
115
129
3
2
45
6
11
10
14
8
13
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
EXVA
EXVC
E SC
T3
T4
T6B
T7C1
T7C
2
T6
A
SV8A SV
4
SV5
SV6
300 steps
FilterFilter
300 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
16
16
V6 VRF 50Hz
23
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
Oil return operation in heating mode and defrosting operation
Figure 2-3.3: 8/10/12HP refrigerant flow during oil return operation in heating mode and during defrosting operation
Heating operation
Figure 2-3.4: 8/10/12HP refrigerant flow during heating operation
7
115
129
3
2
45
6
11
10
14
8
13
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
EXVA
EXVC
E SC
T3
T4
T6B
T7C1
T7C
2
T6
A
SV8A SV
4
SV5
SV6
480 steps
FilterFilter
480 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
480 steps
FilterFilter
480 steps
FilterFilter
Fanoff
Fanoff
Fanoff
Fanoff
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
7
115
129
3
2
45
6
11
10
14
8
13
EXVA
EXVC
E SC
T3
T4
T6B
T7C1
T7C
2
T6A
SV8A SV
4
SV5
SV6
Closed
Closed
FilterFilter
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
era
tio
n
Filter
Normal control
Normal control
FilterFilter
FilterFilter
Fanon
Fanoff
Fanon
Fanon
16
16
V6 VRF 50Hz
24
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
14/16HP
Cooling operation
Figure 2-3.5: 14/16 refrigerant flow during cooling operation
Oil return operation in cooling mode
Figure 2-3.6: 14/16HP refrigerant flow during oil return operation in cooling mode
SV7
7
115
129
3
2
45
6
11
10
14
13
EXVC
E SC
T3
T4
T6B
T7C1
T7C
2
T6A
SV8
A SV4
SV5
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
EXVA EXVB8 8 SV
6Closed
FilterFilter
Closed
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
SV7
EXVA EXVB8 8 SV
67
115
129
3
2
45
6
11
10
14
13
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
EXVC
E SC
T3
T4
T6
B
T7C1
T7C
2
T6A
SV8A SV
4
SV5
300 steps
FilterFilter
300 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
16
16
V6 VRF 50Hz
25
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
Oil return operation in heating mode and defrosting operation
Figure 2-3.7: 14/16HP refrigerant flow during oil return operation in heating mode and during defrosting operation
Heating operation
Figure 2-3.8: 14/16HP refrigerant flow during heating operation
SV7
EXVA EXVB8 8 SV
67
115
129
3
2
45
6
11
10
14
13
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
EXVC
E SC
T3
T4
T6B
T7C1
T7C
2
T6A
SV8
A SV4
SV5
480 steps
FilterFilter
480 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
480 steps
FilterFilter
480 steps
FilterFilter
Fanoff
Fanoff
Fanoff
Fanoff
SV7
EXVA EXVB8 8 SV
6
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
7
115
129
3
2
45
6
11
10
14
13
EXVC
E SC
T3
T4
T6B
T7C1
T7C
2
T6A
SV8
A SV4
SV5
Closed
Closed
FilterFilter
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
era
tio
n
Filter
Normal control
Normal control
FilterFilter
FilterFilter
Fanon
Fanoff
Fanon
Fanon
16
16
V6 VRF 50Hz
26
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
18/20/22HP
Cooling operation
Figure 2-3.9: 18/20/22 refrigerant flow during cooling operation
Oil return operation in cooling mode
Figure 2-3.10: 18/20/22HP refrigerant flow during oil return operation in cooling mode
7
1 1 15
16
129
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6
BT
6A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
Closed
FilterFilter
Closed
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
era
tio
n
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
16
300 steps
FilterFilter
300 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
era
tio
n
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
7
1 1 1512
9
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6
BT
6A
SV8
A
SV8
B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
V6 VRF 50Hz
27
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
Oil return operation in heating mode and defrosting operation
Figure 2-3.11: 18/20/22HP refrigerant flow during oil return operation in heating mode and during defrosting operation
Heating operation
Figure 2-3.12: 18/20/22HP refrigerant flow during heating operation
16
480 steps
FilterFilter
480 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
480 steps
FilterFilter
480 steps
FilterFilter
Fanoff
Fanoff
Fanoff
Fanoff
7
1 1 1512
9
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2T6
BT6
A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
Closed
Closed
FilterFilter
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
Normal control
FilterFilter
FilterFilter
Fanon
Fanoff
Fanon
Fanon
7
1 1 1512
9
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6B
T6A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
16
V6 VRF 50Hz
28
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
24/26/28HP
Cooling operation
Figure 2-3.13: 24/26/28 refrigerant flow during cooling operation
Oil return operation in cooling mode
Figure 2-3.14: 24/26/28HP refrigerant flow during oil return operation in cooling mode
16
15 15
7
1 112
9
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6B
T6A
SV8
A
SV8
B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
Closed
FilterFilter
Closed
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
16
300 steps
FilterFilter
300 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
15 15
7
1 112
9
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6
BT
6A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
V6 VRF 50Hz
29
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
Oil return operation in heating mode and defrosting operation
Figure 2-3.15: 24/26/28HP refrigerant flow during oil return operation in heating mode and during defrosting operation
Heating operation
Figure 2-3.16: 24/26/28HP refrigerant flow during heating operation
16
480 steps
FilterFilter
480 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
480 steps
FilterFilter
480 steps
FilterFilter
Fanoff
Fanoff
Fanoff
Fanoff
15 15
7
1 112
9
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2T6
BT6
A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
Closed
Closed
FilterFilter
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
Normal control
FilterFilter
FilterFilter
Fanon
Fanoff
Fanon
Fanon
15 15
7
1 112
9
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6B
T6A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
16
V6 VRF 50Hz
30
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
30/32HP
Cooling operation
Figure 2-3.17: 30/32 refrigerant flow during cooling operation
Oil return operation in cooling mode
Figure 2-3.18: 30/32HP refrigerant flow during oil return operation in cooling mode
16
15 15
7
1 112
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6B
T6A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
Closed
FilterFilter
Closed
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
9
SV7
16
300 steps
FilterFilter
300 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
era
tio
n
Filter
Normal control
FilterFilter
Normal control
FilterFilter
Fanon
Fanoff
Fanon
Fanon
15 15
7
1 112
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6B
T6A
SV8
A
SV8
B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
9
SV7
V6 VRF 50Hz
31
Part 2
- Co
mp
on
en
t Layou
t and
Refrige
rant C
ircuits
Oil return operation in heating mode and defrosting operation
Figure 2-3.19: 30/32HP refrigerant flow during oil return operation in heating mode and during defrosting operation
Heating operation
Figure 2-3.20: 30/32HP refrigerant flow during heating operation
16
480 steps
FilterFilter
480 steps
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
480 steps
FilterFilter
480 steps
FilterFilter
Fanoff
Fanoff
Fanoff
Fanoff
15 15
7
1 112
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2T6
BT6
A
SV8A
SV8B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
9
SV7
Closed
Closed
FilterFilter
Unit onThermostat off
Unit onThermostat on
Unit onThermostat on
Unit off
Filter Ind
oo
r u
nit
op
erat
ion
Filter
Normal control
Normal control
FilterFilter
FilterFilter
Fanon
Fanoff
Fanon
Fanon
15 15
7
1 112
34
5
6
11 1110 10
14
88
8
13
EXVBEXVA
EXVC
E S CT3
T4
2
T7C1 T7C2
T6
BT
6A
SV8
A
SV8
B
SV9
SV4
SV5
SV6
2
High temperature, high pressure gasHigh temperature, high pressure liquidMedium temperature, medium pressure gasLow temperature, low pressure
9
SV7
16
V6 VRF 50Hz
32
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
V6 VRF 50Hz
33
Part 3
- Co
ntro
l
Part 3
Control
1 General Control Scheme Flowchart ...................................................... 34
2 Stop Operation .................................................................................... 35
3 Standby Control ................................................................................... 35
4 Startup Control .................................................................................... 36
5 Normal Operation Control ................................................................... 38
6 Protection Control ............................................................................... 43
7 Special Control ..................................................................................... 45
V6 VRF 50Hz
34
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
1 General Control Scheme Flowchart
Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated.
Legend
Numbers in the top right-hand corners of boxes indicate the
relevant section of text on the following pages.
Conditions met
for oil return
Conditions met
for defrosting
Thermo on
Special control
Outdoor unit duty cycling
Oil return operation
Defrosting operation
7
Stop operation
Abnormal shutdown
System stops
A unit stops when the load demanded decreases
2
Standby control
Crankcase heater control
3
Startup control
Compressor startup delay control
Startup control for cooling operation
Startup control for heating operation
4
Thermo on
Normal operation control
Component control during normal operation
Compressor output control
Compressor step control
Operation priority and rotation of compressors
Electronic expansion valve control
Outdoor fan control
5
Protection control
High pressure protection control
Low pressure protection control
Discharge temperature protection control
Compressor and inverter module protection
control
Disable heating control
6
V6 VRF 50Hz
35
Part 3
- Co
ntro
l
2 Stop Operation
The stop operation occurs for one of the three following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off' operation and an error code is displayed on the outdoor unit digital displays.
2. The system stops when the set temperature has been reached.
3. A unit stops when the load demanded by the indoor units decreases and can be handled by fewer outdoor units.
When a unit stops because the load demanded by the indoor units has decreased and can be handled by fewer outdoor
units, the unit's four-way valve remains on until the load demanded by the indoor units increases and the unit is required
to operate. When the whole system stops, all the units' four-way valves turn off.
3 Standby Control
3.1 Crankcase Heater Control
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped.
The crankcase heater is controlled according to outdoor ambient temperature and discharge temperature. When the
outdoor ambient temperature is above 40°C, the crankcase heater is off; when the outdoor ambient temperature is below
35°C, the crankcase heater is controlled according to discharge temperature. Refer to Figures 3-3.1 and 3-3.2.
Figure 3-3.1: Crankcase heater controlled according to outdoor ambient temperature
Figure 3-3.2: Crankcase heater controlled according to discharge temperature
Ambient temperature < 35 oC Ambient temperature > 40 oC
Crankcase heater off
Crankcase heater is controlled according to discharge temperature
Discharge temperature < 40 oC Discharge temperature > 50 oC
Crankcase heater off
Crankcase heater on
V6 VRF 50Hz
36
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
4 Startup Control
4.1 Compressor Startup Delay Control
In initial startup control, compressor startup is delayed for 12 minutes in order to let the master unit search for the indoor
units’ addresses. In restart control (except in oil return operation and defrosting operation), compressor startup is delayed
such that a minimum of 7 minutes has elapsed since the compressor stopped, in order to prevent frequent compressor
on/off and to equalize the pressure within the refrigerant system.
4.2 Startup Control for Cooling Operation Table 3-4.1: Component control during startup in cooling mode
Component
Wiring
diagram
label
8-12HP 14-16HP 18-28HP 30-32HP Control functions and states
Inverter compressor A COMP(A) Controlled according to load requirement, operating
frequency increased by 1 step / sec Inverter compressor B COMP(B)
DC fan motor A FANA Fan speed1 controlled according to discharge
pressure (Pc):
At initial speed for 90 seconds.
Subsequently, Pc checked every 10 seconds:
Pc ≥ 2.7MPa => 1 step increase.
Pc ≤ 2.1MPa => 1 step decrease.
DC fan motor B FANB
Electronic expansion valve
A EXVA
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge temperature Electronic expansion valve
B EXVB
Electronic expansion valve
C EXVC
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to temperature different
between plate heat exchanger inlet and outlet
Four-way valve ST1 Off
Solenoid valve (oil
balance) SV4 Closed for 200 secs, open for 600 secs, then closed
Solenoid valve (fast
defrosting (in heating) and
unloading (in cooling))
SV5 Open for 4 mins, then closed
Solenoid valve (EXV
bypass) SV6
Open for 10 mins, then controlled according to
pressure
Solenoid valve (indoor
units bypass) SV7
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
SV8A Controlled according to inverter compressor A
Solenoid valve (inverter
compressor B vapor
injection)
SV8B Controlled according to inverter compressor B
Solenoid valve (inverter
compressor B pressure
balance)
SV9 Open before compressor B startup
Notes:
1. Refer to Table 3-5.3 in Part 3, 5.6 “Outdoor Fan Control” for more information on fan speed steps.
V6 VRF 50Hz
37
Part 3
- Co
ntro
l
4.3 Startup Control for Heating Operation Table 3-4.2: Component control during startup in heating mode
Component
Wiring
diagram
label
8-12HP 14-16HP 18-28HP 30-32HP Control functions and states
Inverter compressor A COMP(A) Controlled according to load requirement,
operating frequency increased by 1 step / sec Inverter compressor B COMP(B)
DC fan motor A FANA Open once the four-way valve has opened,
controlled according to outdoor ambient
temperature and load requirement DC fan motor B FANB
Electronic expansion valve
A EXVA Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge superheat Electronic expansion valve B EXVB
Electronic expansion valve C EXVC
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to temperature
different between plate heat exchanger inlet and
outlet
Four-way valve ST1 On
Solenoid valve (oil balance) SV4 Closed for 200 secs, open for 600 secs, then closed
Solenoid valve (fast
defrosting (in heating) and
unloading (in cooling))
SV5 Open for 4 mins, then closed
Solenoid valve (EXV bypass) SV6 Off
Solenoid valve (indoor units
bypass) SV7
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
SV8A Controlled according to inverter compressor A
Solenoid valve (inverter
compressor B vapor
injection)
SV8B Controlled according to inverter compressor B
Solenoid valve (inverter
compressor B pressure
balance)
SV9 Open before compressor B startup
V6 VRF 50Hz
38
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
5 Normal Operation Control
5.1 Component Control during Normal Operation Table 3-5.1: Component control during normal cooling operation
Component
Wiring
diagram
label
8-12HP 14-16HP 18-28HP 30-32HP Control functions and states
Inverter compressor A COMP(A)
Controlled according to load requirement Inverter compressor B COMP(B)
DC fan motor A FANA Controlled according to discharge pressure
DC fan motor B FANB
Electronic expansion valve
A EXVA
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge
temperature Electronic expansion valve
B EXVB
Electronic expansion valve
C EXVC
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to temperature
different between plate heat exchanger inlet and
outlet
Four-way valve ST1 On
Solenoid valve (oil balance) SV4 Open regularly
Solenoid valve (fast
defrosting (in heating) and
unloading (in cooling))
SV5
Controlled according to ambient temperature,
discharge pressure, discharge temperature,
compressor running frequency and discharge
superheat
Solenoid valve (EXV
bypass) SV6
Controlled according to discharge pressure and
discharge temperature
Solenoid valve (indoor
units bypass) SV7
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
SV8A
Controlled according to inverter compressor A
on/off
Solenoid valve (inverter
compressor B vapor
injection)
SV8B
Controlled according to inverter compressor B
on/off
Solenoid valve (inverter
compressor B pressure
balance)
SV9
Open before compressor B startup and close after
compressor B running for 15 seconds. Open after
compressor B stop 10 seconds and keep open 60
seconds.
V6 VRF 50Hz
39
Part 3
- Co
ntro
l
Table 3-5.2: Component control during heating operation
Component
Wiring
diagram
label
8-12HP 14-16HP 18-28HP 30-32HP Control functions and states
Inverter compressor A COMP(A)
Controlled according to load requirement Inverter compressor B COMP(B)
DC fan motor A FANA Controlled according to outdoor ambient
temperature, outdoor heat exchanger pipe
temperature, discharge pressure and load
requirement
DC fan motor B FANB
Electronic expansion valve
A EXVA
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge superheat Electronic expansion valve
B EXVB
Electronic expansion valve
C EXVC
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to temperature
different between plate heat exchanger inlet and
outlet
Four-way valve ST1 On
Solenoid valve (oil balance) SV4 Open regularly
Solenoid valve (fast
defrosting (in heating) and
unloading (in cooling))
SV5
Controlled according to ambient temperature,
discharge pressure, discharge temperature,
compressor running frequency and discharge
superheat
Solenoid valve (EXV
bypass) SV6 Off
Solenoid valve (indoor
units bypass) SV7
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
SV8A
Controlled according to inverter compressor A
on/off
Solenoid valve (inverter
compressor B vapor
injection)
SV8B
Controlled according to inverter compressor B
on/off
Solenoid valve (inverter
compressor B pressure
balance)
SV9
Open before compressor B startup and close after
compressor B running for 15 seconds. Open after
compressor B stop 10 seconds and keep open 60
seconds.
