E300 UPS Datasheet
Transcript of E300 UPS Datasheet
7/29/2019 E300 UPS Datasheet
http://slidepdf.com/reader/full/e300-ups-datasheet 1/1
UPS DAERSKINE E200 SERIES – 1 PH INPUTRSKINE
Dale Power Solutions plc Salter Road, Eastfield Industrial Estate, Scarborough, North Yorkshire, YO11 3DU, UK
Telephone: +44 (0) 1723 514141/583511Email: [email protected]
Website: www.dalepowersolutions.com S5264EU05rev1
Dale Power Solutions plc
UUPPSS DDAATTAASSHHEEEETT EErrsskkiinnee EE330000 SSeerriieess – – TThhrreeee PPhhaassee 1100 ttoo 440000kkVVAA
FFeeaattuurreess
• High frequency & double conversion on-line technology• Selectable ECO mode with 98% efficiency on 160 – 400kVA units• Fully digitized microprocessor control• Wide input voltage range• LCD display• Cold start• Parallel capacity (maximum of 6 units)• Advanced battery management• Automatic battery charge in UPS off mode• Lightning & surge protection• Short circuit and overload protection• Fan speed auto control when loads varies• EMI/RFI noise filter• Smart RS232 communication with monitoring software• External battery• Optional SNMP Card slot
Common Specifications
Voltage Range 184V AC to 276V AC Line to Neutral
Phase 3 Phase 4 Wire & Earth
Input
Frequency 45Hz to 65Hz
Input Rectifier 6 pulse 10 -120 kVA, 12 pulse 160 - 400 kVAVoltage 220/230/240V AC Line to Neutral (User adjustable)Phase 3 Phase 4 Wire & Earth
Frequency 50HzTHD (linear load) < 2%
THD (non-linear mode) < 6%Wave Form Sine waveOverload Capacity 110%: 300 min, 125%: 10 min, 150%: 1 min
Crest Factor 3:1 (max)Power Factor 0.8
Short Circuit Protection 0.1s 200%
Output
Transfer Time 0 ms ( 2 – 5ms in ECO Mode)
Operating Altitude 1000m at rated power (De-rate at 1% for each 100m over 1000m) max 4000mOperate Temperature 0ºC to 40ºC
Storage Temperature -25ºC to +55ºC
Environment
Relative humidity 95%Communication Standard: RS232, Optional: SNMP
LCD Touch ScreenDisplay
Measurements: Input & output voltage/frequency, battery voltage, load power & kVA, UPS temperatureOperation mode: i.e. Online, On Battery, Bypass
Operation mode Double conversion online technology
LED Indication Mimic of UPS status
Noise Level See table
Safety & EMC CE Marked to 2006/95/EC & 2004/108/EC Tested to EN62040-1-1:2003 & EN62040-2:2006
Standard Accessories Control software, Data lead, & User manuals
Specifications
Input Output Battery Environment Weights & DimensionsModel Part
Number
Output
kVA
Ratings
kW Power factor Efficiency(full load) Efficiency(half load) DC Voltage(Volts) Noise(dBA) Weight (kg)Net/Gross Unit(H x W x D)E310 10 8 0.8 90% 88% 384 48-54 223 / 280 1220 x 555 x 725 mm
E320 20 16 0.8 91% 89% 384 53-60 260 / 317 1220 x 555 x 725 mmE330 30 24 0.8 91% 89% 384 53-60 336 / 390 1220 x 555 x 725 mmE340 40 32 0.8 92% 90% 384 53-62 351 / 408 1220 x 555 x 725 mmE360 60 48 0.8 92% 91% 384 53-62 497 / 574 1400 x 800 x 745 mm
E380 80 64 0.8 92% 91% 384 53-62 556 / 633 1400 x 800 x 745 mm
E3100 100 80 0.8 93% 92% 432 54-62 576 / 856 1400 x 1070 x 745 mmE3120 120 96 0.8 93% 92% 480 54-62 901 / 1001 1400 x 1070 x 745 mm
E3160 160 128 0.9 93% 92% 480 60-65 1300 / 1400 1810 x 1420 x 745 mmE3200 200 160 0.9 93% 92% 480 60-65 1350 / 1450 1810 x 1420 x 745 mm
E3250 250 200 0.9 93% 92% 480 60-65 2100 / 2200 1805 x 1770 x 750 mmE3300 300 240 0.9 93% 93% 480 70 2450 / 2600 1900 x 1630 x 1000 mm
E3400 400 320 0.9 93% 93% 480 70 2850 / 3000 1900 x 1630 x 1000 mm
Dale Power Solutions plc reserves the right to make changes in specification without notice or liability. All information is subject to Dale Power Solutions own data & is considered accurate at time of publishing.