Opbrengstverklaringen Zonneboilers - TNO

77
Opbrengstverklaringen Zonneboilers ATON Solarsaver 125 Bos Solar Bos-200-24/286-4,7 Bos Solar Bos-300-36/429-4,7 Bos Solar Bos-400-48/572-5,6 Dutch Solar Systems ZB 120 TX 2,37 Dutch Solar Systems ZB 120 TX 4,74 Dutch Solar Systems ZB 180 TX 2,37 Dutch Solar Systems ZB 180 TX 4,74 Dutch Solar Systems ZB 95 TX 2,37 Dutch Solar Systems ZB 120 S 2,37 Dutch Solar Systems ZB 95 S 2,37 Duurzame Techniek NAU SPF 1 / NAU SPF 1Q Duurzame Techniek NAU SPF 2 / NAU SPF 2Q Duurzame Techniek NAU SPF 3(-2) / NAU SPF 3Q(-2) Estec-Holland HP 150 LUX Estec-Holland HP 160 EASY IQ MijnZonneboiler Compact 165-20 IQ MijnZonneboiler HR+ 200-24 IQ MijnZonneboiler HR+ 300-36 Leylandi CitrinSolar 1.86 m 2 160 l Leylandi CitrinSolar 3.72 m 2 200 l Leylandi CitrinSolar 3.72 m 2 300 l Ritter Aquapaket CPC Star Azzurro Ritter Aqua System CPC 32 Allstar Rivusol S100-15T Rivusol S100-20T Rivusol S150-15T Rivusol S150-25T Rivusol S150-30T Rivusol S200-25T Rivusol S150-20T Rivusol S200-30T Rivusol S250-30T Rivusol S250-40T Rivusol S300-40T Rivusol S300-50T Rivusol S500-60T

Transcript of Opbrengstverklaringen Zonneboilers - TNO

Page 1: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaringen Zonneboilers

ATON Solarsaver 125

Bos Solar Bos-200-24/286-4,7

Bos Solar Bos-300-36/429-4,7

Bos Solar Bos-400-48/572-5,6

Dutch Solar Systems ZB 120 TX 2,37

Dutch Solar Systems ZB 120 TX 4,74

Dutch Solar Systems ZB 180 TX 2,37

Dutch Solar Systems ZB 180 TX 4,74

Dutch Solar Systems ZB 95 TX 2,37

Dutch Solar Systems ZB 120 S 2,37

Dutch Solar Systems ZB 95 S 2,37

Duurzame Techniek NAU SPF 1 / NAU SPF 1Q

Duurzame Techniek NAU SPF 2 / NAU SPF 2Q

Duurzame Techniek NAU SPF 3(-2) / NAU SPF 3Q(-2)

Estec-Holland HP 150 LUX

Estec-Holland HP 160 EASY

IQ MijnZonneboiler Compact 165-20

IQ MijnZonneboiler HR+ 200-24

IQ MijnZonneboiler HR+ 300-36

Leylandi CitrinSolar 1.86 m2 160 l

Leylandi CitrinSolar 3.72 m2 200 l

Leylandi CitrinSolar 3.72 m2 300 l

Ritter Aquapaket CPC Star Azzurro

Ritter Aqua System CPC 32 Allstar

Rivusol S100-15T

Rivusol S100-20T

Rivusol S150-15T

Rivusol S150-25T

Rivusol S150-30T

Rivusol S200-25T

Rivusol S150-20T

Rivusol S200-30T

Rivusol S250-30T

Rivusol S250-40T

Rivusol S300-40T

Rivusol S300-50T

Rivusol S500-60T

Page 2: Opbrengstverklaringen Zonneboilers - TNO

TNO | Kennis voor zaken

Energetische besparing zonneboiler ATON Solarsaver 125

Opbrengstverklaring 10-60 oC

Deze opbrengstverklaring is geldig tot 1 februari 2012

Op basis van Kiwa Gastec Certification Report number: 178680

Februari 2009

Nummerverklaring:034-DTM-2009-01110

Ondertekening: Goedgekeurd door:

T. Epema BSc Ir. L.J.W.M. KrosseProjectleider Afdelingshoofd

Fabrikant: Aton zonne-energie systemen

Type: Solarsaver 125Aperture oppervlakte: 2,34 m2

Vat volume: 125 liter

Adres: Aton zonne-energie systemenPhileas foggstraat 1457825 AW EmmenTel: 0591-553515Fax: 0591-553566

20

11

/06

/01

In opdracht van Aton zonne-energie systemen is voor de zonneboiler ‘Solarsaver 125’ de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Gevolgde methodiek is gebaseerd op de NPR 7976. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 3,5 GJ/jaar

All rights reserved,

No part of this publication may be reproduced and/or

published by print, photoprint, microfilm or any other

means without the previous written consent of TNO,

In case this report was drafted on instructions, the

rights and obligations of contracting parties are sub-

ject to either the ‘Standard Conditions for Research

Instructions given to TNO’ or the relevant agreement

concluded between the contracting parties. Submitting

the report for inspection to parties who have a direct

interest is permitted.

© TNO 2009

Alle rechten voorbehouden.

Niets uit deze uitgave mag worden vermenigvuldigd

en/of openbaar gemaakt door middel van druk,

fotokopie, microfilm of op welke andere wijze dan ook,

zonder voorafgaande toestemming van TNO.

Indien dit rapport in opdracht werd uitgebracht, wordt

voor de rechten en verplichtingen van opdrachtgever

en opdrachtnemer verwezen naar de ‘Algemene Voor-

waarden voor onderzoeksopdrachten aan TNO’, dan

wel de betreffende terzake tussen partijen gesloten

overeenkomst. Het ter inzage geven van het TNO-

rapport aan direct belanghebbenden is toegestaan.

© TNO 2009

Page 3: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring 10-60 oC Energetische besparing zonneboiler ATON Solarsaver 125

Koude Warmte en Installaties

BezoekadresVan Mourik Broekmanweg 62628 XE Delft

PostadresPostbus 492600 AA Delft

T. Epema BScT 015 27 [email protected]

www.tno.nl

TNO Bouw en Ondergrond

Deze verklaring is tot stand gekomen door een eenmalige

beoordeling door TNO van de specifieke eigenschappen van

een exemplaar van een product of een uitvoering van een

systeem. Deze verklaring geeft geen oordeel over andere

exemplaren van een product of van andere uitvoeringen van

systemen. Deze verklaring geeft geen oordeel over de

kwaliteitsborging van producten of systemen, dit is de

verantwoordelijkheid van de fabrikant.

Prestatie zonneboiler type ATON Solarsaver 125 onder Nederlandse referentie condi-ties.

Referentievraag Jaarlijkse tapvraag, QD

[GJ/jr]

Equivalent tapwaterverbruik[liter/dag], [°C]

Qaux

[GJ/jr]

Qsav

[GJ/jr]

2 6,10 080, 10 - 60 3,02 3,0

3 8,39 110, 10 - 60 4,76 3,5

4 10,68 140, 10 - 60 6,76 3,8

5 12,97 170, 10 - 60 8,77 4,1

6 15,26 200, 10 - 60 10,92 4,2

Parasitair elektriciteitsverbruik

Qpar = 0,12 GJ/jr

De energetische besparing is als volgt berekend::

Qsav = Qaux,ref – (Qaux + Qpar) Met Qaux,ref =QD

Waarin, zoals beschreven in NPR 7976:Qaux Annual auxiliary energyQaux,ref Annual heat consumption of a non-solar reference systemQpar Annual parasitic energyQD Annual heat demanded by the userQsav Annual energy savings

VoorwaardenMet uitzondering van het vat met een volume van 125 liter is de zonneboiler identiek aan het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification Report number: 178680.

Opmerkingen:Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976 (opbrengst bepaald d.m.v. DST test volgens NEN EN 12976), deze beschrijft de standaard berekeningswijze en referentiewaarden voor de bepaling van de Nederlandse besparingsindicatoren, in de Engelse taal, echter met de volgende aanpassingen:– De opbrengst is berekend voor een tapwaterverbruik opgewarmd van 10 naar 60 °C,

conform Europese normeringen betreffende warmwaterinstallaties.– TNO rapport ‘Herziene achtergrondrapportage: Conversie van TNO-zonneboiler-

opbrengst in NEN 5128 formaat’ (TNO rapport 2005-BBE-R0053) beschrijft de aanpas-sing van de NPR 7976 voor zonneboilersystemen met geïntegreerde naverwarming.

– Mogelijkheden voor extrapolatie van de energieopbrengst van het geteste zonneboiler-systeem zijn verruimd. Voor uitvoering van de extrapolatie zijn nu voldoende aantoon-bare technische specificaties van de gewijzigde componenten nodig. TNO beschouwt of met deze gegevens een voldoend nauwkeurige extrapolatie kan worden uitgevoerd.

Page 4: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

7-12

-201

0 10

Opbrengstverklaring

Energetische besparing zonneboiler Bos Solar Bos-200-24/286-4,7 In opdracht van Dijkman Energy Systems is voor de zonneboiler Bos-200-24-286/4,7 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,7 GJ/jaar

Type: Bos-200-24-286/4,7 Opdrachtgever: Systeemtype: voorverwarmer Dijkman Energy Systems methode: afgeleide Badinckstraat 13 7721 ZD Dalfsen Vatvolume: 200 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt tel.: 06 – 3369 5855 Collector oppervlakte: 2,86 m2 (24 buizen) Collector type: vacuüm buis Collectortest rapport: nvt Ondertekening: Goedkeuring:

T.Epema BSc Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-02928 Geldig tot: 1 september 2011 Op basis van testrapport FREE-XT-200L218 TÜV Report No.: 21211834_200 10-09-2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 5: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

7-12

-201

0 10

Opbrengstverklaring Energetische besparing zonneboiler Bos SolarBos-200-24-286/4,7 Nummer verklaring 034-DTM-2010-02928 Prestatie zonneboiler type Bos Solar Bos-200-24-286/4,7 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4052 2051 361 2412 3691 3,7

2 8391 110, 10 – 60 5106 3285 361 3646 4745 4,7 3 10680 140, 10 – 60 5872 4808 361 5169 5511 5,5 4 12968 170, 10 – 60 6432 6536 361 6897 6071 6,1 5 15257 200, 10 – 60 6899 8358 361 8719 6538 6,5 6 17546 230, 10 – 60 7314 10232 361 10593 6953 7,0 7 19834 260, 10 – 60 7529 12305 361 12666 7168 7,2 8 22123 290, 10 – 60 7695 14428 361 14789 7334 7,3 9 24411 320, 10 – 60 7892 16519 361 16880 7531 7,5 10 26700 350, 10 – 60 8045 18655 361 19016 7684 7,7

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport TÜV Report No.: 21211834_200.

Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van geïntegreerde elektrische naverwarming.

Page 6: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

7-12

-201

0 10

Opbrengstverklaring

Energetische besparing zonneboiler Bos Solar Bos-300-36/429-4,7 In opdracht van Dijkman Energy Systems is voor de zonneboiler Bos-300-36/429-4,7 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,7 GJ/jaar

Type: Bos-300-36/429-4,7 Opdrachtgever: Systeemtype: voorverwarmer Dijkman Energy Systems methode: DST Badinckstraat 13 7721 ZD Dalfsen Vatvolume: 300 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt tel.: 06 – 3369 5855 Collector oppervlakte: 4,29 m2 (36 buizen) Collector type: vacuüm buis Collectortest rapport: nvt Ondertekening: Goedkeuring:

T.Epema BSc Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-02790 Geldig tot: 1 september 2011 Op basis van testrapport FREE-XT-300L236 TÜV Report No.: 21211834_300 10-09-2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Page 7: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

7-12

-201

0 10

Opbrengstverklaring Energetische besparing zonneboiler Bos Solar Bos-300-36/429-4,7 Nummer verklaring 034-DTM-2010-02790 Prestatie Dijkman Bos Solar Bos-300-36/429-4,7zonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4005 2098 361 2459 3644 3,6 2 8391 110, 10 – 60 5109 3282 361 3643 4748 4,7 3 10680 140, 10 – 60 6023 4657 361 5018 5662 5,7 4 12968 170, 10 – 60 6749 6219 361 6580 6388 6,4 5 15257 200, 10 – 60 7348 7909 361 8270 6987 7 6 17546 230, 10 – 60 7852 9694 361 10055 7491 7,5 7 19834 260, 10 – 60 8294 11540 361 11901 7933 7,9 8 22123 290, 10 – 60 8641 13482 361 13843 8280 8,3 9 24411 320, 10 – 60 8956 15455 361 15816 8595 8,6 10 26700 350, 10 – 60 9240 17460 361 17821 8879 8,9

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden De zonneboiler is identiek aan het systeem waarvoor de opbrengst is vastgesteld, beschreven

in rapport TÜV Report No.: 21211834_300. Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van

geïntegreerde elektrische naverwarming.

Page 8: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

7-12

-201

0 10

Opbrengstverklaring

Energetische besparing zonneboiler Bos Solar Bos-400-48/572-5,6 In opdracht van Dijkman Energy Systems is voor de zonneboiler Bos-400-48/572-5,6 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 5,6 GJ/jaar

Type: Bos-400-48/572-5,6 Opdrachtgever: Systeemtype: voorverwarmer Dijkman Energy Systems methode: afgeleide Badinckstraat 13 7721 ZD Dalfsen Vatvolume: 400 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt tel.: 06 – 3369 5855 Collector oppervlakte: 5,72 m2 (48 buizen) Collector type: vacuüm buis Collectortest rapport: nvt Ondertekening: Goedkeuring:

T.Epema BSc Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-02927 Geldig tot: 1 september 2011 Op basis van testrapport FREE-XT-400L254 TÜV Report No.: 21211834_400 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 9: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

7-12

-201

0 10

Opbrengstverklaring Energetische besparing zonneboiler Bos Solar Bos-400-48/572-5,6 Nummer verklaring 034-DTM-2010-02927 Prestatie zonneboiler type Bos Solar Bos-400-48/572-5,6 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4651 1452 361 1813 4290 4,3

2 8391 110, 10 – 60 5995 2396 361 2757 5634 5,6 3 10680 140, 10 – 60 7156 3524 361 3885 6795 6,8 4 12968 170, 10 – 60 8088 4880 361 5241 7727 7,7 5 15257 200, 10 – 60 8659 6598 361 6959 8298 8,3 6 17546 230, 10 – 60 9281 8265 361 8626 8920 8,9 7 19834 260, 10 – 60 9761 10073 361 10434 9400 9,4 8 22123 290, 10 – 60 10188 11935 361 12296 9827 9,8 9 24411 320, 10 – 60 10532 13879 361 14240 10171 10,2 10 26700 350, 10 – 60 10822 15878 361 16239 10461 10,5

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport TÜV Report No.: 21211834_400.

Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van geïntegreerde elektrische naverwarming.

Page 10: Opbrengstverklaringen Zonneboilers - TNO

Page 1/14

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler DSS ZB 120 TX 2,37 In opdracht van Dutch Solar Systems is voor de zonneboiler DSS ZB 120 TX 2,37de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 4,8 GJ/jaar Type: DSS ZB 120 TX 2,37 Opdrachtgever: Systeemtype: voorverwarmer Dutch Solar Systems methode: test Postbus 228 7500 AE Enschede Vatvolume: 120 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,37 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04526/A Geldig tot: 1 januari 2012 Op basis van testrapport TNO 2003-DEG-R033 januari 2004 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 11: Opbrengstverklaringen Zonneboilers - TNO

Page 2/14

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler DSS ZB 120 TX 2,37 Nummer verklaring 034-DTM-2010-04526/A Prestatie zonneboiler type DSS ZB 120 TX 2,37 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4037 2066 200 2266 3837 3,8

2 8391 110, 10 – 60 4951 3440 200 3640 4751 4,8

3 10680 140, 10 – 60 5582 5098 200 5298 5382 5,4 4 12968 170, 10 – 60 5992 6976 200 7176 5792 5,8 5 15257 200, 10 – 60 6244 9013 200 9213 6044 6,0 6 17546 230, 10 – 60 6465 11081 200 11281 6265 6,3 7 19834 260, 10 – 60 6623 13211 200 13411 6423 6,4 8 22123 290, 10 – 60 6780 15343 200 15543 6580 6,6 9 24411 320, 10 – 60 6906 17505 200 17705 6706 6,7 10 26700 350, 10 – 60 7001 19699 200 19899 6801 6,8

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden De zonneboiler is identiek aan het systeem waarvoor de opbrengst is vastgesteld, beschreven

in rapport TNO 2003-DEG-R033 echter inclusief correctie voor gebruik van een kunstzoninstallatie zoals voorgeschreven door Zonnekeur criteria ZK 2009 d.d. 22 juni 2010 aanvulling 2010-1

Page 12: Opbrengstverklaringen Zonneboilers - TNO

Page 3/14

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler DSS ZB 120 TX 4,74 In opdracht van Dutch Solar Systems is voor de zonneboiler DSS ZB 120 TX 4,74 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 6,0 GJ/jaar Type: DSS ZB 120 TX 4,74 Opdrachtgever: Systeemtype: voorverwarmer Dutch Solar Systems methode: afgeleid systeem Postbus 228 7500 AE Enschede Vatvolume: 120 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 4,74 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04526/B Geldig tot: 1 januari 2012 Op basis van testrapport TNO 2003-DEG-R033 januari 2004 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 13: Opbrengstverklaringen Zonneboilers - TNO

Page 4/14

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler DSS ZB 120 TX 4,74 Nummer verklaring 034-DTM-2010-04526/B Prestatie zonneboiler type DSS ZB 120 TX 4,74 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4881 1222 200 1422 4681 4,7

2 8391 110, 10 – 60 6242 2149 200 2349 6042 6,0

3 10680 140, 10 – 60 7553 3127 200 3327 7353 7,4 4 12968 170, 10 – 60 8648 4320 200 4520 8448 8,4 5 15257 200, 10 – 60 9407 5850 200 6050 9207 9,2 6 17546 230, 10 – 60 10072 7474 200 7674 9872 9,9 7 19834 260, 10 – 60 10609 9225 200 9425 10409 10,4 8 22123 290, 10 – 60 11105 11018 200 11218 10905 10,9 9 24411 320, 10 – 60 11531 12880 200 13080 11331 11,3 10 26700 350, 10 – 60 11882 14818 200 15018 11682 11,7

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport, TNO 2003-DEG-R033 inclusief correctie voor metingen uitgevoerd met behulp van een kunstzon gebaseerd op Zonnekeur kriteria ZK 2009 d.d. 22 juni 2010 aanvulling 2010-1

Page 14: Opbrengstverklaringen Zonneboilers - TNO

Page 5/14

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler DSS ZB 180 TX 4,74 In opdracht van Dutch Solar Systems is voor de zonneboiler DSS ZB 180 TX 4,74 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 6,1 GJ/jaar Type: DSS ZB 180 TX 4,74 Opdrachtgever: Systeemtype: voorverwarmer Dutch Solar Systems methode: afgeleid systeem Postbus 228 7500 AE Enschede Vatvolume: 180 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 4,74 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04526/C Geldig tot: 1 januari 2012 Op basis van testrapport TNO 2003-DEG-R033 januari 2004 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 15: Opbrengstverklaringen Zonneboilers - TNO

Page 6/14

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler DSS ZB 180 TX 4,74 Nummer verklaring 034-DTM-2010-04526/C Prestatie zonneboiler type DSS ZB 180 TX 4,74 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4800 1303 200 1503 4600 4,6

2 8391 110, 10 – 60 6297 2094 200 2294 6097 6,1

3 10680 140, 10 – 60 7738 2942 200 3142 7538 7,5 4 12968 170, 10 – 60 8868 4100 200 4300 8668 8,7 5 15257 200, 10 – 60 9733 5524 200 5724 9533 9,5 6 17546 230, 10 – 60 10442 7104 200 7304 10242 10,2 7 19834 260, 10 – 60 11013 8821 200 9021 10813 10,8 8 22123 290, 10 – 60 11533 10590 200 10790 11333 11,3 9 24411 320, 10 – 60 11971 12440 200 12640 11771 11,8 10 26700 350, 10 – 60 12332 14368 200 14568 12132 12,1