V6 VRF 50Hz
40
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
5.2 Compressor Output Control
The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor
units first estimate the indoor unit load requirement according to the nominal capacity of indoor units currently running,
and then correct for ambient temperature. The compressors then start up according to the corrected load requirement.
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures. If the actual load requirement can be provided by one unit alone, then only
one unit starts up. If the actual load requirement requires all outdoor unit modules to operate, the weighted average
actual load requirement is sent to each module and each module operates according to this distributed load
requirement.
5.3 Compressor Step Control
The running speed of the compressors in rotations per second (rps) is one third of the frequency (in Hz) of the electrical
input to the compressor motors. The compressor speed can be altered in increments of 1 rps.
5.4 Operating Priority and Rotation of Compressors
Figures 3-5.1 to 3-5.4 show the compressor operating priority and rotation in systems with one, two, three and four
outdoor units. In units with two compressors, inverter compressor A (BP1) operates in priority to inverter compressor B
(BP2). In multi-unit systems, units operate in rotation. In Figures 3-5.2 to 3-5.4 the master unit and slave units 1, 2 and 3
are shown from left to right in that order, and the circled numbers (①, ②, ③, ④) indicate the rotation sequence.
Figure 3-5.1: Compressor priority and rotation – one outdoor unit
Figure 3-5.2: Compressor priority and rotation – two outdoor units
BP
No. 1
BP1
No. 1 No. 2
BP2
BP BP
No. 1 No. 2
No. 2 No. 1
BP1
No. 1 No. 2 No. 3
No. 2 No. 3 No. 1
BP2 BP BP
1
BP1
No. 1 No. 2 No. 3 No. 4
BP2
No. 3 No. 4 No. 1 No. 2
BP2
①
②
①
②
①
②
V6 VRF 50Hz
41
Part 3
- Co
ntro
l
Figure 3-5.3: Compressor priority and rotation – three outdoor units
5.5 Electronic Expansion Valve Control
EXVA and EXVB control
The positions of electronic expansion valves EXVA and EXVB are controlled in steps from 0 (fully closed) to 480 (fully
open).
In cooling mode:
When all outdoor units are in standby:
All EXVAs and EXVBs are at position 352 (steps).
When some outdoor units are running and some outdoor units are in standby:
EXVAs and EXVBs on running outdoor units are controlled according to discharge temperature. EXVAs and EXVBs
of units in standby are fully closed.
When all outdoor units are running:
All EXVAs and EXVBs are controlled according to discharge temperature.
In heating mode:
When all outdoor units are in standby:
All EXVAs and EXVBs are at position 352 (steps).
When some outdoor units are running and some outdoor units are in standby:
EXVAs and EXVBs on running outdoor units are controlled according to discharge superheat. EXVAs and EXVBs of
units in standby are fully closed.
When all outdoor units are running:
All EXVAs and EXVBs are controlled according to discharge superheat.
EXVC control
The positions of electronic expansion valves EXVC are controlled in steps from 0 (fully closed) to 480 (fully open).
In cooling / heating mode:
When all outdoor units are in standby:
BP BP
No. 1 No. 2 No. 3
No. 3 No. 1 No. 2
BP
No. 2 No. 3 No. 1
BP
No. 1 No. 2 No. 3 No. 4
No. 3 No. 4 No. 1 No. 2
BP
No. 2 No. 3 No. 4 No. 1
BP1 BP2
BP1 BP2
No. 1 No. 2 No. 3 No. 4 No. 5
BP
No. 4 No. 5 No. 1 No. 2 No. 3
No. 2 No. 3 No. 4 No. 5 No. 1
BP1 BP2 BP1 BP2 BP1 BP2
No. 3 No. 4 No. 5 No. 6 No. 1 No. 2
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6
No. 5 No. 6 No. 1 No. 2 No. 3 No. 4
BP1 BP2
①
②
③
①
②
③
①
②
③
①
②
③
V6 VRF 50Hz
42
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
All EXVCs are fully closed.
When some outdoor units are running and some outdoor units are in standby:
EXVCs on running outdoor units are controlled according to temperature different between plate heat exchanger
inlet and outlet. EXVCs of units in standby are fully closed.
When all outdoor units are running:
All EXVCs are controlled according to temperature different between plate heat exchanger inlet and outlet.
5.6 Outdoor Fan Control
The speed of the outdoor unit fans is adjusted in steps, as shown in Table 3-5.3.
Table 3-5.3: Outdoor fan speed steps
Fan speed index
Fan speed (rpm)
8-16HP 18-22HP 24-32HP
FANA / FANB FANA / FANB
0 0 0 / 0 0 / 0
1 120 150 / 0 120 / 0
2 150 190 / 0 150 / 0
3 170 230 / 0 170 / 0
4 190 270 / 0 190 / 0
5 210 310 / 0 (150 / 150) 210 / 0
6 230 350 / 0 (180 / 180) 230 / 0
7 250 380 / 0 (210 / 210) 250 / 0 (120 / 120)
8 270 410 / 0 (240 / 240) 270 / 0 ( 150 / 150)
9 290 280 / 280 330 / 0 (170 / 170)
10 310 320 / 320 370 / 0 (190 / 190)
11 330 360 / 360 210 / 210
12 350 400 / 400 230 / 230
13 370 440 / 440 250 / 250
14 390 480 / 480 270 / 270
15 410 520 / 520 290 / 290
16 430 560 / 560 310 / 310
17 450 600 / 600 330 / 330
18 470 640 / 640 350 / 350
19 490 680 / 680 370 / 370
20 510 720 / 720 400 / 400
21 530 760 / 760 430 / 430
22 560 800 / 800 470 / 470
23 580 840 / 840 510 / 510
24 600 880 / 880 550 / 550
25 630 910 / 910 600 / 600
26 650 940 / 940 650 / 650
27 700 980 / 980 700 / 700
28 750 1010 / 1010 750 / 750
29 800 1020 / 1020 800 / 800
30 850 1050 / 1050 830 / 830
31 880 1080 / 1080 850 / 850
32 920 1120 / 1120 870 / 870
33 920 1140 / 1140 890 / 890
34 920 1140 / 1140 920 / 920
35 920 1140 / 1140 920 / 920
36 (ESP 40Pa mode) 950 1200 / 1200 950 / 950
37 (ESP 60Pa mode) 980 1200 / 1200 980 / 980
Note:
1. For 18-22HP unit fan speed 5 to 8 and 24-32HP unit fan speed 7 to 10, when fan speed decreases, the fan speed is shown in the bracket; when fan speed
increases, the fan speed is shown without bracket.
V6 VRF 50Hz
43
Part 3
- Co
ntro
l
6 Protection Control
6.1 High Pressure Protection Control
This control protects the system from abnormally high pressure and protects the compressors from transient spikes in
pressure.
Figure 3-6.1: High pressure protection control
Notes:
1. Pc: Discharge pressure
6.2 Low Pressure Protection Control
This control protects the system from abnormally low pressure and protects the compressors from transient drops in
pressure.
Figure 3-6.2: Low pressure protection control
Notes: 1. Pe: Suction pressure
6.3 Discharge Temperature Protection Control
This control protects the compressors from abnormally high temperatures and transient spikes in temperature. It is
performed for each compressor.
Figure 3-6.3: Discharge temperature protection control
When the discharge temperature rises above 120°C the system displays P4 protection and all units stop running. When P4
protection occurs 3 times in 100 minutes, the H6 error is displayed. When an H6 error occurs, a manual system restart is
required before the system can resume operation.
6.4 Compressor and Inverter Module Protection Control
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally
Pc > 4.4MPa Pc < 3.2MPa
Normal operation
High pressure protection, error code P1 is displayed
Pe < 0.05MPa Pe > 0.15MPa
Normal operation
Low pressure protection, error code P2 is displayed
When P2 protection occurs 3 times
in 60 minutes, the H5 error is
displayed. When an H5 error occurs,
a manual system restart is required
before the system can resume
operation.
120oC
100oC
90oC
Discharge temperature
Compressor off
90oC
V6 VRF 50Hz
44
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
high temperatures. It is performed for each compressor and inverter module.
Figure 3-6.4: Compressor current protection control
Compressor model AA55PHDG –D1YG DC80PHDG –D1YG
Currentmax 24.6 33
Figure 3-6.5: Inverter module temperature protection control
Notes:
1. Tf: Heat sink temperature
6.5 Disable Heating Control
When the outdoor ambient temperature rises above 25°C heating mode is disabled to prevent the mechanical load on
compressors becoming too high and to prevent low compression ratios which can result in insufficient compressor internal
oil lubrication.
Figure 3-6.6: Disable heating control
Current ≥ Currentmax Current < Currentmax
Normal operation
Compressor current protection, error code xP3 is displayed
Tf > 75oC Tf < 73oC
Normal operation
Compressor output reduced
Tf > 80oC
Tf < 65oC
Inverter module temperature protection,
error code PL is displayed
When PL protection occurs 3 times
in 100 minutes, the C7 error is
displayed. When a C7 error occurs, a
manual system restart is required
before the system can resume
operation.
Outdoor ambient temperature > 25oC Outdoor ambient temperature < 23oC
Heating operation
Units stop
V6 VRF 50Hz
45
Part 3
- Co
ntro
l
7 Special Control
7.1 Outdoor Unit Duty Cycling
In systems with multiple outdoor units, outdoor unit duty cycling is used to prevent compressor burn out due to
unbalanced oil levels between outdoor units.
Timing of outdoor unit duty cycling:
After oil return operation.
After defrosting operation.
On restart following compressor stop after set temperatures achieved.
Figure 3-7.1 shows an example of duty cycling in a system with 3 outdoor units.
Figure 3-7.1: Duty cycling in a system with 3 outdoor units1
Notes:
1. The address settings on the outdoor unit main PCBs for “master unit”, “slave unit 1”, and “slave unit 2” do not change.
7.2 Oil Return Operation
In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that
are in standby. When the outdoor unit is running in oil return, the digital display on outdoor main PCB will display “d0”.
Timing of oil return operation:
When the initial cumulative operating time reaches 140 minutes and then every 8 hours.
Startup control
Normal operation
After oil return operation or
after defrosting operation or
on restart following compressor
stop after set temperatures
achieved Normal operation
Outdoor unit
duty cycling
Priority
1
Priority
2
Priority
3
Master Slave 1 Slave 2
Outdoor unit
duty cycling
Priority
3
Priority
1
Priority
2
Master Slave 1 Slave 2
V6 VRF 50Hz
46
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Tables 3-7.1 and 3-7.2 show component control during oil return operation in cooling mode.
Table 3-7.1: Outdoor unit component control during oil return operation in cooling mode
Component Wiring diagram
label 8-12HP 14-16HP 18-28HP 30-32HP Control functions and states
Inverter compressor A COMP(A)
Fixed frequency Inverter compressor B COMP(B)
DC fan motor A FANA Fan speed controlled according to
discharge pressure DC fan motor B FANB
Electronic expansion valve A EXVA
Position 480 (steps) Electronic expansion valve B EXVB
Electronic expansion valve C EXVC Position 96 (steps)
Four-way valve ST1 Off
Solenoid valve (oil balance) SV4 Normal control
Solenoid valve (fast defrosting (in
heating) and unloading (in cooling)) SV5 On
Solenoid valve (EXV bypass) SV6 On
Solenoid valve (indoor units bypass) SV7 Normal control
Solenoid valve (inverter compressor
A vapor injection) SV8A
Controlled according to inverter
compressor A
Solenoid valve (inverter compressor
B vapor injection) SV8B
Controlled according to inverter
compressor B
Solenoid valve (inverter compressor
B pressure balance) SV9 Open before compressor B startup
Table 3-7.2: Indoor unit component control during oil return operation in cooling mode
Component Unit state Control functions and states
Fan
Thermo on Remote controller setting
Standby Off
Thermo off Off
Electronic expansion valve
Thermo on Normal control
Standby 300 (steps)
Thermo off 300 (steps)
V6 VRF 50Hz
47
Part 3
- Co
ntro
l
Tables 3-7.3 and 3-7.4 show component control during oil return operation in heating mode.
Table 3-7.3: Outdoor unit component control during oil return operation in heating mode
Component Wiring diagram
label 8-12HP 14-16HP 18-28HP 30-32HP Control functions and states
Inverter compressor A COMP(A)
Fixed frequency Inverter compressor B COMP(B)
DC fan motor A FANA Fan speed controlled according to
discharge pressure DC fan motor B FANB
Electronic expansion valve A EXVA
Position 480 (steps) Electronic expansion valve B EXVB
Electronic expansion valve C EXVC Position 96 (steps)
Four-way valve ST1 Off
Solenoid valve (oil balance) SV4 Normal control
Solenoid valve (fast defrosting (in
heating) and unloading (in cooling)) SV5 On
Solenoid valve (EXV bypass) SV6 On
Solenoid valve (indoor units bypass) SV7 Normal control
Solenoid valve (inverter compressor
A vapor injection) SV8A Off
Solenoid valve (inverter compressor
B vapor injection) SV8B Off
Solenoid valve (inverter compressor
B pressure balance) SV9 Open before compressor B startup
Table 3-7.4: Indoor unit component control during oil return operation in heating mode
Component Unit state Control functions and states
Fan
Thermo on Off
Standby Off
Thermo off Off
Electronic expansion valve
Thermo on 480 (steps)
Standby 480 (steps)
Thermo off 480 (steps)
V6 VRF 50Hz
48
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
7.3 Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is
performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor
heat exchanger temperature, indoor heat exchanger temperature and outdoor units running time. When the outdoor unit
is running in defrosting, the digital display on outdoor main PCB will display “df”.
