    SCADAPackSmart RTUs that combine the monitoring and

    communications capabilities of remote terminal units

    (RTU) with the processing and data-logging power of

    programmable logic controllers (PLC), providing superior

    functionality wherever remote processes require

    automatic supervision and autonomous control.

    SCADAPack Smart RTUs are the foundation for a range of

    solutions offering specific software and configuration

    tools to enhance performance in oil and gas and water/wastewater applications.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    3/54

    • Modbus core database, DNP3 level 2 layer, optional DF1 support

    • Programming and conguration: TelePACE Studio, IEC61131-3, C/C++

    SCADAPack 100, 300, 32

    314 330 334 350 357 32P 32 P4 32 P4A 32 P4B 100

     Analog Inputs

    On-board1 8: 0-20mA,4-20mA 

    0-5V 0-10V 

    n/a 8: 0-20mA,4-20mA 

    0-5V 0-10V 

    5: 0-10V,0-20mA 

    1: 0-32.7VDC

    5: 0-10V,0-20mA 

    1: 0-32.7VDC8: 0-20mA,

    4-20mA 0-10V 

    0-5V 

    n/a 8: 0-20/4-20mA 

    or 0-5/1-5V 

    8: 0-20mA/ 0-10V 

    1: 0-32.768V 

    8: 0-20/4-20mA 

    0-5/0-10V 

    3: 0-20/4-20mA 

    0-5/1-5 VDC1: 0-32.7

     VDC

     Analog Outputs

    On-board1 2: 0-20mA 4-20mA Optional

    n/a 2: 0-20mA  4-20mA Optional

    2 or 4:0-20mA 4-20mA Optional

    n/a 2: 0-20mA  4-20mA Optional

    n/a

    Digital Inputs

    On-board1 16: 12/24V 48V 

    115/125V 240V 

    n/a 16: 12/24V  48V 

    115/125V 240V 

    8: Drycontact,

    Shared withoutput points.

    8: Drycontact,

    shared withoutput points32: (12/24V,

    48V,115/125V,

    240V)

    3: 24VAC/30VDC,

    shared withCounterinputs1: 30V

    interrupt

    3: 24VAC/30VDC,

    shared withCounterinputs1: 30V

    interrupt16:

    12-24/120/220V-VAC

    3: 24VAC/30VDC,

    shared withCounterinputs1: 30V

    interrupt32: drycontact

    Shared withoutputs

    3: 24VAC/30VDC

    Shared withCounterinputs,1: 30V

    interrupt input32: 12/24V,

    48V,115/125V,

    240V 

    6: selectableas input or

    output

    Digital Outputs

    On-board1 10: drycontact or

    10:solid-state

    n/a 10: drycontact

    or solid-state

    8: open drain,Shared withinput points.

    8: open drain,Shared withinput points.

    16: drycontact

    1: ControllerStatus Output

    1: ControllerStatus Output

    12: Drycontact

    1: ControllerStatus Output

    32: drycontact

    Shared withinputs

    1: ControllerStatus Output

    16: Drycontact

    6: selectableas input or

    output

    Frequency Inputs

    On-board1 1: 0-10Hz or 0-5kHz (dry contact) 3: 0-5 kHz shared with digital inputs, 1: 0-500Hz, interrupt input 1: 0-6 kHzturbine

    or dry contact

    General

     TurbineInputs

    2: 0-10kHz (turbine or dry contact) n/a 1

    Serial Ports 2: RS232/  RS485

    2: RS232/RS4851: RS232

    1: RS485, 1: RS232/RS485,1: RS232

    2: RS2321: RS232/ 

    RS485

    3: RS232, 1: RS232/RS485 2: RS2321: RS232/ 

    RS485

    1: RS2321: RS232/ 

    RS485

    USB Ports 1: Peripheral 1: Host, 1: Peripheral n/a

    EthernetPorts

    n/a 1, 10/100BaseT 1: 10BaseT n/a

    EFM FlowRuns

    4 10 1

    ProgrammingSoftware

     TP Studio, IEC61131-3, C++ TP Studio,IEC61131, C

    Modbus Master and Slave: Modbus RTU, Modbus ASCII, Modbus/TCP, Modbus UDP

    DNP3 Level 2 Slave

    1 Number of on-board I/O may be further expanded for any SCADAPack using Expansion I/O Modules.

    Refer to individual product data sheets for detailed specifications.

    02

    Selection Guide

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    4/54

    03

    Contents

    SCADAPack Smart RTU

    SCADAPack 314

      Specifications ............................................................................................. 4

      Model Code ............................................................................................... 5

    SCADAPack 330 | 334

      Specifications 330 ...................................................................................... 6

      Specifications 334 ...................................................................................... 7

      Model Code ............................................................................................... 8

    SCADAPack 350 | 357

      Specifications 350 .................................................................................... 10

      Specifications 357 .................................................................................... 11

      Model Code ............................................................................................. 12

    SCADAPack 32

      Specifications P4A ................................................................................... 14  Specifications P4 ...................................................................................... 15

      Specifications P4B ................................................................................... 16

      Model Code ............................................................................................. 17

    SCADAPack 100

      Specifications ........................................................................................... 18

      Model Code ............................................................................................. 19

    I/O Expansion Modules*

     Analog Input Modules

      5502 - Differential analog input module ..................................................... 20

      5504 - Thermocouple input module ......................................................... 21

      5505 - RTD input module ......................................................................... 22

      5506 - Analog input module ..................................................................... 23

     Analog Output Modules

      5302 - Analog output module ................................................................... 24

      5304 - Analog output module ................................................................... 25

    Digital Input Modules

      5403 - High level digital input module ....................................................... 26

      5404 - High level digital input module ....................................................... 27

      5405 - Digital input module ...................................................................... 28

      5410 - High speed counter/accumulator .................................................. 29

      5414 - Compact digital input module ....................................................... 30

    Digital I/O Modules  5401 - Configurable digital I/O module ..................................................... 31

      5402 - Configurable digital input or output module ................................... 32

    Digital Output Modules

      5406A - Dry contact relay out module ...................................................... 33

      5407 - Dry contact relay out module ........................................................ 34

      5408 - Triac digital output module .............................................................35

      5409 - FET digital output module ............................................................. 36

      5411 - Digital output module .................................................................... 37

      5415 - Compact relay digital output module ............................................. 38

    Combination I/O Modules

      5606 - Analog/digital I/O module .............................................................. 39

      5607 - Analog/digital I/O module .............................................................. 40

    I/O Simulator Modules

      5421 - Toggle switch digital input module ................................................. 41

      5521 - Potentiometer input module .......................................................... 42

    UPS Power Supply

    5103 - Uninterruptible Power Supply ........................................................ 43

    Non-Programmable Controller Modules

      5201 - RS-485 communication controller ................................................. 44

      5202 - RS-232 communication controller ................................................. 45

    Communication Modules

    Modems, Interface Modules & Gateways5901 - Dial-up modem ............................................................................. 46

      5902 - Bell 202 radio or leased line modem ............................................. 47

      5904 - HART interface module ..................................................................48

      5908 - Wireless data transceiver .............................................................. 49

      5908-WO2 - Wireless data transceiver ..................................................... 50

      5910 - Ethernet switch ............................................................................. 51

      5915 - SDI-12 interface module ............................................................... 52

    * IO Expansion Module Compatibility Notes:

     The SCADAPack 100 does not support IO Expansion modules.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    5/54