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport, TNO 2003-DEG-R033 inclusief correctie voor metingen uitgevoerd met behulp van een kunstzon gebaseerd op Zonnekeur kriteria ZK 2009 d.d. 22 juni 2010 aanvulling 2010-1

Page 16: Opbrengstverklaringen Zonneboilers - TNO

Page 7/14

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler DSS ZB 180 TX 2,37 In opdracht van Dutch Solar Systems is voor de zonneboiler DSS ZB 180 TX 2,37 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 4,9 GJ/jaar Type: DSS ZB 180 TX 2,37 Opdrachtgever: Systeemtype: voorverwarmer Dutch Solar Systems methode: afgeleid systeem Postbus 228 7500 AE Enschede Vatvolume: 180 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,37 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04526/D Geldig tot: 1 januari 2012 Op basis van testrapport TNO 2003-DEG-R033 januari 2004 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 17: Opbrengstverklaringen Zonneboilers - TNO

Page 8/14

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler DSS ZB 180 TX 2,37 Nummer verklaring 034-DTM-2010-04526/D Prestatie zonneboiler type DSS ZB 180 TX 2,37 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4105 1998 200 2198 3905 3,9

2 8391 110, 10 – 60 5071 3320 200 3520 4871 4,9

3 10680 140, 10 – 60 5726 4954 200 5154 5526 5,5 4 12968 170, 10 – 60 6153 6815 200 7015 5953 6,0 5 15257 200, 10 – 60 6417 8840 200 9040 6217 6,2 6 17546 230, 10 – 60 6648 10898 200 11098 6448 6,4 7 19834 260, 10 – 60 6812 13022 200 13222 6612 6,6 8 22123 290, 10 – 60 6976 15147 200 15347 6776 6,8 9 24411 320, 10 – 60 7107 17304 200 17504 6907 6,9 10 26700 350, 10 – 60 7206 19494 200 19694 7006 7,0

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport, TNO 2003-DEG-R033 inclusief correctie voor metingen uitgevoerd met behulp van een kunstzon gebaseerd op Zonnekeur kriteria ZK 2009 d.d. 22 juni 2010 aanvulling 2010-1

Page 18: Opbrengstverklaringen Zonneboilers - TNO

Page 9/14

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler DSS ZB 95 TX 2,37 In opdracht van Dutch Solar Systems is voor de zonneboiler DSS ZB 95 TX 2,37 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 4,7 GJ/jaar Type: DSS ZB 95 TX 2,37 Opdrachtgever: Systeemtype: voorverwarmer Dutch Solar Systems methode: afgeleid systeem Postbus 228 7500 AE Enschede Vatvolume: 95 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,37 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04526/E Geldig tot: 1 januari 2012 Op basis van testrapport TNO 2003-DEG-R033 januari 2004 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 19: Opbrengstverklaringen Zonneboilers - TNO

Page 10/14

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler DSS ZB 95 TX 2,37 Nummer verklaring 034-DTM-2010-04526/E Prestatie zonneboiler type DSS ZB 95 TX 2,37 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3974 2129 200 2329 3774 3,8

2 8391 110, 10 – 60 4862 3529 200 3729 4662 4,7

3 10680 140, 10 – 60 5473 5207 200 5407 5273 5,3 4 12968 170, 10 – 60 5870 7098 200 7298 5670 5,7 5 15257 200, 10 – 60 6115 9142 200 9342 5915 5,9 6 17546 230, 10 – 60 6329 11217 200 11417 6129 6,1 7 19834 260, 10 – 60 6483 13351 200 13551 6283 6,3 8 22123 290, 10 – 60 6636 15487 200 15687 6436 6,4 9 24411 320, 10 – 60 6759 17652 200 17852 6559 6,6 10 26700 350, 10 – 60 6851 19849 200 20049 6651 6,7

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport, TNO 2003-DEG-R033 inclusief correctie voor metingen uitgevoerd met behulp van een kunstzon gebaseerd op Zonnekeur kriteria ZK 2009 d.d. 22 juni 2010 aanvulling 2010-1

Page 20: Opbrengstverklaringen Zonneboilers - TNO

Page 11/14

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler DSS ZB 120 S 2,37 In opdracht van Dutch Solar Systems is voor de zonneboiler DSS ZB 120 S 2,37 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 4,4 GJ/jaar Type: DSS ZB 120 S 2,37 Opdrachtgever: Systeemtype: voorverwarmer Dutch Solar Systems methode: test Postbus 228 7500 AE Enschede Vatvolume: 120 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,37 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04526/F Geldig tot: 1 januari 2012 Op basis van testrapport TNO 2001-DEG-R124 19 november 2001 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 21: Opbrengstverklaringen Zonneboilers - TNO

Page 12/14

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler DSS ZB 120 S 2,37 Nummer verklaring 034-DTM-2010-04526/F Prestatie zonneboiler type DSS ZB 120 S 2,37 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3692 2411 100 2511 3653 3,7

2 8391 110, 10 – 60 4428 3963 100 4063 4410 4,4

3 10680 140, 10 – 60 4917 5763 100 5863 4914 4,9 4 12968 170, 10 – 60 5193 7775 100 7875 5198 5,2 5 15257 200, 10 – 60 5407 9850 100 9950 5419 5,4 6 17546 230, 10 – 60 5561 11985 100 12085 5576 5,6 7 19834 260, 10 – 60 5714 14120 100 14220 5734 5,7 8 22123 290, 10 – 60 5806 16317 100 16417 5829 5,8 9 24411 320, 10 – 60 5899 18512 100 18612 5923 5,9 10 26700 350, 10 – 60 5991 20709 100 20809 6018 6,0

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport, TNO 2001-DEG-R124.

Page 22: Opbrengstverklaringen Zonneboilers - TNO

Page 13/14

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler DSS ZB 95 S 2,37 In opdracht van Dutch Solar Systems is voor de zonneboiler DSS ZB 95 S 2,37 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing:

Qsav = 4,3 GJ/jaar Type: DSS ZB 95 S 2,37 Opdrachtgever: Systeemtype: voorverwarmer Dutch Solar Systems methode: afgeleid systeem Postbus 228 7500 AE Enschede Vatvolume: 95 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,37 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04526/G Geldig tot: 1 januari 2012 Op basis van testrapport TNO 2001-DEG-R124 19 november 2001 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 23: Opbrengstverklaringen Zonneboilers - TNO

Page 14/14

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler DSS ZB 95 S 2,37 Nummer verklaring 034-DTM-2010-04526/G Prestatie zonneboiler type DSS ZB 95 S 2,37 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3692 2411 100 2511 3592 3.6

2 8391 110, 10 – 60 4428 3963 100 4063 4328 4,3

3 10680 140, 10 – 60 4917 5763 100 5863 4817 4,8 4 12968 170, 10 – 60 5193 7775 100 7875 5093 5,1 5 15257 200, 10 – 60 5407 9850 100 9950 5307 5,3 6 17546 230, 10 – 60 5561 11985 100 12085 5461 5,5 7 19834 260, 10 – 60 5714 14120 100 14220 5614 5,6 8 22123 290, 10 – 60 5806 16317 100 16417 5706 5,7 9 24411 320, 10 – 60 5899 18512 100 18612 5799 5,8 10 26700 350, 10 – 60 5991 20709 100 20809 5891 5,9

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport, TNO 2001-DEG-R124.

Page 24: Opbrengstverklaringen Zonneboilers - TNO

Page 1/6

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler NAU SPF 1 / NAU SPF 1Q In opdracht van Duurzame Techniek is voor de zonneboiler NAU SPF 1 / NAU SPF1Q de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3.5 GJ/jaar Type: NAU SPF 1 / NAU SPF 1Q Opdrachtgever: Systeemtype: voorverwarmer Duurzame Techniek methode: afgeleid Oude Rijksweg Noord 64B 6114 JG Susteren Vatvolume: 150 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 1.91 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04010/A Geldig tot: 1 december 2011 Op basis van testrapport ITW 10SYS96 13 okt 2010 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 25: Opbrengstverklaringen Zonneboilers - TNO

Page 2/6

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler NAU SPF 1 / NAU SPF1Q Nummer verklaring 034-DTM-2010-04010/A Prestatie zonneboiler type NAU SPF 1 / NAU SPF1Q onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3675 2428 237 2665 3438 3.4

2 8391 110, 10 – 60 3774 4617 237 4854 3537 3.5

3 10680 140, 10 – 60 3943 6737 237 6974 3706 3.7 4 12968 170, 10 – 60 4074 8894 237 9131 3837 3.8 5 15257 200, 10 – 60 4198 11059 237 11296 3961 4.0 6 17546 230, 10 – 60 4351 13195 237 13432 4114 4.1 7 19834 260, 10 – 60 4468 15366 237 15603 4231 4.2 8 22123 290, 10 – 60 4568 17555 237 17792 4331 4.3 9 24411 320, 10 – 60 4659 19752 237 19989 4422 4.4 10 26700 350, 10 – 60 4724 21976 237 22213 4487 4.5

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport ITW 10SYS96 van 13 oktober 2010

Page 26: Opbrengstverklaringen Zonneboilers - TNO

Page 3/6

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler NAU SPF 2 / NAU SPF 2Q In opdracht van Duurzame Techniek is voor de zonneboiler NAU SPF 2 / NAU SPF2Q de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 5.5 GJ/jaar Type: NAU SPF 2 / NAU SPF 2Q Opdrachtgever: Systeemtype: voorverwarmer Duurzame Techniek methode: afgeleid Oude Rijksweg Noord 64B 6114 JG Susteren Vatvolume: 200 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 3.82 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04010/B Geldig tot: 1 december 2011 Op basis van testrapport ITW 10SYS96 13 okt 2010 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 27: Opbrengstverklaringen Zonneboilers - TNO

Page 4/6

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler NAU SPF 2 / NAU SPF2Q Nummer verklaring 034-DTM-2010-04010/B Prestatie zonneboiler type NAU SPF 2 / NAU SPF2Q onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4713 1390 237 1627 4476 4.5