Table 3-7.5: Outdoor unit component control during defrosting operation
Component Wiring diagram
label 8-12HP 14-16HP 18-28HP 30-32HP Control functions and states
Inverter compressor A COMP(A)
Fixed frequency Inverter compressor B COMP(B)
DC fan motor A FANA
Off DC fan motor B FANB
Electronic expansion valve A EXVA
Position 480 (steps) Electronic expansion valve B EXVB
Electronic expansion valve C EXVC Position 480 (steps)
Four-way valve ST1 Off
Solenoid valve (oil balance) SV4 Normal control
Solenoid valve (fast defrosting (in
heating) and unloading (in cooling)) SV5 On
Solenoid valve (EXV bypass) SV6 On
Solenoid valve (indoor units bypass) SV7 Normal control
Solenoid valve (inverter compressor
A vapor injection) SV8A Off
Solenoid valve (inverter compressor
B vapor injection) SV8B Off
Solenoid valve (inverter compressor
B pressure balance) SV9 Open before compressor B startup
Table 3-7.6: Indoor unit component control during defrosting operation
Component Unit state Control functions and states
Fan
Thermo on Off
Standby Off
Thermo off Off
Electronic expansion valve
Thermo on 480 (steps)
Standby 480 (steps)
Thermo off 480 (steps)
V6 VRF 50Hz
49
Part 4
- Field
Settings
Part 4
Field Settings
1 Outdoor Unit Field Settings ................................................................. 50
V6 VRF 50Hz
50
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings Figure 4-1.1: Outdoor unit main PCB switches
Table 4-1.1: Outdoor unit main PCB switch settings
Switch Setting Switch positions1 Description
S4 Static pressure
Standard static pressure (default)
Low static pressure mode (reserved)
Medium static pressure mode (reserved)
High static pressure mode (reserved)
Super high static pressure mode (reserved)
S5 Priority mode
2
Auto priority (default)
Cooling priority
VIP priority or voting priority
Heating only
Cooling only
Set priority mode via centralized controller (reserved)
S6-1 Reserved
Reserved
S6-2
Clear indoor unit addresses
No action (default)
Clear indoor unit addresses
Table continued on next page …
V6 VRF 50Hz
51
Part 4
- Field
Settings
Table 4-1.1: Outdoor unit main PCB switch settings (continued)
Switch Setting Switch positions1 Description
S6-3
Addressing
mode
Auto addressing (default)
Manual addressing
S8-1 Reserved
Reserved
S8-2 Start-up time
Start-up time is 12 minutes (default)
Start-up time is 7 minutes
S8-3 Reserved
Reserved
S7 Reserved
Reserved
S9 Reserved
Reserved
S13 Controller type
Use the new centralized controller (CCM-180A/WS & CCM-270A/WS) (default)
Use the old centralized controller
ENC1
Outdoor unit address
Only 0, 1, 2 should be selected (default is 0) 0 is for master unit; 1 and 2 are for slave units
ENC2
Outdoor unit capacity3
Only 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C should be selected 0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP; 9: 26HP; A: 28HP; B:30HP; C:32HP
ENC4
Network address
Only 0, 1, 2, 3, 4, 5, 6, 7 should be selected (default is 0)
ENC3 S12
Number of indoor units
The number of indoor units is in the range 0-15 0-9 on ENC3 indicate 0-9 indoor units; A-F on ENC3 indicate 10-15 indoor units
The number of indoor units is in the range 16-31 0-9 on ENC3 indicate 16-25 indoor units; A-F on ENC3 indicate 26-31 indoor units
The number of indoor units is in the range 32-47 0-9 on ENC3 indicate 32-41 indoor units; A-F on ENC3 indicate 42-47 indoor units
The number of indoor units is in the range 48-63 0-9 on ENC3 indicate 48-57 indoor units; A-F on ENC3 indicate 58-63 indoor units
ENC4 Silent mode4
0 Night silent time is 6h/10h (default)
1 Night silent time is 6h/12h
2 Night silent time is 8h/10h
3 Night silent time is 8h/12h
4 No silent mode
5 Silent mode 1 (only limit max. fan speed)
6 Silent mode 2 (only limit max. fan speed)
7 Silent mode 3 (only limit max. fan speed)
8 Super silent mode 1 (limit max. fan speed and compressor frequency)
9 Super silent mode 2 (limit max. fan speed and compressor frequency)
A Super silent mode 3 (limit max. fan speed and compressor frequency)
B Super silent mode 4 (limit max. fan speed and compressor frequency)
F Set silent mode via centralized controller (reserved) Notes:
1. Black denotes the switch position.
2. Refer to Part 4, 1.2.1 “Priority mode setting”.
3. Switch ENC2 is factory-set and its setting should not be changed.
4. Refer to Part 4, 1.2.2 “Silent mode setting”.
V6 VRF 50Hz
52
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
1.2 Modes Set on Main PCB
1.2.1 Priority mode setting
Priority mode can only be set on the master unit. When an indoor unit is in mode conflict with the outdoor units the unit
displays the mode conflict error. If the indoor unit has a digital display, it will display error code E0; if the indoor unit
display board has LED indicators, the “DEF./FAN” LED will flash rapidly.
Figure 4-1.2: Indoor unit digital displays and LED indicators
There are five priority mode options:
1. Auto priority mode (default): In auto priority mode, the outdoor unit will operate in heating priority mode or cooling
priority mode according to the outdoor ambient temperature.
a) When the outdoor ambient temperature is below 13oC, the outdoor units run in heating priority mode. The
heating priority mode does not change until the outdoor ambient temperature is above 18oC.
b) When the outdoor ambient temperature is above 18oC, the outdoor units run in cooling priority mode. The
cooling priority mode does not change until the outdoor ambient temperature is below 13oC.
c) When the outdoor units restart under the outdoor ambient between 13oC and 18oC, the outdoor units run the
same priority as before the last stop.
d) When the outdoor unit is initial startup under outdoor ambient temperature between 13oC and 18oC, the
outdoor units run in heating priority mode.
Figure 4-1.3: Auto priority mode control
1.1. Heating priority mode:
a) During cooling operation: If an indoor unit requests heating, the outdoor units stop and then restart in heating
mode after 5 minutes. Indoor units requesting heating then start in heating mode and indoor units requesting
cooling display the mode conflict error.
b) During heating operation: If an indoor unit requests cooling, the outdoor units ignore the request and continue
to run in heating mode. The indoor unit requesting cooling displays the mode conflict error. If all the indoor units
requesting heating are later turned off and one or more indoor units are still requesting cooling, the outdoor
units restart in cooling mode after 5 minutes and any indoor units requesting cooling then start in cooling mode.
1.2. Cooling priority mode:
a) During heating operation: If an indoor unit requests cooling, the outdoor units stop and then restart in cooling
mode after 5 minutes. Indoor units requesting cooling then start in cooling mode and indoor units requesting
heating display the mode conflict error.
b) During cooling operation: If an indoor unit requests heating, the outdoor units ignore the request and continue
to run in cooling mode. The indoor unit requesting heating displays the mode conflict error. If all the indoor units
requesting cooling are later turned off and one or more indoor units are still requesting heating, the outdoor
units restart in heating mode after 5 minutes and any indoor units requesting heating then start in heating
DEF./FAN LED Digital display
18oC
13oC
Outdoor ambient temperature
Cooling priority
Heating priority
V6 VRF 50Hz
53
Part 4
- Field
Settings
mode.
2. Cooling priority mode: refer to above “1.2. Cooling priority mode” descriptions.
3. VIP priority mode or voting priority mode: The default VIP address is 63, the VIP address also can be changed
through menu mode, refer to Part 5, 1.2.3 “Menu mode” Table 5-1.3 “nb8”. If the VIP indoor unit is operating, the
outdoor units operate in the mode of the VIP indoor unit. Indoor units that are in a mode different to that of the VIP
unit display the mode conflict error. If there is no unit with VIP address or the VIP unit is in standby, the outdoor units
operate in voting priority mode. In voting priority mode, the outdoor units operate in whichever of heating and
cooling modes is being requested by the larger number of indoor units.
4. Heating only mode: The outdoor units only operate in heating mode. Indoor units requesting heating operate in
heating mode. Indoor units requesting cooling or in fan only mode display the mode conflict error.
5. Cooling only mode: The outdoor units only operate in cooling mode. Indoor units requesting cooling operate in
cooling mode; indoor units in fan only mode operate in fan only mode. Indoor units requesting heating display the
mode conflict error.
1.2.2 Silent time setting
1.2.2.1 Night silent time setting
Night silent mode is activated X hours after the peak daytime temperature, and is deactivated after Y hours, where X and Y
are as specified in Table 4-1.2. Table 4-1.2: Night silent time setting
Switch Switch positions Description X Y
ENC4
0 Night silent time is 6h/10h (default) 6 10
1 Night silent time is 6h/12h 6 12
2 Night silent time is 8h/10h 8 10
3 Night silent time is 8h/12h 8 12
Figure 4-1.2: Night silent mode example (default setting, 6h/10h)
Operation sound dB
Load
Maximum output
8:00 14:00 20:00 6:00
Night silent mode activated
The outdoor unit senses the peak daytime outdoor ambient temperature
6 10
Night silent mode deactivated
Max. 15dB reduction
V6 VRF 50Hz
54
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
1.2.2.2 Silent mode setting
In silent mode 1 / 2 / 3, the outdoor fan speed decreases gradually. In super silent mode 1 / 2 / 3 / 4 and night silent mode,
not only the fan speed decreases gradually, but also the compressor frequency decreases gradually.
Table 4-1.3: Silent mode setting
Switch Switch positions Description
ENC4
5 Silent mode 1 (only limit max. fan speed)
6 Silent mode 2 (only limit max. fan speed)
7 Silent mode 3 (only limit max. fan speed)
8 Super silent mode 1 (limit max. fan speed and compressor frequency)
9 Super silent mode 2 (limit max. fan speed and compressor frequency)
A Super silent mode 3 (limit max. fan speed and compressor frequency)
B Super silent mode 4 (limit max. fan speed and compressor frequency)
1.2.2.3 Maximum fan speed and capacity output control in different silent mode
Table 4-1.4: Maximum fan speed and capacity output control in different silent mode
ENC4
Switch positions Description
Max. fan speed index1
Max.
capacity
output
8-10HP 12HP 14-16HP 18-22HP 24-26HP 28-32HP 8-32HP
0 Night silent time is 6h/10h (default)
28 28 28 22 28 28
100%
1 Night silent time is 6h/12h
2 Night silent time is 8h/10h
3 Night silent time is 8h/12h
4 No silent mode 30 31 30 30 30 31
5 Silent mode 1 28 28 28 27 28 28
6 Silent mode 2 26 26 26 25 26 26
7 Silent mode 3 24 24 24 23 24 24
8 Super silent mode 1 28 28 28 22 28 28 80%
9 Super silent mode 2 27 27 27 21 27 27 70%
A Super silent mode 3 26 26 26 20 26 26 60%
B Super silent mode 4 25 25 25 19 25 25 50%
Notes: 1. Fan speed (rpm) for different fan speed index refers to Table 3-5.3 in Part 3, 5.6 “Outdoor Fan Control”.
2. If the system pressure is over 3.5MPa, the system exits silent mode automatically.
V6 VRF 50Hz
55
Part 5
- Electrical C
om
po
ne
nts an
d W
iring D
iagrams
Part 5
Electrical Components and
Wiring Diagrams
1 Outdoor Unit Electric Control Box Layout .............................................. 56
2 Outdoor Unit Main PCB ......................................................................... 58
3 Wiring Diagrams .................................................................................... 66
V6 VRF 50Hz
56
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
1 Outdoor Unit Electric Control Box Layout
8-16HP
Figure 5-1.1: 8-16HP top layer of electric control box
Figure 5-1.2: 8-16HP bottom layer of electric control box
Power supplyterminals
Communicationterminals block
Inductor
Filter boardMain PCB
Invertermodule Reactor
Pipe temp. sensorCompressor connection wire
Fan module
Bridge rectifier
V6 VRF 50Hz
57
Part 5
- Electrical C
om
po
ne
nts an
d W
iring D
iagrams
18-32HP
Figure 5-1.3: 18-32HP top layer of electric control box
Figure 5-1.4: 18-32HP bottom layer of electric control box
Power supplyterminals
Communicationterminals block
Inductor
Inductor
Filter boardMain PCB
Invertermodule
Invertermodule Reactor Reactor
Fan module
Fan module
Pip
ete
mp
. sen
sor
Co
mp
ress
or
con
nec
tio
n w
irin
g
Co
mp
ress
or
con
nec
tio
n w
irin
g
Pip
ete
mp
. sen
sor
Bridge rectifier
Bridge rectifier
V6 VRF 50Hz
58
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2 Outdoor Unit Main PCB
2.1 Ports Figure 5-2.1: Outdoor unit main PCB ports
1
Notes: 1. Label descriptions are given in Table 5-2.1.
V6 VRF 50Hz
59
Part 5
- Electrical C
om
po
ne
nts an
d W
iring D
iagrams
Table 5-2.1: Main PCB ports
Label in
Figure 5-2.1 Port code Content Port voltage
1 CN18 Low pressure switch connection 0V or 5V DC
2 CN19 High pressure switch and discharge temperature switch(es)
connections 0V or 5V DC
3 CN4
Compressor top temperature sensor (single compressor
units) or compressor A compressor top temperature sensor
(dual compressor units) connection
0-5V DC (varying)
4 CN5
Discharge pipe temperature sensor (single compressor units)
or compressor B compressor top temperature sensor (dual
compressor units) connection
0-5V DC (varying)
5 CN3 Inverter module temperature sensor A connection 0-5V DC (varying)
6 CN3_1 Inverter module temperature sensor B connection 0-5V DC (varying)
7 CN17 High pressure sensor connection 0-5V DC (varying)
8 CN15 Inverter compressor A and B current sensor connections 0-7.8V AC (varying)
9 CN16 Reserved /
10 CN8 Plate heat exchanger inlet temperature sensor connection 0-5V DC (varying)
11 CN1 Outdoor ambient temperature sensor and outdoor heat
exchanger temperature sensor connections 0-5V DC (varying)
12 CN8_1 Plate heat exchanger outlet temperature sensor connection 0-5V DC (varying)
13 CN20 Communication port to outdoor units 2.5-2.7V DC
14 CN26 Communication port to compressor drive board 2.5-2.7V DC
15 CN27 Communication port to fan drive board 2.5-2.7V DC
16 CN25 Communication port 2.5-2.7V DC
17 CN28 Reserved /
18 CN71 EEVB drive port 0V or 12V DC
19 CN70 EEVA drive port 0V or 12V DC
20 CN72 EEVC drive port 0V or 12V DC
21 CN82 Control port of relay for AC filter board 0V or 12V DC
22 CN66-CN67 Power supply to compressor crankcase heater 220V AC
23 CN47 Four-way valve drive ports 220V AC
24 CN41-CN46;
CN83-CN85 Solenoid valve drive ports 220V AC
25 CN30 Power input of main board 220V AC between A/B/C and N;
380V AC between A,B and C
V6 VRF 50Hz
60
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.2 Components
Layout 2.2.1
Figure 5-2.2: Outdoor unit main PCB components
Function of buttons SW3 to SW6 2.2.2
Table 5-2.2: Function of buttons SW3 to SW6
Button Function
SW3 (UP) In menu mode: previous and next buttons for menu
modes.
Not in menu mode: previous and next buttons for
system check information.
SW4 (DOWN)
SW5 (MENU) Enter / exit menu mode.
SW6 (OK) Confirm to enter specified menu mode.
V6 VRF 50Hz
61
Part 5
- Electrical C
om
po
ne
nts an
d W
iring D
iagrams
Menu mode 2.2.3
Only master unit has the full menu functions, slaves units only have error codes check and cleaning functions.
