AC Fan Coil Air Conditioning Unit Climate 5000 -...
Transcript of AC Fan Coil Air Conditioning Unit Climate 5000 -...
AC Fan Coil Air Conditioning Unit
Climate 5000 FC02-14CC23/1P1L(R)GE| FC02-14CC23/1P2L(R)GE| FC02-14CC23/1P3L(R)GE|
FC02-14CB23/1P1L(R)GE| FC02-14CB23/1P2L(R)GE| FC02-14CB23/1P3L(R)GE|
FC02-14CD23/1P1L(R)GE| FC02-14CD23/1P2L(R)GE| FC02-14CD23/1P3L(R)GE
en Installation, Operation and Maintenance Manual
8736
863650
(2017/05
)CN
ORIGINAL MANUAL
Observe the warnings in the manuals!
Installation by an authorised person only!
Read the manual carefully prior to installation and operation of this unit!
Welcome | 2
Climate 5000 8736863650(2017/05) en
WELCOME
Distinguished users:
Thank you for choosing and using the products
of our company!
Our products have high quality and excellent
performance. For ease of use, please read the
Manual carefully and operate as per the steps
as described in the Manual. We will be with you
all along. Please feel free to contact us at the
number and address on the Warranty Card
whenever you have any problems. We are
ready to serve you.
Due to product improvement, the product you
have purchased may be slightly different from
those introduced in the Manual. We hereby
apologize for the trouble we cause.
Important prompt:
• Air conditioner with fan coil is the terminal
device of air conditioning system for water
chilling unit, which requires expertise and has
strict specifications and requirements.
Therefore, it must be installed, commissioned,
operated and managed by professionally
trained technical personnel.
• The air conditioner can be used widely,
except wet zone, outdoors, the environment
with blowing dust and corrosion, and the site
with explosion hazard;
• Operating conditions:
- Power supply: 1PH/ 230V/ 50Hz
- Maximum operating pressure: ≤1.6MPa
- Normal testing condition:
Cooling: entering air temp 27˚C DB/19.5˚C
WB, entering water temp 7˚C, leaving water
temp 12˚C;
Heating: entering air temp 21˚C, entering
water temp 60˚C, the same water flow as in
cooling;
- Sound pressure level are measured in
acoustic room, position of the measure
point is 1m in the front and 1m below the
vertical center line of the unit;
- Static pressure is measured without filter
and air outlet;
- Sound pressure level is less than 70dB.
Our company adheres to the principle of
commitment to excellence, and may not inform
you of certain improvement in specification,
performance, material and structure of such
products. Sorry for the inconvenience. Please
contact us for obtaining the latest information.
3 | Table of Contents
8736863650(2017/05) en Climate 5000
Table of Contents
1 Key to symbols and safety instructions ...... 4
1.1 Explanation of symbols .............................. 4
1.2 Safety information ...................................... 4
2 Product descriptions ..................................... 6
2.1 Product characteristics .............................. 6
2.2 Applicable models ...................................... 6
3 Outline dimension drawing and weight ....... 7
4 Unit installation ............................................... 8
4.1 Equipment acceptance .............................. 8
4.2 Installation considerations ......................... 8
4.3 Installation .................................................. 8
4.4 Connection of ventilation duct ................... 9
4.5 Pipeline connection ................................... 9
4.5.1 Connection of chilled water pipeline ... 9
4.5.2 Connection of condensate water
pipeline ......................................................... 9
4.6 Electrical wiring ........................................ 10
4.7 Design and installation of return air case 10
5 Installation inspection and startup ............. 13
5.1 Installation inspection .............................. 13
5.2 Startup and operation .............................. 13
5.3 Air discharge ............................................ 13
6 Unit maintenance ......................................... 14
7 Common faults and solutions ..................... 16
8 Packing list .................................................... 17
9 Appendix ....................................................... 17
Key to symbols and safety instructions | 4
Climate 5000 8736863650(2017/05) en
1 Key to symbols and safety instructions
1.1 Explanation of symbols
Warnings
Warnings in this document are framed and identified by a warning triangle which is printed on a grey back- ground. The signal word attached indicates the type and severity of consequence due to nonobservance of danger prevention measures.