    P314: 5212 controller board and integrated 56O7 I/O board

    Controller

    Processors   • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer

    • Microcontroller co-processor, 20 MHz clock

    Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

    Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power

    Datalog Capacity 465k words

    I/O

     Analog Inputs • 8 software congurable: 0-20/4-20mA / 0-5/0-10V (15-bit)• 3 internal: measure incoming power supply voltage for solar applications, battery voltage, and controller temperature

     Analog Outputs • Standard: None• 2 with optional 5305 on 5607 I/O board: 0-20/4-20mA (12-bit)

    Digi tal I/O • 16 digi tal inputs: 12/24V, 48V, 115/125V, 240V• 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive),

    DC solid state rating: 3A, 60 VDC

    Counter Inputs • 1 dry contact: 0-10Hz or 0-5kHz

    • 2 turbine or dry contact: 0-10kHz

    Communications

    Serial Ports COM1, COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half-duplex, or• RS-485 port, 2-wire, half-duplex

    Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1

    Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward

    USB Peripheral Port USB 2.0 compliant B-type receptacle

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2

    General

    I/O Terminations 5, 6, and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts

    Dimensions 5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep

    Packaging Corrosion resistant, zinc-plated steel with black enamel paint

    Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power

    5212 Controller Board • 11 - 30VDC, 30mW at 12V during sleep mode.• 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, and USB disabled• 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, USB disabled• Add 190mW when enabling the USB port• Add 30 to 90mW when enabling the LEDs• 8.5W at 24V maximum, 5V supply fully-loaded

    5607 I/O Module • 11 - 30VDC, 10.3mA plus analog outputs• 235mA (max.) at 5V required from 5212 controller board

    Warranty 3 years on parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations

    Hazardous LocationsEurope

     ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

    Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2). Does not include Wireless versions.

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    Product Data Sheet SCADAPack 314Specications

    04

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    6/54

    TBUP314-1A20-AB00 represents a sample code for a SCADAPack 314, 5607 I/O board and Modbus protocol emulation

    Model Select: Controller

    TBUP314 SCADAPack 314 , 32 Bit controller, 8 Analog Inputs, 16 Digital Inputs, 10 Digital Outputs, 3 Accumulators

    Code Future Option

    1   None

    Code Select: Gas Flow Run-Time Option

     A None

    Flow Computer Runs

    G 2 Run Gas Flow

    F 4 Run Gas Flow

     V 2 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)

    W   4 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)

    Code Select: Protocol Option

    2 Modbus and DNP 3.0 (Level 2) protocol emulation

    Code Select: Programming Environment

    0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (programming tools sold separately)1   IEC 61131-3 and C Language rmware loaded - Telepace enabled (programming tools sold separately)

    Code Select: Analog Inputs

     A 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V

    Code Select: Digital Inputs/Outputs

    B 16 DI (12/24V) and 10 dry contact relays

    D   16 DI (120V) and 10 dry contact relays

    F 16 DI (12/24V) and 10 DC solid-state relays, ATEX and IECEx certication

    H 16 DI (120V) and 10 solid state relays

    Code Select: Analog Outputs

    0 None

    1   2 channel analog output option, 0 - 20mA 

    Code Select: Integrated Communication Interfaces

    0 None

    FreeWave & MDS Radios (requires one RS232 port)

    1   900Mhz FreeWave Spread Spectrum Radio

     A 900MHz MDS Spread Spectrum Radio

    Trio Radios - 900MHz (requires one RS232 port)

    B 900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

    C 900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)

    D   900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)

    E 900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)

    Trio Radios - 2.4GHz (requires one RS232 port)

    J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

    K   2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

    L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

    Product Data Sheet SCADAPack 314Model Code

    05

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    7/54

    P330: 5210 controller board only

    Controller

    Processors   • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer

    • Microcontroller co-processor, 20 MHz clock

    Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

    Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power

    Datalog Capacity 465k words

    I/O

    Counter Inputs • 1, 0-10Hz or 0-5kHz (dry contact)• 2, 0-10kHz (turbine or dry contact)

    Communications

    Serial Ports COM1, COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or• RS-485 port, 2-wire, half duplex

    Serial Port COM3 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control

    Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1

    Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward

    Ethernet Port RJ45, 10/100BaseT

    Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

    Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP

    USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V

    USB Peripheral Port USB 2.0 compliant “B”-type receptacle

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2

    General

    I/O Terminations 6-pole removable terminal block, 12 to 22AWG, 15A contacts

    Dimensions 5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep

    Packaging Corrosion resistant zinc-plated steel with black enamel paint

    Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power Input • 11 - 30VDC, 15mW at 12V dur ing Sleep• 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled• 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled• Add 800mW when enabling LAN• Add 190mW when enabling USB• Add 25 to 100mW when enabling the LEDs• 8.5W at 24V maximum, 5V supply fully loaded

    Warranty 3 years on parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.

    Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

    Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    Product Data Sheet SCADAPack 330Specications

    06

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    8/54

    P334: 5210 controller board and integrated 5607 I/O board

    Controller

    Processors   • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer

    • Microcontroller co-processor, 20 MHz clock

    Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

    Non-Volalite RAM CMOS SRAM with lithium battery retains contents for 2 years with no power

    Datalog Capacity 465k words

    I/O

     Analog Inputs 8, 0-20/4-20mA / 0-5/0-10V (15-bit) software congurable

     Analog Outputs • Standard: None• 2, 0-20/4-20mA (12-bit) with optional 5305 on 5607 I/O board

    Digi tal I/O • 16, 12/24V, 48V, 115/125V, 240V digital inputs• 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive),

    DC solid state rating: 3A, 60 VDC

    Counter Inputs 1, 0-10Hz or 0-5kHz (dry contact); 2, 0-10kHz (turbine or dry contact)

    Communications

    Serial Ports COM1, COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or• RS-485 port, 2-wire, half duplex

    Serial Port COM3 RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control

    Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1

    Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward

    Ethernet Port RJ45, 10/100BaseT

    Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

    Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP

    USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V

    USB Peripheral Port USB 2.0 compliant “B”-type receptacle

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2

    GeneralI/O Terminations 5, 6 and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts

    Dimensions 5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep

    Packaging Corrosion resistant zinc-plated steel with black enamel paint

    Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power

    5210 Controller Board • 11 - 30VDC, 15mW at 12 V during Sleep• 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled• 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled• Add 800mW when enabling LAN• Add 190mW when enabling USB• Add 25 to 100mW when enabling the LEDs• 8.5W at 24V maximum, 5V supply fully loaded

    5607 I/O Module • 11 - 30VDC, 10.3mA plus analog outputs• 325mA (max.) at 5V required from 5210 controller board

    Warranty 3 years on parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to the require-ments of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.

    Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

    Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    07

    Product Data Sheet SCADAPack 334Specications

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    9/54

    TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation

    Model Select: Controller

    TBUP330 SCADAPack 330, 32 Bit controller, 3 Accumulators

    TBUP334 SCADAPack 334, with Model 5607 I/O board, comes with above I/O plus 8 Analog I/P, 16 Digital I/P and 10 Digital O/P

    Code Future Option

    1   None

    Code Select: Gas Flow Run-Time Option

     A None

    Flow Computer Runs

    G 2 Run Gas Flow

    F 4 Run Gas Flow

     V 2 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)

    W   4 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)

    Code Select: Protocol Option

    2 Modbus and DNP 3.0 (Level 2) protocol emulation

    Code Select: Programming Environment

    0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (Programming Tools sold separately)

    1   IEC 61131-3 and C Language rmware loaded - Telepace enabled (Programming Tools sold separately)

    Code Select: Analog Inputs

     A P330: None – P334: 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V

    Code Select: Digital Inputs/Outputs

     A P330 - None

    B P334 - 16 DI (12/24V) and 10 dry contact relays

    D   P334 - 16 DI (120V) and 10 dry conta ct relays

    F P334 - 16 DI (12/24V) and 10 DC solid state relays, ATEX and IECEx certication

    H P334 - 16 DI (120V) and 10 solid state relays

    Code Select: Analog Outputs

    0 None

    1   P334 only - 2 channel analog output option, 0 - 20mA 

    Model codes continue on next page

    08

    Product Data Sheet SCADAPack 330 | 334Model Code

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    10/54

    TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation

    Code Select: Integrated Communication Interfaces

    0 None

    FreeWave & MDS Radios (requires one RS232 port)

    1   900Mhz FreeWave Spread Spectrum Radio

     A 900MHz MDS Spread Spectrum Radio

    Trio Radios - 900MHz (requires one RS232 port)

    B 900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

    C 900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)

    D   900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)

    E 900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)

    Trio Radios - 2.4GHz (requires one RS232 port)

    J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

    K   2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

    L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

    Product Data Sheet SCADAPack 330 | 334Model Code

    09

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    11/54

    P350: 5209 controller board only

    Controller

    Processors   • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer

    • Two Microcontroller co-processors, 20 MHz clock

    Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

    Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power

    Datalog Capacity 465k words

    I/O

     Analog Inputs • 5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit)• 1, 0-32.7VDC (15-bit)

     Analog Outputs • Standard: None• 2, 0-20/4-20mA (12-bit) with optional 5305

    Digital I/O 8, user selectable as dry contact inputs or open drain outputs

    Counter Inputs • 1, 0-10Hz (dry contact)• 2, 0-10kHz (turbine or dry contact)

    CommunicationsSerial Port COM1 RS-485 port, 2-pole removable terminal block, 2-wire, half duplex

    Serial Port COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or• RS-485 port, 2-wire, half duplex

    Serial Port COM3 RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control

    Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1

    Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward

    Ethernet Port RJ45, 10/100BaseT

    Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

    Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP

    USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V

    USB Peripheral Port USB 2.0 compliant “B”-type receptacle

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2

    General

    I/O Terminations 6 and 12- pole removable terminal blocks, 12 to 22AWG, 15A contacts

    Dimensions 8.40 inch (213mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep

    Packaging Corrosion resistant zinc-plated steel with black enamel paint

    Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power Input • 11 - 30VDC, 12mW at 12V dur ing Sleep• 510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled.• 320mW at 12V during reduced power mode operation. 12MHz., LEDs off, no expansion, LAN and USB disabled• 1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled• Add 25 to 100mW when enabling the LED• 12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded

     Voltage Converter 12VDC to 24VDC

    Warranty 3 years on parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certiedto the requirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.

    Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

    Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    Product Data Sheet SCADAPack 350Specications

    10

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    12/54

    P357: 52O9 controller board and integrated 56O6 I/O board

    Controller

    Processors   • CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer

    • Microcontroller co-processor, 20 MHz clock

    Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

    Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power

    Datalog Capacity 465k words

    I/O

     Analog Inputs • 5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit)• 1, 0-32.7VDC (15-bit) ; 8, 0-20/4-20mA / 0-5/0-10V (15-bit) software congurable

     Analog Outputs • Standard: None• 2, 0-20/4-20mA (12-bit) with optional 5305 on 5209 controller board• 2, 0-20/4-20mA (12-bit) with optional 5305 on 5606 I/O board

    Digital I/O • 8, user selectable as dry contact inputs or open drain outputs• 32, 12/24V, 48V, 115/125V, 240V digital inputs; 16, relay outputs - dry contact or DC solid state

    Counter Inputs 1, 0-10Hz (dry contact); 2, 0-10kHz (turbine or dry contact)

    Communications

    Serial Port COM1 RS-485 port, 2-pole removable terminal block, 2-wire, half duplex

    Serial Port COM2 • RS-232 port, 8-pin modular RJ45 jack, full or half duplex RS-232, or• RS-485 port, 2-wire, half duplex

    Serial Port COM3 RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control

    Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1

    Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward

    Ethernet Port RJ45, 10/100BaseT

    Ethernet Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

    Network Protocols IP, ARP, TCP, TFTP, UDP and ICMP

    USB Host Port USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V

    USB Peripheral Port USB 2.0 compliant “B”-type receptacle

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2

    GeneralI/O Terminations 5, 6, 9, 10 and 12-pole removable terminal blocks, 12 to 22AWG, 15A contacts

    Dimensions 8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep

    Packaging Corrosion resistant zinc-plated steel with black enamel paint

    Environment 5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power

    5209 Controller Board • 11 - 30VDC, 12mW at 12V during Sleep• 510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled• 320mW at 12V during normal operation. 12MHz., LEDs off, no expansion, LAN and USB disabled• 1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled• Add 25 to 100mW when enabling the LEDs• 12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded

    5606 I/O Module • 600mA (max.) at 5V required from 5209 controller board• 11 - 30VDC, 12mA plus analog outputs

     Voltage Converter 12VDC to 24VDC

    Warranty 3 years on parts and laborCertifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certiedto the requirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.• UL Std. No. 1604 - Hazardous (Classied) Locations.

    Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

    Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless version

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    11

    Product Data Sheet SCADAPack 357Specications

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    13/54

    TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation

    Model Select: Controller

    TBUP350 SCADAPack 350 , 32 Bit controller, 5 Analog Inputs, 8 congurable Digital I/O, 3 Accumulators

    TBUP357 SCADAPack 357, with Model 5606 I/O board, comes with above I/O plus 8 Analog I/P, 32 Digital I/P and 16 Digital O/P

    Code Future Option

    1   None

    Code Select: Gas Flow Run-Time Option

     A None

    Flow Computer Runs

    G 2 Run Gas Flow

    F 4 Run Gas Flow

     V 2 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)

    W   4 Run Gas Flow - Gas Transmission Version (Requires Realo 6.72+)

    Code Select: Protocol Option

    2 Modbus and DNP 3.0 (Level 2) protocol emulation

    Code Select: Programming Environment

    0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (Programming Tools sold separately)

    1   IEC 61131-3 and C Language rmware loaded - Telepace enabled (Programming Tools sold separately)

    Code Select: Analog Inputs

     A P350: 5 selectable as 0-10V or 0-20mA inputs. P357: adds another 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V

    Code Select: Digital Inputs/Outputs

     A P350 - 8 congurable Digital I/O, individually selectable as DI (Dry Contact) or DO (Open Drain)

    B P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Dry Contact Relay Outputs on 5606 I/O board

    D   P357 - Includes P350 I/O plus 32 DI (120V) and 16 Dry Contact Relay Outputs on 5606 I/O board

    F P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Solid State Relay Outputs on 5606 I/O board, ATEX and IECEx certication

    H P357 - Includes P350 I/O plus 32 DI (120V) and 16 Solid State Relay Outputs on 5606 I/O board

    Code Select: Analog Outputs

    0 None

    1   P350 or P357 - 2 channel analog output option, 0 - 20mA (P357 - 2 channel A/O option on the 5606)

    2 P357 only - 4 channel analog output option, 0 - 20mA (consists of the 2 channel A/O option board on both modules)

    Model codes continue on next page

    12

    Product Data Sheet SCADAPack 350 | 357Model Code

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    14/54

    TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation

    Code Select: Integrated Communication Interfaces

    0 None

    FreeWave & MDS Radios (requires one RS232 port)