1. Long press SW5 “MENU” button for 5 seconds to enter menu mode, and the digital display displays “n1”;
2. Press SW3 / SW4 “UP / DOWN” button to select the first level menu “n1”, “n2”, “n3”, “n4”or “nb”;
3. Press SW6 “OK” button to enter specified first level menu, for example, enter “n4” mode;
4. Press SW3 / SW4 “UP / DOWN” button to select the second level menu from “n41” to “n47”;
5. Press SW6 “OK” button to enter specified second level menu, for example, enter “n43” mode;
Menu mode selection flowchart:
Start
Long press SW5 “MENU”
button for 5 seconds
Digital display displays “-n1”
Press SW3 / SW4 “UP /
DOWN” button to select
the first level menu “nX”
Digital display displays “-nX”
Press SW6 “OK” button
to enter specified first
level menu “-nX”
Digital display displays “-nX1”
Press SW3 / SW4 “UP /
DOWN” button to select the
second level menu “nXY”
Digital display displays “-nXY”
Press SW6 “OK” button to
enter specified second level
menu “-nXY”
Confirm “-nXY”
Sho
rt p
ress
SW
5
“MEN
U”
bu
tto
n
Sho
rt p
ress
SW
5
“MEN
U”
bu
tto
n
Sho
rt p
ress
SW
5
“MEN
U”
bu
tto
n
Sho
rt p
ress
SW
5
“MEN
U”
bu
tto
n
V6 VRF 50Hz
62
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Menu mode function:
Table 5-2.3: Menu mode function
Digital display
content Menu mode Remarks
n14 Debug mode 1 Only available for the master unit (all indoor units running in cooling mode)
n15 Debug mode 2
Only available for the master unit (if all the indoor unit in the system are the 2nd
generation indoor units, all the indoor units will run in heating mode. Once there is one or
more old indoor unit in the system, all the indoor units will run in force cooling mode)
n16 Maintenance mode Only available for the master unit, the system does not check the indoor units’ number.
n24 Reserved
n25 Reserved
n26 Backup run Only available for outdoor unit with two compressors. If one of the two compressors is
fail, the other compressor will keep running for up to 4 days and then stop automatically.
n27 Vacuum mode It is only used in maintenance process. The digital display displays “R006”, all solenoid
valves are open and EXVs are open to the maximum steps.
n31 History error codes Display recent ten history error codes
n32 Cleaning history error codes
n33 Reserved
n34 Factory reset Only available for the master unit
n41 Power limitation mode 1 Only available for the master unit, 100% capacity output
n42 Power limitation mode 2 Only available for the master unit, 90% capacity output
n43 Power limitation mode 3 Only available for the master unit, 80% capacity output
n44 Power limitation mode 4 Only available for the master unit, 70% capacity output
n45 Power limitation mode 5 Only available for the master unit, 60% capacity output
n46 Power limitation mode 6 Only available for the master unit, 50% capacity output
n47 Power limitation mode 7 Only available for the master unit, 40% capacity output
nb1 Fahrenheit degree setting (oF) Only available for the master unit
nb2 Celsius degree setting (oC) Only available for the master unit
nb3 Exit auto power save mode1 Only available for the master unit
nb4 Enter auto power save mode1 Only available for the master unit
nb5 Auto snow-blowing mode 1 (customized) According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
15 minutes and run for 2 minute
nb6 Auto snow-blowing mode 2 (customized) According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
30 minutes and run for 2 minute
nb7 Exit auto snow-blowing mode
nb8 VIP address setting The digital display will display “IdXX”, “XX” stands for VIP address, use UP / DOWN button
to change the VIP address and press OK button to confirm the specified VIP address.
nF1 Reserved
nF2 Reserved
Notes:
1. Auto power save mode means EMS mode, the evaporating temperature (in cooling) and condensing temperature (in heating) are automatically adjusted
according to both indoor and outdoor temperature to maximize the comfort and energy efficiency. Exit auto power save mode, the evaporating temperature
(in cooling) and condensing temperature (in heating) are fixed.
V6 VRF 50Hz
63
Part 5
- Electrical C
om
po
ne
nts an
d W
iring D
iagrams
How to exit specified menu mode:
Table 5-2.4: Exit specified menu mode method:
Menu mode Manual exit method Automatic exit method System restart
Debug mode 1 (2) Long press SW6 “OK” button when the digital
display is not in menu selection state After running 120 minutes Invalid
Maintenance mode / After running 60 minutes Invalid
Backup run / After running 4 days or both
two compressors are failed Invalid
Vacuum mode Long press SW6 “OK” button when the digital
display is not in menu selection state After running 8 hours Invalid
Power limitation mode Select power limitation mode 1 “n41” / Valid
Auto power save mode Select “nb3” / Valid
Auto snow-blowing mode 1 (2) Select “nb7” / Valid
VIP address setting / / Valid
oF / oC setting / / Valid
UP / DOWN system check button 2.2.4
Before pressing UP or DOWN button, allow the system to operate steadily for more than an hour. On pressing UP or DOWN
button, the parameters listed in Table 5-2.5 will be displayed in sequence.
Table 5-2.5: System check
DSP1 content
Parameters displayed on DSP2 Remarks
0.-- Unit address Master unit: 0; slave units: 1, 2, 3
1.-- Unit capacity Refer to Note 1
2.-- Number of outdoor units Displayed on master unit PCB only
3.-- Number of indoor units as set on PCB Displayed on master unit PCB only
4.-- Total capacity of outdoor unit Only available for master unit, displayed on slave units has no sense
5.-- Total capacity requirement of indoor units Displayed on master unit PCB only
6.-- Total corrected capacity requirement of indoor units Displayed on master unit PCB only
7.-- Operating mode Refer to Note 2
8.-- Outdoor unit actual operating capacity
9.-- Fan A speed index Refer to Note 3
10.-- Fan B speed index Refer to Note 3
11.-- Indoor heat exchanger pipe (T2/T2B) temperature (°C) Actual value = value displayed
12.-- Main heat exchanger pipe (T3) temperature (°C) Actual value = value displayed
13.-- Outdoor ambient (T4) temperature (°C) Actual value = value displayed
14.-- Plate heat exchanger cooling refrigerant inlet (T6A) temperature (°C) Actual value = value displayed
15.-- Plate heat exchanger cooling refrigerant outlet (T6B) temperature (°C) Actual value = value displayed
16.-- Inverter compressor A discharge temperature (°C) Actual value = value displayed
17.-- Inverter compressor B discharge temperature (°C) Actual value = value displayed
18.-- Inverter module A heatsink temperature (°C) Actual value = value displayed
19.-- Inverter module B heatsink temperature (°C) Actual value = value displayed
20.-- Plate heat exchanger cooling refrigerant outlet temperature minus inlet temperature (°C) Actual value = value displayed
21.-- Discharge superheat degree (°C) Actual value = value displayed
22.-- Inverter compressor A current (A) Actual value = value displayed
23.-- Inverter compressor B current (A) Actual value = value displayed
24.-- EXVA position Refer to Note 4
25.-- EXVB position Refer to Note 4
26.-- EXVC position Refer to Note 4
27.-- Compressor discharge pressure (MPa) Actual value = value displayed × 0.1
28.-- Reserved
29.-- Number of indoor units currently in communication with master unit Actual value = value displayed
30.-- Number of indoor units currently operating Displayed on master unit PCB only
31.-- Priority mode Refer to Note 5
32.-- Silent mode Refer to Note 6
33.-- Static pressure mode Refer to Note 7
Table continued on next page …
V6 VRF 50Hz
64
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Table 5-2.5: System check (continued)
DSP1 content
Parameters displayed on DSP2 Remarks
34.-- Reserved
35.-- Reserved
36.-- DC voltage A Actual value = value displayed × 10
37.-- DC voltage B Actual value = value displayed × 10
38.-- Reserved
39.-- Address of VIP indoor unit
40.-- Reserved
41.-- Reserved
42.-- Refrigerant quantity Refer to Note 8
43.-- Reserved
44.-- Power mode Refer to Note 9
45.-- Most recent error or protection code “--“ is displayed if no error or protection events have occurred since start-up
-- -- -- End Notes:
1. Outdoor unit capacity setting: 0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP; 9: 26HP; A: 28HP; B: 30HP; C: 32HP.
2. Operating mode: 0: off; 2: cooling; 3: heating; 4: forced cooling.
3. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 35 (fastest). 4. 480P: steps = value displayed × 4; 3000P: steps = value displayed × 24. 5. Priority mode:
0: auto priority; 1: cooling priority; 2: VIP priority or voting priority; 3: heating only; 4: cooling only. 6. Silent mode:
0: night silent time 6h/10h; 1: night silent time 6h/12h; 2: night silent time 8h/10h; 3: night silent time 8h/12h; 4: no silent mode; 5: silent mode 1; 6: silent mode 2; 7: silent mode 3; 8: super silent mode 1; 9: super silent mode 2; 10: super silent mode 3; 11: super silent mode 4.
7. Static pressure mode: 0: standard static pressure; 1: low static pressure; 2: medium static pressure; 3: high static pressure; 4: super high static pressure.
8. Refrigerant quantity: 0: normal; 1: slightly excessive; 2: significantly excessive; 3: slightly insufficient; 4: significantly insufficient; 5: critically insufficient.
9. Power mode: 0: 100% capacity output; 1: 90% capacity output; 2: 80% capacity output; 3: 70% capacity output; 4: 60% capacity output; 5: 50% capacity output; 6:
40% capacity output; 10: auto power save mode, 100% capacity output; 11: auto power save mode, 90% capacity output; 12: auto power save mode, 80% capacity output; 13: auto power save mode, 70% capacity output; 14: auto power save mode, 60% capacity output; 15: auto power save mode, 50% capacity output; 16: auto power save mode, 40% capacity output;
Digital display output 2.2.5
Table 5-2.6: Digital display output in different operating states
Outdoor unit state Parameters displayed on DSP1 Parameters displayed on DSP2
Standby Unit's address The number of indoor units in
communication with the outdoor units
Normal
operation
For single
compressor units --
Running speed of the compressor in
rotations per second
For dual
compressor units
Running speed of compressor B in
rotations per second
Running speed of compressor A in
rotations per second
Error or protection -- or placeholder Error or protection code
In menu mode Refer to Table 5-2.3 Refer to Table 5-2.3
System check Refer to Table 5-2.5 Refer to Table 5-2.5
DSP1
DSP2
V6 VRF 50Hz
65
Part 5
- Electrical C
om
po
ne
nts an
d W
iring D
iagrams
3 Compressor Inverter Module
Layout 3.1.1
Figure 5-3.1: Compressor inverter module components
LED indicators LED1 and LED2 3.1.2
Table 5-3.1: LED indicators LED1 and LED2
Indicator LED indicator function and status
LED 1 Inverter module operating indicator. Continuously on if the compressor is running normally and
flashing if an inverter module error has occurred1.
LED 2 Inverter module error indicator. Continuously on if an inverter module error has occurred1.
Note:
1. If an inverter module error occurs, refer to Part 6, “Xh4 Troubleshooting”. The error code is displayed on the digital display.
Dial switch S7 setting 3.1.3
Dial switch S7 is used to set compressor inverter module A/B address. The compressor inverter module A/B location refers
to the wiring diagram. S7 on inverter module Inverter module address
0 for compressor inverter module A
1 for compressor inverter module B
V6
66
Mid
ea V
6 Se
ries S
ervi
ce M
anua
l
4 W8-28Figur
VRF 50HWiring Dia8HP re 5‐4.1: 8‐28HP
No
ut
RA
No
ut
RB
CN
10
CN
10
Red(B
lack)
Bl u
e
Whi
te
Red(B
lack)
Hz grams
P wiring diagra
CN
5P
_o
ut
CN
3
N_in
CN
1P
_in
N_
ou
t
UV w
CN
4
S7
CN
6
CN
7
CN
11
L1
L2
L3
CN
5P
_o
ut
CN
3
N_in
CN
1P
_in
N_
ou
t
UV w
CN
4
S7
CN
10
CN
6
CN
7
CN
11
L1
L2
L3
CN
10
ON
ON
k
ck
L8
L8
Red
Bla
ck
Blu
eC
om
pre
sso
r
Red(B
lack)
Red
Whi
te
Blu
e
Co
mp
ress
or
Red
Whi
te
Blu
e
Red(B
lack)
Red
Blac
k
Blu
e
XT
1
RA
RB
Mai
nbo
ard
AC
filt
erbo
ard
Up
laye
rC
omm
. bo
ard
CN2
CN2
Bla
ck
Blu
e
m
UV
W
CN
8(C
N9)IC17
CO
MP
A
UV
W
IC17
CO
MP
BC
N12
CN1
3C
N14
CN1
2C
N13
CN
14
12
12
Bla
ck
Black
Blac
Blu
e
dri
ve b
oa
rd A
Re
dBl
ack
Blu
e
dri
ve b
oa
rd B
Re
dBl
ack
Bl u
e
Blu
eR
AR
B
BR
1
BR
2
Com
pres
sor
driv
e bo
ard
BC
ompr
esso
rdr
ive
boar
d A
DC
fan
dri
vebo
ard
A
DC
fan
driv
ebo
ard
B
Dow
n la
yer
PC
BA
L
ayo
ut
Bro
wn
CN
8(C
N9)
+
-~
~B
R1
TP
1-P
RO
TP
2-P
RO
L-P
RO
L3’
L1’
L2’
L3’
N’
FA
N A
CN
30
Red
White
Blu
e
Red
White
Blu
eB
lack
Red
Blu
eFA
NA
/B
H-P
RO
/L-P
RO
EE
VA
/EE
VB
/EE
VC
HE
ATA
/HE
AT
B
BR
1/B
R2
CO
MP
A/C
OM
P B
DC
Fan
Hig
h/Lo
w p
ress
ure
ON
/OF
F s
witc
h
Ele
ctro
nic
expa
nsio
n va
lve
Cra
nkca
se h
eate
r
Inve
rter
com
pres
sor
A/B
CO
DE
NA
ME
Sin
gle-
phas
e B
ridge
Rec
tifie
r
H-P
RO
L-PRO
CN19
H-PRO
CN18 DS
P1
DS
P2
CN17
H-YL1T7C1
OK
UP
ME
NU
DO
WN
EN
C3
S12
IN_
NU
M
TF
1
T7
C1
CN4
T7C2
CN5 CN8
T6A
CN
T
T7
C2
CN1
T4 T3
CN3
TF2
CN3_1
TF
2
CN15
T6A
T4
T3
EN
C2
PO
WE
R
L3
CN
12
L1
L2
L3
NC
N9
CN
10
CN
11
CN
3N
P
CN
30
H-Y
L1
CN31
(CN3
2)
1
ON
23
+~
BR
2CN
32(C
N31)
EN
C1
NU
M_
S
(Left)
AC
filt
er
bo
ard
Red
Bl u
e
Blu
eBl
ack
DC
fa
n d
rive
bo
ard
A
ST
1
HP
RO
/LP
RO
T3
H-Y
L1
RA
/RB
IC17
SV
2/S
V4-
SV
9
Mai
n ex
chan
ger
pipe
tem
pera
ture
sens
or
4-w
ay v
alve
Rea
ctan
ce
Cur
rent
sen
sor
gp
Hig
h pr
essu
re s
enso
r
Sol
enoi
d va
lve
L8C
urre
nt s
enso
r
CN100
N8_1
T6B
CN70
EEVA
CN27
O-FAN
CN26
O-C
CN20
O-O
EE
VA
T6
B
CN25
NC
N5
CN
51
L1
L2
L3
CN
6C
N7
CN
8
1
ON
23
4
CN1(
CN4)
-~
SW1
Blu
eBl
ack
bo
ard
A
Mai
n bo
ard
XT
1
TP
1/T
P2-
PR
O
T4
T7C
1/T
7C2
TF
1/T
F2
Pla
te h
eat
exch
ange
r co
olin
g re
frig
eran
tin
let/
outle
t te
mpe
ratu
re s
enso
r
seso
T6A
/T6B
Term
inal
bloc
k
Out
door
am
bien
t te
mpe
ratu
re s
enso
r
Dis
char
ge t
empe
ratu
re O
N/O
FF
sw
itch
Dis
char
ge t
empe
ratu
re s
enso
r
Inve
rter
-mod
ule
heat
sink
tem
pera
ture
sens
orCN
21(C
N22)
CN28
O-D
FA
N B
CN84
CN45
CN67_1
CN66_1
CN85
CN83
CN46
CN44
CN43
CN47
CN67
CN66
0
A
CN72
EEVC
EE
VC
CN71
EEVBE
EV
B
ST
1S
V4
SV
5S
V7
SV
8A
SV
9
SV
6S
V8
BH
EA
TB
HE
AT
BH
EA
TA
HE
ATA
CN30
CN82
N-ON
CN41
SV
2
(Rig
ht)
Red
Blac
kW
hite
Blu
e
Red
Blac
kW
hite
Bl u
e
Blac
kBl
ack
Blac
kBl
ack
CN
4C
N6
Com
m.
boar
d
capa
city
sett
ing
EN
C2
1
8HP
2
10H
P
3
12H
P
4
14H
P
5
16H
P
6
18H
P
capa
city
sett
ing
EN
C2
7
22H
P
8
24H
P
9
26H
P
A
28H
P
0
20H
P
EN
C2
PO
WE
R
XT
1Te
rmin
al b
lock
CN
3N
P
ST
1S
V4
SV
5S
V7
SV
8AS
V9
SV
6S
V8B
HEA
TA HEA
TAHEAT
B HEAT
B
AB
CX
T1
N
SV
2
1
ON
23
4
CN1(
CN4)
SW1
DC
fa
n d
rive
bo
ard
B
Pow
er in
Att
entio
n:
EN
C2
is f
acto
ry s
ettin
g,
do n
ot c
hang
e at
will;
E
NC
1 is
ava
ilabl
e in
mul
ti ou
tdoo
r un
it sy
stem
.