Keywords indicate the seriousness of the
hazard in terms of the consequences of not
following the safety instructions.
• NOTICE indicates that material damage may
occur.
• CAUTION indicates that minor to medium
injury may occur.
• WARNING indicates that serious injury may
occur.
• DANGER indicates possible risk to life.
Important information
Important information in cases where there is no risk of personal injury or material losses is identified by the symbol shown on the left. It is bordered by horizontal lines above and below the text.
Additional symbols
Symbol Meaning
a step in an action sequence
a reference to a related part in the document or to other related document
a list entry
- a list entry (second level)
Table 1: Additional symbols
1.2 Safety information
Notice: Please entrust the dealer or professionals with the installation.
Notice: Maintain the unit regularly as per the requirements in the Manual to ensure good running state of the unit.
Notice: If the unit stops due to failure, please refer to the Section "Common faults and solutions"/ contact local dealer/ after-sales service personnel of our company. Restart the unit after the trouble is removed. It is not allowed to start up the unit with the problem unsolved.
Caution: Please use the fuse with specified capacity. Do not replace it with copper wire and iron wire.
Caution: Please connect the cables correctly. Wrong cable connection may damage electrical components.
Caution: In case there is a fire, shut off main power source and put out the fire with a fire extinguisher immediately. Confirm whether the installation foundation and hoisting are secure and reliable. If the foundation and hoisting are not secure and reliable enough, falling accident may occur.
5 | Key to symbols and safety instructions
8736863650(2017/05) en Climate 5000
Warning: Be sure to use the product designated by our company if the goods must be purchased in local place.
Warning: Comply with regulations of local electric company when connecting power supply.
Warning: If the unit needs to be moved or reinstalled, please entrust the dealer or professionals with the operation.
Danger: It is forbidden to install in the place where combustible gas is easy to leak. The leakage of combustible gas may easily cause fire.
Danger: Ground reliably as per standard provisions. Poor grounding may cause people to get an electric shock.
Danger: Confirm whether leakage circuit breaker is installed. The circuit breaker must be installed; otherwise electric shock may occur.
Danger: Inappropriate installation may lead to fire, electric shock and personal injury. No modification or repair without permission shall be allowed.
Danger: Inappropriate repair may lead to fire, electric shock and personal injury. Be sure to entrust the dealer/ professionals with the repair.
Pay attention to the following issues:
• This appliance can be used by children aged
from 8 years and above and persons with
reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they
have been given supervision or instruction
concerning use of the appliance in a safe way
and understand the hazards involved. Children
shall not play with the appliance. Cleaning and
user maintenance shall not be made by children
without supervision.
• Operate the fan coil within this range:
- Regarding installation altitude below 1000m;
- Regarding frequency of supply power within
±1%Hz of rated frequency;
- Regarding electric supply voltage within
+/-10%;
- Regarding transport / storage temperature
within -25~55°C.
• The appliance is not accessible to the general
public.
Warning: The installation height of unit should be no less than 2.5 meters from ground.
Product descriptions | 6
Climate 5000 8736863650(2017/05) en
2 Product descriptions
The fan coil type air conditioner consists mainly
of centrifugal fan, coil heat exchanger and other
components. As the terminal device of air
conditioning system for water chilling unit, it is
wildly used in hotel, restaurant, factory, hospital,
exhibition hall, shopping mall and office building
and other houses with many rooms or
large-sized industrial and civil buildings required
for air conditioning to meet the demand for
cooling, dehumidification and heating, thus
creating a working and living environment which
is full of fresh air, peacefulness and spring-like
weather.
2.1 Product characteristics
• Safe, reliable and long service life
Each coil heat exchanger is subject to pressure
test; made of forging brass, the pipes (water
collecting head) for inlet and outlet water are
reliable and durable; water collection pan is
produced through one-step molding with
stamping die, and sprayed with anti-rust paint;
motor is equipped with low-noise rolling bearing
which can run for more than 60000 h without the
need for lubricating and maintenance; the long
shaft of motor is specially treated to eliminate
corrosion.
• High efficiency and sufficient capacity
The fan coil is formed by wrapping seamless
copper pipe through slit aluminum fins and
allowing them to tightly combine into one by
mechanical expansion. This technology enables
high heat transfer efficiency and adequate
cooling (heating) capacity.