2 8391 110, 10 – 60 5706 2685 237 2922 5469 5.5

3 10680 140, 10 – 60 6450 4230 237 4467 6213 6.2 4 12968 170, 10 – 60 6991 5977 237 6214 6754 6.8 5 15257 200, 10 – 60 7419 7838 237 8075 7182 7.2 6 17546 230, 10 – 60 7856 9690 237 9927 7619 7.6 7 19834 260, 10 – 60 8206 11628 237 11865 7969 8.0 8 22123 290, 10 – 60 8503 13620 237 13857 8266 8.3 9 24411 320, 10 – 60 8768 15643 237 15880 8531 8.5 10 26700 350, 10 – 60 8974 17726 237 17963 8737 8.7

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport ITW 10SYS96 van 13 oktober 2010

Page 28: Opbrengstverklaringen Zonneboilers - TNO

Page 5/6

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler NAU SPF 3(-2) / NAU SPF 3Q(-2) In opdracht van Duurzame Techniek is voor de zonneboiler NAU SPF 3(-2) / NAU SPF3Q(-2) de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 6.0 GJ/jaar Type: NAU SPF 3(-2) / NAU SPF3Q(-2) Opdrachtgever: Systeemtype: voorverwarmer Duurzame Techniek methode: afgeleid Oude Rijksweg Noord 64B 6114 JG Susteren Vatvolume: 300 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 5.73 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-04010/C Geldig tot: 1 december 2011 Op basis van testrapport ITW 10SYS96 13 okt 2010 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 29: Opbrengstverklaringen Zonneboilers - TNO

Page 6/6

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler NAU SPF 3(-2) / NAU SPF3Q(-2) Nummer verklaring 034-DTM-2010-04010/C Prestatie zonneboiler type NAU SPF 3(-2) / NAU SPF3Q(-2) onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4878 1225 237 1462 4641 4.6

2 8391 110, 10 – 60 6253 2138 237 2375 6016 6.0

3 10680 140, 10 – 60 7561 3119 237 3356 7324 7.3 4 12968 170, 10 – 60 8673 4295 237 4532 8436 8.4 5 15257 200, 10 – 60 9581 5676 237 5913 9344 9.3 6 17546 230, 10 – 60 10362 7184 237 7421 10125 10.1 7 19834 260, 10 – 60 11010 8824 237 9061 10773 10.8 8 22123 290, 10 – 60 11565 10558 237 10795 11328 11.3 9 24411 320, 10 – 60 12059 12352 237 12589 11822 11.8 10 26700 350, 10 – 60 12460 14240 237 14477 12223 12.2

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport ITW 10SYS96 van 13 oktober 2010

Page 30: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

7-12

-201

0 11

Opbrengstverklaring

Energetische besparing zonneboiler Estec-Holland HP 150 LUX In opdracht van Estec-Holland BV is voor de zonneboiler Estec-Holland HP 150 LUX de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3,7 GJ/jaar

Type: Estec-Holland HP 150 LUX Opdrachtgever: Systeemtype: thermosifon Estec-Holland BV methode: afgeleide Industriestraat 30 5931 PJ TEGELEN Vatvolume: 150 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,34 m2 Collector type: vlakke plaat Collectortest rapport: niet beschikbaar Ondertekening: Goedkeuring:

T.Epema BSc Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-02707 Op basis van testrapport HP 160 Easy SPF test report S124EN 31-8-2009 Geldig tot: 1 september 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Page 31: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

7-12

-201

0 11

Opbrengstverklaring Energetische besparing zonneboiler Estec-Holland HP 150 LUX Nummer verklaring 034-DTM-2010-02707 Prestatie zonneboiler type Estec-Holland HP 150 LUX zonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3627 2945 0 2945 3158 3,2 2 8391 110, 10 – 60 4352 4690 0 4690 3701 3,7 3 10680 140, 10 – 60 4857 6576 0 6576 4104 4,1 4 12968 170, 10 – 60 5172 8627 0 8627 4341 4,3 5 15257 200, 10 – 60 5393 10714 0 10714 4543 4,5 6 17546 230, 10 – 60 5550 12868 0 12868 4678 4,7 7 19834 260, 10 – 60 5708 15021 0 15021 4813 4,8 8 22123 290, 10 – 60 5834 17209 0 17209 4914 4,9 9 24411 320, 10 – 60 5897 19428 0 19428 4983 5,0 10 26700 350, 10 – 60 5992 21650 0 21650 5050 5,1

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport SPF test report S124EN.

Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van geïntegreerde elektrische naverwarming.

Besparing is berekend bij installatie op vlakke ondergrond waarbij het opslag vat buiten staat. Indien de zonneboiler in een schuin dak wordt ingebouwd, met het vat binnen de gebouwschil, kan ook met dit getal gerekend worden.

Page 32: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Estec-Holland HP 160 EASY In opdracht van Estec-Holland BV is voor de zonneboiler Estec-Holland HP 160 Easy de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3,8 GJ/jaar

Type: Estec-Holland HP 160 Easy Opdrachtgever: Systeemtype: thermosifon Estec-Holland BV methode: test Industriestraat 30 5931 PJ TEGELEN Vatvolume: 160 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,23 m2 Collector type: vlakke plaat Collectortest rapport: niet beschikbaar Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-03622 Op basis van testrapport HP 160 Easy SPF test report S124EN 31-8-2009 Geldig tot: 1 oktober 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Page 33: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Estec-Holland HP 160 Easy Nummer verklaring 034-DTM-2010-03622 Prestatie zonneboiler type Estec-Holland HP 160 Easy zonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3217 2886 0 2886 3217 3.2 2 8391 110, 10 – 60 3784 4607 0 4607 3784 3.8 3 10680 140, 10 – 60 4163 6517 0 6517 4163 4.2 4 12968 170, 10 – 60 4447 8521 0 8521 4447 4.4 5 15257 200, 10 – 60 4636 10621 0 10621 4636 4.6 6 17546 230, 10 – 60 4793 12753 0 12753 4793 4.8 7 19834 260, 10 – 60 4888 14946 0 14946 4888 4.9 8 22123 290, 10 – 60 4983 17140 0 17140 4983 5 9 24411 320, 10 – 60 5077 19334 0 19334 5077 5.1 10 26700 350, 10 – 60 5140 21560 0 21560 5140 5.1

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem is identiek aan het geteste systeem waarvan de opbrengst is

vastgesteld beschreven in rapport SPF test report S124EN. Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van

geïntegreerde elektrische naverwarming. Besparing is berekend bij installatie op vlakke ondergrond waarbij het opslag vat buiten

staat. Indien de zonneboiler in een schuin dak wordt ingebouwd, met het vat binnen de gebouwschil, kan ook met dit getal gerekend worden.

Page 34: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

7-12

-201

0 10

Opbrengstverklaring

Energetische besparing zonneboiler MijnZonneboiler Compact 165-20 In opdracht van IQ Energy Control BV is voor de zonneboiler MijnZonneboiler Compact 165-20 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3,0 GJ/jaar

Type: MijnZonneboiler Compact 165-20 Opdrachtgever: Systeemtype: thermosifon;voorverwarmer IQ Energy Control BV methode: DST Ceintuurbaan Noord 124 A 9301 NZ Roden Vatvolume: 165 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 1,72 m2 Collector type: vacuüm buis (20 buizen) Collectortest rapport: nvt Ondertekening: Goedkeuring:

T.Epema BSc Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-02794 Geldig tot: 1 september 2011 Op basis van testrapport TZ47/1500-20c Fraunhofer ISE STB Nr.: 2009-03 2 september 2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 35: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

7-12

-201

0 10

Opbrengstverklaring Energetische besparing zonneboiler IQ Energy Control BV MijnZonneboiler Compact 165-20 Nummer verklaring 034-DTM-2010-02794 Prestatie zonneboiler type MijnZonneboiler Compact 165-20 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 2617 3486 0 3486 2617 2,6

2 8391 110, 10 – 60 3027 5364 0 5364 3027 3,0 3 10680 140, 10 – 60 3343 7337 0 7337 3343 3,3 4 12968 170, 10 – 60 3564 9404 0 9404 3564 3,6 5 15257 200, 10 – 60 3753 11504 0 11504 3753 3,8 6 17546 230, 10 – 60 3879 13667 0 13667 3879 3,9 7 19834 260, 10 – 60 4005 15829 0 15829 4005 4,0 8 22123 290, 10 – 60 4100 18023 0 18023 4100 4,1 9 24411 320, 10 – 60 4194 20217 0 20217 4194 4,2 10 26700 350, 10 – 60 4257 22443 0 22443 4257 4,3

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden De zonneboiler is identiek aan het systeem waarvoor de opbrengst is vastgesteld, beschreven

in rapport Fraunhofer ISE STB Nr.: 2009-03. Deze verklaring is geldig bij gebruik als voorverwarmer; zonder gebruikmaking van

eventuele geïntegreerde elektrische naverwarming.

Page 36: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

7-12

-201

0 10

Opbrengstverklaring

Energetische besparing zonneboiler MijnZonneboiler HR+ 200-24 In opdracht van IQ Energy Control BV is voor de zonneboiler MijnZonneboiler HR+ 200-24 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,7 GJ/jaar

Type: MijnZonneboiler HR+ 200-24 Opdrachtgever: Systeemtype: voorverwarmer IQ Energy Control BV methode: afgeleide van FREE-XT-200L218 Ceintuurbaan Noord 124 A 9301 NZ Roden Vatvolume: 200 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,86 m2 Collector type: vacuüm buis (24 buizen) Collectortest rapport: niet beschikbaar Ondertekening: Goedkeuring:

T.Epema BSc Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-02793 Geldig tot: 1 september 2011 Op basis van testrapport FREE-XT-200L218 TÜV Report No.: 21211834_200 10-09-2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 37: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

7-12

-201

0 10

Opbrengstverklaring Energetische besparing zonneboiler MijnZonneboiler HR+ 200-24 Nummer verklaring 034-DTM-2010-02793 Prestatie zonneboiler type MijnZonneboiler HR+ 200-24 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4052 2051 361 2412 3691 3,7

2 8391 110, 10 – 60 5106 3285 361 3646 4745 4,7 3 10680 140, 10 – 60 5872 4808 361 5169 5511 5,5 4 12968 170, 10 – 60 6432 6536 361 6897 6071 6,1 5 15257 200, 10 – 60 6899 8358 361 8719 6538 6,5 6 17546 230, 10 – 60 7314 10232 361 10593 6953 7,0 7 19834 260, 10 – 60 7529 12305 361 12666 7168 7,2 8 22123 290, 10 – 60 7695 14428 361 14789 7334 7,3 9 24411 320, 10 – 60 7892 16519 361 16880 7531 7,5 10 26700 350, 10 – 60 8045 18655 361 19016 7684 7,7

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport TÜV Report No.: 21211834_200.

Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van geïntegreerde elektrische naverwarming.

Page 38: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

7-12

-201

0 10

Opbrengstverklaring

Energetische besparing zonneboiler MijnZonneboiler HR+ 300-36 In opdracht van IQ Energy Control BV is voor de zonneboiler MijnZonneboiler HR+ 300-36 de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,7 GJ/jaar

Type: MijnZonneboiler HR+ 300-36 Opdrachtgever: Systeemtype: voorverwarmer IQ Energy Control BV methode: DST Ceintuurbaan Noord 124 A 9301 NZ Roden Vatvolume: 300 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 4,29 m2 (36 buizen) Collector type: vacuüm buis Collectortest rapport: nvt Ondertekening: Goedkeuring:

T.Epema BSc Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-02791 Geldig tot: 1 september 2011 Op basis van testrapport FREE-XT-300L236 TÜV Report No.: 21211834_300 10-09-2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 39: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

7-12

-201

0 10

Opbrengstverklaring Energetische besparing zonneboiler MijnZonneboiler HR+ 300-36 Nummer verklaring 034-DTM-2010-02791 Prestatie zonneboiler MijnZonneboiler HR+ 300-36 onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4005 2098 361 2459 3644 3,6

2 8391 110, 10 – 60 5109 3282 361 3643 4748 4,7 3 10680 140, 10 – 60 6023 4657 361 5018 5662 5,7 4 12968 170, 10 – 60 6749 6219 361 6580 6388 6,4 5 15257 200, 10 – 60 7348 7909 361 8270 6987 7 6 17546 230, 10 – 60 7852 9694 361 10055 7491 7,5 7 19834 260, 10 – 60 8294 11540 361 11901 7933 7,9 8 22123 290, 10 – 60 8641 13482 361 13843 8280 8,3 9 24411 320, 10 – 60 8956 15455 361 15816 8595 8,6 10 26700 350, 10 – 60 9240 17460 361 17821 8879 8,9

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden De zonneboiler is identiek aan het systeem waarvoor de opbrengst is vastgesteld, beschreven

in rapport TÜV Report No.: 21211834_300. Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van

geïntegreerde elektrische naverwarming.

Page 40: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Estec-Holland HP 160 EASY In opdracht van Estec-Holland BV is voor de zonneboiler Estec-Holland HP 160 Easy de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3,8 GJ/jaar

Type: Estec-Holland HP 160 Easy Opdrachtgever: Systeemtype: thermosifon Estec-Holland BV methode: test Industriestraat 30 5931 PJ TEGELEN Vatvolume: 160 dm3 [email protected] Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,23 m2 Collector type: vlakke plaat Collectortest rapport: niet beschikbaar Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-03622 Op basis van testrapport HP 160 Easy SPF test report S124EN 31-8-2009 Geldig tot: 1 oktober 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Page 41: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Estec-Holland HP 160 Easy Nummer verklaring 034-DTM-2010-03622 Prestatie zonneboiler type Estec-Holland HP 160 Easy zonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3217 2886 0 2886 3217 3.2 2 8391 110, 10 – 60 3784 4607 0 4607 3784 3.8 3 10680 140, 10 – 60 4163 6517 0 6517 4163 4.2 4 12968 170, 10 – 60 4447 8521 0 8521 4447 4.4 5 15257 200, 10 – 60 4636 10621 0 10621 4636 4.6 6 17546 230, 10 – 60 4793 12753 0 12753 4793 4.8 7 19834 260, 10 – 60 4888 14946 0 14946 4888 4.9 8 22123 290, 10 – 60 4983 17140 0 17140 4983 5 9 24411 320, 10 – 60 5077 19334 0 19334 5077 5.1 10 26700 350, 10 – 60 5140 21560 0 21560 5140 5.1

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem is identiek aan het geteste systeem waarvan de opbrengst is

vastgesteld beschreven in rapport SPF test report S124EN. Deze verklaring is alleen geldig bij gebruik als voorverwarmer; zonder gebruikmaking van

geïntegreerde elektrische naverwarming. Besparing is berekend bij installatie op vlakke ondergrond waarbij het opslag vat buiten

staat. Indien de zonneboiler in een schuin dak wordt ingebouwd, met het vat binnen de gebouwschil, kan ook met dit getal gerekend worden.

Page 42: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler CitrinSolar 1.86 m² 160 l In opdracht van Leylandi Consultancy vof is voor de zonneboiler CitrinSolar 1.86 m² 160 l de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3.1 GJ/jaar

Type: CitrinSolar 1.86 m2 160 l Opdrachtgever: Systeemtype: voorverwarmer Leylandi Consultancy vof methode: test Proosdijstraat 11 6191 AH Beek Vatvolume: 160 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 1.86 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-03964 Geldig tot: 1 december 2011 Op basis van testrapport TNO 99-BBI-R065 23 juni 1999 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 43: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler CitrinSolar 1.86 m² 160 l Nummer verklaring 034-DTM-2010-03964 Prestatie zonneboiler type CitrinSolar 1.86 m² 160 l onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3091 3012 300 3312 2791 2.8

2 8391 110, 10 – 60 3405 4986 300 5286 3105 3.1

3 10680 140, 10 – 60 3734 6946 300 7246 3434 3.4 4 12968 170, 10 – 60 3976 8992 300 9292 3676 3.7 5 15257 200, 10 – 60 4145 11112 300 11412 3845 3.8 6 17546 230, 10 – 60 4238 13308 300 13608 3938 3.9 7 19834 260, 10 – 60 4294 15540 300 15840 3994 4.0 8 22123 290, 10 – 60 4348 17775 300 18075 4048 4.0 9 24411 320, 10 – 60 4377 20034 300 20334 4077 4.1 10 26700 350, 10 – 60 4416 22284 300 22584 4116 4.1

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport TNO 99-BBI-R065.

Page 44: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler CitrinSolar 3.72 m² 200 l In opdracht van Leylandi Consultancy vof is voor de zonneboiler CitrinSolar 3.72 m² 200 l de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4.9 GJ/jaar

Type: CitrinSolar 3.72 m2 200 l Opdrachtgever: Systeemtype: voorverwarmer Leylandi Consultancy vof methode: test Proosdijstraat 11 6191 AH Beek Vatvolume: 200 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 3.72 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-03961 Geldig tot: 1 december 2011 Op basis van testrapport TNO 99-BBI-R065 23 juni 1999 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 45: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler CitrinSolar 3.72 m² 200 l Nummer verklaring 034-DTM-2010-03961 Prestatie zonneboiler type CitrinSolar 3.72 m² 200 l onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4194 1909 300 2209 3894 3.9

2 8391 110, 10 – 60 5235 3156 300 3456 4935 4.9

3 10680 140, 10 – 60 6086 4594 300 4894 5786 5.8 4 12968 170, 10 – 60 6749 6219 300 6519 6449 6.4 5 15257 200, 10 – 60 7253 8004 300 8304 6953 7 6 17546 230, 10 – 60 7600 9946 300 10246 7300 7.3 7 19834 260, 10 – 60 7852 11982 300 12282 7552 7.6 8 22123 290, 10 – 60 8073 14050 300 14350 7773 7.8 9 24411 320, 10 – 60 8231 16180 300 16480 7931 7.9 10 26700 350, 10 – 60 8389 18311 300 18611 8089 8.1

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden De zonneboiler is identiek aan het systeem waarvoor de opbrengst is vastgesteld, beschreven

in rapport TNO 99-BBI-R065.

Page 46: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

9-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler CitrinSolar 3.72 m² 300 l In opdracht van Leylandi Consultancy vof is voor de zonneboiler CitrinSolar 3.72 m² 300 l de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 5.0 GJ/jaar

Type: CitrinSolar 3.72 m2 300 l Opdrachtgever: Systeemtype: voorverwarmer Leylandi Consultancy vof methode: test Proosdijstraat 11 6191 AH Beek Vatvolume: 300 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 3.72 m2 Collector type: vlakke plaat Collectortest rapport: Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring 034-DTM-2010-03963 Geldig tot: 1 december 2011 Op basis van testrapport TNO 99-BBI-R065 23 juni 1999 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 47: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

9-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler CitrinSolar 3.72 m² 300 l Nummer verklaring 034-DTM-2010-03963 Prestatie zonneboiler type CitrinSolar 3.72 m² 300 l onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4173 1930 300 2230 3873 3.9

2 8391 110, 10 – 60 5295 3096 300 3396 4995 5.0

3 10680 140, 10 – 60 6193 4487 300 4787 5893 5.9 4 12968 170, 10 – 60 6888 6080 300 6380 6588 6.6 5 15257 200, 10 – 60 7411 7846 300 8146 7111 7.1 6 17546 230, 10 – 60 7767 9779 300 10079 7467 7.5 7 19834 260, 10 – 60 8026 11808 300 12108 7726 7.7 8 22123 290, 10 – 60 8252 13871 300 14171 7952 8.0 9 24411 320, 10 – 60 8413 15998 300 16298 8113 8.1 10 26700 350, 10 – 60 8574 18126 300 18426 8274 8.3

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport TNO 99-BBI-R065.

Page 48: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Ritter AquaPaket CPC Star Azzurro In opdracht van Ritter Energie- und Umwelttechnik GmbH & Co. KG is voor de zonneboiler ‘AquaPaket CPC Star Azzurro’ de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Gevolgde methodiek is gebaseerd op de NPR 7976:2004. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,6GJ/jaar

Type: AquaPaket CPC Star Azzurro Opdrachtgever:

Systeemtype: voorverwarmer Ritter Energie- und Umwelttechnik Gmbh & Co. KG

methode: test Küchenäcker 2

D-72135 Dettenhausen Duitsland

Vatvolume: 410 dm3 Tel. +49 7157 5359 1200 Volume geïntegreerde naverwarmer:150 dm3 Fax. +49 7157 5359 1209 www.ritter-gruppe.com Collector oppervlakte: 4.67 m2 Collector type: CPC Vacuümbuis collectoren Collectortest rapport: beschikbaar Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM- 2009-02754 Op basis van testrapport TZSB Prüfbericht Nr.: Sys07_06 Novermber 2007 Geldig tot: 1 december 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant.

Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Page 49: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Aqua Paket CPC Star Azzurro Nummer verklaring TNO-034-DTM- 2009-02754 Prestatie zonneboiler type Aqua Paket CPC Star Azzurro zonneboiler onder Nederlandse

referentie condities.

Referentievraag Jaarlijkse

tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

Paux [W]

Qaux,ref [GJ/jr]

Qaux [GJ/jr]

Qsav [GJ/jr]

2 6,10 080, 10 – 60 128 8.06 4.04 3.8 3 8,39 110, 10 – 60 174 10.34 5.49 4.6 4 10,68 140, 10 – 60 225 12.63 7.10 5.3 5 12,97 170, 10 – 60 280 14.92 8.83 5.8 6 15,26 200, 10 – 60 338 17.21 10.66 6.3

Parasitair elektriciteitsverbruik

Qpar = 0,27 GJ/jr

De energetische besparing is als volgt berekend: ( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2004: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system Qpar Annual parasitic energy QD Annual heat demanded by the user Qsav Annual energy savings Voorwaarden Het zonneboilersysteem is identiek aan het geteste systeem waarvan de opbrengst is

vastgesteld beschreven in rapport TZSB Prüfbericht Nr.: Sys07_06. Opmerkingen: Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2004, deze beschrijft de standaard berekeningswijze en referentiewaarden voor de bepaling van de Nederlandse besparingsindicatoren, in de Engelse taal, echter met de volgende aanpassing: De opbrengst is berekend voor een tapwaterverbruik opgewarmd van 10 naar

60 °C, conform Europese normeringen betreffende warmwaterinstallaties.

Page 50: Opbrengstverklaringen Zonneboilers - TNO

Page 1/2

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Ritter Aqua System CPC 32 Allstar In opdracht van Ritter Energie- und Umwelttechnik GmbH & Co. KG is voor de zonneboiler ‘Aqua System CPC 32 Allstar’ de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Gevolgde methodiek is gebaseerd op de NPR 7976:2004. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,4 GJ/jaar

Type: Aqua System CPC 32 Allstar Opdrachtgever:

Systeemtype: voorverwarmer Ritter Energie- und Umwelttechnik Gmbh & Co. KG

methode: test Küchenäcker 2

D-72135 Dettenhausen Duitsland

Vatvolume: 185 dm3 Tel. +49 7157 5359 1200 Volume geïntegreerde naverwarmer: nvt Fax. +49 7157 5359 1209 www.ritter-gruppe.com Collector oppervlakte: 3.22 m2 Collector type: CPC Vacuümbuis collectoren Collectortest rapport: beschikbaar Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM- 2009-02756 Op basis van testrapport TZSB Prüfbericht Nr.: Sys08_03 Juli 2009 Geldig tot: 1 december 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant.

Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Page 51: Opbrengstverklaringen Zonneboilers - TNO

Page 2/2

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Aqua System CPC 32 Allstar Nummer verklaring TNO-034-DTM- 2009-02756 Prestatie zonneboiler type Aqua System CPC 32 Allstar zonneboiler onder Nederlandse referentie condities.

Referentievraag Jaarlijkse

tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

PL [W]

Qaux [GJ/jr]

Qsav [GJ/jr]

2 6,10 080, 10 – 60 122 2.26 3.6 3 8,39 110, 10 – 60 147 3.76 4.4 4 10,68 140, 10 – 60 163 5.54 4.9 5 12,97 170, 10 – 60 175 7.45 5.3 6 15,26 200, 10 – 60 182 9.52 5.5

Parasitair elektriciteitsverbruik

Qpar = 0,26 GJ/jr

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2004: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system Qpar Annual parasitic energy QD Annual heat demanded by the user Qsav Annual energy savings Voorwaarden Het zonneboilersysteem is identiek aan het geteste systeem waarvan de opbrengst is

vastgesteld beschreven in rapport TZSB Prüfbericht Nr.: Sys08_03. Opmerkingen: Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2004, deze beschrijft de standaard berekeningswijze en referentiewaarden voor de bepaling van de Nederlandse besparingsindicatoren, in de Engelse taal, echter met de volgende aanpassing: De opbrengst is berekend voor een tapwaterverbruik opgewarmd van 10 naar

60 °C, conform Europese normeringen betreffende warmwaterinstallaties.

Page 52: Opbrengstverklaringen Zonneboilers - TNO

Page 1/12

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Rivusol S100-15T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S100-15T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3,2 GJ/jaar

Type: Rivusol S100-15T Opdrachtgever: Systeemtype: voorverwarmer Rivusol BV methode: afgeleide Waldeck Pyrmontstraat 12 5653 AD Eindhoven Vatvolume: 100 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 1,395 m2 Collector type: vacuüm buis Collectortest rapport: KTB Nr. 2007-07-p-en Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 3512 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-03175/A Geldig tot: 1 september 2011 Op basis van testrapport Kiwa Gastec Certification report number 178422 oktober 2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 53: Opbrengstverklaringen Zonneboilers - TNO

Page 2/12

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S100-15T Nummer verklaring 034-DTM-2010-03175/A Prestatie zonneboiler type Rivusol S100-15T onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 2895 3208 200 3408 2695 2.7

2 8391 110, 10 – 60 3376 5015 200 5215 3176 3.2

3 10680 140, 10 – 60 3701 6979 200 7179 3501 3.5 4 12968 170, 10 – 60 3891 9077 200 9277 3691 3.7 5 15257 200, 10 – 60 4020 11237 200 11437 3820 3.8 6 17546 230, 10 – 60 4109 13437 200 13637 3909 3.9 7 19834 260, 10 – 60 4204 15630 200 15830 4004 4.0 8 22123 290, 10 – 60 4279 17844 200 18044 4079 4.1 9 24411 320, 10 – 60 4310 20101 200 20301 4110 4.1 10 26700 350, 10 – 60 4366 22334 200 22534 4166 4.2

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178422.

Page 54: Opbrengstverklaringen Zonneboilers - TNO

Page 3/12

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Rivusol S100-20T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S100-20T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,1 GJ/jaar

Type: Rivusol S100-20T Opdrachtgever: Systeemtype: voorverwarmer Rivusol BV methode: afgeleide Waldeck Pyrmontstraat 12 5653 AD Eindhoven Vatvolume: 100 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 1,86 m2 Collector type: vacuüm buis Collectortest rapport: KTB Nr. 2007-07-p-en Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-03175/B Geldig tot: 1 september 2011 Op basis van testrapport Kiwa Gastec Certification report number 178422 oktober 2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 55: Opbrengstverklaringen Zonneboilers - TNO

Page 4/12

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S100-20T Nummer verklaring TNO-034-DTM-2010-03175/B Prestatie zonneboiler type Rivusol S100-20T onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3560 2543 200 2743 3360 3.4

2 8391 110, 10 – 60 4261 4130 200 4330 4061 4.1

3 10680 140, 10 – 60 4748 5932 200 6132 4548 4.5 4 12968 170, 10 – 60 5054 7914 200 8114 4854 4.9 5 15257 200, 10 – 60 5268 9989 200 10189 5068 5.1 6 17546 230, 10 – 60 5421 12125 200 12325 5221 5.2 7 19834 260, 10 – 60 5574 14260 200 14460 5374 5.4 8 22123 290, 10 – 60 5696 16427 200 16627 5496 5.5 9 24411 320, 10 – 60 5757 18654 200 18854 5557 5.6 10 26700 350, 10 – 60 5849 20851 200 21051 5649 5.6

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178422.

Page 56: Opbrengstverklaringen Zonneboilers - TNO

Page 5/12

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Rivusol S150-15T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S150-15T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 3.2 GJ/jaar

Type: Rivusol S150-15T Opdrachtgever: Systeemtype: voorverwarmer Rivusol BV methode: afgeleide Waldeck Pyrmontstraat 12 5653 AD Eindhoven Vatvolume: 100 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 1.395 m2 Collector type: vacuüm buis Collectortest rapport: KTB Nr. 2007-07-p-en Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 3512 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-03175/C Geldig tot: 1 september 2011 Op basis van testrapport Kiwa Gastec Certification report number 178422 oktober 2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 57: Opbrengstverklaringen Zonneboilers - TNO

Page 6/12

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S150-15T Nummer verklaring TNO-034-DTM-2010-03175/C Prestatie zonneboiler type Rivusol S150-15T onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 2865 3238 200 3438 2665 2.7

2 8391 110, 10 – 60 3363 5028 200 5228 3163 3.2

3 10680 140, 10 – 60 3700 6980 200 7180 3500 3.5 4 12968 170, 10 – 60 3898 9070 200 9270 3698 3.7 5 15257 200, 10 – 60 4032 11225 200 11425 3832 3.8 6 17546 230, 10 – 60 4124 13422 200 13622 3924 3.9 7 19834 260, 10 – 60 4223 15611 200 15811 4023 4.0 8 22123 290, 10 – 60 4301 17822 200 18022 4101 4.1 9 24411 320, 10 – 60 4333 20078 200 20278 4133 4.1 10 26700 350, 10 – 60 4392 22308 200 22508 4192 4.2

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178422.