CN
4C
N6
To kilo
wat
t-h
our
me
ter
To cent
rali-
zed
cont
rolle
r
To indo
or u
nits
com
mun
i-ca
tion
To out
doo
run
its c
omm
-u
nica
tion
bus
Res
erve
d
Out
door
uni
tad
dres
sse
ttin
g
EN
C1
0
Mas
ter
unit
(Fac
tory
sett
ing)
12
EN
C1
NU
M_S
Sla
veun
it 1
Sla
veun
it 2
yT
he d
otte
d fr
ame
sect
ion
is u
se b
y so
me
mod
els.
Thi
s co
nnec
tion
diag
ram
is f
or r
efer
ence
onl
y.P
leas
e re
fer
to t
he a
ctua
l pro
duct
.
me
ter
bus
30-3Figur
32HP re 5‐4.2: 30‐32H
N_
ou
tR
A
CN
4N
_o
ut
RB
CN
4CN10
CN
10
Red(Black)
L8
Blu
e
Red
Re
d
Whi
te
Red(B
lack)
HP wiring diagr
CN
5P
_o
ut
CN
3
N_in
CN
1P
_in
UV w
S7
CN
6
CN
7
CN
11
L1
L2
L3
CN
5P
_o
ut
CN
3
N_in
CN
1P
_in
UV w
S7
CN
6
CN
7
CN
11
L1
L2
L3
1
ON
21
ON
2
ack
ack
L8
L8
Red
Bla
ck
Blu
eC
om
pres
sor
driv
eb
oard
A
Red(B
lack)
Red
Whi
te
Blu
e
Co
mpr
esso
rd
rive
boar
dB
Re
d
Whi
te
Blu
e
Red(B
lack)
Red
Bla
ck
Blu
e
XT
1
RB
RA
Mai
nbo
ard
AC
filt
erbo
ard
Up
laye
rC
omm
. bo
ard
CN2
CN2
Bla
ck
Blu
e
ram
UV
W
CN
8(C
N9)IC17
CO
MP
A
UV
W
IC17
CO
MP
BC
N12
CN1
3CN
14CN
12C
N13
CN
14
12
Bla
ck
Bla
Bla
driv
e b
oard
A
Re
dBl
ack
Bl u
e
dri
ve b
oar
d B
Red
Blac
kB
lue
BR
1
BR
2
Com
pres
sor
driv
e bo
ard
AC
ompr
esso
rdr
ive
boar
d B
DC
fan
driv
ebo
ard
A
DC
fan
driv
ebo
ard
B
Dow
n la
yer
PC
BA
L
ayo
ut
Bro
wn
CN
8(C
N9)
+
-~
~B
R1
T
TP
1-P
RO
TP
2-P
RO
C
L-P
RO
L3’
L1’
L2’
L3’
N’
FA
N A
CN
30
Red
White
Blu
e
Red
White
Blu
eB
lack
Red
Bl u
e
H-P
RO
FA
NA
/B
EE
VA
/EE
VB
/EE
VC
BR
1/B
R2
CO
MP
A/C
OM
P B
DC
Fan
Ele
ctro
nic
expa
nsio
n va
lve
Ck
ht
Inve
rter
com
pres
sor
A/B
CO
DE
NA
ME
Sin
gle-
phas
e B
ridge
Rec
tifie
r
L-PRO
CN19
H-PRO
CN18 DS
P1
DS
P2
CN17
H-YL1T7C1
OK
UP
ME
NU
DO
WN
EN
C3
S12
IN_
NU
M
TF
1
T7
C1
CN4
T7C2
CN5 CN8
T6A
C
T
T7
C2
CN1
T4 T3
CN3
TF2
CN3_1
TF
2
CN15
T6A
T4
T3
EN
C2
PO
WE
R
CN
12
CN
9C
N10
CN
11
CN
3N
P
CN
30
H-Y
L1
CN31
(CN3
2)
1
ON
23
+~
BR
2CN
32(C
N31)
EN
C1
NU
M_
S
(Left)
AC
filte
rb
oa
rd
Red
Blu
e
Blu
eBl
ack
DC
fa
n d
rive
bo
ard
A
ST
1
H-P
RO
/L-P
RO
H-Y
L1
RA
/RB
IC17
SV
2/S
V4-
SV
9
HE
ATA
/HE
AT
B
4-w
ay v
alve
Rea
ctan
ce
Cur
rent
sen
sor
Hig
h/Lo
w p
ress
ure
ON
/OF
F s
witc
h
Hig
h pr
essu
re s
enso
r
Cra
nkca
se h
eate
r
Sol
enoi
d va
lve
L8C
urre
nt s
enso
r
CN100
CN8_1
T6B
CN
EE
CN27
O-FAN
CN26
O-C
CN20
O-O
EE
VA
T6
B
CN25
NC
N5
CN
51
L1
L2
L3
CN
6C
N7
CN
8
1
ON
23
4
CN1(
CN4)
-~
SW1
AC
filt
er b
oa
rd
Bl u
eBl
ack
bo
ard
A
Mai
n bo
ard
T3
T4
T7C
1/T
7C2
TF
1/T
F2
Pla
te h
eat
exch
ange
r co
olin
g re
frig
eran
tin
let/
outle
t te
mpe
ratu
re s
enso
r
Mai
n ex
chan
ger
pipe
tem
pera
ture
sens
or
T6A
/T6B
Out
door
am
bien
t te
mpe
ratu
re s
enso
r
Dis
char
ge t
empe
ratu
re s
enso
r
Inve
rter
-mod
ule
heat
sink
tem
pera
ture
sens
or
CN21
(CN2
2)
CN28
O-D
FA
N B
CN
CN
CN6
CN6
CN85
CN83
CN46
CN44
CN43
CN47
CN67
CN66
N70
EVA
CN72
EEVC
EE
VC
CN71
EEVB
EE
VB
ST
1S
V4
SV
5S
V7
SV
8A
SV
9
SV
6S
V8B
HE
AT
B
HE
AT
BH
EA
TA
HE
ATA
CN30
CN82
N-ON
CN41
SV
2
(Rig
ht)
Red
Blac
kW
hite
Bl u
e
Re
dBl
ack
Whi
teB
lue
Blac
kBl
ack
Blac
kBl
ack
capa
city
sett
ing
EN
C2
B
30H
P
C
32H
P
EN
C2
PO
WE
RC
omm
. bo
ard
XT
1
TP
1/T
P2-
PR
O
Term
inal
blo
ck
Dis
char
ge t
empe
ratu
re O
N/O
FF
sw
itch
V
CN
3
CN1 (
CN4)
NP
ST
1
N84
N45
67_1
66_1
SV
4S
V5
SV
7S
V8A
SV
9
SV
6S
V8
B
HEA
TA HEA
TAHEAT
B HEAT
B
AB
CX
T1
N
SV
2
1
ON
23
4SW1
DC
fa
n d
rive
bo
ard
B
Pow
erin
Att
entio
n:
EN
C2
isfa
ctor
yse
ttin
g,
dono
tch
ange
atw
ill;
CN4
CN6
To kilo
wat
t-To ce
ntra
li-ze
d
To indo
or u
nits
com
mun
i
To outd
oor
units
com
mR
eser
ved
Out
door
uni
tad
dres
sse
ttin
g
EN
C1
0
Mas
ter
unit
(Fac
tory
sett
ing)
12
EN
C1
NU
M_S
Sla
veun
it 1
Sla
veun
it 2
V6 VRF 50
16
02
70
00
00
75
28
Pow
er in
Att
entio
n:
EN
C2
is f
acto
ry s
ettin
g,
do n
ot c
hang
e at
will;
E
NC
1 is
ava
ilabl
e in
mul
ti ou
tdoo
r un
it sy
stem
.T
he d
otte
d fr
ame
sect
ion
is u
se b
y so
me
mod
els.
Thi
s co
nnec
tion
diag
ram
is f
or r
efer
ence
onl
y.P
leas
e re
fer
to t
he a
ctua
l pro
duct
.
hour
met
er
zed
cont
rolle
rco
mm
uni-
catio
nbu
s
units
com
m-
unic
atio
n bu
sR
eser
ved
0Hz
67
Part 5 - Electrical Components and W
iring Diagrams
V6 VRF 50Hz
68
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
V6 VRF 50Hz
69
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Part 6
Diagnosis and
Troubleshooting
1 Error Code Table .................................................................................... 70
2 Troubleshooting .................................................................................... 71
3 Appendix to Part 6 .............................................................................. 131
V6 VRF 50Hz
70
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
1 Error Code Table
Table 6-1.1: Error code table
Error
code1
Content Remarks Manual re-start
required2
E0 Communication error between outdoor units Only displayed on the slave unit
with the error No
E1 Phase sequence error Displayed on the unit with the error Yes
E2 Communication error between indoor and master unit Only displayed on the master unit No
E4 Outdoor heat exchanger temperature sensor (T3) error or
outdoor ambient temperature sensor (T4) error Displayed on the unit with the error No
E5 Abnormal power supply voltage Displayed on the unit with the error No
E7 Compressor top or discharge pipe temperature sensor (T7C1/2)
error Displayed on the unit with the error Yes
E8 Outdoor unit address error Displayed on the unit with the error Yes
xE9 EEPROM mismatch Displayed on the unit with the error Yes
xF1 DC bus voltage error Displayed on the unit with the error No
F3 Plate heat exchanger cooling refrigerant outlet temperature
sensor (T6B) error Displayed on the unit with the error No
F5 Plate heat exchanger cooling refrigerant inlet temperature sensor
(T6A) error Displayed on the unit with the error No
F6 Electronic expansion valve connection error Displayed on the unit with the error
Refer to Note 3 Yes
xH0 Communication error between main control chip and inverter
driver chip Displayed on the unit with the error No
H2 Number of slave units detected by master unit has decreased Only displayed on the master unit No
H3 Number of slave units detected by master unit has increased Only displayed on the master unit No
xH4 Inverter module protection Displayed on the unit with the error Yes
H5 P2 protection appears three times in 60 minutes Displayed on the unit with the error Yes
H6 P4 protection appears three times in 100 minutes Displayed on the unit with the error Yes
H7 Number of indoor units detected by master unit not same as
number set on main PCB Only displayed on the master unit No
H8 High pressure sensor error Displayed on the unit with the error No
H9 P9 protection appears ten times in 120 minutes Displayed on the unit with the error Yes
yHd Slave unit malfunction Only displayed on the master unit No
C7 PL protection appears three times in 100 minutes Displayed on the unit with the error Yes
P1 Discharge pipe high pressure protection Displayed on the unit with the error No
P2 Suction pipe low pressure protection Displayed on the unit with the error No
xP3 Compressor current protection Displayed on the unit with the error No
P4 Discharge temperature protection Displayed on the unit with the error No
P5 Outdoor heat exchanger temperature protection Displayed on the unit with the error No
P9 Fan module protection Displayed on the unit with the error No
Table continued on next page …
V6 VRF 50Hz
71
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Table 6-1.1: Error code table (continued)
Error
code1
Content Remarks Manual re-start
required2
PL Inverter module temperature protection Displayed on the unit with the error No
PP Compressor discharge insufficient superheat protection Displayed on the unit with the error No
xL0 Inverter module protection Displayed on the unit with the error Yes
xL1 DC bus low voltage protection Displayed on the unit with the error Yes
xL2 DC bus high voltage protection Displayed on the unit with the error Yes
xL4 MCE error Displayed on the unit with the error Yes
xL5 Zero speed protection Displayed on the unit with the error Yes
xL7 Phase sequence error Displayed on the unit with the error Yes
xL8 Compressor frequency variation greater than 15Hz within one
second protection Displayed on the unit with the error Yes
xL9 Actual compressor frequency differs from target frequency by
more than 15Hz protection Displayed on the unit with the error Yes
Notes:
1. 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and 2
representing compressor system B. 'y' is a placeholder for the address (1 or 2) of the slave unit with the error.
2. For some error codes, a manual restart is required before the system can resume operation.
3. Once the EXV has been connected properly, the error code will flash to indicate that the connection has been re-established. A manual restart is then
required before the system can resume operation.
2 Troubleshooting
2.1 Warning
All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
Warning
V6 VRF 50Hz
72
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.2 E0: Communication error between outdoor units
Digital display output 2.2.1
Description 2.2.2
Communication error between outdoor units.
All units stop running.
Error code is only displayed on the slave unit with the error.
Trigger / recover condition 2.2.3
Trigger condition: Slave unit cannot receive signal from master unit for 60s.
Recover condition: Slave unit can receive signal from master unit.
Reset method: Resume automatically.
Possible causes 2.2.4
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged main PCB or electric control box communication terminals block.
V6 VRF 50Hz
73
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.2.5
E0
ODU addresses on switch ENC1 are set
incorrectly1 Yes Set the ODU addresses correctly
No
Communication wires between ODUs are
not connected properly2 Yes
Ensure the communication wires are
three-core shielded cable and are
connected properly
No
Wires between outdoor main PCB and
electric control box communication
terminals block are loose
Yes Ensure the wires are connected properly
No
Replacing outdoor main PCB resolves the
error
No
Replace electric control box
communication terminals block
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system. 2. All the wires for H1, H2, E connections should be three-core shielded cable, the wiring should be connected according to polarity (H1 to H1, etc), the wiring
should not be open or short circuited.
V6 VRF 50Hz
74
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.3 E1: Phase sequence error
Digital display output 2.3.1
Description 2.3.2
Phase sequence error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.3.3
Trigger condition: Wrong phase connection for 1.6s or phase missing for 48s.
Recover condition: Correct phase connection.
Reset method: Manually restart.
Possible causes 2.3.4
Power supply phases not connected in correct sequence.
Power supply terminals loose.
Power supply abnormal.
Main PCB damaged.
V6 VRF 50Hz
75
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.3.5
E1
The phase sequence of the 3-phase
power supply is incrorrect1
Yes Exchange any two of the 3 phase wires
No
Some power supply terminals are loose2 Yes Ensure all supply terminals are securely
fastened
No
The power supply is abnormal Yes Check the power supply equipment
No
Replace outdoor main PCB
Notes:
1. The A, B, C terminals of the 3-phase power supply should match compressor phase sequence requirements. If the phase sequence is inverted, the compressor will operate inversely. If the wiring connection of each outdoor unit is in A, B, C phase sequence, and multiple units are connected, the current difference between C phase and A, B phases will be very large as the power supply load of each outdoor unit will be on C phase. This can easily lead to
tripped circuits and terminal wiring burnout. Therefore if multiple units are to be used, the phase sequence should be staggered, so that the current is distributed among the three phases equally.
2. Loose power supply terminals can cause the compressors to operate abnormally and compressor current to be very large.
V6 VRF 50Hz
76
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.4 E2: Communication error between indoor and master unit
Digital display output 2.4.1
Description 2.4.2
Communication error between indoor and master unit.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition 2.4.3
Trigger condition: Indoor units and outdoor units cannot communication for 2 minutes after the system power on 20
minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes 2.4.4
Communication wires between indoor and outdoor units not connected properly.
Indoor unit power supply abnormal.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB or electric control box communication terminals block.