• Large air volume and low noise
With metal volute and centrifugal impeller
featuring many blades available, the fan coil
comes in many desirable matches between
motor and fan to accommodate its needs for
various specifications.
• Versatility
The fan coil is provided with heat exchanger
which permits right and left interchange and
offers ease for maintenance and servicing. Water
can be supplied either from the left or from the
right, and the interchange can be done easily to
meet the personalized needs of each customer.
2.2 Applicable models − FC02-14CC23/1P1L(R)GE
− FC02-14CC23/1P2L(R)GE
− FC02-14CC23/1P3L(R)GE
− FC02-14CB23/1P1L(R)GE
− FC02-14CB23/1P2L(R)GE
− FC02-14CB23/1P3L(R)GE
− FC02-14CD23/1P1L(R)GE
− FC02-14CD23/1P2L(R)GE
− FC02-14CD23/1P3L(R)GE
Note:
There are not FC14**23/1P3*GE for countries
with CE certificate requirement.
7 | Outline dimension drawing and weight
8736863650(2017/05) en Climate 5000
3 Outline dimension drawing and weight Outline dimension drawing andweight of concealed horizontal unit
Outline dimension drawing of concealedhorizontal unit with down return air box
Outline dimension drawing of concealedhorizontal unit with rear return air box
Figure 1: Outline dimension and installation drawing
Model
Outline Dimension Drawing and Weight of Concealed Horizontal Fan Coil Unit
Outline Dimension Drawing and Weight of Concealed Horizontal Fan Coil Unit With Air Return Cast
Dimension Weight (kg)
Dimension Weight (kg)
A/mm B/mm C/mm 3RR A/mm B/mm C/mm D/mm 3RR
FC-02 700 508 478 11.5 700 508 478 444 13.9
FC-03 850 668 638 14.3 850 668 638 604 17.4
FC-04 1000 808 778 16.2 1000 808 778 744 19.6
FC-05 1000 808 778 16.2 1000 808 778 744 19.6
FC-06 1150 938 908 18.0 1150 938 908 874 21.5
FC-08 1470 1238 1208 23.3 1470 1238 1208 1174 28.3
FC-10 1630 1498 1468 28.8 1630 1498 1468 1434 34.2
FC-12
FC-14 1900 1758 1728 33.6 1900 1758 1728 1694 39.5
Table 2: Outline dimension and weight
1900 1758 1728 33.6 1900 1758 1728 1694 39.5
Unit installation | 8
Climate 5000 8736863650(2017/05) en
4 Unit installation
4.1 Equipment acceptance
Each fan coil unit is wrapped with corrugated
box to prevent the unit from damage during
hauling, handling and on-site storage. To
ensure there is no damage during hauling,
please inspect as per the following steps during
acceptance:
► Before signing off, please inspect whether
each unit is in good condition, and the edges
and corners of carton are intact without
obvious damage sign;
► If the carton is obviously damaged, open it
immediately and inspect main part of the unit.
If main part is damaged, please expound
actual situation in the receiving note and
reject the goods. Additionally, inspect the
accessories;
► Inspect the unit for concealed damage. Do
not move the unit at the receiving site in
case of any such damage. The recipient has
the obligation to prove that the concealed
damage doesn't occur after delivery. If there
is concealed damage, stop unloading and
take pictures as evidence;
► If any damage is found, please inform the
carrier and require the carrier and consignee
to carry out joint inspection;
► Do not repair before the inspection and
confirmation by the carrier's representative.
► If damage is confirmed, contact relevant
personnel for replacement.
4.2 Installation considerations Notice: To ensure smooth installation and operation, please inspect the following items before installing the unit:
► There is sufficient space for installing and
maintaining the unit. See the outline
dimension drawing for specific unit size.
Movable ceiling or access hole must be
reserved for daily maintenance;
► Please confirm the position of pipeline and
electrical wiring before installation;
► Please inspect whether the hoisting
structure can bear the weight of unit;
► All the units must be installed horizontally to
the extent of ensuring smooth drainage and
normal operation;
► Make sure the unit connecting to the
ventilation duct has static pressure within
allowable range;
► The heat preservation of chilled water valve
(tee valve) and pipeline shall be provided by
the installation contractor.