    1   900Mhz FreeWave Spread Spectrum Radio

     A 900MHz MDS Spread Spectrum Radio

    Trio Radios - 900MHz (requires one RS232 port)

    B 900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

    C 900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)

    D   900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)

    E 900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ)

    Trio Radios - 2.4GHz (requires one RS232 port)

    J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

    K   2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

    L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

    Product Data Sheet SCADAPack 350 | 357Model Code

    13

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    15/54

    P4A, integrated 56O4 I/O board

    Controller

    Processor   Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer

    Memory 8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM

    Non Volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power

    I/O

     Analog Inputs • 8, user selectable 0 - 10V (15 bit) or 0 - 20mA (14 bit)• 1, 0 - 32.678V (10 bit)

     Analog Outputs 2 with optional 5305 analog output module, output range 0-20mA 

    Digital Inputs 4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation

    Digi tal Outputs 1, 30V / 60mA (used as status output)

    Digital I/O (5604 I/O board) 32 congurable as input or output (1 Amp DC max output / dry contact input)

    Communications

    Serial Port COM1 Congurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex

    Serial Ports COM2, COM4 • RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control• Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V

    Serial Port COM3 Located on 5604 I/O module. Same specications as COM2 and COM4

    Baud RatesCOM1, COM2, COM4

    300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

    Baud Rate COM3 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1, PPP

    Ethernet Port RJ45, 10BaseT

    Network Protocols IP: ARP, TCP, TFTP, UDP, ICMP

    Ethernet Port Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2

    General

    I/O Terminations 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

    Dimensions 8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power Input 11 - 30 VDC, 4.3W typical (10.8W ful l I/O capacity in use )

    Warranty 3 years on parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations

    Safety CSA (  cCSA us ) certied to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,Industrial Control Equipment) UL ( cULus ) listed: UL508 (Industrial Control Equipment)

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    Product Data Sheet SCADAPack 32Specications

    14

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    16/54

    P4, integrated 56O1A I/O board

    Controller

    Processor   Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer

    Memory 8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM

    Non Volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power

    I/O

     Analog Inputs 8, user selectable 0 - 5V (15 bit) or 0 - 20mA (14 bit)

     Analog Outputs 2 with optional 5303 analog output module, output range 0-20mA 

    Digital Inputs • 4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation• 16 on 5601A I/O module - 6.5mA typical at 24V and 3.5mA typical at 115V

    Digital Outputs • 1 on controller board , 30V, 60mA (used as status output)• 12 on 5601A I/O module - Sealed mechanical relay:  • 0.4A at 125 Vrms, 2A at 30V resistive loads  • 1.0A at 30V, 0.2A at 125Vrms inductive load with pf=0.4, L/R=7ms  • 250Vrms, 220V maximum operating voltage

    Communications

    Serial Port COM1 Congurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex

    Serial Ports COM2, COM4 RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control. Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V

    Serial Port COM3 Located on 5601A I/O module. Same specications as COM2 and COM4

    Baud RatesCOM1, COM2, COM4

    300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

    Baud Rate COM3 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1, PPP

    Ethernet Port 10BaseT, RJ45

    Network Protocols IP:ARP, TCP, TFTP, UDP, ICMP

    Ethernet Port Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4 GHz2

    GeneralI/O Terminations 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

    Dimensions 8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power Input: 11 - 30 VDC, 3.5W typical all relays off, 6.5W typical all relays on

    Warranty 3 years on parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certied to therequirements of:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations

    Safety CSA (  cCSA us ) certied to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,

    Industrial Control Equipment) UL ( cULus ) listed: UL508 (Industrial Control Equipment)

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    15

    Product Data Sheet SCADAPack 32Specications

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    17/54

    P4B, integrated 56O6 I/O board

    Controller

    Processor   Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer

    Memory 8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM

    Non Volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power

    I/O

     Analog Inputs 8, single-ended, software selectable 0-5V / 0-10 V or 0-20mA / 4-20mA (15 bit resolution)

     Analog Outputs 2 with optional 5305 analog output module, output range 0-20mA 

    Digital Inputs 4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation,32 on 5606 I/O module:• 0.67 mA typical at 24V on the 12/24V range• 0.37 mA typical at 48V on the 48V range• 0.35 mA typical at 120V on the 115/125V range• 0.35 mA typical at 240V on the 240V range

    Digital Outputs 1 on controller board, 30V, 60mA (used as status output)16 relay outputs on 5606 I/O module - dry contact or DC solid state:• Dry contact rating: 3A, 30VDC or 240VAC (Resistive)

    • DC solid state rating: 3A, 60 VDC

    Communications

    Serial Port COM1 Congurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex

    Serial Ports COM2, COM4 RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS controlImplemented Td, Rd, CTS, RTS, DCD, DTR, +5V

    Baud RatesCOM1, COM2, COM4

    300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1, PPP

    Ethernet Port RJ45, 10BaseT

    Network Protocols IP: ARP, TCP, TFTP, UDP, ICMP

    Ethernet Port Protocols Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4 GHz2

    General

    I/O Terminations 5, 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

    Dimensions 8.40 inch (213mm) wide, 6.48 inch (164mm) high, 2.80 inch (72mm) deep

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)

    Power Input: 11 - 30 VDC, 4.3W typical (10.8W ful l I/O capacity in use )

    Warranty 3 years on parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4UL Listed and CSA certied to the following standards:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations

    Hazardous LocationsEurope Model “5606 SSR, 24DI version only” ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)Does not include Wireless versions.

    Hazardous Locations Model “5606 SSR version only” IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    16

    Product Data Sheet SCADAPack 32Specications

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    18/54

    TBUP4-102-02-0-0 represents a sample code for a P4 with DNP, 0-5V inputs, 12-24V outputs

    Model Select: Controller

    TBUP4 SCADAPack 32, 32 Bit controller with Integrated Ethernet Port

    Code Select: Lower I/O Module

    5601A lower I/O module, includes 16 Digital Inputs, 12 Digital Outputs and 8 Analog Inputs (see options below)

     A 5604 lower I/O module, includes 32 congurable Digital I/O and 8 selectable Analog Inputs (0-10v or 0-20mA)

    B 5606 lower I/O module, includes 32 D/I, 16 Dry Contact D/O and 8 software congurable A/I

    C 5606-A lower I/O module, includes 32 D/I, 16 Solid State Relay D/O and 8 software congurable A/I

    N   No lower I/O module (provides controller module only)

    Code Select: Communications Serial Ports

    1   TBUP4/P4A/P4N: 3 RS232, 1 RS232/485, 1 Ethernet TBUP4B/P4C: 2 RS232, 1 RS232/485, 1 Ethernet

    Integrated FreeWave & MDS Radios (requires one RS232 port)

     A 900Mhz FreeWave Spread Spectrum Radio Consult CMI for availability in your market area

    3 900MHz MDS Spread Spectrum Radio Consult CMI for availability in your market area

    Trio Radios - 900MHz (requires one RS232 port)

    B 900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

    C 900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)

    D   900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)

    E 900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)

    Trio Radios - 2.4GHz (requires one RS232 port)

    J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

    K   2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

    L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

    Code Select: Gas Flow Run-time Option

    0 None

    Flow Computer Runs

    G 2 Run Gas Flow

    F 4 Run Gas Flow

    T 10 Run Gas Flow

    Flow Computer Runs - Gas Transmission Version (Requires Realflo 6.72+) V 2 Run Gas Flow