V6 VRF 50Hz
77
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.4.5
E2
Communication wires P Q E have short
circuited or disconnected1 Yes Reconnect the communication wires
No
Communication wires P Q E are not
connected in a daisy chain Yes Connect the communication wires in a
daisy chain
No
IDU power supply is abnormal Yes Ensure normal power supply
No
Wires between outdoor main PCB and
electric control box communication
terminals block are loose
Yes Ensure the wires are connected properly
No
Interference from high voltage (220V or
higher) wires Yes Ensure the communication wires and
high voltage wires are separated
No
Communication wires are close to a
source of electromagnetic radiation such
as transformer or strong fluorescent lamp
Yes Remove the source of interference, or
add additional shielding to the
communication wires
No
The length of communication wire is over
1200m Yes Reduce the wire length to less than
1200m or strengthen the signal
No
Replacing outdoor main PCB resolves the
error
No
Replace electric control box
communication terminals block
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.
V6 VRF 50Hz
78
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.5 E4: Temperature sensor (T3/T4) error
Digital display output 2.5.1
Description 2.5.2
Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.5.3
Trigger condition: The main control board cannot receive the feedback signal of temperature sensor T3 or T4.
Recover condition: The main control board can receive the feedback signal of temperature sensor T3 or T4.
Reset method: Resume automatically.
Possible causes 2.5.4
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
V6 VRF 50Hz
79
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.5.5
E4
Temperature sensor connection on main
PCB is loose1 Yes Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed2 Yes Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Outdoor ambient temperature sensor (T4) and heat exchanger temperature sensor (T3) connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
V6 VRF 50Hz
80
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.6 E5: Abnormal power supply voltage
Digital display output 2.6.1
Description 2.6.2
Abnormal power supply voltage.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.6.3
Trigger condition: Outdoor unit power supply phase voltage < 165V.
Recover condition: Outdoor unit power supply phase voltage is > 180V.
Reset method: Resume automatically.
Possible causes 2.6.4
Outdoor unit power supply voltage is abnormal or a phase is missing.
Loosened wiring within electric control box.
High voltage circuit error.
Main PCB damaged.
V6 VRF 50Hz
81
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.6.5
E5
ODU power supply is abnormal or a
phase is missing1 Yes Provide normal power supply
No
Wires between outdoor main PCB, AC
filter boards and electric control box
power supply terminals are loose
Yes Ensure the wires are connected properly
No
High voltage circuit error has occurred,
such as the compressor has
malfunctioned2, the fan motor has
short-circuited3, or the inverter module
has short-circuited4
Yes Replace or repair the relevant parts
No
Replace outdoor main PCB
Notes:
1. The normal voltage between A and N, B and N, and C and N is 198-242V. 2. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
3. The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited. 4. Set a multi-meter to buzzer mode and test any two terminals of P N U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
Figure 6-2.1: Inverter module terminals
V6 VRF 50Hz
82
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.7 E7: Temperature sensor (T7C1/2) error
Digital display output 2.7.1
Description 2.7.2
A compressor top temperature sensor or discharge pipe temperature sensor (T7C1/2) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.7.3
Trigger condition: Discharge pressure ≥ 3MPa and discharge temperature < 15oC for 2 minutes.
Recover condition: Discharge pressure and temperature go back to normal.
Reset method: Manually restart.
Possible causes 2.7.4
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
V6 VRF 50Hz
83
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.7.5
E7
Temperature sensor connection on main
PCB is loose1 Yes Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed2 Yes Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4, respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
V6 VRF 50Hz
84
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.8 E8: Outdoor unit address error
Digital display output 2.8.1
Description 2.8.2
Outdoor unit address error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.8.3
Trigger condition: Outdoor unit address is set more than 3.
Recover condition: Outdoor unit addresses are set from 0 to 3.
Reset method: Manually restart.
Possible causes 2.8.4
Invalid outdoor unit address.
Main PCB damaged.
V6 VRF 50Hz
85
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.8.5
E8
The ODU's address is not in the valid
range1 Yes Slave units addresses should be set from
1 to 3
No
Replace the outdoor main PCB
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system.
V6 VRF 50Hz
86
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.9 xE9: EEPROM mismatch
Digital display output 2.9.1
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description 2.9.2
1E9 indicates a compressor A EEPROM mismatch.
2E9 indicates a compressor B EEPROM mismatch.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.9.3
Trigger condition: Compressor drive parameter is mismatch.
Recover condition: Compressor drive parameter is match.
Reset method: Manually restart.
Possible causes 2.9.4
Outdoor unit was powered on immediately after being powered off.
Main PCB damaged.
V6 VRF 50Hz
87
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.9.5
xE9
The outdoor unit was powered on
immediately after being powered off1 Yes
Power off the unit and wait for the digital
display to turn off before restarting the
unit
No
Replace outdoor main PCB
Notes:
1. When performing a manual restart of an outdoor unit, once the unit has been powered off it should not be powered on again until the digital display has
turned off.
V6 VRF 50Hz
88
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.10 xF1: DC bus voltage error
Digital display output 2.10.1
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
Description 2.10.2
1F1 indicates compressor A DC bus voltage error; 2F1 indicates compressor B DC bus voltage error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.10.3
Trigger condition: DC bus voltage < 350V or DC bus voltage > 700V continuously for 10 seconds.
Recover condition: DC bus voltage goes back to normal.
Reset method: Restart automatically.
Possible causes 2.10.4
Loosened wiring of the compressor inverter module.
Incorrect wiring of the reactor and DC bus wire.
Abnormal power supply.
Inverter module damaged.
V6 VRF 50Hz
89
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.10.5
Note:
1. The DC bus wire should run from the N_in terminal on the inverter module, through the current sensor (in the direction indicated by the
arrow on the current sensor), and end at the N_out terminal on the inverter module.
Figure 6-2.2: DC detection wire connection method
F1 error
Compressor inverter module wiring is loosened
Reconnect cables based on wiring diagram
Reactor and DC bus wiring is incorrectly1
Reconnect the reactor and DC bus wire based on wiring
diagram
The power supply is abnormal
No
No
Yes
YesDisconnect the power supply
Check the power supply equipment
Yes
Replace the inverter module
No
V6 VRF 50Hz
90
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.11 F3, F5: Temperature sensor (T6B/T6A) error
Digital display output 2.11.1
Description 2.11.2
F3 indicates plate heat exchanger cooling refrigerant outlet temperature sensor (T6B) error.
F5 indicates plate heat exchanger cooling refrigerant inlet temperature sensor (T6A) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.11.3
Trigger condition: Temperature sensor T6A(B) is open or short-circuit.
Recover condition: Temperature sensor T6A(B) connection ports can detect load.
Reset method: Resume automatically.
Possible causes 2.11.4
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
V6 VRF 50Hz
91
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.11.5
F3 / F5
Temperature sensor connection on main
PCB is loose1 Yes Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed2 Yes Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Plate heat exchanger cooling refrigerant inlet temperature sensor (T6A) and plate heat exchanger cooling refrigerant outlet temperature sensor (T6B) connection are port CN8 and CN8_1 on the main PCB (labeled 10 and 12, respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
V6 VRF 50Hz
92
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.12 F6: Electronic expansion valve connection error
Digital display output 2.12.1
Description 2.12.2
Electronic expansion valve connection error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.12.3
Trigger condition: The main control board cannot receive the feedback signal of EXV.
Recover condition: The main control board can receive the feedback signal of EXV.
Reset method: When the main control board can receive the feedback signal of EXV, F6 flashes, a manual system
restart id required before the system can resume operation.
Possible causes 2.12.4
Electronic expansion valve coil not connected properly or has malfunctioned.
Damaged main PCB.
V6 VRF 50Hz
93
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.12.5
F6
Electronic expansion valve coil
connection on main PCB is loose1 Yes Ensure the sensor is connected properly
No
Electronic expansion valve coil has
malfunctioned2 Yes Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Electronic expansion valve coil connections are port CN70, CN71 and CN72 on the main PCB (labeled 18, 19 and 20, respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. The normal resistances between EXV coil wiring terminals RED and white / yellow / orange / blue are 40-50Ω. If any of the resistances differ from the value, the EXV coil has malfunctioned.
Figure 6-2.3: EXV coil wiring terminals
V6 VRF 50Hz
94
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.13 xH0: Communication error
Digital display output 2.13.1
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description 2.13.2
1H0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2H0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.13.3
Trigger condition: Main control chip and inverter driver chip cannot communication for 2 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes 2.13.4
Incorrect compressor inverter module address setting.
Loosened communication wiring from the main PCB to
the inverter module.
Bridge rectifier damaged.
Main PCB damaged.
Compressor inverter module damaged.
Procedure 2.13.5
H0 error
Compressor inverter module address setting is incorrect
Reset the compressor inverter module address via
dial switch S7 on inverter module
1
Communication wire from outdoor main PCB CN26 to inverter module CN8/
CN9 is loosened2
Reconnect the communication wire
Both LED1 and LED2 on inverter module are off when power on
3
No
No
Yes
Yes
Check the power supply circuit
4Yes
Replace the outdoor main PCB, is the malfunction solved?
No
NormalYes
No
Replace the inverter module
V6 VRF 50Hz
95
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Notes: 1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.
S7 on inverter module Inverter module address
0 for compressor inverter module A
1 for compressor inverter module B
2. Communication wire from outdoor main PCB CN26 to inverter module CN8/CN9.
Communication port CN26 on main PCB Communication port CN8/CN9 on inverter module
3. LED1/2 on inverter module
4. Check the power supply for the compressor inverter module, port CN41 on filter board, the normal voltage should be DC310V; check the high pressure switch connection port CN61 on filter board, the normal resistance should be zero; Check the single phase bridge and fuse on filter board; check the connection cable from ODU main PCB port CN82 to filter board port CN30 which is DC310V power control port.
CN41 Power for
SMPS of
Compressor inverter
module
CN61 High
pressure switch
connection port
Fuse 30A CN30
V6 VRF 50Hz
96
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.14 H2, H3: Slave units decreased/increased
Digital display output 2.14.1
Description 2.14.2
H2 indicates that the number of slave units detected by master unit has decreased.
H3 indicates that the number of slave units detected by master unit has increased.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition 2.14.3
Trigger condition: Number of slave units detected by master unit has decreased or increased.
Recover condition: Number of slave units detected by master unit goes back to normal.
Reset method: Resume automatically.
Possible causes 2.14.4
Some outdoor units are powered off.
Power supply abnormal.
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged main PCB or electric control box communication terminals block.
V6 VRF 50Hz
97
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Procedure 2.14.5
H2 / H3
Some outdoor units in the system are
powered off Yes Power on all the outdoor units
No
The power supply is abnormal Yes Check the power supply equipment
No
Troubleshoot as for an E0 error2
Notes:
1. See “E0 Troubleshooting”.
V6 VRF 50Hz
98
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
2.15 xH4: Inverter module protection
Digital display output 2.15.1
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description 2.15.2
1H4 indicates compressor A inverter module protection.
2H4 indicates compressor B inverter module protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.15.3
Trigger condition: Compressor appears three inverter module protections.
Recover condition: Inverter module goes back to normal.
Reset method: Manually restart.
Possible causes 2.15.4
Inverter module protection.
DC bus low or high voltage protection.
MCE error.
Zero speed protection.
Phase sequence error.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
Specific error codes for xH4 inverter module protection 2.15.5
If an xH4 error code is displayed, enter menu mode “n31” (refer to Part 5, 2.2.3 “menu mode”) to check the history error
code to check the following specific error code: xL0, xL1, xL2, xL4, xL5, xL7, xL8, xL9.
Table 6-2.1: Specific error codes for error xH4
Specific error code1 Content
xL0 Inverter module protection
xL1 DC bus low voltage protection
xL2 DC bus high voltage protection
xL4 MCE error
xL5 Zero speed protection
xL7 Phase sequence error
xL8 Compressor frequency variation greater than 15Hz within one second protection
xL9 Actual compressor frequency differs from target frequency by more than 15Hz protection
Notes: 1. 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and
2 representing compressor system B.
V6 VRF 50Hz
99
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
The specific error codes xL0, xL1, xL2 and xL4 can also be obtained from the inverter module LED indicators. If an inverter
module error has occurred, LED2 is continuously on and LED1 flashes.
Figure 6-2.4: LED indicators LED1 and LED2 on inverter module
Table 5-3.2: Errors indicated on LED1
LED1 flashing pattern Corresponding error
Flashes 8 times and stops for 1 second, then repeats xL0 - Inverter module protection
Flashes 9 times and stops for 1 second, then repeats xL1 - DC bus low voltage protection
Flashes 10 times and stops for 1 second, then repeats xL2 - DC bus high voltage protection
Flashes 12 times and stops for 1 second, then repeats xL4 - MCE error
V6 VRF 50Hz
100
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
L0: Inverter module protection 2.15.6
Note:
2. The DC bus wire should run from the N_in terminal on the inverter module, through the current sensor (in the direction indicated by the
arrow on the current sensor), and end at the N_out terminal on the inverter module.
Figure 6-2.5: DC detection wire connection method
L0 protection
The DC bus wire connected incorrectly1 Ensure the wire is
connected properly
The compressor wiring is connected incorrectly
Reconnect the cables based on wiring diagram
Replace the compressor
The inverter module is not well heat dissipation
The IPM screws is loosenFasten IPM screws again
The silica gel is coated not well for heat radiation
Coat with silica gel
The compressor has less than 12 hours preheating before initial operating
Switch on power again to detect whether the compressor can start
Refer to “P3 over current protection”
Replace the inverter module
Ensure enough preheating time
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
Disconnectthe powersupply
The resistance between 3 phases of compressor is over 5Ω
The insulation resistance of compressor is less than 100kΩ
V6 VRF 50Hz
101
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
L1: DC bus low voltage protection 2.15.7
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is lower than 350V, L1
protection will be appeared.
Figure 6-2.6: Inverter module terminals
L1 protection
The power supply is abnormalCheck the power supply
equipment
No output from bridge rectifier
Replace the inverter module
No
No
No
Yes
Yes
Yes
Yes
The DC bus voltage (P, N) is abnormal1
The reactor performs wellReplace the
reactorNo
V6 VRF 50Hz
102
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
L2: DC bus high voltage protection 2.15.8
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
Figure 6-2.7: Inverter module terminals
L2 protection
The power supply is abnormalCheck the power supply
equipment
The DC bus voltage (P, N) is abnormal1 Replace the 3-phase bridge
rectifier
Replace the inverter module
No
No
Yes
Yes
V6 VRF 50Hz
103
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
L4: MCE error 2.15.9
Notes: 1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.
S7 on inverter module Inverter module address
0 for compressor inverter module A
1 for compressor inverter module B
L4 protection
ODU ventilation is not goodRemove barriers from heat
exchanger and air outlet of ODU
ODU stop valves are closed Open the ODU stop valves
Reconnect the cables based on wiring diagram
The resistance between 3 phases of compressor is over 5Ω
Replace the compressor
The insulation resistance of compressor is less than 100Ω
Replace the compressor inverter board, restart the unit and the error is
solved
Refer to P1 or P3 troubleshooting
No
No
Yes
Yes
Disconnectthe powersupply
Compressor wiring is not properly
Inverter module address setting1 and
discharge temperature sensor wiring is not properly
Reset the inverter module address and reconnect the discharge temperature sensor cables
YesNormal
Yes
Yes
Yes
Yes
No
No
No
No
No
V6 VRF 50Hz
104
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
L7: Phase sequence error 2.15.10
L7 protection
Compressor wiring is looseReconnect cables based on
wiring diagram
An open circuit in the 3-phase U/V/W of compressor terminals
Replace the compressor
Replace the inverter module
No
No
Yes
YesDisconnect the power supply
V6 VRF 50Hz
105
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
L8: Compressor frequency variation greater than 15Hz within one second protection 2.15.11
L9: Actual compressor frequency differs from target frequency by more than 15Hz protection
L8 protection
ODU stop valves are closed Open the ODU stop valves
Reconnect the cables based on wiring diagram
The resistance between 3 phases of compressor is over 5Ω
Replace the compressor
The insulation resistance of compressor is less than 100Ω
Replace the compressor inverter board, restart the unit and the error is
solved
Refer to P1 or P3 troubleshooting
No
Yes
Disconnect the power supply
Compressor wiring is not properly
YesNormal
Yes
Yes
Yes
No
No
No
No
L9 protection
The compressor has less than 12 hours preheating before initial operating
Ensure enough preheating timeYes
V6 VRF 50Hz
106
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Compressor replacement procedure 2.15.12
Step 1: Remove faulty compressor and remove oil
Remove the faulty compressor from the outdoor unit.