Page 58: Opbrengstverklaringen Zonneboilers - TNO

Page 7/12

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Rivusol S150-25T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S150-25T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav =4.9 GJ/jaar

Type: Rivusol S150-25T Opdrachtgever: Systeemtype: voorverwarmer Rivusol BV methode: afgeleide Waldeck Pyrmontstraat 12 5653 AD Eindhoven Vatvolume: 150 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2.325 m2 Collector type: vacuüm buis Collectortest rapport: KTB Nr. 2007-07-p-en Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-03175/D Geldig tot: 1 september 2011 Op basis van testrapport Kiwa Gastec Certification report number 178422 oktober 2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 59: Opbrengstverklaringen Zonneboilers - TNO

Page 8/12

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S150-25T Nummer verklaring TNO-034-DTM-2010-03175/D Prestatie zonneboiler type Rivusol S150-25T onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4107 1996 200 2196 3907 3.9

2 8391 110, 10 – 60 5077 3314 200 3514 4877 4.9

3 10680 140, 10 – 60 5759 4921 200 5121 5559 5.6 4 12968 170, 10 – 60 6208 6760 200 6960 6008 6.0 5 15257 200, 10 – 60 6530 8727 200 8927 6330 6.3 6 17546 230, 10 – 60 6767 10779 200 10979 6567 6.6 7 19834 260, 10 – 60 6994 12840 200 13040 6794 6.8 8 22123 290, 10 – 60 7178 14945 200 15145 6978 7.0 9 24411 320, 10 – 60 7282 17129 200 17329 7082 7.1 10 26700 350, 10 – 60 7419 19281 200 19481 7219 7.2

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178422.

Page 60: Opbrengstverklaringen Zonneboilers - TNO

Page 9/12

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Rivusol S150-30T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S150-30T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 5,4 GJ/jaar

Type: Rivusol S150-30T Opdrachtgever: Systeemtype: voorverwarmer Rivusol BV methode: afgeleide Waldeck Pyrmontstraat 12 5653 AD Eindhoven Vatvolume: 150 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2.79 m2 Collector type: vacuüm buis Collectortest rapport: KTB Nr. 2007-07-p-en Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-03175/E Geldig tot: 1 september 2011 Op basis van testrapport Kiwa Gastec Certification report number 178422 oktober 2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 61: Opbrengstverklaringen Zonneboilers - TNO

Page 10/12

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S150-30T Nummer verklaring TNO-034-DTM-2010-03175/E Prestatie zonneboiler type Rivusol S150-30T onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4384 1719 200 1919 4184 4.2

2 8391 110, 10 – 60 5641 2750 200 2950 5441 5.4

3 10680 140, 10 – 60 6543 4137 200 4337 6343 6.3 4 12968 170, 10 – 60 7135 5833 200 6033 6935 6.9 5 15257 200, 10 – 60 7571 7686 200 7886 7371 7.4 6 17546 230, 10 – 60 7898 9648 200 9848 7698 7.7 7 19834 260, 10 – 60 8203 11631 200 11831 8003 8.0 8 22123 290, 10 – 60 8452 13671 200 13871 8252 8.3 9 24411 320, 10 – 60 8605 15806 200 16006 8405 8.4 10 26700 350, 10 – 60 8790 17910 200 18110 8590 8.6

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178422.s

Page 62: Opbrengstverklaringen Zonneboilers - TNO

Page 11/12

1-12

-201

0 15

Opbrengstverklaring

Energetische besparing zonneboiler Rivusol S200-25T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S200-25T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 liter/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4.9 GJ/jaar

Type: Rivusol S200-25T Opdrachtgever: Systeemtype: voorverwarmer Rivusol BV methode: afgeleide Waldeck Pyrmontstraat 12 5653 AD Eindhoven Vatvolume: 200 dm3 Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2.325 m2 Collector type: vacuüm buis Collectortest rapport: KTB Nr. 2007-07-p-en Ondertekening: Goedkeuring:

Ing. H.P. Oversloot Mevr. Ir. L.J.W.M. Krosse Projectleider Afdelingshoofd

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft Ing. H.P. Oversloot T 015 276 35 12 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-03175/F Geldig tot: 1 september 2011 Op basis van testrapport Kiwa Gastec Certification report number 178422 oktober 2009 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Page 63: Opbrengstverklaringen Zonneboilers - TNO

Page 12/12

1-12

-201

0 15

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S200-25T Nummer verklaring TNO-034-DTM-2010-03175/F Prestatie zonneboiler type Rivusol S200-25T onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4105 1998 200 2198 3905 3.9

2 8391 110, 10 – 60 5094 3297 200 3497 4894 4.9

3 10680 140, 10 – 60 5792 4888 200 5088 5592 5.6 4 12968 170, 10 – 60 6250 6718 200 6918 6050 6.1 5 15257 200, 10 – 60 6580 8677 200 8877 6380 6.4 6 17546 230, 10 – 60 6822 10724 200 10924 6622 6.6 7 19834 260, 10 – 60 7054 12780 200 12980 6854 6.9 8 22123 290, 10 – 60 7241 14882 200 15082 7041 7.0 9 24411 320, 10 – 60 7347 17064 200 17264 7147 7.1 10 26700 350, 10 – 60 7486 19214 200 19414 7286 7.3

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178422.

Page 64: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring

Pagina 1/2

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-02508/A Geldig tot: 1 september 2011 Op basis van testrapport Kiwa Gastec Certification report number 178421 oktober 2008 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant.

Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

7-12

-201

0 11

Energetische besparing zonneboiler Rivusol S150-20T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S150-20T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 4,2 GJ/jaar

Type: Rivusol S150-20T Systeemtype: Voorverwarmer methode: Getest systeem Vatvolume: 150 dm3

Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 1,86 m2 Collector type: Vacuümbuis (20 buizen) Collectortest rapport:

Opdrachtgever: Rivusol Waldeck Pyrmontstraat 11 5652 AD Eindhoven

Fraunhofer ISE; KTB Nr. 2007-07-p-en Ondertekening:

T.Epema BSc Projectleider

Goedgekeurd door:

Mevr. Ir. L. J.W.M. Krosse Afdelingshoofd

Page 65: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S150-20T Nummer verklaring TNO-034-DTM-2010-02508/A

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Pagina 2/2

Prestatie zonneboiler type Rivusol S150-20Tzonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 3627 2476 200 2676 3427 3,4

2 8391 110, 10 – 60 4352 4039 200 4239 4152 4,2 3 10680 140, 10 – 60 4857 5823 200 6023 4657 4,7 4 12968 170, 10 – 60 5172 7796 200 7996 4972 5,0 5 15257 200, 10 – 60 5393 9864 200 10064 5193 5,2 6 17546 230, 10 – 60 5550 11996 200 12196 5350 5,4 7 19834 260, 10 – 60 5708 14126 200 14326 5508 5,5 8 22123 290, 10 – 60 5834 16289 200 16489 5634 5,6 9 24411 320, 10 – 60 5897 18514 200 18714 5697 5,7 10 26700 350, 10 – 60 5992 20708 200 20908 5792 5,8

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden De zonneboiler is identiek aan het systeem waarvoor de opbrengst is vastgesteld,

beschreven in rapport Kiwa Gastec Certification report number 178421.

Page 66: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring

Pagina 1/2

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-02508/B Op basis van testrapport Kiwa Gastec Certification report number 178421 oktober 2008 Geldig tot: 1 september 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

7-12

-201

0 11

Energetische besparing zonneboiler Rivusol S200-30T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S200-30T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 5,5 GJ/jaar

Type: Rivusol S200-30T Systeemtype: Voorverwarmer methode: Afgeleid systeem Vatvolume: 200 dm3

Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,79 m2 Collector type: Vacuümbuis (30 buizen) Collectortest rapport:

Opdrachtgever: Rivusol Waldeck Pyrmontstraat 11 5652 AD Eindhoven

Fraunhofer ISE; KTB Nr. 2007-07-p-en Ondertekening:

T.Epema BSc Projectleider

Goedgekeurd door:

Mevr. Ir. L. J.W.M. Krosse Afdelingshoofd

Page 67: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S200-30T Nummer verklaring TNO-034-DTM-2010-02508/B

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Pagina 2/2

Prestatie zonneboiler type Rivusol S200-30Tzonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4420 1683 200 1883 4220 4,2

2 8391 110, 10 – 60 5698 2693 200 2893 5498 5,5 3 10680 140, 10 – 60 6635 4045 200 4245 6435 6,4 4 12968 170, 10 – 60 7241 5727 200 5927 7041 7,0 5 15257 200, 10 – 60 7687 7570 200 7770 7487 7,5 6 17546 230, 10 – 60 8022 9524 200 9724 7822 7,8 7 19834 260, 10 – 60 8334 11500 200 11700 8134 8,1 8 22123 290, 10 – 60 8589 13534 200 13734 8389 8,4 9 24411 320, 10 – 60 8745 15666 200 15866 8545 8,5 10 26700 350, 10 – 60 8934 17766 200 17966 8734 8,7

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178421.

Page 68: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring

Pagina 1/2

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-02508/C Op basis van testrapport Kiwa Gastec Certification report number 178421 oktober 2008 Geldig tot: 1 september 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

7-12

-201

0 11

Energetische besparing zonneboiler Rivusol S250-30T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S250-30T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 5,5 GJ/jaar

Type: Rivusol S250-30T Systeemtype: Voorverwarmer methode: Afgeleid systeem Vatvolume: 250 dm3

Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 2,79 m2 Collector type: Vacuümbuis (30 buizen) Collectortest rapport:

Opdrachtgever: Rivusol Waldeck Pyrmontstraat 11 5652 AD Eindhoven

Fraunhofer ISE; KTB Nr. 2007-07-p-en Ondertekening:

T.Epema BSc Projectleider

Goedgekeurd door:

Mevr. Ir. L. J.W.M. Krosse Afdelingshoofd

Page 69: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S250-30T Nummer verklaring TNO-034-DTM-2010-02508/C

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Pagina 2/2

Prestatie zonneboiler type Rivusol S250-30Tzonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4402 1701 200 1901 4202 4,2

2 8391 110, 10 – 60 5692 2699 200 2899 5492 5,5 3 10680 140, 10 – 60 6638 4042 200 4242 6438 6,4 4 12968 170, 10 – 60 7254 5714 200 5914 7054 7,1 5 15257 200, 10 – 60 7707 7550 200 7750 7507 7,5 6 17546 230, 10 – 60 8046 9500 200 9700 7846 7,8 7 19834 260, 10 – 60 8363 11471 200 11671 8163 8,2 8 22123 290, 10 – 60 8621 13502 200 13702 8421 8,4 9 24411 320, 10 – 60 8779 15632 200 15832 8579 8,6 10 26700 350, 10 – 60 8971 17729 200 17929 8771 8,8

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178421.