    W   4 Run Gas Flow

    Code Select: Protocol Option/Programming Environment

    2 Modbus and DNP 3.0 (Level 2) protocol with Telepace Ladder Logic and C Language rmware loaded - IEC enabled

    5 Modbus and DNP 3.0 (Level 2) protocol with IEC 61131-3 and C Language rmware loaded - Telepace enabled

    Code Select: Analog Inputs

    01 0-20mA, single ended (On TBUP4 & TBUP4A, Default on TBUP4B which is software congurable to 0-5v or 0-10v)

    02 0-5 volt, single ended (TBUP4 Only)

    03 0-10 volt, single ended (TBUP4A Only)

    Code Select: Digital Inputs/Outputs

    0 24 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: SS Relay D/O TBUP4A: Cong I/O TBUP4N: No I/O

    1   120 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: Solid State Relay D/O (Not for TBUP4A or TBUP4N)

    Code Select: Analog Outputs0 None (required for TBUP4N)

    1   2 channel Analog Output option, 0-20 mA 

    Product Data Sheet SCADAPack 32Model Code

    17

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    19/54

    SCADAPack 100

    Controller

    Processors   • 16-bit CMOS micro-controller, 14.74MHz clock, integrated watchdog timer

    • micro-controller co-processor: 14.74MHz clock

    Memory • 256KBytes CMOS RAM (control ler ID number A182921 or less)• 1024KBytes CMOS RAM (controller ID number A182922 or greater)• 512kBytes ash ROM, 1kBytes EEPROM

    Non-volatile RAM CMOS RAM with lithium battery retains contents for 2 years with no power

    I/O

     Analog Inputs • 3 at 5V/20mA: 250W resistance user congurable with jumper link• 1 at 32.768V

    Resolution 12 bits over the 5V and 32.768V measurement range

    Digital I/O 6 points, each point is an input and an output, dry contact input, 1.0A max output rating

    Counter Inputs 1, maximum frequency 5kHz, dry contact input, wetting current typically 5mA with 24V input power

    Communications

    Communication Port COM1 RS-485 serial port, 2 pole removable terminal block, 2 wire half duplex, bias resistors installed

    Communication Port COM1 RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex,implemented Td, Rd, +5V

    Communication Port COM2 RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex with RTS/CTScontrol, implemented Td, Rd, CTS, RTS, DCD, DTR, +5V

    Baud Rates COM1 & COM2 300, 600, 1200, 2400, 4800, 9600, 19200, 38400

    Serial Protocols Modbus RTU, Modbus ASCII, DNP3, DF1

    Serial Protocol Modes Slave, Master, Master/Slave, Store and Forward

    Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2

    General

    I/O Terminations 5 and 12 pole, removable terminal blocks. 12 to 22 AWG 15A contacts Screw termination 6 lb.-in. (0.68 Nm) torque

    Dimensions 5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)

    DC Power Input: 30V maximum, 10.0 to 11.5V turn on, 9.5V typical turn off, UL508 rated 13.75-28Vdc. Class 2, less than 500mW (at 12V) LEDs off,2.9W maximum

    Output Capacity 5V at 0.425A capacity, 5V at 0.060A required by 5208 controller, 5V at 0.365A available on COM1 and COM2

    Warranty 3 years parts and labor

    Certifications

    Hazardous LocationsNorth America

    Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations.Temperature Code T4 per CSA Std C22.2 No. 213-M1987 / UL1604 UL listed and CSA certied to the following standards:• CSA Std. C22.2 No. 213-M1987 - Hazardous Locations• UL Std. No. 1604 - Hazardous (Classied) Locations

    Hazardous Locations ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) Does not include Wireless versions

    Safety CSA (  cCSA us ) certied to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,Industrial Control Equipment) UL ( cULus ) listed: UL508 (Industrial Control Equipment)

    1 Available only with optional integrated wireless modules or with stand-alone wireless modules.2 Not applicable in all countries.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    Product Data Sheet SCADAPack 100Specications

    18

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    20/54

    TBUP100-1A20-AA00 represents a sample code for a TBUP100 with DNP, 0-5V inputs

    Model Select: Controller

    TBUP100 SCADAPack 100, comes with 3 Analog Inputs, 6 congurable Digital I/O, 1 Accumulator

    TBUP110 SCADAPack 100, Gas Flow Controller with 1 Gas Flow Run (I/O as above)

    Code Select: Communication Serial Ports

    1   2 Communication Ports (RJ45 Type) : 1 RS-232 and 1 RS232/485

    Code Select: Memory Configuration

     A 1 MB CMOS RAM (512K OS, 512K APP), 512K FLASH ROM

    Code Select: Protocol Option

    2 Modbus and DNP 3.0 (Level 2) protocol emulation

    Code Select: Programming Environment

    0 Telepace Ladder Logic and C Language rmware loaded - IEC enabled (Programming Tools sold separately)

    1   IEC 61131-3 and C Language rmware loaded - Telepace enabled (Programming Tools sold separately)

    Code Select: Analog Inputs A 3 Analog Inputs, individually selectable as 0-20mA or 0-5 volts

    Code Select: Digital Inputs/Outputs

     A 6 congurable Digital I/O, individually selectable as Digital Input (Dry Contact) or Digital Output (Open Drain)

    Code Select: Analog Outputs

    0 None

    Code Select: Integrated Communication Interfaces

    0 None

    FreeWave & MDS Radios (requires one RS232 port)

    1   900Mhz FreeWave Spread Spectrum Radio – consult CMI for availability in your market area

     A 900Mhz MDS Spread Spectrum Radio – consult CMI for availability in your market area

    Trio Radios - 900MHz (requires one RS232 port)

    B 900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

    C 900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)

    D   900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)

    E 900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ)

    Trio Radios - 2.4GHz (requires one RS232 port)

    J 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

    K   2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

    L 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

    Product Data Sheet SCADAPack 100Model Code

    19

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    21/54

    Product Data Sheet 5502 – Differential analog input moduleSpecications

    20

    5502 Differential analog input module

    General

    Input Points 8: voltage or current inputs, each input is switch selectable as voltage or current

    Ranges Voltage -10V to +10V, Current -20mA to +20mA  

    Resolution Voltage 1.22mV, Current 4.88µA  

    Input Resistance Voltage > 10MΩ, Current 250Ω

    Converter Type 13-bit plus sign successive approximation

     Accuracy • +/- 0.1% of full scale at 25°C (77°F)• +/- 0.2% of full scale over temperature range

    Isolation • 550VAC from any input to the chassis or the system power supplies.• 140VAC/200VDC between inputs

    Common Mode Rejection • >96dB at 50/60Hz, >50dB at 10KHz. with 1KΩ imbalance• >50dB at 1KHz. with 10KΩ imbalance

    Normal Mode Rejection >45dB at 50/60Hz

    Transient Protection • Transient suppressors and fuses on each input• 2.5kV surge withstand capability as per ANSI/IEEE, C37.90.1-1989

    Over-Scale Input Capacity 12VDC maximum. Exceeding 12V will cause the fuse to blow.

    Input Fuses 1/8 Amp.

    Reading Update Time 170ms with 60Hz. rejection selected. 185mS with 50Hz rejection selected.