4.3 Installation
9 | Unit installation
8736863650(2017/05) en Climate 5000
Notice: The levelness of fan coil shall be adjusted on the basis of its shell, because the coil and water pan have been designed with certain slope for smooth drainage.
Refer to outline dimension and installation
drawing for installation of fan coil unit. There are
mounting holes on the top of the unit and
therefore can be lifted under the slab by boom.
Please complete the following steps during
installation:
► The installation contractor installs the boom
or other hoisting parts;
► Screw in the upper nut and gasket on the top
to ensure the unit will not move during
operation;
► Put the boom into the mounting hole;
► Screw in the lower nut and gasket to fix the
unit, tighten the lower nut, adjust the unit's
levelness to ensure smooth drainage of
condensate water, screw up the upper nut.
4.4 Connection of ventilation duct
The ventilation duct (supplied by the installation
contractor) made of galvanized steel sheet with
certain thickness can be connected to the
turnups (flanges) of unit inlet and outlet. Refer
to outline dimension drawing for size. Insert the
ventilation duct into the turnups and fix with
screws; a adapter fabricated at the site will be
used if the sizes of turnup and ventilation are
inconsistent. Method for connecting with air
supply case and ventilation duct: insert the
ventilation duct into the turnups, fasten it with
screws or rivets horizontally, and flush the
ventilation duct with the turnups. Connect the
return air pipe by the method described above.
4.5 Pipeline connection Notice: Provide heat preservation measures for both chilled water pipe and condensate water pipe and pay special attention to the treatment at the ends of heat preservation materials to prevent condensation during in cooling mode running.
4.5.1 Connection of chilled water pipeline
Connect chilled water pipeline with fan coil by
using 3/4" male adapter. Keep the water inlet
and outlet of fan coil down and up respectively.
See the outline dimension drawing for the size
of coil interface. If the direction for pipe
connection needs to be changed, replace
before hoisting.
For fixing pipe adapter, be sure to fix the base
of square adapter on fan coil with one wrench,
and then tighten the pipe adapter with another
wrench. Do not fasten the pipe adapter directly
because this may result in deformed and even
damaged unit adapter.
4.5.2 Connection of condensate water pipeline
The pipe for condensate water can be made
either of PVC materials or steel. It should be
connected with hose whose length is not greater
than 300 m. The hose should be preferably
Unit installation | 10
Climate 5000 8736863650(2017/05) en
rubber hose. Connect condensate pipe with
hose by hose clamp to prevent leaks. It is
recommended that the gradient of drain pipe
should be 1:50 at least.
4.6 Electrical wiring Warning: Be sure to disconnect power supply before unit maintenance to prevent personal injury. The wire to be connected should be made of copper as conductors of other types may overheat and damage unit.
• Refer to electrical wiring diagram in page 11
for electrical wiring→Figure 4.
• The earth points provided by the unit are
required to connect to the earthing system at
the installation site.
• All electrical wiring must conform to local
electrical appliance installation specification.
4.7 Design and installation of return air
case
• Pay attention to the following issues:
N For the fan exposed model of the unit, returnair case must be installed.
N For low static pressure model unit, be sure to connect the terminals for high, medium and low speeds to three-speed switch (or fan coil controller);
N For high static pressure model unit, be sure to connect the terminals for ultrahigh, high and medium speeds to three-speed switch (or fan coil controller);
N One three-speed switch (or fan coil controller) is designed only to control one fan coil unit.
Figure 2: Installation of return air case
In concealed installation, return air case must be
designed and provided.
The distance between outlet of air duct and of air
conditioner depends on the length of actually
installed air duct and static pressure terminal used,
as shown in the schematic diagram for installation
of long and short air ducts. When short air duct is
used, the outlet of air duct should be no more than
0.5 m away from that of air conditioner if motor runs
with speed under low static pressure; when long air
duct is applied, their distance can be within 5 m if
motor runs with speed under high static pressure.
All lifting holes of the unit shall be provided with
booms.
Warning: Be sure to wire as per requirements, otherwise motor may burn out.