Before removing the oil, shake the compressor so as to not allow
impurities to remain settled at the bottom.
Drain the oil out of the compressor and retain it for inspection.
Normally the oil can be drained out from the compressor discharge
pipe.
Step 2: Inspect oil from faulty compressor
The oil should be clear and transparent. Slightly yellow oil is not an indication of any problems. However, if the oil is
dark, black or contains impurities, the system has problems and the oil needs to be changed. Refer to Figure 5-4.16
for further details regarding inspecting compressor oil. (If the compressor oil has been spoiled, the compressor will
not be being lubricated effectively. The scroll plate, crankshaft and bearings will wear. Abrasion will lead to a larger
load and higher current. More electric energy will get dissipated as heat and the temperature of the motor will
become increasingly high. Finally, compressor damage or burnout will result.)
Step 3: Check oil in other compressors in the system
If the oil drained from the faulty compressor is clean, go to Step 6.
If the oil drained from the faulty compressor is only lightly spoiled, go to Step 4.
If the oil drained from the faulty compressor is heavily spoiled, check the oil in the other compressors in the system.
Drain the oil from any compressors where the oil has been spoiled. Go to Step 4.
Step 4: Replace oil separator(s) and accumulator(s)
If the oil from a compressor is spoiled (lightly or heavily), drain the oil from the oil separator and accumulator in that
unit and then replace them.
Step 5: Check filters(s)
If the oil from a compressor is spoiled (lightly or heavily), check the filter between the gas stop valve and the 4-way
valve in that unit. If it is blocked, clean with nitrogen or replace.
Step 6: Replace the faulty compressor and re-fit the other compressors
Replace the faulty compressor.
If the oil had been spoiled and was drained from the non-faulty compressors
in Step 3, use clean oil to clean them before re-fitting them into the units. To
clean, add oil into the compressor through the discharge pipe using a funnel,
shake the compressor, and then drain the oil. Repeat several times and then
re-fit the compressors into the units. (The discharge pipe is connected to the
oil pool of the compressor by the inner oil balance pipe.)
Step 7: Add compressor oil
Add 1.2L of oil to the new compressor through the discharge pipe, using a
funnel.
Add 1.2L of oil to each of the compressors from which oil was drained in Step 3.
Only use FV68H oil. Different compressors require different types of oil. Using the wrong type of oil leads to various
problems.
Add additional oil to the accumulators such that the total amount of oil is 5L in 8-12HP units, 6L in 14-16HP units 7L in
18-22HP units, 9L in 24-28HP units and 10L in 30-32HP units.
Figure 6-2.8: Draining oil from a compressor
Figure 6-2.9: Compressor piping
Discharge pipe
Inner oilbalance
pipe
V6 VRF 50Hz
107
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Step 8: Vacuum drying and refrigerant charging
Once all the compressors and other components have been fully connected, vacuum dry the system and recharge
refrigerant. Refer to the V6 Engineering Data Book, Part 3.
Figure 6-2.10: Inspecting compressor oil
This oil is black
- it has been
carbonized
This oil is a little
yellow, but is clear
and transparent and
the condition is
acceptable
This oil is still
transparent but there
are impurities which
may clog the filter Cloudy or gray
oil indicates
abnormal
system
operation This oil contains
particles of copper
V6 VRF 50Hz
108
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Figure 6-2.11: Effects of spoiled compressor oil
Worn scroll plate
Worn scroll plate
Normal compressor
bearings
Seriously worn and
damaged bearings
Filter blocked by impurities,
which leads to abnormal
compressor suction
Worn crankshaft
V6 VRF 50Hz
109
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.16 H7: Unmatched total number of indoor units
Digital display output 2.16.1
Description 2.16.2
Number of indoor units detected by master unit not same as number set on main PCB.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition 2.16.3
Trigger condition: Only one indoor unit cannot be detected by master unit for 8 hours or more than one indoor unit
cannot be detected by master unit for 3 minutes.
Recover condition: Number of indoor units detected by master unit is same as number set on main PCB.
Reset method: Resume automatically.
Possible causes 2.16.4
Number of indoor units set on main PCB not same as actual number of indoor units.
Some indoor units are powered off.
Communication wires between indoor and outdoor units not connected properly.
Indoor unit PCB damaged.
Indoor unit without address or indoor unit address duplicated.
Main PCB damaged.
V6 VRF 50Hz
110
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Procedure 2.16.5
H7
Number of indoor units set on main PCB
not same as actual number of indoor
units1
Yes Change the setting on the PCB to be the
same as the actual number of indoor
units
No
Some indoor units are powered off Yes Power on all indoor units
No
After re-starting the ODUs and IDUs and
then waiting 2 minutes, an IDU displays
an E1 or FE error2
Yes Refer to indoor unit troubleshooting
guide. Resolving the indoor unit error
resolves the outdoor unit error
No
Two or more indoor units are assigned
the same address3 No
Yes
Setting the indoor units’ addresses
uniquely resolves the error No Replace outdoor main PCB
Notes:
1. The number of indoor units can be set on switches EN3 and S12 on the main PCB. 2. Indoor unit error code E1 indicates a communication error between indoor and master unit. Indoor unit error code FE indicates that an indoor unit has not
been assigned an address. 3. Indoor unit addresses can be checked and manually assigned using indoor unit remote/wired controllers. Alternatively, indoor unit addresses can be
automatically assigned by the master outdoor unit.
V6 VRF 50Hz
111
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.17 H8: High pressure sensor error
Digital display output 2.17.1
Description 2.17.2
High pressure sensor error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.17.3
Trigger condition: Discharge pressure ≤ 0.3MPa.
Recover condition: Discharge pressure > 0.3MPa.
Reset method: Resume automatically.
Possible causes 2.17.4
Outdoor unit stop valves are closed.
Pressure sensor not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.
V6 VRF 50Hz
112
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Procedure 2.17.5
H8
ODU stop valves are closed Yes Open the stop valves
No
High pressure sensor connection on main
PCB is loose1 Yes Ensure the sensor is connected properly
No
High pressure sensor has short-circuited
or failed2 Yes Replace the sensor
No
Insufficient refrigerant caused by
refrigerant leakage3 Yes Add refrigerant and inspect system for
leaks
No
The low pressure side is blocked, caused
by crushed or bent pipe, closed EXV or
dirty filter4
Yes Inspect the system and fix the error. If the
filter is blocked by ice, the piping should
be cleaned
No
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Replace the outdoor main PCB
Notes:
1. High pressure sensor connection is port CN17 on the main PCB (labeled 7 in Figure 5-2.1 in Part 5, 2.1 “Ports”). 2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed.
3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”. 4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and
6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 5. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
V6 VRF 50Hz
113
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.18 yHd: Slave unit malfunction
Digital display output 2.18.1
In the error code, 'y' is a placeholder for the address (1, 2 or 3) of the slave unit with the error.
Description 2.18.2
1Hd indicates an error on the slave unit with address 1.
2Hd indicates an error on the slave unit with address 2.
3Hd indicates an error on the slave unit with address 3.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition 2.18.3
Trigger condition: Slave unit is malfunction.
Recover condition: Slave unit goes back to normal.
Reset method: Resume automatically.
Possible causes 2.18.4
Slave unit malfunction.
V6 VRF 50Hz
114
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Procedure 2.18.5
yHd
Check relevant slave unit
V6 VRF 50Hz
115
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.19 P1: Discharge pipe high pressure protection
Digital display output 2.19.1
Description 2.19.2
Discharge pipe high pressure protection. If the system has a 3-phase protector and the 3-phase protector is connected
with the high pressure switch, the system will display P1 protection when initially powered on, and P1 protection will
disappear once the system reaches a steady state.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.19.3
Trigger condition: Discharge pressure ≥ 4.4MPa.
Recover condition: Discharge pressure ≤ 3.2MPa.
Reset method: Resume automatically.
Possible causes 2.19.4
Outdoor unit stop valves are closed.
Pressure sensor/switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.
Procedure 2.19.5
P1
ODU stop valves are closed Yes Open the stop valves
No
High pressure sensor connection on main
PCB is loose1 Yes Ensure the sensor is connected properly
No
High pressure sensor has short-circuited
or failed2 Yes Replace the sensor
No
Flowchart continued on next page …
V6 VRF 50Hz
116
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
… flowchart continued from previous page
Excess refrigerant3 Yes Discharge part of the refrigerant. Add oil
if it leaks during discharge
No
System contains air or nitrogen4 Yes Flush all refrigerant then vacuum the
system and recharge the refrigerant. Add
oil to the system if it leaks
No
The high pressure side is blocked, caused
by crushed or bent pipe or blocked EXV5 Yes Inspect the system and fix the error
No
The condenser heat exchange is poor6 Yes Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1. The high pressure sensor connection is port CN17 on the main PCB (labeled 7 in Figure 5-2.1 in Part 5, 2.1 “Ports”). 2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed. 3. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to be lower than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
V6 VRF 50Hz
117
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.20 P2, H5: Suction pipe low pressure protection
Digital display output 2.20.1
Description 2.20.2
Suction pipe low pressure protection. If the system has a 3-phase protector and the 3-phase protector is connected to
the low pressure switch, the system will display P2 protection when initially powered on, and P2 protection will
disappear once the system reaches a steady state.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.20.3
Trigger condition:
For P2 protection: Suction pressure ≤ 0.05MPa.
For H5 protection: P2 protection appears three times in 60 minutes.
Recover condition: Suction pressure ≥ 0.15MPa.
Reset method:
For P2 protection: Resume automatically.
For H5 protection: Manually restart.
Possible causes 2.20.4
Outdoor unit stop valves are closed.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.
V6 VRF 50Hz
118
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Procedure 2.20.5
P2 / H5
ODU stop valves are closed Yes Open the stop valves
No
Insufficient refrigerant caused by
refrigerant leakage1 Yes Add refrigerant or inspect the system for
leaks
No
The low pressure side is blocked, caused
by crushed or bent pipe, blocked EXV, or
dirty filter2
Yes Inspect the system and fix the error. If the
filter is blocked by ice, the piping should
be cleaned
No
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”. 2. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and
6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 3. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
V6 VRF 50Hz
119
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.21 xP3: Compressor current protection
Digital display output 2.21.1
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
Description 2.21.2
1P3 indicates current protection on compressor A; 2P3 indicates current protection on compressor B.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.21.3
Trigger condition: Current of compressor AA55PHDG –D1YG ≥ 24.6A or DC80PHDG –D1YG ≥ 33A.
Recover condition: Current of compressor AA55PHDG –D1YG < 24.6A or DC80PHDG –D1YG < 33A.
Reset method: Resume automatically.
Possible causes 2.21.4
Outdoor unit stop valves are closed.
Indoor load too large.
Power supply abnormal.
Sudden interruption of power to IDUs.
Excess refrigerant.
System contains air or nitrogen.
Poor condenser heat exchange.
High pressure side blockage.
Inverter module damaged.
Compressor damaged.
Main PCB damaged.
Procedure 2.21.5
xP3
ODU stop valves are closed Yes Open the stop valves
No
The indoor load is too large1 Yes Make sure the combination ratio is less
than 130%
No
The power supply is abnormal Yes Check the power supply equipment
No
Sudden interruption of power to IDUs Yes Inspect the system and fix the error
No Flowchart continued on next page …
V6 VRF 50Hz
120
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
… flowchart continued from previous page
Excess refrigerant2 Yes Discharge part of the refrigerant. Add oil
if it leaks during discharge
No
System contains air or nitrogen3 Yes Flush all refrigerant then vacuum the
system and recharge refrigerant. Add oil
to the system if it leaks
No
The condenser heat exchange is poor4 Yes Inspect the system and fix the error
No
The high pressure side is blocked, caused
by crushed or bent pipe or blocked EXV5 Yes Inspect the system and fix the error
No
Inverter module has short-circuited6 Yes Replace the inverter module
No
Compressor has malfunctioned7 Yes Replace the compressor
No
Replace outdoor main PCB
Notes:
1. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
2. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 3. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 4. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to be lower than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. Set a multi-meter to buzzer mode and test any two terminals of P N U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited. 7. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
V6 VRF 50Hz
121
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.22 P4, H6: Discharge temperature protection
Digital display output 2.22.1
;
Description 2.22.2
Discharge temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.22.3
Trigger condition:
For P4 protection: Discharge temperature (T7C1/2) ≥ 120oC.
For H6 protection: P4 protection appears three times in 100 minutes.
Recover condition: Discharge temperature (T7C1/2) ≤ 90 oC.
Reset method:
For P4 protection: Resume automatically.
For H6 protection: Manually restart.
Possible causes 2.22.4
Outdoor unit stop valves are closed.
Temperature sensor/switch not connected
properly or has malfunctioned.
Insufficient refrigerant.
System blockage.
Indoor load too large.
System contains air or nitrogen.
Poor condenser heat exchange.
Main PCB damaged.
Procedure 2.22.5
P4 / H6
ODU stop valves are closed Yes Open the stop valves
No
Compressor top temperature sensor,
discharge pipe temperature sensor
and/or discharge temperature switch
connections on main PCB are loose1
Yes Ensure the sensors and switch are
connected properly
No
Compressor top temperature sensor
and/or discharge pipe temperature
sensor have short circuited or failed2
Yes Replace the faulty sensor(s)
No Flowchart continued on next page …
… flowchart continued from previous page
V6 VRF 50Hz
122
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Insufficient refrigerant caused by
refrigerant leakage3 Yes Add refrigerant and inspect the system
for leaks
No
The system is blocked, caused by crushed
or bent pipe, blocked EXV or dirty filter4 Yes
Inspect the system and fix the error. If the
filter is blocked by ice, the piping should
be cleaned
No
The indoor load is too large5 Yes Make sure the combination ratio is less
than 130%
No
System contains air or nitrogen6 Yes Flush all refrigerant then vacuum the
system and recharge refrigerant. Add oil
to the system if it leaks
No
The condenser heat exchange is poor7 Yes Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”). The discharge temperature switch connection is port CN19 on the main PCB (labeled 2 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”. 3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4
and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 6. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 7. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
V6 VRF 50Hz
123
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.23 P5: Outdoor heat exchanger temperature protection
Digital display output 2.23.1
Description 2.23.2
Outdoor heat exchanger temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.23.3
Trigger condition: Outdoor heat exchanger temperature (T3) ≥ 65oC.
Recover condition: Outdoor heat exchanger temperature (T3) < 55 oC.
Reset method: Resume automatically.
Possible causes 2.23.4
Outdoor unit stop valves are closed.
Temperature sensor not connected properly or has malfunctioned.
Indoor load too large.
System contains air or nitrogen.
Poor condenser heat exchange.
High pressure side blockage.
Main PCB damaged.