    Power Requirements 5V @ 100mA 

    Terminations 2: 8 pole, removable terminal blocks, 12 - 22 AWG, 15A contacts

    Dimensions 144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety Class 1, Division 2 for use in hazardous locations

    Part Number TBUX297211

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    22/54

    Product Data Sheet 5504 – Thermocouple input moduleSpecications

    21

    5504 Thermocouple input module

    General

    Input Points 8 thermocouples or millivolt signals

    Thermocouple Typesand Ranges

    J: -200°C to 760°C (-328°F to 1400°F)K: -270°C to 1370°C (-454°F to 2498°F)E: -270°C to 1000°C (-454°F to 1832°F)T: -270°C to 400°C (-454°F to 752°F)mV ±80mV

    Resolution 0.004mV, approximately 0.10°C (0.18°F)

    Input Resistance 1MΩ

     Accuracy Over -40°C to 60°COperating Temperature Range

    J: ±0.20% of full scaleK: ±0.20% of full scaleE: ±0.15% of full scaleT: ±0.50% of full scalemV ±0.15% of full scale

    Cold Junction Compensation • ±0.5°C (0.9°F) maximum error from 0°C to 60°C (32°F to 140°F)• ±1°C (1.8°F) maximum error from -40°C to 0°C (-40°F to 32°F)

    Converter Type ±20000 count, integrat ing

    Common Mode Voltage Range ±10V can be applied to the inputs, relative to the -24V power supply input

    Isolation 500VAC from the logic power

    Transient Protection MOVs on each input

    Response Time 0.5 seconds

    Power Requirements • > 5V @40mA • > 20 to 28V @ 45mA 

    Terminations 10 pole and 8 pole, two xed terminal blocks, 12 - 22 AWG, 15 amp contacts

    Dimensions 144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety Class 1, Division 2 for use in hazardous locations

    Part Number TBUX297166

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    23/54

    Product Data Sheet 5505 – RTD input moduleSpecications

    22

    5505 RTD input module

    General

    Input Points 4, RTD

    RTD Type 100-ohm platinum, 3 and 4-wire, auto-detection and compensation

    Calibration 0.00385Ω / Ω /°C standard based on ASTM E 1137/E 1137M-04, ITS-90

    Ranges 5505: Can be congured to return data in ohms, °C, °F or °K• -200°C to 800°C (-328°F to 1472°F)• 0 to 500Ω5503 Emulation: Dipswitch selectable• 0°C to 200°C (32°F to 392°F)• -100°C to 100°C (-148°F to 212°F)• -200°C to 0°C (-328°F to 32°F)• 0°C to 800°C (32°F to 1472°F)• 0°C to 400°C (32°F to 752°F)• 0 to 400Ω

    Data Format • 5505: 32-bi t oating point and 12 status bi ts• 5503 Emulation: 16-bit signed integer

    Resolution • 5505: > 17-bit effective

    • 5505 Emulation: 15-bitRTD Status • RTD is good (not open)

    • RTD in range• RTD 3 or 4-wire• RTD status not available in 5503 Emulation

     Accuracy on RTD Ranges Percent of full scale over operational temperature range including linearization errors: +0.10%/-0.05%

     Accuracy on 0 to 500ohms Percent of full scale over operational temperature range: ±0.03%

    Excitation Current 4mA, 7.2% duty cycle in 4-wire mode, 14.4% in 3-wire mode, 250ms scan interval

    Line Resistance 100Ω max., in each line

    Converter Type 24-bit delta-sigma

    Response Time 380ms typical for 10% to 90% signal change at minimum lter setting

    Transient Protection 2.5kV surge-withstand capability as per ANSI/IEEE C37.90.1-1989

    Isolation Isolation from logic supply and chassis, voltage 500Vrms

    5V Power Requirements 6mA 

    11 - 30VDCPower Requirements

    12V operation: 4mA • plus 0.6mA per 4-wire RTD• plus 1.2mA per 3-wire RTD24V operation: 2.2mA • plus 0.3mA per 4-wire RTD• plus 0.6mA per 3-wire RTD

    11-30VDC - Connector Removable. Shared with RTD inputs 0-1

    11-30VDC - Isolation Isolation from logic supply and chassis

    Terminations 8 and 10 pole, removable terminal block,12 to 22 AWG, 15A contacts

    Dimensions 74mm wide x 124mm high x 45mm deep (2.9in. x 4.9in. x 1.8in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion-resistant zinc-plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F) operation, -40°C to 85°C (-40°F to 185°F) storage

    Safety • Non-Incendive Electrical Equipment for Use in Class I, Divis ion2• Groups A, B C and D Hazardous Locations• ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)

    Part Number TBUX297318

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    24/54

    Product Data Sheet 5506 – Analog input moduleSpecications

    23

    5506 Analog input module

    General

    Input Points 8

    Ranges • 0-20mA  • 4-20mA • 0-5V• 1-5V

    LED Indicators 8 red LEDs, indicating current input, voltage input and under or over-range signal applied

    Input Conguration Individual inputs congurable with 4mA/1V (20%) offset and for voltage/current operation when congured as a 5506. All inputsdipswitch-selectable with 4mA/1V (20%) offset and for voltage/current operation when congured to emulate a 5501 module.

    Input Resistance 250 ohms - Current conguration ; 66k ohms - Voltage conguration

    Resolution 15-bits over the 0-5V and 0-20mA measurement range

    Type Single-ended

     Accuracy ±0.1% of full scale at 25°C (77°F) ; ±0.2% over temperature range

    Transient Protection 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989

    Normal Mode Rejection At 60 Hz with 60Hz Scanning

    • 53dB with 3Hz lter• 50dB with 6Hz lter• 49dB with 11Hz lter• 45dB with 30Hz lter

    Normal Mode Rejection At 50 Hz with 50Hz Scanning

    • 73dB with 3Hz lter• 56dB with 6Hz lter• 52dB with 11Hz lter• 49dB with 30Hz lter

    Response Time for 10% to90% Signal Change(60Hz Scanning)

    • 250ms with 3Hz lter• 130ms with 6Hz lter• 60ms with 11Hz lter• 30ms with 30Hz lter

    Response Time for 10% to90% Signal Change(50Hz Scanning)

    • 300ms with 3Hz lter• 140ms with 6Hz lter• 80ms with 11Hz lter• 40ms with 30Hz lter

    Over-Scale Input Capacity

    (without damage)

    Continuous: 0.10A/14V on the 20mA inputs ; 0.05A/14V on the 5V inputs

    Isolation 500Vac isolation f rom logic supply and chassis

    5V Power Requirements • 22mA, LEDs off• 45mA, LEDs on

    11-30VDC Power Requirements 11mA 

    11-30VDC - Connector Removable, 4 positions

    11-30VDC - Isolation Isolation from logic supply and chassis

    Terminations 10 pole, removable terminal block,12 to 22 AWG, 15A contacts

    Dimensions 2.9 inch (74 mm) wide, 4.9 inch (124 mm) high, 1.8 inch (45 mm) deep

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion-resistant zinc-plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F) operation, -40°C to 85°C (-40°F to 185°F) storage

    Safety • Non-Incendive Electrical Equipment for Use in Class I, Divis ion2• Groups A, B C and D Hazardous Locations• ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)

    Part Number TBUX297319

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    25/54

    Product Data Sheet 5302 – Analog output moduleSpecications

    24

    5302 Analog output module

    General

    Output points 4 ( 2 when used with 5201 and 5201 control lers)

    Output signal ranges 0-20mA or 4-20mA, switch congurable

    Output Type Single ended regulation on positive side with common negative return

    Maximum Load Resistance 1000W with 24VDC loop power, 400W with 12VDC loop power , 250Wwith 9VDC loop power

    Isolation 1500VAC eld to logic

    D/A Resolution 12-bit over the 0-20mA ranges

     Absolute Accuracy +/- 0.05% of full scale at 25ºC (77ºF), +/- 0.2% of full scale over temperature range

    Noise and Ripple 0.04% maximum

    Transient Protection 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989

    Response Time 250ms typical for 10% to 90% signal change

     Addressing DIP switch congurable

    Power Requirements 5V @ 45mA, 9 - 30V @ 15mA quiescent plus 80mA max.