Warning: Completely cut off all power devices during installation work and keep 3mm gap at least.
Top surface of building for installation
/
Outtake
Return air
Return air case
Machine
Air supply
Ceiling
Return air Return air
case Machine
Air supply
Outlet grid
A enlarged
No obstructions within 1 m
11 | Unit installation
8736863650(2017/05) en Climate 5000
Figure 3: Installation diagram
Figure 4: Electric wiring diagram
Note:
• The terminals on terminal block for low, medium,
high and ultrahigh speeds are connected with
controller of fan coil (or three-speed switch).
• The controller of fan coil is connected with
terminals for low, medium and high speeds when
the static pressure at unit outlet is 12 Pa;
− The controller of fan coil is connected with
terminals for medium, high and ultrahigh
speeds when the static pressure at unit outlet
is 30 Pa;
− The controller of fan coil is connected with
terminals for medium, high and ultrahigh
speeds when the static pressure at unit outlet
is 50 Pa. Alternatively, user can interchange at
site as required.
• The motor 2 is used for fan coil equipped with
single motor and wired appropriately.
• Appliance
• Power supply wiring specification
- Power supply: 230±10%V, 50Hz;
- Specification of power line: H05VV-F
3G0.75mm2;
- Specification of communication line: connect
4*0.75 mm2 wires. Communication line
adopts metallic hose for insulation.
Fuse match: Fusing current is no less than twice
the load current.
Circuit breaker match: Rated current of circuit
breaker is more than maximum current of all loads.
An all-pole disconnection device which has at
least 3mm separation distance in all pole and a
residual current device (RCD) with the rating of
above 10mA shall be incorporated in the fixed
wiring according to the local rule.
Expansion bolt of M8 wide
Locking washer of M8 wide
Unit
Air discharge
pipe
Transition air pipe
Return air louver
Return air pipe
Drain pipe
Lifting hook M8 hanging bolt
M8 nut Air outlet
Installation inspection and startup | 12
Climate 5000 8736863650(2017/05) en
5 Installation inspection and startup
5.1 Installation inspection
Warning: Be sure to disconnect power supply before inspection to avoid personnel injury.
Installation personnel must check and verify the
installation steps mentioned above as per the
following requirements.
N Unit is securely connected with boom and slab;
N Ventilation pipes are connected firmly;
N Water pipes are connected without leakage;
N Drain pipes are connected without leakage;
N Electrical control system is wired, without loose
contact, missed connections and other
undesirable signs.
N Installation personnel have read manual, have
been basically familiar with the unit and capable
of operating.
5.2 Startup and operation The operation of fan coil unit can be controlled by
three-speed switch of motor or temperature
controller.
The temperature controller consists of one
three-speed switch of motor, one ON/OFF switch
and one component for temperature control. The
component for temperature control is designed to
control the opening/close of chilled water valve,
and generally provided with one dial for setting
temperature.
The three-speed switch is marked with
Off/High/Medium/Low for controlling the speed of
motor and thus adjusting air volume.
5.3 Air discharge When water flows in the system for the first time,
partial gas may remain in the coil and mainly
appear at the top of the coil. A manual vent valve
is installed on the top of water outlet adapter of
the coil. Rotate the valve's rotary knob to exhaust
when residual air in the coil makes abnormal
noise. If the rotary knob is too tight, use pliers to
rotate for one to two rounds anticlockwise, so as
to exhaust the air, until water flows out from the
vent valve steadily. After that, tighten up the rotary
knob.
13 | Unit maintenance
8736863650(2017/05) en Climate 5000
6 Unit maintenance
• Checklist for Periodical Maintenance
Warning: Be sure to disconnect the power supply before unit maintenance to avoid electric shock. Moreover, set up signboard marking "Under Maintenance, Do Not Turn On” to prevent danger due to incorrect operation.
The unit should be maintained by authorized
person, through daily monitoring and regular
servicing. Below is a recommended maintenance
plan.
Frequency Checklist for maintenance inspection
Each month
N Inspect filter screen of unit, clean or replace it regularly; carry out more frequent maintenance when system operates under high load or air quality is quite poor.
N Inspect water pan for contamination and condensate water for its ability to flow into drain pipe naturally.