Page 70: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring

Pagina 1/2

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-02508/D Op basis van testrapport Kiwa Gastec Certification report number 178421 oktober 2008 Geldig tot: 1 september 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

7-12

-201

0 11

Energetische besparing zonneboiler Rivusol S250-40T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S250-40T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 6,1 GJ/jaar

Type: Rivusol S250-40T Systeemtype: Voorverwarmer methode: Afgeleid systeem Vatvolume: 250 dm3

Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 3,72 m2 Collector type: Vacuümbuis (40 buizen) Collectortest rapport:

Opdrachtgever: Rivusol Waldeck Pyrmontstraat 11 5652 AD Eindhoven

Fraunhofer ISE; KTB Nr. 2007-07-p-en Ondertekening:

T.Epema BSc Projectleider

Goedgekeurd door:

Mevr. Ir. L. J.W.M. Krosse Afdelingshoofd

Page 71: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S250-40T Nummer verklaring TNO-034-DTM-2010-02508/D

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Pagina 2/2

Prestatie zonneboiler type Rivusol S250-40Tzonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4756 1347 200 1547 4556 4,6

2 8391 110, 10 – 60 6267 2124 200 2324 6067 6,1 3 10680 140, 10 – 60 7556 3124 200 3324 7356 7,4 4 12968 170, 10 – 60 8655 4313 200 4513 8455 8,5 5 15257 200, 10 – 60 9455 5802 200 6002 9255 9,3 6 17546 230, 10 – 60 10006 7540 200 7740 9806 9,8 7 19834 260, 10 – 60 10503 9331 200 9531 10303 10,3 8 22123 290, 10 – 60 10915 11208 200 11408 10715 10,7 9 24411 320, 10 – 60 11196 13215 200 13415 10996 11,0 10 26700 350, 10 – 60 11504 15196 200 15396 11304 11,3

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178421.

Page 72: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring

Pagina 1/2

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-02508/E Op basis van testrapport Kiwa Gastec Certification report number 178421 oktober 2008 Geldig tot: 1 september 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

7-12

-201

0 11

Energetische besparing zonneboiler Rivusol S300-40T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S300-40T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 6,1 GJ/jaar

Type: Rivusol S300-40T Systeemtype: Voorverwarmer methode: Afgeleid systeem Vatvolume: 300 dm3

Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 3,72 m2 Collector type: Vacuümbuis (40 buizen) Collectortest rapport:

Opdrachtgever: Rivusol Waldeck Pyrmontstraat 11 5652 AD Eindhoven

Fraunhofer ISE; KTB Nr. 2007-07-p-en Ondertekening:

T.Epema BSc Projectleider

Goedgekeurd door:

Mevr. Ir. L. J.W.M. Krosse Afdelingshoofd

Page 73: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S300-40T Nummer verklaring TNO-034-DTM-2010-02508/E

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Pagina 2/2

Prestatie zonneboiler type Rivusol S300-40Tzonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4726 1377 200 1577 4526 4,5

2 8391 110, 10 – 60 6259 2132 200 2332 6059 6,1 3 10680 140, 10 – 60 7559 3121 200 3321 7359 7,4 4 12968 170, 10 – 60 8664 4304 200 4504 8464 8,5 5 15257 200, 10 – 60 9471 5786 200 5986 9271 9,3 6 17546 230, 10 – 60 10027 7519 200 7719 9827 9,8 7 19834 260, 10 – 60 10529 9305 200 9505 10329 10,3 8 22123 290, 10 – 60 10945 11178 200 11378 10745 10,7 9 24411 320, 10 – 60 11229 13182 200 13382 11029 11,0 10 26700 350, 10 – 60 11539 15161 200 15361 11339 11,3

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178421.

Page 74: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring

Pagina 1/2

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-02508/F Op basis van testrapport Kiwa Gastec Certification report number 178421 oktober 2008 Geldig tot: 1 september 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

7-12

-201

0 11

Energetische besparing zonneboiler Rivusol S300-50T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S300-50T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 6,4 GJ/jaar

Type: Rivusol S300-50T Systeemtype: Voorverwarmer methode: Afgeleid systeem Vatvolume: 300 dm3

Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 4,65 m2 Collector type: Vacuümbuis (50 buizen) Collectortest rapport:

Opdrachtgever: Rivusol Waldeck Pyrmontstraat 11 5652 AD Eindhoven

Fraunhofer ISE; KTB Nr. 2007-07-p-en Ondertekening:

T.Epema BSc Projectleider

Goedgekeurd door:

Mevr. Ir. L. J.W.M. Krosse Afdelingshoofd

Page 75: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S300-50T Nummer verklaring TNO-034-DTM-2010-02508/F

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Pagina 2/2

Prestatie zonneboiler type Rivusol S300-50Tzonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4815 1288 200 1488 4615 4,6

2 8391 110, 10 – 60 6631 1760 200 1960 6431 6,4 3 10680 140, 10 – 60 8068 2612 200 2812 7868 7,9 4 12968 170, 10 – 60 9323 3645 200 3845 9123 9,1 5 15257 200, 10 – 60 10455 4802 200 5002 10255 10,3 6 17546 230, 10 – 60 11466 6080 200 6280 11266 11,3 7 19834 260, 10 – 60 12262 7572 200 7772 12062 12,1 8 22123 290, 10 – 60 12850 9273 200 9473 12650 12,7 9 24411 320, 10 – 60 13281 11130 200 11330 13081 13,1 10 26700 350, 10 – 60 13724 12976 200 13176 13524 13,5

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178421.

Page 76: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring

Pagina 1/2

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Bouw en installaties Van Mourik Broekmanweg 6 Postbus 49 2600 AA Delft T. Epema BSc T 015 276 34 94 [email protected] www.tno.nl Nummer verklaring TNO-034-DTM-2010-02508/G Op basis van testrapport Kiwa Gastec Certification report number 178421 oktober 2008 Geldig tot: 1 september 2011 Deze verklaring is tot stand gekomen door een eenmalige beoordeling van de specifieke eigenschappen van een exemplaar van een product of een uitvoering van een systeem. Deze verklaring geeft geen oordeel over andere exemplaren van een product of van andere uitvoeringen van systemen. Deze verklaring geeft geen oordeel over de kwaliteitsborging van producten of systemen, dit is de verantwoordelijkheid van de fabrikant. Alle rechten voorbehouden. Niets uit dit rapport mag worden vermenigvuldigd en/of openbaar gemaakt door middel van druk, fotokopie, microfilm of op welke andere wijze dan ook, zonder voorafgaande schriftelijke toestemming van TNO. Indien dit rapport in opdracht werd uitgebracht, wordt voor de rechten en verplichtingen van opdrachtgever en opdrachtnemer verwezen naar de Algemene Voorwaarden voor onderzoeksopdrachten aan TNO, dan wel de betreffende terzake tussen de partijen gesloten overeenkomst. Het ter inzage geven van het TNO-rapport aan direct belanghebbenden is toegestaan. © 2010 TNO

7-12

-201

0 11

Energetische besparing zonneboiler Rivusol S500-60T In opdracht van Rivusol BV is voor de zonneboiler Rivusol S500-60T de energetische besparing vastgesteld, bestemd voor subsidieregeling “duurzame warmte voor bestaande woningen”. Opbrengstberekeningen zijn uitgevoerd overeenkomstig de NPR 7976:2009. Het hieronder beschreven systeem geeft, bij een referentie warmtapwaterverbruik van 110 l/dag verwarmd van 10 naar 60°C, de volgende jaarlijkse energetische besparing: Qsav = 6,5 GJ/jaar

Type: Rivusol S500-60T Systeemtype: Voorverwarmer methode: Afgeleid systeem Vatvolume: 500 dm3

Volume geïntegreerde naverwarmer: nvt Collector oppervlakte: 5.58 m2 Collector type: Vacuümbuis (60 buizen) Collectortest rapport:

Opdrachtgever: Rivusol Waldeck Pyrmontstraat 11 5652 AD Eindhoven

Fraunhofer ISE; KTB Nr. 2007-07-p-en Ondertekening:

T.Epema BSc Projectleider

Goedgekeurd door:

Mevr. Ir. L. J.W.M. Krosse Afdelingshoofd

Page 77: Opbrengstverklaringen Zonneboilers - TNO

Opbrengstverklaring Energetische besparing zonneboiler Rivusol S500-60T Nummer verklaring TNO-034-DTM-2010-02508/G

Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research

Pagina 2/2

Prestatie zonneboiler type Rivusol S500-60Tzonneboiler onder Nederlandse referentie condities.

Referentie-vraag

Jaarlijkse tapvraag, QD [GJ/jr]

Equivalent tapwaterverbruik

[liter/dag], [°C]

QL [MJ/jr]

Qaux [MJ/jr]

Qpar [MJ/jr]

Qext [MJ/jr]

Qsav [MJ/jr]

Qsav [GJ/jr]

1 6103 080, 10 – 60 4544 1559 200 1759 4344 4,3

2 8391 110, 10 – 60 6663 1728 200 1928 6463 6,5 3 10680 140, 10 – 60 8393 2287 200 2487 8193 8,2 4 12968 170, 10 – 60 9771 3197 200 3397 9571 9,6 5 15257 200, 10 – 60 11033 4224 200 4424 10833 10,8 6 17546 230, 10 – 60 12214 5332 200 5532 12014 12,0 7 19834 260, 10 – 60 13321 6513 200 6713 13121 13,1 8 22123 290, 10 – 60 14334 7789 200 7989 14134 14,1 9 24411 320, 10 – 60 15039 9372 200 9572 14839 14,8 10 26700 350, 10 – 60 15639 11061 200 11261 15439 15,4

De energetische besparing is als volgt berekend:

( )parauxrefauxsav QQQQ +−= ,

Met Drefaux QQ =,

Waarin, zoals beschreven in NPR 7976:2009: Qaux Annual auxiliary energy Qaux,ref Annual heat consumption of a non-solar reference system QD Annual heat demanded by the user Qext Annual total external energy QL Annual solar energy delivered to the load Qpar Annual parasitic energy Qsav Annual energy savings Voorwaarden Het zonneboilersysteem voldoet aan de criteria voor afgeleide systemen uit een

productfamilie zoals gesteld in Annex C van NPR 7976:2009 en behoort tot de productfamilie van het systeem waarvoor de opbrengst is vastgesteld, beschreven in rapport Kiwa Gastec Certification report number 178421.