    Terminations 10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

    Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F)

    Safety   cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

    Part Number TBUX297176

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    26/54

    Product Data Sheet 5304 – Analog output moduleSpecications

    25

    5304 Analog output module

    General

    Output points 4

    Output Modes • Current mode, jumper link selectable• Voltage mode, 5V full scale, jumper link selectable,• Voltage mode, 10V full scale, jumper link selectable

    Output signal ranges • 0-20mA or 4-20mA, switch congurable• 0-5V or 1-5V, switch congurable, 0-10V or 2-10V, switch congurable

    Output Type Single ended regulation on positive side with common negative return

    Maximum Load Resistance 1000Ω with 24VDC loop power, 400Ω with 12VDC loop power, 250Ω with 9VDC loop power

    Minimum Load Resistancein Voltage Mode

    • 2kΩ for 10V full scale, with min 20VDC power applied• 1kΩ for 5V full scale, with min 15VDC power applied

    Isolation 500VAC eld to logic

    D/A Resolution 12-bit over the 0-20mA / 0-5V/ 0-10V ranges

     Absolute Accuracy +/- 0.05% of full scale at 25ºC (77ºF), +/- 0.2% of full scale over temperature range

    Noise and Ripple 0.04% maximum

    Transient Protection • 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989• Inductive load protection diodes included

    Response Time 2ms typical to 90% signal change

     Addressing DIP switch congurable

    12-24V Operating Voltage Limits

    • 9V or (20mA x load resistance) +4V (whichever is greater) in current mode• (1.5 x Range / load resistance) + Range + 2.5V in voltage mode, 30V maximum

    Power Requirements • 6mA min., 25mA maximum• 15mA quiescent plus 80mA max. in current mode• 15mA quiescent plus 20mA max. in voltage mode

    Terminations 10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

    Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paintEnvironment 5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F)

    Safety   cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

    Model Part Number Description

    5304-20 TBUX297248 4 channel isolated analog output module, 0-20mA 

    5304-10 TBUX297252 4 channel isolated analog output module, 0-10 vol ts

    5304-5 TBUX297253 4 channel isolated analog output module, 0-5 volts

    5304-C TBUX297254 4 channel isolated analog output module, Custom (specify range of each input)

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    27/54

    Product Data Sheet 5403 – High level digital input moduleSpecications

    26

    5403 High level digital input module

    General

    Number of Digi tal Inputs 8

    Input Logic-HI Level OFF to ON transition threshold is typically 50% of full scale signal range

    Over-Voltage Tolerance 150% sustained over-voltage without damage

    Input Current 5mA typical

    Response Time • OFF to ON: 7ms typical• ON to OFF: 24ms typical

    Isolation 1500VAC in groups of 4 inputs

     Addressing DIP switch congurable

    Power Requirements 5V @ 45mA all LEDs ON, 5V @ 25mA with LEDs disabled

     Visual Indicators 16: red LEDs controlled for power reduction

    Field Terminations • 1: 10 pole, removable terminal block• 12 to 22 AWG• 15A contacts

    Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety   cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

    Model Part Number Signal range

    5403-12 TBUX297110 12 volts AC/DC

    5403-24 TBUX297109 24 volts AC/DC

    5403-48 TBUX297108 48 volts AC/DC

    5403-120 TBUX297107 120 volts AC/DC

    5403-240 TBUX297106 240 volts AC/DC

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    28/54

    Product Data Sheet 5404 – High level digital input moduleSpecications

    27

    5404 High level digital input module

    General

    Number of Digital Inputs   16

    Input Logic-HI Level OFF to ON transition threshold is typically 50% of full scale signal range

    Over-Voltage Tolerance 150% sustained over-voltage without damage

    Input Current 5mA typical

    Response Time • OFF to ON: 7ms typical• ON to OFF: 24ms typical

    Isolation 1500VAC in groups of 4 inputs

     Addressing DIP switch congurable

    Power Requirements 5V @ 80mA all LEDs ON, 5V @ 25mA with LEDs disabled

     Visual Indicators 16: red LEDs controlled for power reduction

    Field Terminations • 2: 10 pole, removable terminal block• 12 to 22 AWG• 15A contacts

    Dimensions 144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety   cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

    Model Part Number Signal range

    5404-12 TBUX297158 12 volts AC/DC

    5404-24 TBUX297157 24 volts AC/DC

    5404-48 TBUX297156 48 volts AC/DC

    5404-120 TBUX297155 120 volts AC/DC

    5404-240 TBUX297154 240 volts AC/DC

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    29/54

    Product Data Sheet 5405 – Digital input moduleSpecications

    28

    5405 Digital input module

    General

    Input Points 32

    Ranges 12-24VDC, 16-24VAC, 120VAC/DC

    Over-Voltage Tolerance 150% sustained over-voltage without damage

    Input Current • 6.0mA typical @ 24VDC on the 24V range• 3.5mA typical @ 24VAC on the 24V range• 2.5mA typical @ 120VDC on the 120V range• 1.5mA typical @ 120VAC on the 120V range

    DC Input Logic Levels • OFF to ON transition threshold is typically 7.5VDC on the 24VDC range• OFF to ON transition threshold is typically 55VDC on the 120VDC range

     AC Input Levels • OFF to ON transition threshold is typically 6VAC on the 24VAC range• OFF to ON transition threshold is typically 45VAC on the 120VAC range

    Transient Protection 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989

    Isolation • Isolated in 4 groups of 8. Inputs 0-15 are on the bottom edge.• Inputs 16-31 are on the top edge. Isolation 500VAC/DC from chassis and logic ground

    Power Requirements 5V @ 10mA with all inputs ON

    Terminations 4: 9 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

    Dimensions 144mm wide x 127mm high x 45mm deep (5.65in. x 5.00in. x 1.88in.)