Each year
N Inspect the shell of unit for corrosion, and clean and set it right;
N Inspect fan blade and scroller for damage. Rotate fan blade manually to verify its smooth rotation without obstruction;
N Inspect coil fins for dirt and damage;
N Clean and tighten all connected wires.
N Drain chilled water from the whole system, remove fouling and replace with water.
Table 3: Checklist for periodical maintenance
If it is necessary to drain all chilled water in heat
exchanger, open drain valve and supply
compressed air to the system to force the
chilled water in heat exchanger out.
• Pay attention to the following issues when
maintaining the unit:
► Untreated water may result in unit showing
scaling, corrosion and poor water quality,
system commissioning and maintenance
should be done under guidance from
expert in water treatment. Our company
does not assume responsibility for any
consequence caused by poor water
quality.
► When unit is not in use, its fan coil should
be filled with water to mitigate corrosion in
summer, and should be drained
completely in winter to prevent internal
pipe from breaks due to expansion arising
from freezing.
► Do not use to one temperature controller
or one three-speed switch to control
several fan coil units, otherwise motor may
burn out.
• Coil cleaning
The fan coil may show degraded cooling
capacity if it is blocked or dirty. Clean coil as per
the following steps:
Unit maintenance | 14
Climate 5000 8736863650(2017/05) en
► Disconnect power supply and remove wire
connected with motor, and stop fan blade
from rotating;
► Loosen set screw between side plate and
water collector;
► Remove water collector from unit shell,
and loosen the set screw between fixed
plate and side plate, Also loose the set
screw between side plate and top cover;
► Take out the heat exchanger on fan coil,
use hard nylon bristle to brush and wash
coil fins, and clear with vacuum cleaner;
► Reinstall the heat exchanger on fan coil
and water collector, and fix them with
screw;
► Connect electricity and water pipe, and
conduct test run to verify effects.
To reduce the frequency for cleaning coil, it is
better to equip unit with filter screen and clean
the screen on a regular basis.
• Water collector
The water collector must be clean to facilitate
removal of condensate water. And it must be
cleaned when showing dirt.
• Line collector
- Communication line must be connected to
Terminal Block through fixing clip.
- Communication line adopts metallic hose
for insulation.
Figure 5: Installation and disassembly diagram
15 | Common faults and solutions
8736863650(2017/05) en Climate 5000
7 Common faults and solutions
Failure Cause Recommended solution
Small air volume
Dirty filter Clean or replace
Blocked air inlet Remove blockages
Resistance of ventilation pipeline higher than design value (or incorrect unit type)
Reduce resistance in pipeline or configure unit again
High levels of unit noise
Damaged motor axletree Replace motor
Loose set screw of fan or fan blade Tighten set screw
Collision between impeller and deformed volute Replace volute or impeller
Dirty filter Clean or replace the filter
Insufficient heating or cooling capacity
Cold water not cold, or hot water not hot Decrease (increase) water temperature
Small water flow Increase water flow
Small air volume Increase air volume
Leak
Leaky pipeline or poor insulation of pipe fitting Keep insulated
Uneven installation Keep it even again
Cracked heat exchanger due to freezing Repair or replace
Poor coil drainage or undesirable drainage of condensate water
Clogged system pipeline Inspect valve on pipeline for opening or for foreign bodies
Inadequate unit installation angle Adjust unit height to ensure drainage angle
Table 4: Common failures and troubleshooting methods
Packing list | 16
Climate 5000 8736863650(2017/05) en
8 Packing list
Packing List CTN: 1
Type Name Model and specification Unit Quantity Remarks
Main part Fan coil unit See nameplate Set 1
Printed accessories
Instructions on use and installation (with certificate of quality)
Set 1
Table 5: Packing list
17 | Appendix
8736863650(2017/05) en Climate 5000
9 Appendix Notice: Correct disposal of this product. Pay attention to the following issues:
Figure 6: WEEE
This marking indicates that this product should
not be disposed with other household wastes. To
prevent potential harm to the environment or
human health from uncontrolled waste disposal,
recycle it responsibly to promote the sustainable
reuse of material resources. To return your used
device, please use the return and collection
systems or contact the retailer where the product
was purchased. They can take this product for
environmental safe recycling.