V6 VRF 50Hz
124
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Procedure 2.23.5
P5
ODU stop valves are closed Yes Open the stop valves
No
Outdoor heat exchanger temperature
sensor connection on main PCB is loose1 Yes Ensure the sensor is connected properly
No
Outdoor heat exchanger temperature
sensor has short-circuited or failed2 Yes Replace the sensor
No
The indoor load is too large3 Yes Make sure the combination ratio is less
than 130%
No
System contains air or nitrogen4 Yes Flush all refrigerant then vacuum the
system and recharge the refrigerant. Add
oil to the system if it leaks
No
The condenser heat exchange is poor5 Yes Inspect the system and fix the error
No
The high pressure side is blocked, caused
by crushed or bent pipe or blocked EXV6 Yes Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1. Outdoor heat exchanger temperature sensor connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”
3. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4
and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 5. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
6. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to be lower than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
V6 VRF 50Hz
125
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.24 P9, H9: Fan module protection
Digital display output 2.24.1
;
Description 2.24.2
Fan module protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.24.3
Trigger condition:
For P9 protection: Fan speed is too low.
For H9 protection: P9 protection appears ten times in 120 minutes.
Recover condition: Fan speed go back to normal.
Reset method:
For P9 protection: Resume automatically; For H9 protection: Manually restart.
Possible causes 2.24.4
Switch ENC2 incorrectly set.
Power or communication wires not connected properly.
Fan motor blocked or has failed.
Power supply abnormal.
AC filter board damaged.
Fan module damaged.
Main PCB damaged.
Procedure 2.24.5
P9 / H9
The capacity set on switch ENC2 on the
main PCB and the capacity given on the
unit’s nameplate do not match
Ensure the setting on switch ENC2
matches the unit capacity given on the
unit’s nameplate
No
Some power wires or communication
wires of fan module are not connected
properly
Yes Ensure power and communication wires
are connected properly
No
The fan motor is blocked or has failed Yes Remove obstruction or replace the fan
motor
No Flowchart continued on next page …
V6 VRF 50Hz
126
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
… flowchart continued from previous page
The power supply is abnormal Yes Check the power supply equipment
No
Voltage between P and N on fan module
is abnormal1 Yes Replace AC filter board
No
Replacing the fan module resolves the
error
No
Replace outdoor main PCB
Notes:
1. The normal voltage between P and N on the fan module is 310V DC.
Figure 6-2.12: Fan module P N terminals
V6 VRF 50Hz
127
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.25 PL, C7: Inverter module temperature protection
Digital display output 2.25.1
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
Description 2.25.2
1PL indicates inverter module A temperature protection.
2PL indicates inverter module B temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.25.3
Trigger condition:
For PL protection: Inverter module heat sink temperature (TF1/2) ≥ 80oC.
For C7 protection: PL protection appears three times in 100 minutes.
Recover condition: Inverter module heat sink temperature (TF1/2) < 65oC
Reset method:
For PL protection: Resume automatically.
For C7 protection: Manually restart.
Possible causes 2.25.4
Blocked, dirty or loose heat sink.
Temperature sensor not connected properly or has malfunctioned.
Main PCB damaged.
V6 VRF 50Hz
128
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Procedure 2.25.5
PL / C7
The inverter module heat sink is blocked
or dirty Yes Clean or replace the heat sink
No
The screws connecting the heat sink to
the inverter module are loose Yes Tighten the screws and make sure the
heat sink is well-connected
No
Inverter module temperature sensor
connection on main PCB is loose1 Yes Ensure the sensor is connected properly
No
Inverter module temperature sensor has
short circuited or failed2 Yes Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Inverter module temperature sensor connection is port CN3 and CN3_1 on the main PCB (labeled 5 and 6, respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance characteristics table, the sensor has failed. Refer to Table 6-3.3 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
V6 VRF 50Hz
129
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
2.26 PP: Compressor discharge insufficient superheat protection
Digital display output 2.26.1
Description 2.26.2
Compressor discharge insufficient superheat protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.26.3
Trigger condition: Discharge gas superheat is ≤ 0oC for 20 minutes or ≤ 5oC for 60 minutes.
Recover condition: Discharge gas superheat go back to normal value.
Reset method: Resume automatically.
Possible causes 2.26.4
Temperature sensor not connected properly or has malfunctioned.
Poor temperature sensor heat insulation.
Excess refrigerant.
Discharge pressure too high.
Main PCB damaged.
V6 VRF 50Hz
130
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Procedure 2.26.5
PP
Compressor top temperature sensor
and/or discharge pipe temperature
sensor connections on main PCB are
loose1
Yes Ensure the sensors are connected
properly
No
Compressor top temperature sensor
and/or discharge pipe temperature
sensor have short circuited or failed2
Yes Replace the faulty sensor(s)
No
Poor heat insulation of compressor top
temperature sensor resulting in
temperature reading lower than actual
temperature
Yes Ensure sufficient heat insulation for
compressor top temperature senor
No
Excess refrigerant3 Yes Discharge part of the refrigerant. Add oil
if it leaks during discharge
No
Discharge pressure is too high Yes Troubleshoot as for a P1 error4
No
Replace outdoor main PCB
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4, respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
3. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 4. See “P1 Troubleshooting”.
V6 VRF 50Hz
131
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
3 Appendix to Part 6
3.1 Temperature Sensor Resistance Characteristics Table 6-3.1: Outdoor ambient temperature sensor and outdoor heat exchanger temperature sensor resistance characteristics
Temperature
(°C)
Resistance
(kΩ)
Temperature
(°C)
Resistance
(kΩ)
Temperature
(°C)
Resistance
(kΩ)
Temperature
(°C)
Resistance
(kΩ)
-20 115.3 20 12.64 60 2.358 100 0.6297
-19 108.1 21 12.06 61 2.272 101 0.6115
-18 101.5 22 11.50 62 2.191 102 0.5939
-17 96.34 23 10.97 63 2.112 103 0.5768
-16 89.59 24 10.47 64 2.037 104 0.5604
-15 84.22 25 10.00 65 1.965 105 0.5445
-14 79.31 26 9.551 66 1.896 106 0.5291
-13 74.54 27 9.124 67 1.830 107 0.5143
-12 70.17 28 8.720 68 1.766 108 0.4999
-11 66.09 29 8.336 69 1.705 109 0.4860
-10 62.28 30 7.971 70 1.647 110 0.4726
-9 58.71 31 7.624 71 1.591 111 0.4596
-8 56.37 32 7.295 72 1.537 112 0.4470
-7 52.24 33 6.981 73 1.485 113 0.4348
-6 49.32 34 6.684 74 1.435 114 0.4230
-5 46.57 35 6.400 75 1.387 115 0.4116
-4 44.00 36 6.131 76 1.341 116 0.4006
-3 41.59 37 5.874 77 1.291 117 0.3899
-2 39.82 38 5.630 78 1.254 118 0.3796
-1 37.20 39 5.397 79 1.2133 119 0.3695
0 35.20 40 5.175 80 1.174 120 0.3598
1 33.33 41 4.964 81 1.136 121 0.3504
2 31.56 42 4.763 82 1.100 122 0.3413
3 29.91 43 4.571 83 1.064 123 0.3325
4 28.35 44 4.387 84 1.031 124 0.3239
5 26.88 45 4.213 85 0.9982 125 0.3156
6 25.50 46 4.046 86 0.9668 126 0.3075
7 24.19 47 3.887 87 0.9366 127 0.2997
8 22.57 48 3.735 88 0.9075 128 0.2922
9 21.81 49 3.590 89 0.8795 129 0.2848
10 20.72 50 3.451 90 0.8525 130 0.2777
11 19.69 51 3.318 91 0.8264 131 0.2708
12 18.72 52 3.192 92 0.8013 132 0.2641
13 17.80 53 3.071 93 0.7771 133 0.2576
14 16.93 54 2.959 94 0.7537 134 0.2513
15 16.12 55 2.844 95 0.7312 135 0.2451
16 15.34 56 2.738 96 0.7094 136 0.2392
17 14.62 57 2.637 97 0.6884 137 0.2334
18 13.92 58 2.540 98 0.6682 138 0.2278
19 13.26 59 2.447 99 0.6486 139 0.2223
V6 VRF 50Hz
132
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
Table 6-3.2: Compressor top temperature sensor and discharge pipe temperature sensor resistance characteristics
Temperature
(°C)
Resistance (kΩ)
Temperature
(°C)
Resistance (kΩ)
Temperature
(°C)
Resistance (kΩ)
Temperature
(°C)
Resistance (kΩ)
-20 542.7 20 68.66 60 13.59 100 3.702
-19 511.9 21 65.62 61 13.11 101 3.595
-18 483.0 22 62.73 62 12.65 102 3.492
-17 455.9 23 59.98 63 12.21 103 3.392
-16 430.5 24 57.37 64 11.79 104 3.296
-15 406.7 25 54.89 65 11.38 105 3.203
-14 384.3 26 52.53 66 10.99 106 3.113
-13 363.3 27 50.28 67 10.61 107 3.025
-12 343.6 28 48.14 68 10.25 108 2.941
-11 325.1 29 46.11 69 9.902 109 2.860
-10 307.7 30 44.17 70 9.569 110 2.781
-9 291.3 31 42.33 71 9.248 111 2.704
-8 275.9 32 40.57 72 8.940 112 2.630
-7 261.4 33 38.89 73 8.643 113 2.559
-6 247.8 34 37.30 74 8.358 114 2.489
-5 234.9 35 35.78 75 8.084 115 2.422
-4 222.8 36 34.32 76 7.820 116 2.357
-3 211.4 37 32.94 77 7.566 117 2.294
-2 200.7 38 31.62 78 7.321 118 2.233
-1 190.5 39 30.36 79 7.086 119 2.174
0 180.9 40 29.15 80 6.859 120 2.117
1 171.9 41 28.00 81 6.641 121 2.061
2 163.3 42 26.90 82 6.430 122 2.007
3 155.2 43 25.86 83 6.228 123 1.955
4 147.6 44 24.85 84 6.033 124 1.905
5 140.4 45 23.89 85 5.844 125 1.856
6 133.5 46 22.89 86 5.663 126 1.808
7 127.1 47 22.10 87 5.488 127 1.762
8 121.0 48 21.26 88 5.320 128 1.717
9 115.2 49 20.46 89 5.157 129 1.674
10 109.8 50 19.69 90 5.000 130 1.632
11 104.6 51 18.96 91 4.849
12 99.69 52 18.26 92 4.703
13 95.05 53 17.58 93 4.562
14 90.66 54 16.94 94 4.426
15 86.49 55 16.32 95 4.294
16 82.54 56 15.73 96 4.167
17 78.79 57 15.16 97 4.045
18 75.24 58 14.62 98 3.927
19 71.86 59 14.09 99 3.812
V6 VRF 50Hz
133
Part 6
- Diagn
osis an
d Tro
ub
lesh
oo
ting
Table 6-3.3: Inverter module temperature sensor resistance characteristics
Temperature
(°C)
Resistance (kΩ)
Temperature
(°C)
Resistance (kΩ)
Temperature
(°C)
Resistance (kΩ)
Temperature
(°C)
Resistance (kΩ)
-30 971.4 10 109.0 50 19.70 90 5.000
-29 912.8 11 103.9 51 18.97 91 4.855
-28 858.2 12 99.02 52 18.26 92 4.705
-27 807.3 13 94.44 53 17.59 93 4.566
-26 759.7 14 90.11 54 16.94 94 4.431
-25 715.3 15 86.00 55 16.32 95 4.301
-24 673.6 16 82.09 56 15.73 96 4.176
-23 634.7 17 78.38 57 15.16 97 4.055
-22 598.2 18 74.87 58 14.62 98 3.938
-21 564.1 19 71.53 59 14.10 99 3.825
-20 532.2 20 68.36 60 13.60 100 3.716
-19 502.2 21 65.34 61 13.12 101 3.613
-18 474.1 22 62.47 62 12.65 102 3.514
-17 447.7 23 59.75 63 12.22 103 3.418
-16 423.0 24 57.17 64 11.79 104 3.326
-15 399.8 25 54.71 65 11.39 105 3.235
-14 378.0 26 52.36 66 10.99 106 3.148
-13 357.5 27 50.13 67 10.62 107 3.063
-12 338.2 28 48.01 68 10.25 108 2.982
-11 320.1 29 45.99 69 9.909 109 2.902
-10 303.1 30 44.07 70 9.576 110 2.826
-9 287.1 31 42.23 71 9.253 111 2.747
-8 272.0 32 40.48 72 8.947 112 2.672
-7 257.8 33 38.81 73 8.646 113 2.599
-6 244.4 34 37.23 74 8.362 114 2.528
-5 231.9 35 35.71 75 8.089 115 2.460
-4 220.0 36 34.27 76 7.821 116 2.390
-3 208.7 37 32.89 77 7.569 117 2.322
-2 198.2 38 31.58 78 7.323 118 2.256
-1 188.2 39 30.33 79 7.088 119 2.193
0 178.8 40 29.13 80 6.858 120 2.132
1 169.9 41 27.98 81 6.640 121 2.073
2 161.5 42 26.89 82 6.432 122 2.017
3 153.6 43 25.85 83 6.230 123 1.962
4 146.1 44 24.85 84 6.033 124 1.910
5 139.1 45 23.90 85 5.847 125 1.859
6 132.3 46 22.98 86 5.667
7 126.0 47 22.10 87 5.492
8 120.0 48 21.26 88 5.322
9 114.3 49 20.47 89 5.159
V6 VRF 50Hz
134
Mid
ea
V6
Se
rie
s Se
rvic
e M
anu
al
3.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 5-5.4 and 5-5.5 should be observed:
The master outdoor unit can detect all the indoor units.
The number of indoor units displayed on DSP2 is steady and is equal to the actual number of indoor units installed.
All stop valves are open and all indoor unit EXVs are connected to their unit’s PCB.
If the combination ratio is 100% or less, all the indoor units are currently running and if the combination ratio is more
than 100%, indoor units with total capacity equal to the total capacity of the outdoor units are currently running.
If the outdoor ambient temperature is high, the system is being run in cooling mode with the following settings:
temperature 17°C; fan speed high.
If the outdoor ambient temperature is low, the system is being run in heating mode with the following settings:
temperature 30°C; fan speed high.
The system has been running normally for more than 30 minutes.
Table 6-3.4: Outdoor unit cooling mode operating parameters
Outdoor ambient temperature °C < 10 10 to 26 26 to 31 31 to 41 > 41
Average discharge temperature °C 60-76 62-78 65-82 67-92 69-92
Average discharge superheat °C 17-30 17-33 17-34 17-36 10-32
Discharge pressure MPa 2.3-2.8 2.3-2.8 2.4-3.6 2.6-3.8 3.1-4.2
Suction pressure MPa 0.6-0.7 0.7-0.9 0.8-1.0 1.0-1.2 1.2-1.4
DC inverter compressor current A 9-20 11-22 12-25 15-29 20-26
Table 6-3.5: Outdoor unit heating mode operating parameters
Outdoor ambient temperature °C < -10 -10 to 0 0 to 5 5 to 10 10 to 17 > 17
Average discharge temperature °C 56-74 57-76 58-78 61-82 63-82 63-82
Average discharge superheat °C 17-35 17-35 17-35 17-33 14-33 14-33
Discharge pressure MPa 1.7-2.4 1.8-2.5 1.9-3.0 2.2-3.2 2.3-3.2 2.3-3.2
Suction pressure MPa 1.4-1.6 1.5-1.7 1.6-2.2 1.8-2.6 1.8-2.6 2.0-2.4
DC inverter compressor current A 11-25 13-27 12-28 11-28 11-25 15-20
Ver. 2017-12
Commercial Air Conditioner Division
Midea Group
Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan,
Guangdong, China
Postal code: 528311
Tel: +86-757-26338346
Fax: +86-757-22390205
cac.midea.com / global.midea.com
Note: Product specifications change from time to time as product improvements
and developments are released and may vary from those in this document.
Midea CAC After-service Application
Midea CAC News Application
iOS Android iOS