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

     Addressing Congurable with 4 DIP switches

     AC/DC Operation 2: DIP switches determine AC/DC and 50/60Hz operation

     Visual Indicators 32: Red LED’s, eld powered. Cannot be disabled to conserve power

    Safety   cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

    Model Part Number Description

    5405-120 TBUX297249 32 point , 120V discrete input module

    5405-24 TBUX297247 32 point , 12-24V discrete input module

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    30/54

    Product Data Sheet 5410 – High speed counter/accumulatorSpecications

    29

    5410 High speed counter/accumulator

    General

    Counter Input Points 4

    Count Length 32-bit, range is 0 to 4,294,967,295

    Over-Voltage Protection Transient suppressor on each input

    Input Voltage Range Typical operating inputs 5 to 24V, 3V minimum, 28V maximum

    Input Current 8mA typical, 13mA maximum

    Input Logic Level OFF to ON threshold is typically 2V

    Maximum Input Frequency 10kHz with lters off, 5kHz with quadrature counters, 60Hz with de-bounce lters on

    Maximum Pulse High Width • 50 microseconds (µs), 100µs with quadrature counters• 8.3 milliseconds with de-bounce lters

    Minimum Pulse Low Width • 50 microseconds (µs), 100µs with quadrature counters• 8.3 milliseconds with de-bounce lters

    Isolation 500VAC input to input, 500VAC input to logic circuit

     Addressing DIP switch congurable

    Terminations 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

     Visual Indicators • 4: red LEDs• LED on time stretched for easy viewing controlled for power reduction

    Power Requirements 5V @ 35mA with all LEDs on, 5V @ 15mA with LEDs disabled

    Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety   Class 1, Division 2 for use in hazardous locations

    Part Number TBUX297149

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    31/54

    Product Data Sheet 5414 – Compact digital input moduleSpecications

    30

    5414 Compact digital input module

    General

    Number of Digital Inputs   16

    Ranges Factory congurable as:• 12/24V• 48V• 115/125V• 240V

    Input Current • 0.6 – 0.9mA at 24V on the 12/24V range• 0.3 – 0.4mA at 48V on the 48V range• 0.3 – 0.4mA at 120V on the 115/125V range• 0.3 – 0.4mA at 240V on the 240V range

    Over-voltage Tolerance 150% sustained over-voltage without damage

    Power Requirements • 5V@6mA with LEDs off• 5V@40mA with LEDs on

     Visual Indicators Logic powered LEDs. Can be disabled to conserve power

    Field Terminations 12 to 22 AWG, 15A contacts

    Dimensions 74mm wide x 124mm high x 45mm deep (2.90in. x 4.90in. x 1.80in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment • 5% RH to 95% RH, non-condensing• –40ºC to 70ºC (–40ºF to 158ºF) operation• –40ºC to 85ºC (–40ºF to 185ºF) storage

    Safety • Class I, Division 2, Groups A, B, C and D and CSA certied to UL508 standards• ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) (5414-24 only)• Maximum permitted voltage in Canada or North America is 240VAC• Maximum permitted voltage outside of Canada or North America is 30VAC/42.4PK/60VDC

    Model Part Number Signal Range

    5414-24 TBUX297378 12/24V AC/DC, ATEX and IECEx

    5414-48 TBUX297379 48V AC/DC (Not avai lable outside of North America)

    5414-120 TBUX297380 115/125V AC/DC (Not available outside of North America)

    5414-240 TBUX297381 240V AC/DC (Not available outside of North America)

    Note: Module not supported on 16-bit SCADAPack platform (SCADAPack, SCADAPack Light, SCADAPack Plus, SCADAPack 100 and SCADAPack LP)

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    32/54

    Product Data Sheet 5401 – Congurable digital I/O moduleSpecications

    31

    5401 Congurable digital I/O module

    General

    Number of Inputs or Outputs 8

     Voltage Range See relay specications below

    Load Current See relay specicat ions below

    Surge Current See relay specicat ions below

    Off-State Leakage See relay specications below

    Transient Protection Integral to the solid-state relay

    Response Time See relay specications below

    Isolation 1500VAC

     Addressing DIP switch congurable

    Input/Output Assignment DIP switch selection for each I/O point

    Power Requirements 5V @ 90mA 

     Visual Indicators 8: red LEDs, permanently enabled

    Field Terminations 2: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

    Dimensions 108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety   cCSA us and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

    TBUX297121   8-point input or output module (requires solid-state relays)

    Model Part Number Solid-State Relays for use with Model 5401

    IACM-5 TBUX297122 90-140 VAC/VDC input relay

    IACM-5A TBUX297132 180-280 VAC/VDC input relay

    IACM-5E TBUX297133 10-32VDC, 15-32VAC, no polarity

    IDCM-5 TBUX297124 3-32VDC input relay

    OACM-5 TBUX297123 24-140VAC output relay, 3A  

    OACM-5H TBUX297134 24-280VAC output relay, 5A 

    ODCM-5 TBUX297125 3-60VDC output relay, 3A  

    ODCM-5A TBUX297135 10-200VDC, 1A  

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    33/54

    Product Data Sheet 5402 – Congurable digital input or output moduleSpecications

    32

    5402 Congurable digital input or output module

    General

    Number of Inputs or Outputs   16

     Voltage Range See relay specications below

    Load Current See relay specicat ions below

    Surge Current See relay specicat ions below

    Off-State Leakage See relay specications below

    Transient Protection Integral to the solid-state relay

    Response Time See relay specications below

    Isolation 1500VAC

     Addressing DIP switch congurable

    Input/Output Assignment DIP switch selectable as all inputs or outputs

    Power Requirements 5V @ 150mA 

     Visual Indicators 16: red LEDs, permanently enabled

    Field Terminations 4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

    Dimensions 215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety   Class 1, Division 2 for use in hazardous locations

    Part Number TBUX297153 - 16-point input or output module (requires solid-state relays)

    Model Part Number Solid-State Relays for use with Model 5402

    IACM-5 TBUX297122 90-140 VAC/VDC input relay

    IACM-5A TBUX297132 180-280 VAC/VDC input relay

    IACM-5E TBUX297133 10-32VDC, 15-32VAC, no polarity

    IDCM-5 TBUX297124 3-32VDC input relay

    OACM-5 TBUX297123 24-140VAC output relay, 3A  

    OACM-5H TBUX297134 24-280VAC output relay, 5A 

    ODCM-5 TBUX297125 3-60VDC output relay, 3A  

    ODCM-5A TBUX297135 10 - 200VDC output relay, 1A 

    This IO Expansion module is not supported by the SCADAPack E RTU.

    Disclaimer: Schneider Electric reserves the right to change product specications. For more information visit www.schneider-electric.com.

    https://www.aquatechnologygroup.com/product-category/electrical/controllers/rtus-and-plcs/

  • 8/17/2019 SCADAPack RTUs Controllers IO Datasheet

    34/54

    Product Data Sheet 5406A – Dry contact relay out moduleSpecications

    33

    5406A Dry contact relay out module

    General

    Number of Relay Outputs   16

    Type Sealed mechanical relay, Form A (normally open) contacts

    Contact Ratings • 6A @ 250VAC resistive loads, 6A @ 30VDC resistive loads• 3.5A at 30VDC/250VAC inductive load (pf=0.4. L/R=7 ms), 1/4 HP 125VAC• 3A maximum in Class 1, Division 2 hazardous locations

    Operating Frequency 18,000 operations/hour mechanically, 1,800 electrically at rated load

    Service Life • 1,500,000 operations at 0-250mA loads, 600,000 operations at 1A resistive load• 100,000 operations at 6A resistive load, 300,000 operations at 1A inductive loads (pf=0.4)• 100,000 operations at 3.5A inductive loads (pf=0.4)

    Operate Time 10mS maximum, 5mS typical

    Release Time 10mS maximum, 2mS typical

    Bounce Time 3mS typical

    Contact Isolation 1000VAC

    Logic Isolation 1500VAC

     Addressing DIP switch congurable

    Power Requirements • 5V Bus Power - 5V @ 600mA with all LEDs and all relays energized• External Power - 5V @ 65mA with all LEDs and all relays energized

     Visual Indicators 16: red LEDs, controlled for power reduction

    Field Terminations • 4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts• Additional three pins on connector P3 to support external power

    Dimensions 215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)

    Mounting 7.5 x 35 DIN rail

    Packaging Corrosion resistant zinc plated steel with black enamel paint

    Environment 5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)

    Safety   cCSA us and cULus Class I, Division 2 Hazardous Area Rating,